Tender For Maintenance Of Electrical Installation In Non-Residential Building At Chandigarh. (Replacement Of Defective Electrical Points, Accessories & Switchgear Installed In The Various Govt. Model High & Senior Secondary Schools In Various Sector-
Tender Overview
Project Description
Tender for Maintenance Of Electrical Installation In Non-Residential Building At Chandigarh. (Replacement Of Defective Electrical Points, Accessories & Switchgear Installed In The Various Govt. Model High & Senior Secondary Schools In Various Sector-31,32,46,47, 48 & 49, Chandigarh.)
BOQ
| Sl. No. | Item Description |
| 1 | DSR item No. 1.17 Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 2 | 3 x 1.5 sq. mm |
| 3 | 3 x 2.5 sq. mm |
| 4 | 3 x 4 sq. mm |
| 5 | DSR item No. 1.21 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 6 | 25 mm |
| 7 | DSR 1.23 Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. |
| 8 | 5/6 A switch |
| 9 | 15/16 amps switch |
| 10 | 3 Pin 5/6 A. socket outlet |
| 11 | 6 Pin 15/16 A. socket outlet |
| 12 | DSR item No.1.24 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 13 | 5/6 A switch |
| 14 | 15/16 A switch |
| 15 | 3 pin 5/6 A socket outlet |
| 16 | 6 pin 15/16 A socket outlet |
| 17 | DSR 1.25 Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 18 | DSR item No.2.2 Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 19 | 125 A,36KA,FPMCCB |
| 20 | 200 A,36KA,FPMCCB |
| 21 | 400 A,50KA,FPMCCB |
| 22 | DSR Item No. 2.4 Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without (MCB/RCCB/Isolator) |
| 23 | 4 way (4 + 12), Double door |
| 24 | 6 way (4 + 18), Double door |
| 25 | DSR item No. 2.10 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 26 | Single pole |
| 27 | Triple Pole & Neutral |
| 28 | DSR Item 2.16 Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A, 240 V “C” curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 29 | S/E of electronic fan regulator step type socket type in the existing bakelite sheet including cutting the sheet and making connection etc. The job includes all labour and petty material required to complete the job to the entire satisfaction of the Engineer-in-chaege of the work. The fan regulator should be of Anchor(Penta)/ Havells (Reo)/ SSK make only. |
| 30 | Supply & erection MCB 4 pole 63 Amp 415 Volt 10KA Breaking Capacity ‘C’ curve without enclosure. The job includes the labour charges and other petty material required to complete the job. |
| 31 | DSR item No.8.9 LED Batten light (System lumen efficacy ≥105 <120 lm/Watt).(Please refer DNIT for complete specification of item no.12) |
| 32 | 18- 22 Watt |
| 33 | Supply, Erection, Testing and commissioning of the following accessories after dismantling the burnt out/ defective accessories with the help of ladder if required which shall be arranged by the firm at his own cost. The job includes cost of making connections with suitable rating copper wire and petty material required to complete the job to the entire satisfaction of Engineer-in-charge. |
| 34 | S/E of Electronic Driver suitable for existing 2'x2'/ 1'x4' LED fitting. The Driver should be same make of existing fitting i.e. Philips/ Wipro/ Bajaj/ Havells/ Crompton/ Jaquar / Trilux/ Panasonic/ Lighting Technologies/ Surya make only. |
| 35 | S/E of 18Watt./20Watt. 4’ long LED tube rod made of polycarbonate material should be installed in existing LED fitting base only. The make of LED tube rod should be same make of existing LED fitting i.e. Philips/ Wipro/ Bajaj/ Crompton/ Havells/ Trilux/ Panasonic/ Lighting Technologies/ Surya/ Jaquar make only. The job includes cost of carriage, erection, testing and commissioning of the LED tube rod etc. as required to complete the job to the entire satisfaction of Engineer In Charge. (Please refer DNIT for complete specification of item no.14) |
| 36 | DSR item No.2.22 Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enamelled white on both sides, and with inscription in single red colour on front side as required. |
| 37 | DSR item No.8.1 LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt ) (Please refer DNIT for complete specification of item no.16) |
| 38 | 12 -15 watt |
| 39 | DSR item No.8.7 LED Panel light 2x2 ft. (System lumen efficacy ≥120 <135 lm/Watt) (Recessed/ Surface type) (Please refer DNIT for complete specification of item no.17) |
| 40 | 36 watt |
| 41 | DSR item No.8.16 LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 and <135 lm/Watt). (Please refer DNIT for complete specification of item no.18) |
| 42 | 150 Watt. |
| 43 | DSR item No.9.2 Brush Less Direct Current (BLDC) Fan without Remote (Please refer DNIT for complete specification of item no.19) |
| 44 | 1400mm, service value ≥ 6.0 CM/Min/Watt, air delivery 245 CM/Min (Minimum) |
| 45 | S/E of 3mm thick white glazed Bakelite sheet on the existing M.S box. The job includes the cost of sheets and making holes and cutting charges of switches & sockets. The job includes the cost of all labour & petty material required to complete the job. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 4 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 4 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender