Defence Statutory Bodies & Commissions/Committees Closing in 19 days TDR #57321608

Tender For Repair/Maint Of Geysers, Solar Water Heaters And Heating Appliances At Shillong Cantt, Happy Valley And Se Falls And Repair/Maint Of D G Sets And Other Misc Services At Cantt Area Under Ge Shillong

Issued by Statutory Bodies & Commissions/Committees · East Khasi Hills, Meghalaya
Tender Value
40 Lakhs
Estimated cost
Bid Submission
23 Sep 2026
19 days left
EMD
80000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
East Khasi Hills → Meghalaya
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair/Maint Of Geysers, Solar Water Heaters And Heating Appliances At Shillong Cantt, Happy Valley And Se Falls And Repair/Maint Of D G Sets And Other Misc Services At Cantt Area Under Ge Shillong

BOQ

Name of Work:- REPAIR/MAINT OF GEYSERS, SOLAR WATER HEATERS AND HEATING APPLIANCES AT SHILLONG CANTT, HAPPY VALLEY AND SE FALLS AND REPAIR/MAINT OF D G SETS AND OTHER MISC SERVICES AT CANTT AREA UNDER GE SHILLONG
Sl. No. Item Description
1Dismantling electric and water connection of the geyser, taking down from its position on ground, dismantling geyser complete such as removing tank from its outer body, removing apparatus plate from the tank, descaling the geyser inner tank and apparatus plate complete, testing its thermostate, element , and tank from leakage, reassembling the geyser, replacement of unserviceable parts such as heating element, thermostate, indication lamp, plug top , three core wire, rubber gasket, inner tank, split plate, outer bottom cover, apparatus plate if required (Spares will be paid under relevant item of the Sch) testing the geyser and installation of the geyser into its original position and connecting all electric and water supply connection complete all as specified and directed of capacity 25/35/50 liters.
2Supply and replace heating element any type as per site requirement of capacity 2 KW ISI Mark complete all as specified and directed.
3Supply and replace heating element any type as per site requirement of capacity 1.5 KW ISI Mark complete all as specified and directed.
4Supply and replace thermostat for geyser as per site requirement temp setting on 60 degree Centigrade ISI Mark complete all as specified and directed.
5Supply and replace indication lamp for above geyser complete all as specified and directed.
6Supply and replace Apparatus plate 06/09 hole for 25/50 liters capacity geyser made out of brass and chromium plated as per site requirement complete all as directed.
7Supply and replace split plate for 25/50 litrs capacity geyser as per site requirement and made out of 20 gauge MS sheet complete all as specified and directed.
8Supply and replace geyser inner tank made out of stainless steel sheet conforming to I.S. for 50 liters geyser complete all as specified and directed.
9Supply and replace geyser inner tank made out of stainless steel sheet conforming to I.S. for 35 liters geyser complete all as specified and directed.
10Supply and replace geyser inner tank made out of stainless steel sheet conforming to I.S. for 25 ltrs capacity geyser complete all as specified and directed.
11Supply and replace geyser Outer cover complete with upper cover & bottom cover made out of MS sheet, duly painted with one coat of red oxide primer and two coat of first quality super enamalled white paint complete all as directed for 25 liters capacity geyser complete all as specified and directed.
12Supply and replace glass wool for 25/50 ltrs capacity geyser complete all as specified and directed.
13M&L for painting of geyser of capacity 25/50Ltrs with one coat of first quality super enamalled white paint complete all as directed.
14Supply and replace fusible plug made out of brass and lead complete all as specified and directed.
15S&F three core PVC insulated and over all PVC round cable of size 40/0076 with stranded copper conductor complete all as specified and directed.
16S&F in repair plug top 3 pin 16 Amps capacity complete all as specified and directed.
17Switch socket combination 15 Amps complete all as specified and as directed
18S&F switch piano flush button type 15 Amps SP complete all as specified and directed.
19S&F in replacement of water supply PVC connection 15 mm dia with washer up to 500 Cm long complete all as specified and directed.
20S&F in replacement of water supply PVC connection 15 mm dia with washer up to 650 Cm longcomplete all as specified and directed.
21M&L for brazing / soldering work with copper brass alloy to rectify leakage/cracked of inner copper container of storage type electrically operated water heater (Geyser) & testing of inner shell up to the entire satisfaction of the Engr-in- Charge including reassembling / reinstalling at site etc complete all as directed.
22Supply and safety valve for geyser spring loaded 15 mm dia complete all as directed.
23Supply only replace rubber gasket as per site requirement for 25/50 ltr Geyser complete all as specified and directed.
24Supply and fix in replacement of metal clad plug top for metal clad socket complete all as specified and directed.
25Supply and fix in replacement of metal clad plug and socket complete with 20 Amps MCB complete all as specified and directed.
26M&L sub main wiring with 2 Single core, PVC insulated unsheathed cable 1100 Volts grade heavy duty copper conductor multistaranded of size 2.5 Sq.mm. (nominal area) drawing in and including PVC casing caping and fittings. Including one single core green colour PVC Insulated unsheathed multistranded copper conductor cable of size 1.5 Sq. mm. as earth wire upto common earth and connected to earth dolly complete including Cutting chases in brick/stone masonry wall complete all as specified and directed.
27S&F GI wall fastner of size 100 mm long 8 mm dia with double washer grouting to a suitable depth and hight in wall to a suitable depth and hight with cement sand mortar 1:4 for fixing / holding storage type electrically operated water heater including necessary GI nuts bolts and washer etc complete all as specified and as directed.
28S&F in replacement of MCB single pole 240 Volt, 10 KA 5 to 32 Amps in existing DBs all as specified and directed.
29S&F in replacement of MCB single pole and neutral 240 V 10 KA, 40 Amps existing DBs all as specified and as directed.
30S&F in replacement printed circuit board (PCB), ISI Marked, suitable for electrically operated water heater (Geyser) of different capacity complete all as specified and as directed.
31Taking up or down old serviceable/unserviceable pipe the 20 mm size with any connection including cleaning for re fixing or removal from the side complete all as specified and directed.
32Re fixing/Re laying of old servicalbe GI pipe 20mm as obtained from taking out against items No 31 complete all as specified and as directed
33Supply and fixing in in replacement GI tubing 20mm, medium grade, including fittings such as tee, bend, nipple, socket, reducer, flange, union etc complete all as specified and directed.
34S&F Gun metal gate valve 20 mm class I (ISI) marked with iron wheel head, screwed both ends for iron pipe, suitable for following bore of pipe including taking down old existing unserviceable gate valve complete all as specified and directed.
35Dismantling complete solar water heating of capacity 100 ltr per day including hot & cold water pipes and hot water tank complete. Repairing the sys fixing back in position and testing complete all as specified and as directed. Note:- Rate quoted by the contractor shall deemed to be included for :- (a) Making good the worn out missing nuts bolts, washers, union socket, flanges and screws etc. (b) Dismantling the solar panel descaling of hot water pipes by using appropriate chemicals, cleaning and washing all copper tube throughly cleaning the complete panel, making the tubes scale free and reassembling the panel. (c) Cleaning cold water tanks. (d) All other materials shall be measured and paid separately under respective item.
36All as per item No 35 but cap 500 LPD complete all as specified and directed.
37S&F in repairs solar energy collector panel complete of cap 100 Ltrs per day camplete all as specified and as directed.
38S&F in repairs solar energy collector panel glass (collector toughened glass) complete of cap 100 Ltrs per day complete all as specified and as directed.
39S&F in repairs solar panel gasket made out of fine rubber to make sys air tight, dust, and water proof complete all as specified and as directed.
40S&F in repairs solar energy collector panel copper tubes with collector fins complete of same dia and thickness, brazing by rod with the existing inlet/outlet and hot / cold water pipes to make the panel water tight complete all as specified and as directed.
41S&F in repairs compressed glass wool 48 mm thick between solar energy collector panel copper tubes frame and aluminium body of panel including securing it on panel by means of necessary adhesive complete all as specified and as directed.
42S&F in repairs aluminium sheet cover to protect glass wool on solar energy collector panel fixing with frame of solar panel by means of screw complete all as specified and as directed.
43S&F in repairs solar energy collector panel manifold 1.40 mtr long /suitable size, made of 20 mm dia copper tube having 1 no MS flange 74 mm dia welded to each end duly drilled for nut & bolts. rate quated to be included for welding of solar collector tubes with manifold complete all as specified and as directed.
44Disconnecting solar hot water storage tank, cleaning with brush and drain out complete sludge / sand diposited in the hot water tank and connecting after complete cleaning up to the entire satisfaction, complete all as specified and as directed.
45S&F in replacement heating element up to 3 KW rating , ISI marked, suitable for solar water heater of any type including rubber washer of any make complete all as specified and as directed.
46S&F in replacement of hot water pipe PVC insulation including necessary rubber gasket complete all as specified and as directed.
47Supply and fixing in in replacement GI tubing 15 mm, medium grade, including fittings such as tee, bend, nipple, socket, reducer, flange, union etc complete all as specified and directed.
48M&L for Maintenance and servicing of standby DG Set complete including draining out of diesel from tank , cleaning the tank thoroughly and refilling the drained out diesel, draining out engine oil from the sump, cleaning the sump thoroughly and refilling the sump with new engine oil to it’s required level, replacing the fuel filter, lubricating oil filter , check & clean air cleaner , change air cleaner elements, check coolant level & make up the same ,drain the fuel filter & water separator ,filling the starting batteries with electrolyte/distilled water to maintain the required specific gravity, replace the u/s brass connectors for batteries, cleaning of battery terminals & applying petroleum jelly to battery terminal posts & brass connectors, including V Belts, checking of exhaust leakage, governor, breathers etc, adjust/set the same for proper functioning of DG Set, checking of fuel, oil and water/ coolant level etc, adjusting and keeping the fan belts to the desired tension, tightening all the bolts and nuts to the required torque etc, cleaning the DG Set with accessories as prescribed by the manufacturer and test for satisfactory running of DG set for two hour at connected load and record shall be made in respect of RPM , oil pressure , oil temperature , coolant temperature, voltage , frequency , load current , battery charging , fuel consumption etc complete all as specified and directed.(a). Engine oil for refilling will be measured & paid separately.(b). Coolant for make up will be measured & paid separately(c). The Make of Fuel filter , Oil Filter , V belt & component will be as per manufactures recommendations and rate of fuel filter, oil filter, air filter and V belt is under supply only items.Capacity of DG 10 to 40 KVA complete all as specified and directed.
49(a) Supply only Gasket set complete all as specified and directed.
50(b) Supply only Head gasket complete all as specified and directed.
51(c) Supply only Valve steam seal complete all as specified and directed.
52(d) Supply only Rear oil seal complete all as specified and directed.
53(e) Supply only Front oil seal complete all as specified and directed.
54(f) Supply only Hose pipe set complete all as specified and directed.
55(g) Supply only Hose clamp set complete all as specified and directed.
56(h) Supply only Flexible pipe set complete all as specified and directed.
57(j) Supply only Copper washer set complete all as specified and directed.
58(k) Supply only Air filter set complete all as specified and directed.
59(l) Supply only Diesel filter complete all as specified and directed.
60(m) Supply only Oil filter set complete all as specified and directed.
61(n) Supply only Fan belt complete all as specified and directed.
62(o) Supply only Solonied switch complete all as specified and directed.
63(p) Supply only Oil temperature gauge complete all as specified and directed.
64(q) Supply only Oil pressure gauge complete all as specified and directed.
65(r) Supply only Lube oil pump complete all as specified and directed.
66(s) Supply only Stop Solonied assy complete all as specified and directed.
67(t) Supply only High Pressure pipe complete all as specified and directed.
68(u) Supply only Door Lock complete all as specified and directed.
69All as per Srl Item No. 48 here-in-before but capacity of DG set 57 to 125 KVA complete all as specified and directed.
70(a) Supply only Gasket set complete all as specified and directed.
71(b) Supply only Head gasket complete all as specified and directed.
72(c) Supply only Valve steam seal complete all as specified and directed.
73(d) Supply only Rear oil seal complete all as specified and directed.
74(e) Supply only Front oil seal complete all as specified and directed.
75(f) Supply only Hose pipe set complete all as specified and directed.
76(g) Supply only Hose clamp set complete all as specified and directed.
77(h) Supply only Flexible pipe set complete all as specified and directed.
78(j) Supply only Copper washer set complete all as specified and directed.
79(k) Supply only Air filter set complete all as specified and directed.
80(l) Supply only Diesel filter set complete all as specified and directed.
81(m) Supply only Oil filter set complete all as specified and directed.
82(n) Supply only Fan belt complete all as specified and directed.
83(o) Supply only Solonied switch complete all as specified and directed.
84(p) Supply only Oil temperature gauge complete all as specified and directed.
85(q) Supply only Oil pressure gauge complete all as specified and directed.
86(r) Supply only Lube oil pump complete all as specified and directed.
87(s) Supply only Stop Solonied assy complete all as specified and directed.
88(t) Supply only High Pressure pipe complete all as specified and directed.
89(u) Supply only Door Lock complete all as specified and directed.
90All as per Srl Item No.48 here-in-before but capacity of DG set 160/180/200 KVA complete all as specified and directed.
91(a) Supply only Gasket set complete all as specified and directed.
92(b) Supply only Head gasket complete all as specified and directed.
93(c) Supply only Valve steam seal complete all as specified and directed.
94(d) Supply only Rear oil seal complete all as specified and directed.
95(e) Supply only Front oil seal complete all as specified and directed.
96(f) Supply only Hose pipe set complete all as specified and directed.
97(g) Supply only Hose clamp set complete all as specified and directed.
98(h) Supply only Flexible pipe set complete all as specified and directed.
99(j) Supply only Copper washer set complete all as specified and directed.
100(k) Supply only Air filter set complete all as specified and directed.
101(l) Supply only Diesel filter set complete all as specified and directed.
102(m) Supply only Oil filter set complete all as specified and directed.
103(n) Supply only Fan belt complete all as specified and directed.
104(o) Supply only Solonied switch complete all as specified and directed.
105(p) Supply only Oil temperature gauge complete all as specified and directed.
106(q) Supply only Oil pressure gauge complete all as specified and directed.
107(r) Supply only Lube oil pump complete all as specified and directed.
108(s) Supply only Stop Solonied assy complete all as specified and directed.
109(t) Supply only High Pressure pipe complete all as specified and directed.
110(u) Supply only Door Lock complete all as specified and directed.
111Repair/maintenance of existing control panel of DG set by replacing the connected items such as leads, copper wire, thimble , Analogue Ammeter, Analogue voltmeter,frequancy meter etc along with other minor parts required for carrying out maintenance complete all as specified and directed.Note- Ammeter, Voltmeter and frequancy meter shall be measured and paid separately as supply only items below and labour element involve for replacing the same shall deemed to be included in the rate quoted against these item.
112(a) Supply only Analogue Ammeter Class 1, 5 A, 3 phase complete all as specified and directed.
113(b) Supply only Analogue Voltmeter Class 1, 3 Ph complete all as specified and directed.
114(c) Supply only Frequancy meter single phase, Class 0.20 complete all as specified and directed.
115Repair/ over hauling of self starter assembly of any type/make/ model including replacement of bearing bushing, washer, bendix pinion, carbon bush etc complete as required for proper functioning for the following capacities of DG sets complete all as specified and directed.
116(a) DG set 180 to 200 KVA complete all as specified and directed.
117(b) DG set 125 to 160 KVA complete all as specified and directed.
118(c) DG set 57 to 100 KVA complete all as specified and directed.
119(d) DG set 10 to 40 KVA complete all as specified and directed.
120Note: (i) Make of DG Sets shall be as specified against Tender documents.(ii) Repair works shall be carried out by authorised agent / dealer of DG Sets.
121Disconnecting the Exhaust Pipe Line with mufler of DG set from Exhaust Manifold of the Engine and removing the Unserviceable Asbestos Rope from the Exhaust Pipe, Cleaning the Exhaust Pipe and cutting the mufler removing all Carbon Particles Inside including wrapping of existing asbestos rope complete all as specified and directed. for the following capacities of DG Sets:
122(a) DG set 180 to 200 KVA complete all as specified and directed.
123(b) DG set 125 to 160 KVA complete all as specified and directed.
124(c) DG set 57 to 100 KVA complete all as specified and directed.
125(d) DG set 10 to 40 KVA complete all as specified and directed.
126Dismantaling Radiator assembly from DG set Engine from inside and out side , Cleaning and Washing the RadiatorS&Fins by Compressed Air with Chemical Water, removing all dust, etc. from the Radiator and Filling Coolant, re-assemble the same in Original Position with new gaskets, radiator connecting hoses and clamps complete all as specified and directed, for the following capacities DG Sets:- Note:- (i) Coolant shall be measured and paid seperatly under relevnt items of these schudule. (ii) Asbestos rope shall be measured and paid separately under relevant items of these schedule.(iii) Repair works shall be carried out by authorised agent / dealer of DG Sets. (iv) Make of DG Sets shall be as spesified against Tender documents.
127(a) DG set 180 to 200 KVA complete all as specified and directed.
128(b) DG set 125 to 160 KVA complete all as specified and directed.
129(c) DG set 57 to 100 KVA complete all as specified and directed.
130(d) DG set 10 to 40 KVA complete all as specified and directed.
131Disconnecting the fuel tank including Inlet/Outlet Connections of the following capacities of DG sets and cleaning the Tank properly and removing all dusts, mud, etc. and refixing the fuel tank and Inlet/Outlet Pipe connections in orginal position complete all as specified and directed.
132(a) DG set 180 to 200 KVA complete all as specified and directed.
133(b) DG set 125 to 160 KVA complete all as specified and directed.
134(c) DG set 57 to 100 KVA complete all as specified and directed.
135(d) DG set 10 to 40 KVA complete all as specified and directed.
136Note :- (i) Repair/ maintenance & servicing shall be carried out through authorized representative of manufacturer's of DG Sets.
137Material and labour for Rewinding of starter armature complete for the following capacities of DG sets With super enamelled copper winding wire including taking out old unserviceable winding complete all as specified and directed.
138(a) DG set 180 to 200 KVA complete all as specified and directed.
139(b) DG set 125 to 160 KVA complete all as specified and directed.
140(c) DG set 57 to 100 KVA complete all as specified and directed.
141(d) DG set 10 to 40 KVA complete all as specified and directed.
142Note: (i) Make of DG Set shall be as specified against Tender documents. (ii) Repair/ maintenance & servicing shall be carried out through authorized representative of manufacturer's of DG Sets.
143Repair / over hauling of automatic/manual, Governor assembly of any make/type/model complete including calibration and replacement of spare parts as required to make the governor 100 % trouble free ccomplete all as specified and directed.
144(a) DG set 180 to 200 KVA complete all as specified and directed.
145(b) DG set 125 to 160 KVA complete all as specified and directed.
146(c) DG set 57 to 100 KVA complete all as specified and directed.
147(d) DG set 10 to 40 KVA complete all as specified and directed.
148Note: (i) Make of DG Set shall be as specified against Tender documents.(ii) Cost of spare parts shall deemed to be included in the rate quoted .
149M&L in repair to taking down demage/unserviceble Battery of 12 Volts 150/180 AH by replace new battery of same capcity complete all as required including charging etc for proper functioning complete all as specified and directed.
150All as per item No. 149 above but for 80 to 120 AH Battery as per requirement complete all as specified and directed.
151Repair/ over hauling, servicing of alternator for battery charger of 12 Volt Battery of any make / type / rewinding of armature and field coil including replacement of bearing / bushing etc and make the alternator 100% serviceable complete all as specified and directed.
152S&F MCCB 4 pole 400 Amps, 36 KA,415 Volts, with thermal magenetic release, etc complete including taking down old unserviceable MCCB complete all as specified and directed.
153S&F MCCB 250 Amps Four pole 25 KA 415 Volts ,adjustable thermal & fixed Magnetic setting Make including taking down old unserviceable MCCB complete all as specified and directed.
154Repair/ servicing of alternator of any make/type/model including grinding/polishing of slip rings assembly cleaning and re-tensioning of carbon bush holder including replacement of carbon bush for the alternators of following DG Sets :
155(a) DG set 125 to 200 KVA complete all as specified and directed.
156(b) DG set 57 to 100 KVA complete all as specified and directed.
157(c) DG set 10 to 40 KVA complete all as specified and directed.
158Note: (i) Make of DG Set shall be as specified against Tender documents. (ii) Cost of spare shall demand to be included in the rate quoted by the tender
159Taking out of defective automatic voltage regulator (AVR) of DG set (alternator side) and supply and fix New automatic voltage regulator (AVR) including necessary connection, testing and cable work etc complete all as specified and directed. for the following capacities of DG Sets :-
160(a) DG set 160 to 200 KVA complete all as specified and directed.
161(b) DG set 10 to 125 KVA complete all as specified and directed.
162Supply only Engine Oil (20 W 40) complete all as specified and directed.
163Supply only Coolent complete all as specified and directed.
164Supply only Distilled water for Battery as per sample complete all as specified and directed.
165Supply and Fix Asbestos rope of required size complete all as specified and directed.
166S&F in repairs Battery connection cable of length 1.2 Mtr with solid brass clamp lugs for \\"+\\" terminals at one side and copper lug on other side complete all as specified and directed.
167S&F in repairs Battery connection cable of length 1.2 Mtr with solid brass clamp lugs for \\"-\\" terminals at one side and copper lug on other side complete all as specified and directed.
168M&L Earthing with galvanized steel earth plate electrode of size 600 mm x 600 mm x 6.00 mm buried directly in ground connected to galvanized earth lead strip of size 32 mm x 6 mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel including 40mm dia medium grade GI tubing for protection of earth lead, MS sheet metal funnel with wire mesh, watering pipe light grade 20mm dia, charcoal or coke and common salt in alternative layer of 15 Cm compacted thickness all around the electrode with concrete earth pit of PCC type C1 (1:3:6, using 20mm graded crushed stone aggregates) 50mm thick precast RCC type B1, (1:2:4, using 20mm graded crushed stone aggregates) pit cover reinforced with 8mm dia deformed bar and suitable handle made of 10mm dia round bar including galvanised strip of size 32mm x 6mm for extension of earth lead and necessary excavation, earth work, in soft/loose soil and disposal of spoils to a distance n.exc 50m and necessary connection and testing complete all as shown in electrical plate No 3 of SSR Part-I, 2009 and all as specified and directed including taking down old unserviceable earth pit and accessories.Note : GI Strip upto 7.5m length shall be deemed to include in the cost of above item. This quantity required over and above shall be measured under relevant items of these schedule complete all as specified and directed.
169S&F, GI strip 32 x 6 mm as eath continuity conductor or main earthing lead buried in ground or drawn through pipes or fixed to wall or poles or any other situation for loop earthing etc including dismantling old unserviceable strip complete all as specified and directed.
170Excavation In trenches not exceeding 1.5m wide and not exceeding 1.5m deep and getting out in soft/soil for laying/removing of XLPE cables complete all as specified and directed.
171Returning, filling in, including, spreading, levelling, watering and wall ramming, in layers not exceeding 25Cm in soil obtained from excavation complete all as specified and directed.
172Removal of surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above starting point complete all as specified and directed.
173M&L for providing dry river sand as in sand cushioning to UG cable including punning gently complete all as specified and directed.
174M&L Sub class'B' old size well burnt brick laid flat in trenches as protection to LT cable complete all as specified and as directed.
175S&F XLPE insulated, screened, PVC bedded, galvanized steel strip of wire armoured, electric power cables (heavy duty) 1100 Volts grade, with stranded aluminium conductor of size 25 Sqmm 3 core, including taking out old unserviceable cable including PVC flexible pipe for cable protection complete all as specified and as directed.
176S&F XLPE insulated, screened, PVC bedded, galvanized steel strip of wire armoured, electric power cables (heavy duty) 1100 Volts grade, with stranded aluminium conductor of size 120 Sqmm 3.5 core, including taking out old unserviceable cable including PVC flexible pipe for cable protection complete all as specified and as directed.
177All as per item No. 176 above but size of XLPE cables 95 Sqmm 3.5 core complete all as specified and directed.
178All as per item No. 176 above but size of XLPE cables 70 Sqmm 3.5 core complete all as specified and directed.
179All as per item No. 176 above but size of XLPE cables 50 Sqmm 3.5 core complete all as specified and directed.
180S&F Changeover switch 630 Amps, in sheet steel enclosure, 4 Pole, side handle operated complete including taking down old unserviceable one complete all as specified and directed.
181S&F Changeover switch 400 Amps, in sheet steel enclosure, 4 Pole, side handle operated complete including taking down old unserviceable one complete all as specified and directed.
182S&F Changeover switch 250 Amps, in sheet steel enclosure, 4 Pole, side handle operated complete including taking down old unserviceable one complete all as specified and directed.
183S&F Changeover switch 160/200 Amps, in sheet steel enclosure, 4 Pole, side handle operated complete including taking down old unserviceable one complete all as specified and directed.
184S&F Changeover switch 63 Amps, in sheet steel enclosure, 4 Pole, side handle operated complete including taking down old unserviceable one complete all as specified and directed.
185S&F MCCB, 3 pole, 415 Volts,160 Amps, 36 kA breaking capacity with thermal and magnetic release including taking down old unserviceable one complete all as specified and directed.
186S&F MCCB, 3 pole, 415 Volts,125 Amps, 16 kA breaking capacity with thermal and magnetic release including taking down old unserviceable one complete all as specified and directed.
187S&F MCCB, 3 pole, 415 Volts,100 Amps, 16 kA breaking capacity with thermal and magnetic release including taking down old unserviceable one complete all as specified and directed.
188Supply only MCCB, 3 pole, 415 Volts, 63 Amps, 16 kA breaking capacity with thermal and magnetic release including taking down old unserviceable on complete all as specified and directed.Note:- Materials shall be fixed to panel board as mentioned here in after.
189M&L 25mm thick PCC type B2 ( 1:2:4, using 40 mm graded aggregates) as in floor, finished even and smooth without using extra cement including demolition of old unserviceable concrete complete all as specified and as directed.
190Supply only First aid Kit with all accessories including necessary medicines made by fibre sheet of size Length -45cm, width 30 cm and hight 15cm complete all as specified and directed.
191Supplying and laying insulated Electrical matting class 1, proof voltage tested upto 10 KV, 2mm thick ness of size 1.00 mtr (wide) with one side fabric and other side plain finish as per IEC 61111 including taking out old unserviceable rubber matting complete all as specified and directed.
192Shifting of DG Set from one location to another location by removing of cable cannection, earthings and lifting up with the help of recory van and installed at new location complete with all T&P, Labours and make connection, earthing connection, testing after installation complete all as specified and directed. Note- If any damaged in DG Set during moving , contractor held fully responcible for make it serviceable with in 3-4 hrs.
193S&F in repair of multi function meter for measuring line voltage,current frequency, power factor suitable for DG set of suitable capacity complete all as specified and directed.
194M&L for Caliberation of FIP of 10 to 40 KVA DG Set with removal of plungers, delivery valve, O ring, diaphram springs and seal washers etc including caliberation of injector holders with renewal of nozzles complete all as specified and directed.
195M&L for Caliberation of FIP of 10 to 63 KVA DG Set with removal of plungers, delivery valve, O ring, diaphram springs and seal washers etc including caliberation of injector holders with renewal of nozzles complete all as Specified and directed
196M&L for Caliberation of FIP of 82.5 to125 KVA DG Set with removal of plungers, delivery valve, O ring, diaphram springs and seal washers etc including caliberation of injector holders with renewal of nozzles complete all as Specified and directed.
197M&L for Caliberation of FIP of 160/180/200 KVA DG Set with removal of plungers, delivery valve, O ring, diaphram springs and seal washers etc including caliberation of injector holders with renewal of nozzles complete all as Specified and directed.
198Supply and mixing of Calcium Hypochlorite 65% to 70% chlorine content in packed with 45 kg each drum (calcium based granular disinfectant for water treatment (in swimming pool/OHT/UG sump/Well) much more stable than chlorine gas and stronger than bleaching powder & sodium hypochlorite complete all as specified and directed.Make :- The contractor must submit the COC (Certificate of Compliance) in original from manufacturer by All India Authorised MES Distributor for each batch of product delivered indicating and including Chemical Analysis Report by All India Authorised MES Distributor.Note :- 1. The contractor must submit the COC (Certificate of Compliance) in original from manufacturer for each batch of product delivered including chemical analysis report. Contractor has to get approval of Accepting officer before placing purchase order complete all as specified and directed.
199Supply and Fix air ciculator fans 230 V single phase oscillationing 450 mm sweep suitable for wall mounting complete all as specified and direted. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57321608
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 40 Lakhs
LAST DATE 23-09-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair/Maint Of Geysers, Solar Water Heaters And Heating Appliances At Shillong Cantt, Happy Valley And Se Falls And Repair/Maint Of D G Sets And Other Misc Services At Cantt Area Under Ge Shillong
Basic Detail
Tender No GE/SHL/TOKEN-76 OF 2026-27
Bidding Type Tender
Location
City East Khasi Hills
State Meghalaya
Key Dates
Publish Date 02 Sep 2026
Submission Date 23 Sep 2026
Open Date 24 Sep 2026
Finance
Tender Value 40 Lakhs
Tender Fee 500
EMD 80000
Exemption Available
Document List
567a503d-60cf-4bc9-a6b8-d19f68feb662.html
BOQ_882646.xls
TENDERDOCU76.pdf
Tendernotice_1 (8).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 02, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 23, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 19 days
Sep 24, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 20 days

Tender Documents

Download All (ZIP) ↓
html

567a503d-60cf-4bc9-a6b8-d19f68feb662.html

xls

BOQ_882646.xls

pdf

TENDERDOCU76.pdf

pdf

Tendernotice_1 (8).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders