Tender For Design, Drawing, Construction, Testing & Commissioning Of Sewerage System, 170 Kld Sewage Treatment Plant (Stp) & 40 Kld Effluent Treatment Plant (Etp) For Sub-Divisional Hospital (Sdh) In Dharmagada Including Operation & Maintenance For A
Tender Overview
Project Description
Tender for Design, Drawing, Construction, Testing & Commissioning Of Sewerage System, 170 Kld Sewage Treatment Plant (Stp) & 40 Kld Effluent Treatment Plant (Etp) For Sub-Divisional Hospital (Sdh) In Dharmagada Including Operation & Maintenance For A Period Of Five Years
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 05-Sep-2026 | 1st Corrigendum | Technical Bid | 23-Sep-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Dismantling of cement concrete pavement by mechanical means using pneumatic tools, breaking into pieces not exceeding 0.02 cum in volume, and stacking serviceable materials at designated locations and disposing of dismantled materials up to a lead of 1000 metres, including stacking serviceable and unserviceable materials separately, complete as per the direction of the Engineer-in-Charge. |
| 2 | Dismantling of cement concrete paver block flooring/pavement, including removal of paver blocks and bedding layer, sorting and stacking of serviceable materials, disposal of rubbish within specified lead, as directed by Engineer-in-Charge. |
| 3 | Earthwork excavation in all kind of soil and hard rock / laterite rock.For laying of waste water pipe line (SWR (Type-B) Pipe)Supplying all labours and T&P for earth work in all kind of soil within 50mtr intitial lead including rough dressing and breaking of clods maximum 5cmto 7cm size and laying in layers not exceeding 0.30mtr in depth as per direction of Engineer -in -charge. Upto 1.50 mtr. Depth |
| 4 | Excavation of foundation in laterite rock or any hard rock(other than granite )removed by chiselling including dressing and leveling the bed not exceeding 1.5mtr depth and depositing the soil within 50mtr initial lead as per specification approved by the Deptt.Upto 1.50 mtr. Depth |
| 5 | Cutting in disintegrated rock not requiring blasting including dressing and leveling the bed not exceeding 1.5mtr depth and depositing the soil within 50mtr initial lead as per specification approved by the Deptt. Beyond 1.50 - 3.00 mtr. Depth |
| 6 | For laying of Waste water pipe line from Inspection chamber to manhole chamber (DWC Pipe)Supplying all labours and T&P for earth work in all kind of soil within 50mtr inttial lead including rough dressing and breaking of clods maximum 5cmto 7cm size and laying in layers not exceeding 0.30mtr in depth as per direction of Engineer -in -charge. Upto 1.50 mtr. Depth |
| 7 | Excavation of foundation in laterite rock or any hard rock (other than granite )removed by chiselling including dressing and leveling the bed not exceeding 1.5mtr depth and depositing the soil within 50mtr initial lead as per specification approved by the Deptt. Upto 1.50 mtr. Depth |
| 8 | Cutting in disintegrated rock not requiring blasting including dressing and leveling the bed not exceeding 1.5mtr depth and depositing the soil within 50mtr initial lead as per specification approved by the Deptt. Beyond 1.50 - 3.00 mtr. Depth |
| 9 | For laying of Waste water pipe line from MH to MH & MH to STP (RCC NP3 Hume Pipe)Supplying all labours and T&P for earth work in all kind of soil within 50mtr inttial lead including rough dressing and breaking of clods maximum 5cmto 7cm size and laying in layers not exceeding 0.30mtr in depth as per direction of Engineer -in -charge. Upto 1.50 mtr. |
| 10 | Excavation of foundation in laterite rock or any hard rock (other than granite) removed by chiselling including dressing and leveling the bed not exceeding 1.5mtr depth and depositing the soil within 50mtr initial lead as per specification approved by the Deptt. Upto 1.50 mtr. Depth |
| 11 | Cutting in disintegrated rock not requiring blasting including dressing and leveling the bed not exceeding 1.5mtr depth and depositing the soil within 50mtr initial lead as per specification approved by the Deptt.Beyond 1.50 - 3.00 mtr. Depth |
| 12 | For construction of Manhole chamberSupplying all labours and T&P for earth work in all kind of soil within 50mtr inttial lead including rough dressing and breaking of clods maximum 5cmto 7cm size and laying in layers not exceeding 0.30mtr in depth as per direction of Engineer -in -charge.Upto 1.50 mtr. Depth (Manhole 1.2 x 0.9 m Depth) |
| 13 | Upto 1.50 mtr. Depth (Manhole 1.2 x 1.67 m Depth) |
| 14 | Excavation of foundation in laterite rock or any hard rock (other than granite) removed by chiselling including dressing and leveling the bed not exceeding 1.5mtr depth and depositing the soil within 50mtr initial lead as per specification approved by the Deptt. Upto 1.50 mtr. Depth (Manhole 1.2 x 0.9 m Depth) |
| 15 | Upto 1.50 mtr. Depth (Manhole 1.2 x 1.67 m Depth) |
| 16 | Cutting in disintegrated rock not requiring blasting including dressing and leveling the bed not exceeding 1.5mtr depth and depositing the soil within 50mtr initial lead as per specification approved by the Deptt. Beyond 1.50 - 3.00 mtr. Depth |
| 17 | Pipe BeddingProviding and laying sand bedding for sewer line trenches, including watering, ramming and consolidation by punners, complete with an initial lead of 50 metres as per specification and direction of Engineer-in-Charge. |
| 18 | Construction of granular sub base by providing closed gradded granular Bedding materials as per table 400-1 spreading in uniform layers with mortor grader on prepared surface, mixing by in place method with rovator at OMC and campacting with vibratory roller to achieve the desired density complete as per clause 401 of MoSRT&H specification for road & bridge work etc complete. |
| 19 | Providing and laying cement concrete in proportion 1:3:6 using 40 mm CBHG metal, in floor / bedding / base as required, including cost, conveyance, royalties, taxes of all materials, labour charges, mixing, laying, watering and curing, complete as per specification and direction of the Engineer-in-Charge. |
| 20 | Supplying all materials, labour, T & P for refilling the trenches with Sand in layers of 300mm thick, including watering, ramming and consolidation, etc complete as per specification and direction of the Engineer-in-Charge. |
| 21 | Disposal of debris/surplus excavated material to the site about 5km away from the work site, complete as per standard detailed technical specifications and approved design and drawings, including hire charges of machineries, loading and unloading charges, with all lead and lift and any other incidental charges, complete direction of Engineer-in-charge. |
| 22 | Supplying all materials, labour, T&P for construction of circular type manholes with cover slab of Reinforced cement concrete M25,HD 20 precast manhole cover and ring, bottom slab & shaft made of Reinforced cement concrete M25 below 1.5m upto required depth with graded granite stone aggregate, foundation concrete(1:3:6) using graded HG stone aggregate 40mm nominal size, inside plastering 6mm thick (1:4) finished smooth with neat cement punning, outside plaster 12mm thick(1:4) and making benching with cement concrete M25 using graded granite stone aggregate, making smooth to the surface of benching and channel, testing & commissioning, lighting, watch & ward etc., all complete as per approved design & drawing & direction of Engineer in charge. Size:- 1.20 x 0.90mtr (Circular) |
| 23 | Every Additional Depth of 0.10 mtr or part there of upto 1.50 mtr. |
| 24 | Size:- 1.20 x 1.67mtr (Circular) |
| 25 | Every Additional Depth of 0.10 mtr or part there of upto 2.30 mtr. |
| 26 | Supplying all materials,labour and T&P for Construction of Gully trap with R.C.P.C. top slab in (1:1.5:3 ) mix with inside plaster 12mm. thick with cement mortar (1:3) finished with neat cement punning, 12mm. thick out side plaster (1:3), flyash brick work with flyash bricks with crushing strength not less than 75kg/sqcm. in cement mortar (1:3) finished smooth complete as per specification & direction of Engineer in charge. Size 250 x 250 x 675 mm |
| 27 | Supplying all materials,labour and T&P for Constructing Inspection chamber with top slab in (1:1.5:3 ) mix & R.C.P.C. with inside plaster 12mm. thick with cement mortar (1:3) finished with neat cement punning, 12mm. thick out side plaster (1:3), flyash brick work with flyash bricks with crushing strength not less than 75kg/sqcm. in cement mortar (1:3) finished smooth complete as per specification & direction of Engineer in charge. Inspection Chamber 0.75 x 0.75 x 0.45 M |
| 28 | Every Additional Depth of 0.10 mtr or part thereof |
| 29 | 0.75 x 0.75 x 0.75 |
| 30 | Every Additional Depth of 0.10 mtr or part thereof |
| 31 | Supplying all materials,labour and T&P for Re-Construction of damaged Inspection chamber with R.C.P.C. top slab in (1:1.5:3) mix with inside plaster 12mm. thick with cement mortar (1:3) finished with neat cement punning, 12mm. thick out side plaster (1:3), flyash brick work with flyash bricks with crushing strength not less than 75kg/sqcm. in cement mortar (1:3) finished smooth complete as per direction of Engineer-in-charge.0.75 x 0.75 x 0.45 M |
| 32 | Every Additional Depth of 0.10 mtr or part thereof |
| 33 | 0.75 x 0.75 x 0.75 |
| 34 | Every Additional Depth of 0.10 mtr or part thereof |
| 35 | Supply, delivery & laying the following size of ISI marked PVC SWR S/S house sewer pipes (ISI Type - B) of approved diameter and rubber ring gasket and all other materials, labour, T & P, and lowering the pipes in to the trench, aligning, laying to approved level or slope as per P.H. specification and direction of Engineer-in-charge.90mm OD SWR Pipe |
| 36 | 110mm OD SWR Pipe |
| 37 | 160mm OD SWR Pipe |
| 38 | Providing, supplying, lowering and Hydraulic Testing instandard length (PE material) DWC pipe Structured-Wall plastic piping system for non pressure underground drainage and sewerage with smooth internal & corrugated external surface confirming to IS16098:Part-2 2013with spigot or plain endwith necessary jointing material coupler including transportation and freight charges, inspection charges, loading and unloading charges, conveyance to departmental store and stacking the same in closed shadeduly protecting from direct sun ray and rains excluding GST levied by Gol and GoM in all respect , etc. complete. Best NABL Approved Vendor tets Report submitted and Approved by Client Engineer-In-charge. PE / DWC SN-8150 mm Dia |
| 39 | 200 mm Dia |
| 40 | Providing and supplying ISI standard HDPE / DWC specials / specials such as bend,tee, all angleand other on site required Specails excluding GST levied by GOI & GOM in all respect, railway freight, insurance, unloading from railway wagon, loading into truck transport to departmental store/site,unloading stacking etc. complete as per direction of Engineer-in-charge. 100 mm to 200 mm dia |
| 41 | Supply and delivery of the following sizes of sulphate Resistant Cement RCC pipes of NP3 class confirming to IS 458, 1988 in Standard lengths wih socket and spigot ends with Suitable rubber rings, lowering in the ready made trenches, laying true to alignment and gradient, jointing with rubber rings, testinng as per the specifications including cost and conveyance of all materials to site, labour charges, all other incidental and operational charges etc, complete as per the direction of Engineer in chief.200 mm Dia |
| 42 | DEWATERINGDewatering of excavated trenches and pools of water in building trenches / pipeline trenches, well works by using pumps and other devices, including disposal of water to a safe distance as directed by the Engineer-in-Charge, complete as per specification. |
| 43 | BARRICADINGProviding and fixing minimum 50 mm dia Bamboo for covering the barricading in one/two rows one above another and painiting in red and white sheets as per the specifications and direction of Engineer in charge with proper fixing arrangements with Gl implet washers nuts & bolts complete in all respect. |
| 44 | Supplying all labour, tools & plants for rigid & smooth shoring and shuttering with wooden planks of suitable thickness, hoisting & placing in position of wooden planks and runner, bracing with wooden posts and fixing with sutiable wooden runner etc. wherever necessary at suitable intervals, including cost of all materials, royality, taxes, conveyance of all materials to site and installing in trench on both side upto required depth to retain earth for sewer lines and manholes, dismantling the shoring and shuttering etc. all complete as per direction of Engineer-in-chargeLift upto 1.50 m depth |
| 45 | ROAD RESTORATIONCC ROADCement concrete (1:3:6) with 40mm. Size crusher broken hard Granite 1 metal including cost of all labour m³, materials with all taxes, lead, T & P etc all complete. |
| 46 | Cement concrete (1:1.5:3)with 12mm size crusher broken hard granite chips including cost of all labour, materials with all taxes, lead, T & P etc all complete. |
| 47 | Providing and laying of 60mm thick factory made cement concrete interlocking paver block of M 30 grade and approved make, colour and size made by block making machine with strong vibratory compaction of approved size design and shape laid in required colour and pattern over and including 50mm thick compacted bed of sand etc complete coarse sand , filling the joints with the sand etc all complete including cost conveyance, royalties and taxes of all materials and cost of all labour, etc. complete as directed by Engineer in charge.material for reuse |
| 48 | new material for restoration |
| 49 | R.C.C DRAINSupplying all material, labour, T & P for construction of R.C.C surface drain for disposal of rain water etc from the premises of ETP / STP (0.25m width x 0.30m depth) etc all complete as per approved design and drawings and as per direction of Engineer-in-charge. |
| 50 | PLANT CUM SCADA ROOMSupplying all material, labour, T & P for construction of Plant cum SCADA room using R.C.C Column, R.C.C Beam, Lintel, Chajja, Roof Slab, Fly ash brick work in C.M( 1:6), Cement plaster & painting works with lead and lift of all materials to site as per approved drawings, specifications and direction of Engineer-in-Charge.Room size (30 sqm.) |
| 51 | CHEMICAL STORAGE ROOMSupplying all material, labour, T & P for construction of Chemical storage room using R.C.C Column, R.C.C Beam, Lintel, Chajja, Roof Slab, Fly ash brick work in C.M( 1:6), Cement plaster & painting works with lead and lift of all materials to site as per approved drawings, specifications and direction of Engineer-in-Charge. |
| 52 | COMPOUND WALLSupplying all material, labour, T & P for Construction of RCC framed Boundary Wall with fly ash brick including earthwork, sand filling, CC (1:3:6), R.C.C work, brick work, plastering, painting, etc. all complete as per design and drawings and as per direction of Engg.-in-charge. |
| 53 | Supplying all material, labour, T & P for provision of SS Gate including construction of 2 nos. R.C.C pillar, plastering, finishing etc all complete as per approved drawings and direction of Engg.-in-charge.2 Leaf SS Gate (size 6.0M X 1.8 M Ht.)-1 No.1 Leaf SS Gate (size 1.3M X 1.8 M Ht.)-1 No. |
| 54 | Construction of STP & ETPDesigning, drawing, supplying, constructing, testing & commissioning of Effluent Treatment Plant (ETP) & Sewage Treatment Plant (STP) of required capacity and appropriate technology (MBBR / Advanced MBBR / MBR/ SABRE) including all civil, electro-mechanical works, tertiary treatment system, automation etc all complete to achieve desired effluent quality as per NGT norms. (Excluding cost of SCADA system, PLC, plant room, chemical storage room, yard lighting, compound wall, external electrification, treated water storage sump and re-use/disposal arrangements) (Technology to be adopted as approved by Engineer-in-ChargeSewage Treatment Plant of capacity 170 KLDEffluent Treatment plant of capacity 40 KLD |
| 55 | Supply, Installation, Testing and Commissioning of Multiparametric Online Continuous Effluent Monitoring System having facilities for pH, COD, BOD TSS analyzer as per technical specifications attached including ( One) year guarantee. Make XYLEM /SCAN /HORIBA /Equivalent make with approval of authority. |
| 56 | Supply,Installation & Commissioning of SCADA software (Make-Schiender/Simens/Rockwell/Equivalent make with approval of authority) with Graphical processor visualisation Advanced alarm management,historical and Real time trending,Built-inreporting, Stastical process control,Multithreaded citect VBA and Cicode programming language with 2048 Tag SCADA Software (ES+OS) (Make-Schiender / Simens / Rockwell / Equivalent make with approval of authority),1KVa online Ups with 30Min batery backup- 1Nos,CPU Having Preloaded win-10 Proffessional, I3-10gen 2.4 Ghz Prrocessor, DDR4 8gb Ram, 500 gb 7200 Rpm HDD-1 Nos (Make-HP, DELL, LENOVO), USB based keyboard - 1Nos,USB based Optical Mouse- 1Nos,43'' LED monitor - 1Nos,A4 size laserPrinter - 1Nos,Wooden Computer table - 1 Nos ,Preparation of P&I diagram, Creation of Multi visualization screen for Process control,alarm managenent, Historical and realtime process trend, Daily reporting etc complete as per requirement & direction of Engineer - in - Charge. (Including license key) |
| 57 | Supply,installation & commissioning of PLC Panel with following technical specification i,e. Enclosure: 800x800x2100mm-01 No with double door & lock, CPU should have 1 MB program memory with extended memory slut ,Redundand-24VDC,SMPS 10Amp along with 24V DC SPD,IO count as DI-16,DO-20,AI-20,AO-08 & MODBUS-10 subsystem shall be of same series as CPU,10\\" Panel Mounted HMI,Modem should have support MQTT Protocol by default, 24volt DC Industrial switch with minimum 6 eathernate, 4 SFP Port each AI shall be equiped with sutitable signal isolator of 20 Nos & surge protection device 20 nos LIU Isolater, 230Volt AC/230volt AC torroidal transformer,1KVA 230V AC industrial grade UPS of 8 hrs backup to charge 3 nos 12 VDC 65 AH Battery ,DP MCB of Adequate current capacity,LED tube light 10\\" 5 watt,door limit switch,Fan 6\\" with louver,4 sqmm straight through terminal & fuse terminal 90 nos, with PE & EE.The Approved Make : (Make:- Siemens,Schnider,ABB,Mitsubishi/Equivalent make with approval of authority) including cost of material with all taxes transporataion to Site/Storage with insurance.Programme to be handed over with upload & download facilities for departmental use. |
| 58 | Treated water storage sumpConstruction of Treated water storage sump of required capacity using RCC including plastering, painting, epoxy treatment, etc. all complete as per approved design and drawings and as per direction of Engineer-in-charge. For Capacity of 40,000 ltrs |
| 59 | Supply, Installation, Testing and Commissioning of Submersible pump set with required control panel and electrical installation all complete as per approved design and drawings and as per direction of Engineer-in-charge. (1W + 1S) |
| 60 | Providing and supplying in standard lengths High Density Polyethelene Pipes, confirming to IS 4984 / 14151 / 12786 / 13488 with nesessary jointing material like mechanical connector i. e. thread / insert joint / quick release coupler joint / compression fitting joint or flanged joint excluding coupler/specials, including transportation and freight charges, inspection charges, loading / unloading charges, conveyance to the departmental stores & stacking the same in closed shade duly protecting from sunrays & rains, excluding GST levied by GI & GOM in all respect etc complete as per direction of Engineer-in-charge.75 mm dia HDPE (PE-80) pipe |
| 61 | 90 mm dia HDPE (PE-80) pipe |
| 62 | 110 mm dia HDPE (PE-80) pipe |
| 63 | YARD LIGHTINGSupply of Elegant look 60 W (+/-10%) AIO LED Solar Street lights having extruded aluminum housing, 180Wp or more Mono Crystalline Panel/Laminates fixed on the top of the luminaire housing, maintenance free 12.8 volts 78 Ah or more LiFePO4 battery (BIS certified), BMS, MPPT charge controller, PIR sensor to provide 2 days (24 hrs.) back up. The luminaire is having IP 65 protection for critical components, IK 07 and having lumen output of > 10000 lumen and having minimum lumen efficacy >160 Im/w) as per LM 79 report third party NABL lab to justify the lumen output & lumen efficacy. Lenses should be provided on the LED chip for better lighting distribution to avoid glare on human eyes. Both the luminaire and Mono Crystalline Panel must be manufactured in India. The Solar lighting company must submit the third party NABL lab reports to justify the lumen efficacy, luminaire output, IK 07 and IP 65 protection. The Luminaire should be supplied along with adjustable type mounting bracket which can be fitted directly on the pole. The Solar Street light and solar panel having capacity of 180 Wp or more must be designed to take the wind load at 180 KM/HR wind speed (As per wind load test report). The Solar lighting manufacturer must submit the declaration letter by mentioning that complete solar light and the solar panel are manufactured in India and warranty certificate on their company's letterhead by mentioning warranty period as 5 years and necessary aftersales service will be provided through their toll-free base service network located within 100 KM from the project site |
| 64 | Supply of 8 mtr long hot dip galvanized Octagonal pole having base dia of 155 mm and top dia of 70 mm and plate thick ness of 4 mm or more. complete with base plate and 4 nos. Type En 8 grade foundation bolts to withstand 180 KM/HR or more wind speed considering the weight & dimension of 1 nos 60 W AIO Solar light to be fitted in the pole at two different heights (One light on Pole Top and second light on the differential bracket)(Make - Bajaj/RR Ispat Valmont/Utkarsh or equivalent) |
| 65 | Construction of RCC foundation by using M20 grade RCC and Fe415 grade reinforcement in the foundation by considering the SBC as 10 T per sq mtr and fixing 4 nos. EN8 grade foundation bolts in that foundation for installation of pole with solar lighten that foundation. The work shall be executed as per the instruction of Engineer-in-charge. |
| 66 | Supply & fixing of GI Adapter plate of 14 mm thickness or more to withstand the load on 8 mtr Octagonal pole & Solar light complete with mounting bolts of suitable size & all accessories required for fixing the plate on the ROB by using suitable machinery without cutting crash barrier/bridge surface. The Adapter plate shall be designed in a proper manner to install the 8 mtr Octagonal pole with Solar light on the side of the ROB/Bridge. |
| 67 | Installation of 8 mtr pole on the adaptor plate/ foundation after fixing the 60 W AIΟ Light in the pole by using suitable machinery by taking all safety precautions as per the direction of EIC. (make- as approved by PWD Odisha) |
| 68 | EXTERNAL ELECTRIFICATIONProviding for supply, installation, testing and commissioning of 3-phase, 11/0.4 kV LT power supply system including 100 KVA, 11/0.4 kV transformer with all associated materials, accessories, fittings and allied works complete in all respects as per relevant Electrical/IS specifications and as required by the concerned Electricity Distribution Utility. The provision shall also include LT overhead line up to the transformer yard, including conductor, GI poles, stays, insulators, cable from transformer to panel room and all other allied materials and works as required by TPCODL/TPSODL/TPWODL/TPNODL, including necessary supervision, inspection and approval charges. (Work shall be executed under the supervision of TPCODL/ TPSODL/ TPNODL/ TPWODL Authorities as per their estimate and payment shall be made accordingly as per actual).Transformer capacity -100 kVA |
| 69 | DG SETDesign, engineering, procurement of materials and bought out components, manufacturing, assembly at shop, inspection, testing and painting at manufactures works, packing, supply, unloading/ transportation/ handling/ storage at site, assembly at site, installation including touch-up painting, hook-up, pre-commissioning, commissioning, inspection and testing of the complete of the following capacity (prime power) DG sets along with AMF panels. Acoustic enclosure, supply of all erection & commissioning spares, special tools and tackles (as required), instrumentation, all auxiliaries, Exhaust system & silencer, Fuel tank, Fuel piping etc all complete including RCC foundation,DG set Shed,Chemical earthing 4 nos,Al power cable of required length,trial run with required amount of diesel as per directrion of EIC in complience with CPCB IV+ norms. (Make:- Mahindra Power/ Kirloskar/Ashok Leyland/Sterling/Jackson/ Cumin Powers/ Greaves Cotton/ Greaves/TMTL/Captiva/Equivalent make with approval of the authority)DG capacity -125 kVA |
| 70 | Design, manufacture, supply, inspection, handling, installation, testing and commissioning of floor-mounted, extensible type, cubical Main LT Panel fabricated out of 1.6/2.0 mm thick CRCA sheet steel, dust and vermin proof, front operated construction, enclosure protection class IP-42, conforming to IEC 60439. The panel shall be surface treated with 9-tank process and provided with top/bottom removable gland plates, double compression type cable glands, earth bus, hinged and lockable doors, and all internal interconnections complete as required for plant operation, as per the direction of the Engineer-in-Charge. |
| 71 | 5 years of Operation & MaintenanceWaste Water Collection System Operation and Maintenance for the first 5 years from Commissioning of the Work and Treatment plant O&M, including deployment of Skilled Man Power, Chemical consumption, operation consumables for ETP & STP plant operation.For 1st Year O & M |
| 72 | For 2nd Year O & M |
| 73 | For 3rd Year O & M |
| 74 | For 4th Year O & M |
| 75 | For 5th Year O & M Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 10 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 10 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender