Tender For Augmentation Of Sewerage Scheme For Mandi Town And Providing Sewerage Facility To Adjoining Villages Of Mandi Town Distt. Mandi (Hp) (Sh :-Installation Of Pumping Machinery And Its Allied Accessories Inside Wet Well Near Vishwakarma Temple
Tender Overview
Project Description
Tender for Augmentation Of Sewerage Scheme For Mandi Town And Providing Sewerage Facility To Adjoining Villages Of Mandi Town Distt. Mandi (Hp) (Sh :-Installation Of Pumping Machinery And Its Allied Accessories Inside Wet Well Near Vishwakarma Temple)
BOQ
| Sl. No. | Item Description |
| 1 | Installation, testing and commissioning of KSB make submersible pumping machinery, Model KRTF 40-250/52, 5.0 kW, including carriage of pumping machinery from Divisional store to the site of work, lowering/installation, alignment, connection of delivery pipe, necessary accessories, nuts, bolts, supports and all other incidental works, complete in all respects |
| 2 | Providing, Supplying and Fixing of 250 mm dia Cast Iron Sluice Valve of BIR / KARTAR / PELICON/LEADER make BIS No. 14846 with flange Table - 5 .The sluice valve conforming to IS - 780 having class PN 1.60. The dia of valve as mentioned below complete in all leads and lifts and to the entire satisfaction of the Engineer - in - Charge in all leads and lifts. |
| 3 | Providing, Supplying and Fixing of 65 mm dia Cast Iron Non-Return Valve of BIR / KARTAR / PELICON/LEADER make BIS No. 14846 with flange Table - 5 .The valve conforming to IS - 5312 having class PN 16.0. The dia of valve as mentioned below complete in all leads and lifts and to the entire satisfaction of the Engineer - in - Charge in all leads and lifts. |
| 4 | Providing & Fixing 3.5 Core aluminium armoured Cable 35.00 Sqmm PVC insulated PVC flexible industrial cable 1100 volts ISI marked conforming to IS 7098 (Part 1) 1988 with upto Date mendments in all respects all leads and lifts. |
| 5 | Providing and fixing Busbar Chamber (Wall Mounted) fabricated from 16 SWG/1.6 mm thick CRCA sheet steel, duly powder coated, complete with insulated supports, copper busbars of ETP Grade electrolytic copper, including necessary hardware, nuts, bolts, washers, connections and earthing arrangements, complete in all respects as required at site. (i) 100 Ampere |
| 6 | Providing and fixing 100 Ampere, 3-Phase MCCB with suitable sheet steel enclosure/box, complete with thermal-magnetic overload and short-circuit protection, including necessary lugs, terminals, mounting arrangements, interconnections, hardware and accessories, complete in all respects as per HPPWD specifications and direction of Engineer-in-Charge. |
| 7 | Providing and fixing HRC (Switch Disconnector Fuse) Full Set, 100 Ampere, comprising fuse carriers, fuse bases, HRC/rewirable fuse links and necessary contacts, clamps and connecting hardware, complete in all respects as per HPPWD specifications and as directed by the Engineer-in-Charge.(i) 100 Ampere |
| 8 | Providing and Supplying INDEF/POWER FULL make Chain pully blocks 1.00 MT (ISI marked) with moving trolley ISI Marked M along with Chain complete in all respects and to the entire satisfaction of the Engineer - in- charge. |
| 9 | Providing and fixing of water proof PVC Cable 12 core, suitalbe for machinery as per IS-674-Part-II-1964 suitable for above pump set from starter to pump set subject to the approval of HPSEB authority as per the satisfaction of Engineer-in-Charge. |
| 10 | Providing and laying Double Flanged (Screwed/ Welded) Centrifugally (Spun) Ductile Iron Pipes of Class K - 9 conforming to IS : 8329 : (i) 250mm dia |
| 11 | Providing, laying, jointing, testing and commissioning of HDPE (High Density Polyethylene pipes) of following diameter and class confirming to IS 4984-1995 with fusion welding process including all necessary fittings in all leads and lifts to the entire satisfaction of Engineer-in-charge (Earth work in trenches to be measured and separately). )(i) HDPE pipe 80mm dia PE 100 PN 10.00 |
| 12 | Providing and fixing DI Equal Tee 250 mm dia × 250 mm diax80mm, conforming to IS: 4984 / relevant IS standards, including jointing by butt-fusion welding, complete in all respects as per specifications and direction of Engineer-in-Charge. |
| 13 | Providing and fixing DI Bend 90 degree of 80mm dia , conforming to IS: 4984 / relevant IS standards, including jointing by butt-fusion welding, complete in all respects as per specifications and direction of Engineer-in-Charge. |
| 14 | Providing and fixing M.S. flanges, pair of 250 mm dia, Table-17, conforming to relevant IS/BS standards, including bolts, nuts, washers and 3 mm thick rubber gasket, welding/fixing to M.S. pipe, complete in all respects as directed by the Engineer-in-Charge. |
| 15 | Providing and Installation of 2 Meter copper bonded Chemical Earthing with Ground Enhancing Compound Including excavation and refilling 8SWG GI wire from earthing to Inside pump house with connection to Bus-Bar or MCCB. complete in all respect. (i) Copper Strip 20x3 Sqmm |
| 16 | Providing and laying Insulation mat for preventing Electrical Shocks and Hazards. Class ‘B’ having maximum use voltage Of 11KV and Thickness between 2 and 3mm of reputed make. |
| 17 | Providing and fixing PVC insulated and PVC Round Sheathed, Multicore Annealed Bare Copper Conductor (flexible) industrial cable for Voltage Grade 1100 Volt, Conforming to IS 694 : 2010 of 1.50 Sqmm complete in all respect in all leads and lifts. |
| 18 | Providing and fixing New generation energy saving & environmental friendly, long life, High-pressure die-cast aluminium housing Flood Light with toughened Glass cover. 150W LED of reputed make and other fittings etc.complete in all respect in all leads and lifts. |
| 19 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. |
| 20 | Reconditioning of existing electrical control panel of pumping machinery including checking, servicing, replacement of defective/damaged electrical components such as MCCB/MCB, contactors, overload relays, single-phasing preventor, push buttons, selector switches, indicating lamps, fuses, internal wiring, terminals, lugs, etc., as required, including cleaning, tightening of connections, insulation testing, testing and commissioning complete in all respects as directed by the Engineer-in-Charge. Please Enable Macros to View BoQ information TERMS AND CONDITIONS. |
| 21 | The work shall be executed as per HPIPH specifications, CPHEEO manual with latest amendments on sewerage and sewage treatment, relevant IS codes and to the entire specification of the Engineer-in-Charge. |
| 22 | All rates should be inclusive of all taxes i/c G.S.T. |
| 23 | Security, Income tax ,G.S.T, labour cess and surcharge as applicable under various clauses of form PWD 6&12 will be deducted from the each running bill of the contractor by Executive Engineer under building and other construction for workers welfare cess act 1996. |
| 24 | The rates of all the items shall be inclusive of the carriage of all the materials to charged all leads and lifts to the site of work. |
| 25 | The final payment will be made to the contractor after testing/completion of work. |
| 26 | Nothing shall be paid for rejected work/material |
| 27 | No deviation shall be allowed without the prior permission of the Engineer-in-charge. |
| 28 | Prices of all items shall be F.O.R. site of work inclusive of all leads and lifts and shall be inclusive of all charges of transportation, insurance,packing,taxes and duties such as sale tax, excise duty, local taxes etc. |
| 29 | The location of site can be ascertained from the concerned Assistant Enginweer, and the rates quoted by the firm shall be inclusive of all machanical and manual transport within all leads and lifts to the site of work. |
| 30 | The contractor is requested to inspact the site before quoting his rate. |
| 31 | The general specifications of work shall conform to Punjab PWD/HPPWD specifications as per direction of the Engineer-in-charge. |
| 32 | Non-clog submersible pumps & DG Sets are already available in this divisional store at Raghunath Ka Padhar. The successful bidder shall arrange transportation of the above materials to site and carry out erection, installation, testing and commissioning at site complete in all respects.\\" |
| 33 | The pumping machinery/electrical equipment shall be subjected to a trial run for a minimum period of 72 hours under actual working conditions after completion of installation/reconditioning The trial run shall be carried out in the presence of the Engineer-in-Charge. |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 6 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender