Shipping Government Departments Closing in 1 days TDR #57314503

Tender For General-Pmmsy Expansion Of Muthalapozhy Fishing Harbour -Urgent Electrical Maintenance Work Of Yard Lighting At Thazh Ally And Perumathura Fishing Harbours -General Electrical Work

Issued by Government Departments · Thiruvananthapuram, Kerala
Tender Value
12.70 Lakhs
Estimated cost
Bid Submission
15 Sep 2026
1 days left
EMD
31763
Bank guarantee accepted
Document Fee
2760
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Thiruvananthapuram → Kerala
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for General-Pmmsy Expansion Of Muthalapozhy Fishing Harbour -Urgent Electrical Maintenance Work Of Yard Lighting At Thazh Ally And Perumathura Fishing Harbours -General Electrical Work

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 11-Sep-2026 DATE EXTENSION Date 15-Sep-2026

BOQ

Name of Work:- GENERAL-PMMSY Expansion of Muthalapozhy Fishing Harbour -Urgent Electrical Maintenance work of Yard Lighting at Thazh ally and Perumathura Fishing Harbours -General Electrical Work
Sl. No. Item Description
1Thazhampally Yard Lighting
21.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
31.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
41.17.1:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.1 x 1.5 sq. mm
52.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
61.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
72.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole
814.4:Excavation for cable trenches in soft soil, depth upto 1.2 m including dressing of sides lift upto 1.5 m, including getting out the excavated soil, refilling with sand and or good soil after laying of cable/ pipe etc in layers of 20 cm, ramming, watering and disposal of surplus excavated soil as directed, within a lead of 50 metres.
97.10:Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
1014.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
1114.13.1:Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required50 mm dia
121.28.1:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.1 or 2 Module
132.10.3:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Double pole
142.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
152.15.1:Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCCB), having a sensitivity current 30milli Amperes in the existing MCB DB complete with connections, testing andcommissioning etc. as required.25 amps
162.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Triple pole
179.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
1890.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
1990.14.10.3:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
2090.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
2190.6.6.1:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.1.50 sq mm
2290.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size
2390.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
2490.10.1.2:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )2 module moulded plastic box on surface
2590.12.5.40:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 10 sq mm
26OD4608/2026-2027:Supply and fixing Cable Junction Boxes IP 65 weather proof type for outdoor applications Thermoplastic Polycarbonate ) suitable for cable sizes 2.5 sq.mm , ,80 X 80X 52 mm and accessories for Cable Junction Boxes such as Copper Terminal Set 2.5 sq.mm 5 Pole 1 No,including fixing the accessories using suitable size Stainless steel Bolt and nut, giving necessary connections, making good the damages etc. as required .
27OD4606/2026-2027:Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of Vertical TPN DB - IP65, Weather proof Polycarbonate , dust protected, , inclusive of 125 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCCB's and MCCB as incomer (but without MCCB's and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)4 Way including all accessories complete as required.
28OD4609/2026-2027:Supply Conveyance, installation, testing and commissioning of 200 W LED Flood light output greater than 130 lumen/W 5700 K with IP 66 protection, IK 07, with power factor greater than 0.95 at full load, internal surge protection up to 4 KV, and Aluminum pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant and including SPD , duly wired up for use on 230 V AC supply . Driver compartment should be separately accessible for maintenance .
29OD4610/2026-2027:Supply and installation of wall/structure-mounting cubicle type outdoor Thermoplastic Polycarbonate Mast Foot Box ,Size 4, 315 X 600 X 170mm with opaque/transparent hinged lid, degree of protection IP65/IP66, complete with internal base plate/DIN rails for accommodating 4-Pole RCCB, Isolator, and outgoing 2-Pole MCBs. Box shall include 4 Nos. 35sq.mm channelmounted Elmex/equivalent terminal connectors suitable for looping up to 16 sq.mm aluminum armoured cables, tin-plated copper earth bus, and necessary IP-rated cable gland knockouts/holes for cable entry and exit. Internal interconnections shall be completed using 2.5 sq.mm flexible copper wiring with insulated pin/fork lugs. The mast foot box supply excludes RCCB and MCBs as required.
30OD4611/2026-2027:Fabricating and supplying special clamping arrangement for fixing an asymmetrical beam integral LED flood light on 50 mm dia GI pipe ring with two clamps each made out of 50 x6mm MS flat and 8x40mm SS nuts and bolts for one luminaire. The clamps are to be linked with 40x6mm MS flat with suitable holes 8mm,10mm, or 12mm size with suitable size SS Bolt& Nut to fix the luminaire. All the items are to be painted with two coats of epoxy-basedindustrial primer of approved quality and two coats of epoxy paint of approved color as per drawing.
31OD4612/2026-2027:Scaffolding Charges for mounting the flood light fixture in existing street light pole upto a length upto 15 mtr from ground level. The charges including hire charge, transportation, loading, unloading and all expense complete as required.
32OD4613/2026-2027:Engaged Labour for maintenance work for dismounting/fixing the existing light fittings, cables and other electrical accessories from the existing poles upto 12 meter including rectifying minor defects, tightening nut and bolts ,overall check-up, change the cable and welding and fabrication work for minor defects including materials complete as directed by engineer in charge at site including all maintenance work complete as required.
33Perumathura Yard and Street Light Electrification
341.17.1:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.1 x 1.5 sq. mm
351.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
361.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
371.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
382.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole
392.10.3:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Double pole
402.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Triple pole
412.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
422.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
437.10:Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
449.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
459.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
4614.13.1:Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required50 mm dia
4714.4:Excavation for cable trenches in soft soil, depth upto 1.2 m including dressing of sides lift upto 1.5 m, including getting out the excavated soil, refilling with sand and or good soil after laying of cable/ pipe etc in layers of 20 cm, ramming, watering and disposal of surplus excavated soil as directed, within a lead of 50 metres.
481.28.1:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.1 or 2 Module
4990.10.1.2:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )2 module moulded plastic box on surface
5090.12.5.40:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 10 sq mm
5190.12.5.41:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 16 sq mm
5290.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
5390.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
5490.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size
5590.14.10.3:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
5690.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
5790.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
5890.6.6.1:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.1.50 sq mm
59OD4619/2026-2027:Engaged Labour for maintenance work for dismounting/fixing the existing light fittings, cables and other electrical accessories from the existing poles upto 12 meter including rectifying minor defects, tightening nut and bolts ,overall check-up, change the cable and welding and fabrication work for minor defects including materials complete as directed by engineer in charge at site including all maintenance work complete as required.
60OD4620/2026-2027:Scaffolding Charges for mounting the flood light fixture in existing street light pole upto a length upto 15 mtr from ground level. The charges including hire charge, transportation, loading, unloading and all expense complete as required.
61OD4623/2026-2027:Supply Conveyance, installation, testing and commissioning of 200 W LED Flood light output greater than 130 lumen/W 5700 K with IP 66 protection, IK 07, with power factor greater than 0.95 at full load, internal surge protection up to 4 KV, and Aluminum pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant and including SPD , duly wired up for use on 230 V AC supply . Driver compartment should be separately accessible for maintenance .
62OD4628/2026-2027:Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of Vertical TPN DB - IP65, Weather proof Polycarbonate , dust protected, , inclusive of 125 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCCB's , MCCB as incomer (but without MCB's and incomer ) as required .(Note : Vertical type MCCB TPDB is normally used where 3 phase outlets are required.)8 Way including all accessories complete as required.
63OD4643/2026-2027:Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 130 lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 4 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant with SPD, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)- preferred make philips BRP274 LED 84 CW M2 SLR PSU SPD S2
64OD4644/2026-2027:Supply and installation of wall mounting cubicle type dust and vermin proof, Hinged lid 300 x 300 x 214 mm, Hensel make polycarbonate Enclosure - IP66 size 2 box MI 0210 or equivalent in wall with all fixing accessories and cutting holes for cable entry etc complete as required.
65OD5138/2026-2027:Dismantling of existing 90° single arm bracket from the top of tubular pole of height up to 8.0 metres, safely lowering to ground, and supplying, fabricating, and erecting 1.5 metre long, 45° angle curved single arm bracket made out of 50 mm nominal bore Class 'B' (Medium) Galvanised Iron (G.I.) pipe conforming to IS: 1239 (Part 1) with ISI mark, suitable for mounting existing LED street light fitting on existing tubular pole; including fabrication of heavy-duty M.S./G.I. sleeve collar adapter and pole clamping brackets (minimum 5 mm thick) with hot-dip galvanised bolts, nuts, and spring washers (Grade 4.6/8.8); welding, surface preparation to SSPC-SP 10 / St 3, application of one coat of two-pack zinc phosphate epoxy primer and two coats of high-build coastal-grade aliphatic polyurethane / epoxy finish paint of approved shade and make; including anti-chafing neoprene/PVC cable entry grommets, re-connecting existing LED luminaire, all labour, height work, hire charges of working platform/ladder, hoisting, loading, unloading, transport, and site clearance complete as required and as directed by the Engineer-in-Charge.
66Civil WORK
6715.3:Demolishing R.C.C. work manually / by mechanical means including stacking of steel bars and disposal of unserviceable material with in 50 metres lead as per direction of Engineer -in-Charge. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57314503
AUTHORITY Government Departments
TENDER VALUE 12.70 Lakhs
LAST DATE 15-09-2026
Authority
Authority Name Harbour Engineering Department
Work Description Tender for General-Pmmsy Expansion Of Muthalapozhy Fishing Harbour -Urgent Electrical Maintenance Work Of Yard Lighting At Thazh Ally And Perumathura Fishing Harbours -General Electrical Work
Basic Detail
Tender No HED/CEHED/TR/539/2026_6_1_1/1
Bidding Type Tender
Location
City Thiruvananthapuram
State Kerala
Key Dates
Publish Date 11 Sep 2026
Submission Date 15 Sep 2026
Open Date 15 Sep 2026
Finance
Tender Value 12.70 Lakhs
Tender Fee 2760
EMD 31763
Exemption Not Available
Document List
5968c20c-de3c-4e0b-a476-5c3aecea073f.html
BOQ_1468780.xls
Tendernotice_1 (14).pdf
viewsbd.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 11, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 15, 2026
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 1 day
Sep 15, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 1 day
Sep 15, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 1 day

Tender Documents

Download All (ZIP) ↓
html

5968c20c-de3c-4e0b-a476-5c3aecea073f.html

xls

BOQ_1468780.xls

pdf

Tendernotice_1 (14).pdf

pdf

viewsbd.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders