Tender For Construction Of Academic Block (G+1), Laboratory 4 Nos, With Canteen(G+1), Area Development, Car Parking Shed And Entrance Gate With Security Post At Inside C Us Of Diet At Khordha- Building
Tender Value
3.74 Crore
Estimated cost
Bid Submission
21 Sep 2026
5 days left
EMD
3.75 Lakhs
Bank guarantee accepted
Document Fee
10000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Khordha → Odisha
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Construction Of Academic Block (G+1), Laboratory 4 Nos, With Canteen(G+1), Area Development, Car Parking Shed And Entrance Gate With Security Post At Inside C Us Of Diet At Khordha- Building
BOQ
| Sl. No. | Item Description |
| 1 | CIVIL WORKClearing and grubbing road land including uprooting rank vegetation, grass, bushes, shrubs, saplings and trees girth up to 300 mm, removal of stumps of trees cut earlier and disposal of unserviceable materials and stacking of serviceable material to be used or auctioned, up to a lead of 1000 metres including removal and disposal of top organic soil not exceeding 150 mm in thickness.Ground FloorAcademic Building |
| 2 | Earth work in hard soil or gravelly soil within 50m. Initial lead and 1.5m initial lift including rough dressing and breaking clods to maximum 5cm to 7cm and laying in layers not exceeding 0.3m in depth and as per the direction of the Engineer-in-charge.Ground FloorAcademic Building |
| 3 | Earth work in hard soil or gravelly soil within 50m. Initial lead and 1.5m initial lift including rough dressing and breaking clods to maximum 5cm to 7cm and laying in layers not exceeding 0.3m in depth and as per the direction of the Engineer-in-charge.Ground FloorLAB 4 NOS & CANTEEN BUILDING |
| 4 | Earth work in hard soil or gravelly soil within 50m. Initial lead and 1.5m initial lift including rough dressing and breaking clods to maximum 5cm to 7cm and laying in layers not exceeding 0.3m in depth and as per the direction of the Engineer-in-charge.Ground FloorAREA DEVLOPEMENT (Paver Block) |
| 5 | Earth work in hard soil or gravelly soil within 50m. Initial lead and 1.5m initial lift including rough dressing and breaking clods to maximum 5cm to 7cm and laying in layers not exceeding 0.3m in depth and as per the direction of the Engineer-in-charge.Ground FloorCar Parking Shed |
| 6 | Earth work in hard soil or gravelly soil within 50m. Initial lead and 1.5m initial lift including rough dressing and breaking clods to maximum 5cm to 7cm and laying in layers not exceeding 0.3m in depth and as per the direction of the Engineer-in-charge.Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 7 | Filling foundation & Plinth with excavated materials well watered & rammed etc. completeGround FloorAcademic Building |
| 8 | Filling foundation & Plinth with excavated materials well watered & rammed etc. completeGround FloorLAB 4 NOS & CANTEEN BUILDING |
| 9 | Filling foundation & Plinth with excavated materials well watered & rammed etc. completeGround FloorCar Parking Shed |
| 10 | Filling foundation & Plinth with excavated materials well watered & rammed etc. completeGround Floor'Entrance Gate With Security Post With Cow Catcher. |
| 11 | Supplying, filling in foundation & plinth with sand in layers including watering and ramming with cost conveyance, royalities, taxes of all materials and labour with T&P required for the work etc. complete Ground FloorAcademic Building |
| 12 | Supplying, filling in foundation & plinth with sand in layers including watering and ramming with cost conveyance, royalities, taxes of all materials and labour with T&P required for the work etc. complete Ground FloorLAB 4 NOS & CANTEEN BUILDING |
| 13 | Supplying, filling in foundation & plinth with sand in layers including watering and ramming with cost conveyance, royalities, taxes of all materials and labour with T&P required for the work etc. complete Ground FloorAREA DEVLOPEMENT (Paver Block) |
| 14 | Supplying, filling in foundation & plinth with sand in layers including watering and ramming with cost conveyance, royalities, taxes of all materials and labour with T&P required for the work etc. complete Ground FloorCar Parking Shed |
| 15 | Supplying, filling in foundation & plinth with sand in layers including watering and ramming with cost conveyance, royalities, taxes of all materials and labour with T&P required for the work etc. complete Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 16 | Providing & applying Post constrution of Antitermite treatment by drilling 12 mm dia holes at a distance of 30cm@ junction of wall and floor about 300mm apart deep enough to each the soil below and chemical emulsion(PREMISE,IMIDACHLOPRIED 30.5SC OF BAYER MAKE mixed with475 ltr water) pumped these holes to soak the soil @1Ltr solution of each holea as per manufactures specification and the holes should be pluged with filling materials including cost of all materials,labour charges,conveyance and all taxes and hiring charges of machinaries as per direction of Engineer in chargesGround FloorAcademic Building |
| 17 | Providing & applying Post constrution of Antitermite treatment by drilling 12 mm dia holes at a distance of 30cm@ junction of wall and floor about 300mm apart deep enough to each the soil below and chemical emulsion(PREMISE,IMIDACHLOPRIED 30.5SC OF BAYER MAKE mixed with475 ltr water) pumped these holes to soak the soil @1Ltr solution of each holea as per manufactures specification and the holes should be pluged with filling materials including cost of all materials,labour charges,conveyance and all taxes and hiring charges of machinaries as per direction of Engineer in chargesGround FloorCar Parking Shed |
| 18 | Providing & applying Post constrution of Antitermite treatment by drilling 12 mm dia holes at a distance of 30cm@ junction of wall and floor about 300mm apart deep enough to each the soil below and chemical emulsion(PREMISE,IMIDACHLOPRIED 30.5SC OF BAYER MAKE mixed with475 ltr water) pumped these holes to soak the soil @1Ltr solution of each holea as per manufactures specification and the holes should be pluged with filling materials including cost of all materials,labour charges,conveyance and all taxes and hiring charges of machinaries as per direction of Engineer in chargesGround Floor'Entrance Gate With Security Post With Cow Catcher. |
| 19 | Cement concrete of proportion (1:3:6) in foundation and floors using 4cm size black broken granite stone aggregates of approved quality and from approved quarry including hoisting, lowering and laying concrete in layers not exceeding 15cm(6\\") thick to the required level ramming, watering, curing etc. complete including cost and conveyance royality taxes of all materials and labour with T&P required for the work etc. complete i as per direction of the Engineer-in-charge.Ground FloorAcademic Building |
| 20 | Cement concrete of proportion (1:3:6) in foundation and floors using 4cm size black broken granite stone aggregates of approved quality and from approved quarry including hoisting, lowering and laying concrete in layers not exceeding 15cm(6\\") thick to the required level ramming, watering, curing etc. complete including cost and conveyance royality taxes of all materials and labour with T&P required for the work etc. complete i as per direction of the Engineer-in-charge.Ground FloorLAB 4 NOS & CANTEEN BUILDING |
| 21 | Cement concrete of proportion (1:3:6) in foundation and floors using 4cm size black broken granite stone aggregates of approved quality and from approved quarry including hoisting, lowering and laying concrete in layers not exceeding 15cm(6\\") thick to the required level ramming, watering, curing etc. complete including cost and conveyance royality taxes of all materials and labour with T&P required for the work etc. complete i as per direction of the Engineer-in-charge.Ground FloorCar Parking Shed |
| 22 | Cement concrete of proportion (1:3:6) in foundation and floors using 4cm size black broken granite stone aggregates of approved quality and from approved quarry including hoisting, lowering and laying concrete in layers not exceeding 15cm(6\\") thick to the required level ramming, watering, curing etc. complete including cost and conveyance royality taxes of all materials and labour with T&P required for the work etc. complete i as per direction of the Engineer-in-charge.Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 23 | Plain Cement concrete M20 grade using 20mm down graded size h.g chips including cost of all materials etc complete.Ground FloorAcademic Building |
| 24 | Plain Cement concrete M20 grade using 20mm down graded size h.g chips including cost of all materials etc complete.Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 25 | Plain Cement concrete M20 grade using 20mm down graded size h.g chips including cost of all materials etc complete.Ground FloorCar Parking Shed |
| 26 | Plain Cement concrete M20 grade using 20mm down graded size h.g chips including cost of all materials etc complete.Ground FloorAREA DEVLOPEMENT (Paver Block) |
| 27 | Plain Cement concrete M20 grade using 20mm down graded size h.g chips including cost of all materials etc complete.First FloorAcademic Building |
| 28 | Plain Cement concrete M20 grade using 20mm down graded size h.g chips including cost of all materials etc complete.First FloorLAB 4 NOS & CANTEEN BUILDING |
| 29 | Plain Cement concrete M20 grade using 20mm down graded size h.g chips including cost of all materials etc complete.Terrace FloorAcademic Building |
| 30 | Brick work with Flyash bricks 25 Cm. x 12 Cm. x 8 cm having crushing strength not less than 75 Kg/cm2 with dimensional tolerance + 2 percent in cement mortar (1:6) in foundation & plinth.Ground FloorFoundationAcademic Building |
| 31 | Brick work with Flyash bricks 25 Cm. x 12 Cm. x 8 cm having crushing strength not less than 75 Kg/cm2 with dimensional tolerance + 2 percent in cement mortar (1:6) in foundation & plinth.Ground FloorFoundation'Entrance Gate With Security Post With Cow Catcher. |
| 32 | Brick work with Flyash bricks 25 Cm. x 12 Cm. x 8 cm having crushing strength not less than 75 Kg/cm2 with dimensional tolerance + 2 percent in cement mortar (1:6) in foundation & plinth.Ground FloorFoundationCar Parking Shed |
| 33 | Brick work with Flyash bricks 25 Cm. x 12 Cm. x 8 cm having crushing strength not less than 75 Kg/cm2 with dimensional tolerance + 2 percent in cement mortar (1:6) in Super-Structure.Ground FloorAcademic Building |
| 34 | Brick work with Flyash bricks 25 Cm. x 12 Cm. x 8 cm having crushing strength not less than 75 Kg/cm2 with dimensional tolerance + 2 percent in cement mortar (1:6) in Super-Structure.Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 35 | Brick work with Flyash bricks 25 Cm. x 12 Cm. x 8 cm having crushing strength not less than 75 Kg/cm2 with dimensional tolerance + 2 percent in cement mortar (1:6) in Super-Structure.Ground FloorCar Parking Shed |
| 36 | Brick work with Flyash bricks 25 Cm. x 12 Cm. x 8 cm having crushing strength not less than 75 Kg/cm2 with dimensional tolerance + 2 percent in cement mortar (1:6) in Super-Structure.First FloorAcademic Building |
| 37 | Brick work with Flyash bricks 25 Cm. x 12 Cm. x 8 cm having crushing strength not less than 75 Kg/cm2 with dimensional tolerance + 2 percent in cement mortar (1:6) in Super-Structure.First FloorLAB 4 NOS & CANTEEN BUILDING |
| 38 | Brick work with Flyash bricks 25 Cm. x 12 Cm. x 8 cm having crushing strength not less than 75 Kg/cm2 with dimensional tolerance + 2 percent in cement mortar (1:6) in Super-Structure.Terrace FloorAcademic Building |
| 39 | Brick work with Flyash bricks 25 Cm. x 12 Cm. x 8 cm having crushing strength not less than 75 Kg/cm2 with dimensional tolerance +2 percent in cement mortar (1:4) in superstructure.Ground FloorAcademic Building |
| 40 | Brick work with Flyash bricks 25 Cm. x 12 Cm. x 8 cm having crushing strength not less than 75 Kg/cm2 with dimensional tolerance +2 percent in cement mortar (1:4) in superstructure.First FloorAcademic Building |
| 41 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorFoundationAcademic Building |
| 42 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorFoundationLAB 4 NOS & CANTEEN BUILDING |
| 43 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorFoundationCar Parking Shed |
| 44 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorFoundation'Entrance Gate With Security Post With Cow Catcher. |
| 45 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorGrade BeamAcademic Building |
| 46 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorGrade BeamLAB 4 NOS & CANTEEN BUILDING |
| 47 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorGrade BeamCar Parking Shed |
| 48 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorGrade Beam'Entrance Gate With Security Post With Cow Catcher. |
| 49 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorColumnAcademic Building |
| 50 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorColumnLAB 4 NOS & CANTEEN BUILDING |
| 51 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorColumnCar Parking Shed |
| 52 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorColumn'Entrance Gate With Security Post With Cow Catcher. |
| 53 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorRoof BeamAcademic Building |
| 54 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorRoof BeamLAB 4 NOS & CANTEEN BUILDING |
| 55 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorRoof BeamCar Parking Shed |
| 56 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorRoof Beam'Entrance Gate With Security Post With Cow Catcher. |
| 57 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorRoof SlabAcademic Building |
| 58 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorRoof SlabLAB 4 NOS & CANTEEN BUILDING |
| 59 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorRoof SlabCar Parking Shed |
| 60 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorRoof Slab'Entrance Gate With Security Post With Cow Catcher. |
| 61 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorLintelAcademic Building |
| 62 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorLintel'Entrance Gate With Security Post With Cow Catcher. |
| 63 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorChajjaAcademic Building'Entrance Gate With Security Post With Cow Catcher. |
| 64 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorChajja'Entrance Gate With Security Post With Cow Catcher. |
| 65 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorStair caseAcademic Building |
| 66 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorStair caseLAB 4 NOS & CANTEEN BUILDING |
| 67 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorR.C.C Wall'Entrance Gate With Security Post With Cow Catcher. |
| 68 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorCow Catcher Raft'Entrance Gate With Security Post With Cow Catcher. |
| 69 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Ground FloorCow Catcher Wall'Entrance Gate With Security Post With Cow Catcher. |
| 70 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.First FloorColumnAcademic BuildingLAB 4 NOS & CANTEEN BUILDING |
| 71 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.First FloorColumnLAB 4 NOS & CANTEEN BUILDING |
| 72 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.First FloorRoof BeamAcademic BuildingLAB 4 NOS & CANTEEN BUILDING |
| 73 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.First FloorRoof BeamAcademic BuildingLAB 4 NOS & CANTEEN BUILDING |
| 74 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.First FloorRoof SlabAcademic Building |
| 75 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.First FloorRoof SlabLAB 4 NOS & CANTEEN BUILDING |
| 76 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.First FloorLintelAcademic Building |
| 77 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.First FloorLintelLAB 4 NOS & CANTEEN BUILDING |
| 78 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.First FloorChajjaAcademic Building |
| 79 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.First FloorChajjaLAB 4 NOS & CANTEEN BUILDING |
| 80 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.First FloorChajjaStair case |
| 81 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Terrace FloorColumnAcademic Building |
| 82 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Terrace FloorRoof BeamAcademic Building |
| 83 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Terrace FloorRoof SlabAcademic Building |
| 84 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Terrace FloorLintelAcademic Building |
| 85 | R.C.C. work M-20 grade with 20mm and down grade black hard granite crusher broken stone chips including hoisting and laying.Terrace FloorChajjaAcademic Building |
| 86 | A/R-P 52/item No.9:Supplying, fitting and placing un-coated HYSD bar reinforcement complete as per drawing and technical specification Ground FloorAcademic Building |
| 87 | A/R-P 52/item No.9:Supplying, fitting and placing un-coated HYSD bar reinforcement complete as per drawing and technical specification Ground FloorLAB 4 NOS & CANTEEN BUILDING |
| 88 | A/R-P 52/item No.9:Supplying, fitting and placing un-coated HYSD bar reinforcement complete as per drawing and technical specification Ground FloorCar Parking Shed |
| 89 | A/R-P 52/item No.9:Supplying, fitting and placing un-coated HYSD bar reinforcement complete as per drawing and technical specification Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 90 | A/R-P 52/item No.9:Supplying, fitting and placing un-coated HYSD bar reinforcement complete as per drawing and technical specification First FloorAcademic Building |
| 91 | A/R-P 52/item No.9:Supplying, fitting and placing un-coated HYSD bar reinforcement complete as per drawing and technical specification First FloorLAB 4 NOS & CANTEEN BUILDING |
| 92 | A/R-P 52/item No.9:Supplying, fitting and placing un-coated HYSD bar reinforcement complete as per drawing and technical specification Terrace FloorAcademic Building |
| 93 | 12mm thick cement plaster (1:4) over brick with cement punnig for exernal wallGround FloorAcademic Building |
| 94 | 12mm thick cement plaster (1:4) over brick with cement punnig for exernal wallGround FloorCar Parking Shed |
| 95 | 12mm thick cement plaster (1:4) over brick with cement punnig for exernal wallGround Floor'Entrance Gate With Security Post With Cow Catcher. |
| 96 | 12mm thick cement plaster (1:6) on brick work.Ground FloorAcademic Building |
| 97 | 12mm thick cement plaster (1:6) on brick work.Ground FloorCar Parking Shed |
| 98 | 12mm thick cement plaster (1:6) on brick work.Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 99 | 12mm thick cement plaster (1:6) on brick work.First FloorAcademic Building |
| 100 | 12mm thick cement plaster (1:6) on brick work.First FloorLAB 4 NOS & CANTEEN BUILDING |
| 101 | 12mm thick cement plaster (1:6) on brick work.Terrace FloorAcademic Building |
| 102 | 6mm thick cement plaster (1:4) to R.C.C. surfaces finished smooth including deep chiping and slury treatement.Ground FloorAcademic Building |
| 103 | 6mm thick cement plaster (1:4) to R.C.C. surfaces finished smooth including deep chiping and slury treatement.Ground FloorLAB 4 NOS & CANTEEN BUILDING |
| 104 | 6mm thick cement plaster (1:4) to R.C.C. surfaces finished smooth including deep chiping and slury treatement.Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 105 | 6mm thick cement plaster (1:4) to R.C.C. surfaces finished smooth including deep chiping and slury treatement.First FloorAcademic Building |
| 106 | 6mm thick cement plaster (1:4) to R.C.C. surfaces finished smooth including deep chiping and slury treatement.First FloorLAB 4 NOS & CANTEEN BUILDING |
| 107 | 6mm thick cement plaster (1:4) to R.C.C. surfaces finished smooth including deep chiping and slury treatement.Terrace FloorAcademic Building |
| 108 | 16mm thick cement plaster (1:6) over brick or stone masonry.Ground FloorAcademic Building |
| 109 | 16mm thick cement plaster (1:6) over brick or stone masonry.Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 110 | 16mm thick cement plaster (1:6) over brick or stone masonry.Ground FloorCar Parking Shed |
| 111 | 16mm thick cement plaster (1:6) over brick or stone masonry.First FloorAcademic Building |
| 112 | 16mm thick cement plaster (1:6) over brick or stone masonry.First FloorLAB 4 NOS & CANTEEN BUILDING |
| 113 | 16mm thick cement plaster (1:6) over brick or stone masonry.Terrace FloorAcademic Building |
| 114 | Finishing plastered surfaces of walls with Cement based Putty & making smooth to receive painting including cost of Birla Putty.Ground FloorAcademic Building |
| 115 | Finishing plastered surfaces of walls with Cement based Putty & making smooth to receive painting including cost of Birla Putty.Ground FloorLAB 4 NOS & CANTEEN BUILDING |
| 116 | Finishing plastered surfaces of walls with Cement based Putty & making smooth to receive painting including cost of Birla Putty.Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 117 | Finishing plastered surfaces of walls with Cement based Putty & making smooth to receive painting including cost of Birla Putty.First FloorAcademic Building |
| 118 | Finishing plastered surfaces of walls with Cement based Putty & making smooth to receive painting including cost of Birla Putty.First FloorLAB 4 NOS & CANTEEN BUILDING |
| 119 | Finishing plastered surfaces of walls with Cement based Putty & making smooth to receive painting including cost of Birla Putty.Terrace FloorAcademic Building |
| 120 | Providing and applying 2 coats plastic emulsion paint of approved quality and shade over a coat of wall primer of approved quality to surfaces (interior) including throughly brushing the surface free from foreign materials, sand papering smooth the intermediate coats, providing necessary putty & primer including of all materials, labour, conveyance, ,, royalties, scaffolding, watering, curing, sundries, tools and plants etc as per the direction of Engineer-in-charge. (colour & shade to be approved before procurment & use)Ground FloorAcademic Building |
| 121 | Providing and applying 2 coats plastic emulsion paint of approved quality and shade over a coat of wall primer of approved quality to surfaces (interior) including throughly brushing the surface free from foreign materials, sand papering smooth the intermediate coats, providing necessary putty & primer including of all materials, labour, conveyance, ,, royalties, scaffolding, watering, curing, sundries, tools and plants etc as per the direction of Engineer-in-charge. (colour & shade to be approved before procurment & use)Ground FloorLAB 4 NOS & CANTEEN BUILDING |
| 122 | Providing and applying 2 coats plastic emulsion paint of approved quality and shade over a coat of wall primer of approved quality to surfaces (interior) including throughly brushing the surface free from foreign materials, sand papering smooth the intermediate coats, providing necessary putty & primer including of all materials, labour, conveyance, ,, royalties, scaffolding, watering, curing, sundries, tools and plants etc as per the direction of Engineer-in-charge. (colour & shade to be approved before procurment & use)Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 123 | Providing and applying 2 coats plastic emulsion paint of approved quality and shade over a coat of wall primer of approved quality to surfaces (interior) including throughly brushing the surface free from foreign materials, sand papering smooth the intermediate coats, providing necessary putty & primer including of all materials, labour, conveyance, ,, royalties, scaffolding, watering, curing, sundries, tools and plants etc as per the direction of Engineer-in-charge. (colour & shade to be approved before procurment & use)First FloorAcademic Building |
| 124 | Providing and applying 2 coats plastic emulsion paint of approved quality and shade over a coat of wall primer of approved quality to surfaces (interior) including throughly brushing the surface free from foreign materials, sand papering smooth the intermediate coats, providing necessary putty & primer including of all materials, labour, conveyance, ,, royalties, scaffolding, watering, curing, sundries, tools and plants etc as per the direction of Engineer-in-charge. (colour & shade to be approved before procurment & use)First FloorLAB 4 NOS & CANTEEN BUILDING |
| 125 | Providing and applying 2 coats plastic emulsion paint of approved quality and shade over a coat of wall primer of approved quality to surfaces (interior) including throughly brushing the surface free from foreign materials, sand papering smooth the intermediate coats, providing necessary putty & primer including of all materials, labour, conveyance, ,, royalties, scaffolding, watering, curing, sundries, tools and plants etc as per the direction of Engineer-in-charge. (colour & shade to be approved before procurment & use)Terrace FloorAcademic Building |
| 126 | Providing and Painting with Two Coats of Acrylic Smooth exterior paint of approved make & shade manufactured by reputed manufacturer like NEROLAC / ASIAN / BERGER / DULOX or equivalent to make an even finished surface over a coat of water bound cement primer in all heights with all scaffolding and staging charges including cost, conveyance, , of all materials, cost of all labours, T & P, sundries etc. as required for the work complete.Ground FloorAcademic Building |
| 127 | Providing and Painting with Two Coats of Acrylic Smooth exterior paint of approved make & shade manufactured by reputed manufacturer like NEROLAC / ASIAN / BERGER / DULOX or equivalent to make an even finished surface over a coat of water bound cement primer in all heights with all scaffolding and staging charges including cost, conveyance, , of all materials, cost of all labours, T & P, sundries etc. as required for the work complete.Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 128 | Providing and Painting with Two Coats of Acrylic Smooth exterior paint of approved make & shade manufactured by reputed manufacturer like NEROLAC / ASIAN / BERGER / DULOX or equivalent to make an even finished surface over a coat of water bound cement primer in all heights with all scaffolding and staging charges including cost, conveyance, , of all materials, cost of all labours, T & P, sundries etc. as required for the work complete.Ground FloorCar Parking Shed |
| 129 | Providing and Painting with Two Coats of Acrylic Smooth exterior paint of approved make & shade manufactured by reputed manufacturer like NEROLAC / ASIAN / BERGER / DULOX or equivalent to make an even finished surface over a coat of water bound cement primer in all heights with all scaffolding and staging charges including cost, conveyance, , of all materials, cost of all labours, T & P, sundries etc. as required for the work complete.First FloorAcademic Building |
| 130 | Providing and Painting with Two Coats of Acrylic Smooth exterior paint of approved make & shade manufactured by reputed manufacturer like NEROLAC / ASIAN / BERGER / DULOX or equivalent to make an even finished surface over a coat of water bound cement primer in all heights with all scaffolding and staging charges including cost, conveyance, , of all materials, cost of all labours, T & P, sundries etc. as required for the work complete.First FloorLAB 4 NOS & CANTEEN BUILDING |
| 131 | Providing and Painting with Two Coats of Acrylic Smooth exterior paint of approved make & shade manufactured by reputed manufacturer like NEROLAC / ASIAN / BERGER / DULOX or equivalent to make an even finished surface over a coat of water bound cement primer in all heights with all scaffolding and staging charges including cost, conveyance, , of all materials, cost of all labours, T & P, sundries etc. as required for the work complete.Terrace FloorAcademic Building |
| 132 | Providing and Applying 1 coats of water bound cement primer over plaster surface including the cost of all material & labour all finishes as per the direction of Engineer-in-Charge.Ground FloorCar Parking Shed |
| 133 | Supplying, fitting & fixing of 8-10 mm thick & size of 600x600 mm vertified floor tile of with veilcraft (VC/FT ) shield( Scratch free/stain free) with water absorption limit between 0.08% to 3% and conforming to IS : 15622:2006 (Group B Ib). laid on 20 mm thick cement mortar (1:4) (1 cement : 4 course sand) and filling joints with white cement of approved quality including cost of all materials, labour T&P etc. required for the work all complete as per direction of the Engineer-in-charge (for New Work only )Ground FloorAcademic Building |
| 134 | Supplying, fitting & fixing of 8-10 mm thick & size of 600x600 mm vertified floor tile of with veilcraft (VC/FT ) shield( Scratch free/stain free) with water absorption limit between 0.08% to 3% and conforming to IS : 15622:2006 (Group B Ib). laid on 20 mm thick cement mortar (1:4) (1 cement : 4 course sand) and filling joints with white cement of approved quality including cost of all materials, labour T&P etc. required for the work all complete as per direction of the Engineer-in-charge (for New Work only )Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 135 | Supplying, fitting & fixing of 8-10 mm thick & size of 600x600 mm vertified floor tile of with veilcraft (VC/FT ) shield( Scratch free/stain free) with water absorption limit between 0.08% to 3% and conforming to IS : 15622:2006 (Group B Ib). laid on 20 mm thick cement mortar (1:4) (1 cement : 4 course sand) and filling joints with white cement of approved quality including cost of all materials, labour T&P etc. required for the work all complete as per direction of the Engineer-in-charge (for New Work only )First FloorAcademic Building |
| 136 | Supplying, fitting & fixing of 8-10 mm thick & size of 600x600 mm vertified floor tile of with veilcraft (VC/FT ) shield( Scratch free/stain free) with water absorption limit between 0.08% to 3% and conforming to IS : 15622:2006 (Group B Ib). laid on 20 mm thick cement mortar (1:4) (1 cement : 4 course sand) and filling joints with white cement of approved quality including cost of all materials, labour T&P etc. required for the work all complete as per direction of the Engineer-in-charge (for New Work only )First FloorLAB 4 NOS & CANTEEN BUILDING |
| 137 | Providing & Fixing Vitrified Tiles in Dados skirting and risers of steps on 12 mm thick cement plaster (1:3) Jointed with Neat cement slurry mixed with pigments to match the shade of the tiles including rubbing and polishing complete as per the direction of Engineer-In-Charge.Ground FloorAcademic Building |
| 138 | Providing & Fixing Vitrified Tiles in Dados skirting and risers of steps on 12 mm thick cement plaster (1:3) Jointed with Neat cement slurry mixed with pigments to match the shade of the tiles including rubbing and polishing complete as per the direction of Engineer-In-Charge.Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 139 | Providing & Fixing Vitrified Tiles in Dados skirting and risers of steps on 12 mm thick cement plaster (1:3) Jointed with Neat cement slurry mixed with pigments to match the shade of the tiles including rubbing and polishing complete as per the direction of Engineer-In-Charge.First FloorAcademic Building |
| 140 | Providing & Fixing Vitrified Tiles in Dados skirting and risers of steps on 12 mm thick cement plaster (1:3) Jointed with Neat cement slurry mixed with pigments to match the shade of the tiles including rubbing and polishing complete as per the direction of Engineer-In-Charge.First FloorLAB 4 NOS & CANTEEN BUILDING |
| 141 | Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. including cost of all materials with ,, transportation, all labour, sundries, T&P etc. complete as per direction of Engineer in charge.Ground FloorAcademic Building |
| 142 | Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. including cost of all materials with ,, transportation, all labour, sundries, T&P etc. complete as per direction of Engineer in charge.Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 143 | Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. including cost of all materials with ,, transportation, all labour, sundries, T&P etc. complete as per direction of Engineer in charge.First FloorAcademic Building |
| 144 | Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. including cost of all materials with ,, transportation, all labour, sundries, T&P etc. complete as per direction of Engineer in charge.First FloorLAB 4 NOS & CANTEEN BUILDING |
| 145 | Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. including cost of all materials with ,, transportation, all labour, sundries, T&P etc. complete as per direction of Engineer in charge.Terrace FloorAcademic Building |
| 146 | Supplying, fitting and fixing of three track UPVC sliding window of approved make with 6mm thick glass of approved quality complete with frame, shutters and all fitting and fixtures.Ground FloorAcademic Building |
| 147 | Supplying, fitting and fixing of three track UPVC sliding window of approved make with 6mm thick glass of approved quality complete with frame, shutters and all fitting and fixtures.First FloorAcademic Building |
| 148 | Supplying, fitting and fixing of three track UPVC sliding window of approved make with 6mm thick glass of approved quality complete with frame, shutters and all fitting and fixtures.First FloorLAB 4 NOS & CANTEEN BUILDING |
| 149 | Supplying , fitting and fixing of two track UPVC sliding window of approved make with 6mm thick glass of approved quality complete with frame, shutters and all fitting and fixtures.'Entrance Gate With Security Post With Cow Catcher. |
| 150 | Providing and fixing of Fixed Glazing with part Top hung of approved make to be fabricated from roll formed sections made of pre-painted steel (base steel as per IS-513 of 0.6 mm thick D quality, galvanized as per IS-277 with zinc of 120 Gm/Sq.mtr) with paint specification being with primer of 5-7 microns and finished paint with polyster paint (Black /Pearl white/ Chocolate Brown) of 12-16 microns alongwith the alkyd backer at the back of 5-7 microns and the sizes of outer frame being of 46x52 mm and with all vertical and horizontal mullions are of 46x70 mm and fixed beadings are of 18x25 mm. Top hung shutter should be of 46 x 46 mm. Accessories / gaskets are to be used as per the manufacturer s supply and specification like handle being made of high grade aluminium powder coated and with nylon receiver and gasket will be made of EPDM. All corner brackets are to be made of CRCA with zinc phosphating. The mullion caps and louvere d-clips should be of glass filled nylon. The sections are to be cut to length ,mitre joined with corner bracket and frames are fixed to the concrete/masonry walls by means of self expanding screws and glass to be used of 5 mm reflective with all taxes complete.Ground FloorAcademic Building |
| 151 | Providing and fixing of Fixed Glazing with part Top hung of approved make to be fabricated from roll formed sections made of pre-painted steel (base steel as per IS-513 of 0.6 mm thick D quality, galvanized as per IS-277 with zinc of 120 Gm/Sq.mtr) with paint specification being with primer of 5-7 microns and finished paint with polyster paint (Black /Pearl white/ Chocolate Brown) of 12-16 microns alongwith the alkyd backer at the back of 5-7 microns and the sizes of outer frame being of 46x52 mm and with all vertical and horizontal mullions are of 46x70 mm and fixed beadings are of 18x25 mm. Top hung shutter should be of 46 x 46 mm. Accessories / gaskets are to be used as per the manufacturer s supply and specification like handle being made of high grade aluminium powder coated and with nylon receiver and gasket will be made of EPDM. All corner brackets are to be made of CRCA with zinc phosphating. The mullion caps and louvere d-clips should be of glass filled nylon. The sections are to be cut to length ,mitre joined with corner bracket and frames are fixed to the concrete/masonry walls by means of self expanding screws and glass to be used of 5 mm reflective with all taxes complete.First FloorAcademic Building |
| 152 | Providing and fixing of Fixed Glazing with part Top hung of approved make to be fabricated from roll formed sections made of pre-painted steel (base steel as per IS-513 of 0.6 mm thick D quality, galvanized as per IS-277 with zinc of 120 Gm/Sq.mtr) with paint specification being with primer of 5-7 microns and finished paint with polyster paint (Black /Pearl white/ Chocolate Brown) of 12-16 microns alongwith the alkyd backer at the back of 5-7 microns and the sizes of outer frame being of 46x52 mm and with all vertical and horizontal mullions are of 46x70 mm and fixed beadings are of 18x25 mm. Top hung shutter should be of 46 x 46 mm. Accessories / gaskets are to be used as per the manufacturer s supply and specification like handle being made of high grade aluminium powder coated and with nylon receiver and gasket will be made of EPDM. All corner brackets are to be made of CRCA with zinc phosphating. The mullion caps and louvere d-clips should be of glass filled nylon. The sections are to be cut to length ,mitre joined with corner bracket and frames are fixed to the concrete/masonry walls by means of self expanding screws and glass to be used of 5 mm reflective with all taxes complete.Terrace FloorAcademic Building |
| 153 | Painting two coats of synthetic enamel paint over Iron Works as per approved shade of approved quality over a coat of primer, sand papering, polishing the surface including cost, conveyance, ,, materials, labour, T&P, scaffolding etc. as required for the work complete as per direction of Engineer-in-charge. (The paints and primer are to be approved before procurement and use)Ground FloorAcademic Building |
| 154 | Painting two coats of synthetic enamel paint over Iron Works as per approved shade of approved quality over a coat of primer, sand papering, polishing the surface including cost, conveyance, ,, materials, labour, T&P, scaffolding etc. as required for the work complete as per direction of Engineer-in-charge. (The paints and primer are to be approved before procurement and use)First FloorAcademic Building |
| 155 | Painting two coats of synthetic enamel paint over Iron Works as per approved shade of approved quality over a coat of primer, sand papering, polishing the surface including cost, conveyance, ,, materials, labour, T&P, scaffolding etc. as required for the work complete as per direction of Engineer-in-charge. (The paints and primer are to be approved before procurement and use)First FloorLAB 4 NOS & CANTEEN BUILDING |
| 156 | Painting two coats of synthetic enamel paint over Iron Works as per approved shade of approved quality over a coat of primer, sand papering, polishing the surface including cost, conveyance, ,, materials, labour, T&P, scaffolding etc. as required for the work complete as per direction of Engineer-in-charge. (The paints and primer are to be approved before procurement and use)Terrace FloorAcademic Building |
| 157 | Supplying and fixing W.I. clamps 33cm to 38cm long of 35mm x 5mm size for doors and windows and ventilators including fixing in cement concrete (1:3:6) with 12 mm. to 20mm hard stone chips or in cement mortar (1:3) including cost of all materials.(SOR-2022 Item no.14 Page no.221)Ground FloorAcademic Building |
| 158 | Supplying and fixing W.I. clamps 33cm to 38cm long of 35mm x 5mm size for doors and windows and ventilators including fixing in cement concrete (1:3:6) with 12 mm. to 20mm hard stone chips or in cement mortar (1:3) including cost of all materials.(SOR-2022 Item no.14 Page no.221)First FloorAcademic Building |
| 159 | Supplying and fixing W.I. clamps 33cm to 38cm long of 35mm x 5mm size for doors and windows and ventilators including fixing in cement concrete (1:3:6) with 12 mm. to 20mm hard stone chips or in cement mortar (1:3) including cost of all materials.(SOR-2022 Item no.14 Page no.221)First FloorLAB 4 NOS & CANTEEN BUILDING |
| 160 | Providing & Fixinng factory made 100% Solid WPC (Wood Polymer Composite) - Door Frame 125 mm x 65 mm Single Rebated, made from Wood Polymer Composite (Single Extruded Process) material comparising of virgin PVC polymer of K Value 57-60 (Suspension Grade ), Calcium Carbonate and Natural Fibers Wood Powder/ Rice Husk/ Wheat Husk) and Non toxic additives fabricated with meter Joints after applying PVC solvent Cement & screwed with full body treaded star headed screws having minimum frame density of 780 kg/ cbm & an ISO 9001- 2015 Certified Company, having good screw holding capacity (Screw Withdrawal strength of (Min. 990 N ), Minimum Compressive Strength of 58 N/mm2, Modulus of elasticity 900N/mm2 and resistance to spread of flame of class A category with property of being termite / borer proof, water/Moisture Proof & Fire retardant & Fixed in position with SS Dash Fasteners / Hold Fast of reuired dia and lenght,, all as per specifications drawings as directed by the Engineer-In-Charge. Material test certificate and authentication should be compulsory provided by the manufacturing companyGround FloorAcademic Building |
| 161 | Providing & Fixinng factory made 100% Solid WPC (Wood Polymer Composite) - Door Frame 125 mm x 65 mm Single Rebated, made from Wood Polymer Composite (Single Extruded Process) material comparising of virgin PVC polymer of K Value 57-60 (Suspension Grade ), Calcium Carbonate and Natural Fibers Wood Powder/ Rice Husk/ Wheat Husk) and Non toxic additives fabricated with meter Joints after applying PVC solvent Cement & screwed with full body treaded star headed screws having minimum frame density of 780 kg/ cbm & an ISO 9001- 2015 Certified Company, having good screw holding capacity (Screw Withdrawal strength of (Min. 990 N ), Minimum Compressive Strength of 58 N/mm2, Modulus of elasticity 900N/mm2 and resistance to spread of flame of class A category with property of being termite / borer proof, water/Moisture Proof & Fire retardant & Fixed in position with SS Dash Fasteners / Hold Fast of reuired dia and lenght,, all as per specifications drawings as directed by the Engineer-In-Charge. Material test certificate and authentication should be compulsory provided by the manufacturing companyFirst FloorAcademic Building |
| 162 | Providing & Fixinng factory made 100% Solid WPC (Wood Polymer Composite) - Door Frame 125 mm x 65 mm Single Rebated, made from Wood Polymer Composite (Single Extruded Process) material comparising of virgin PVC polymer of K Value 57-60 (Suspension Grade ), Calcium Carbonate and Natural Fibers Wood Powder/ Rice Husk/ Wheat Husk) and Non toxic additives fabricated with meter Joints after applying PVC solvent Cement & screwed with full body treaded star headed screws having minimum frame density of 780 kg/ cbm & an ISO 9001- 2015 Certified Company, having good screw holding capacity (Screw Withdrawal strength of (Min. 990 N ), Minimum Compressive Strength of 58 N/mm2, Modulus of elasticity 900N/mm2 and resistance to spread of flame of class A category with property of being termite / borer proof, water/Moisture Proof & Fire retardant & Fixed in position with SS Dash Fasteners / Hold Fast of reuired dia and lenght,, all as per specifications drawings as directed by the Engineer-In-Charge. Material test certificate and authentication should be compulsory provided by the manufacturing companyFirst FloorAcademic BuildingLAB 4 NOS & CANTEEN BUILDING |
| 163 | Supplying fitting & fixing of 32mm thick BWR flash Door shutter using both side pastong of 1mm thick laminated sheet (texture finish) of teakwood beading on edge including cost of all materials,Labour T&P etc.Ground FloorAcademic Building |
| 164 | Supplying fitting & fixing of 32mm thick BWR flash Door shutter using both side pastong of 1mm thick laminated sheet (texture finish) of teakwood beading on edge including cost of all materials,Labour T&P etc.Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 165 | Supplying fitting & fixing of 32mm thick BWR flash Door shutter using both side pastong of 1mm thick laminated sheet (texture finish) of teakwood beading on edge including cost of all materials,Labour T&P etc.First FloorAcademic Building |
| 166 | Supplying fitting & fixing of 32mm thick BWR flash Door shutter using both side pastong of 1mm thick laminated sheet (texture finish) of teakwood beading on edge including cost of all materials,Labour T&P etc.First FloorLAB 4 NOS & CANTEEN BUILDING |
| 167 | Painting two coats of synthetic enamel paint over Wood Works as per approved shade of approved quality over a coat of primer, sand papering, polishing the surface including cost, conveyance, ,, materials, labour, T&P, scaffolding etc. as required for the work complete as per direction of Engineer-in-charge. (The paints and primer are to be approved before procurement and use)Ground FloorAcademic Building |
| 168 | Painting two coats of synthetic enamel paint over Wood Works as per approved shade of approved quality over a coat of primer, sand papering, polishing the surface including cost, conveyance, ,, materials, labour, T&P, scaffolding etc. as required for the work complete as per direction of Engineer-in-charge. (The paints and primer are to be approved before procurement and use)First FloorAcademic Building |
| 169 | Painting two coats of synthetic enamel paint over Wood Works as per approved shade of approved quality over a coat of primer, sand papering, polishing the surface including cost, conveyance, ,, materials, labour, T&P, scaffolding etc. as required for the work complete as per direction of Engineer-in-charge. (The paints and primer are to be approved before procurement and use)First FloorLAB 4 NOS & CANTEEN BUILDING |
| 170 | Supplying, fitting and fixing Industrial vitrified tile laid on 20 mm thick cement mortar (1:4) (1 cement : 4 coarse sand) and filling joints with white cement of approved quality including cost of all materials, labour T&P etc required for the work all complete as per direction of Engineer-in-charge.Ground FloorAcademic Building |
| 171 | Supplying, fitting and fixing Industrial vitrified tile laid on 20 mm thick cement mortar (1:4) (1 cement : 4 coarse sand) and filling joints with white cement of approved quality including cost of all materials, labour T&P etc required for the work all complete as per direction of Engineer-in-charge.Ground FloorLAB 4 NOS & CANTEEN BUILDING |
| 172 | Supplying, fitting and fixing Industrial vitrified tile laid on 20 mm thick cement mortar (1:4) (1 cement : 4 coarse sand) and filling joints with white cement of approved quality including cost of all materials, labour T&P etc required for the work all complete as per direction of Engineer-in-charge.First FloorAcademic Building |
| 173 | Providing & Fixing Industrial vitrified wall tiles in Dados skirting and risers of steps on 12 mm thick cement plaster (1:3) Jointed with Neat cement slurry mixed with pigments to match the shade of the tiles including rubbing and polishing complete as per the direction of Engineer-In-Charge.Ground FloorAcademic Building |
| 174 | Providing & Fixing Industrial vitrified wall tiles in Dados skirting and risers of steps on 12 mm thick cement plaster (1:3) Jointed with Neat cement slurry mixed with pigments to match the shade of the tiles including rubbing and polishing complete as per the direction of Engineer-In-Charge.Ground FloorLAB 4 NOS & CANTEEN BUILDING |
| 175 | Providing & Fixing Industrial vitrified wall tiles in Dados skirting and risers of steps on 12 mm thick cement plaster (1:3) Jointed with Neat cement slurry mixed with pigments to match the shade of the tiles including rubbing and polishing complete as per the direction of Engineer-In-Charge.First FloorAcademic Building |
| 176 | Supplying fitting and fixing of stainless steel of 304 grade in hand railing using 50mm dia of 2mm thick circular pipe with Balustrade of size 32mm x 32mm x 2mm @ 0.90 mtrs C/C and stainless square pipe bracing of size 32mm x 32mm x 2mm in 3 rows in staircase as per approved design and specification, buffing, polishing etc with coist, conveyance, taxes of all materials, labour and T&P required for the work all complete in all respect .Ground FloorAcademic Building |
| 177 | Supplying fitting and fixing of stainless steel of 304 grade in hand railing using 50mm dia of 2mm thick circular pipe with Balustrade of size 32mm x 32mm x 2mm @ 0.90 mtrs C/C and stainless square pipe bracing of size 32mm x 32mm x 2mm in 3 rows in staircase as per approved design and specification, buffing, polishing etc with coist, conveyance, taxes of all materials, labour and T&P required for the work all complete in all respect .Ground FloorLAB 4 NOS & CANTEEN BUILDING |
| 178 | Supplying fitting and fixing of stainless steel of 304 grade in hand railing using 50mm dia of 2mm thick circular pipe with Balustrade of size 32mm x 32mm x 2mm @ 0.90 mtrs C/C and stainless square pipe bracing of size 32mm x 32mm x 2mm in 3 rows in staircase as per approved design and specification, buffing, polishing etc with coist, conveyance, taxes of all materials, labour and T&P required for the work all complete in all respect .First FloorAcademic Building |
| 179 | A/R-P 218/item No.16:Dismantling G.C.I., or A.C. sheet roofing after carefully removing the bolts and nuts including stacking of the materials for reuse and removing the debris within 50 meter lead.Ground FloorAcademic Building |
| 180 | A/R-P 221/item No.24:Dismantling & removing R.C.C. Columns, beams,slab, staircase landing lintels includingstacking the useful material for reuse and removing the debris within 50 meter lead.Ground FloorAcademic Building |
| 181 | A/R-P 214/item No.3:Dismantling brickwork, stone Masonry in Cement mortar under 3meter height including stacking the useful material for reuse and removing the debris within 50 meter lead.Ground FloorAcademic Building |
| 182 | A/R-P 219/item No.18:Dismantling and removing doors, windows, and ventilaters after carefully removing the bolts and nuts including stacking of the materials for reuse and removing the debris within 50 meter lead.Ground FloorAcademic Building |
| 183 | A/R-P 221/item No.23:Dismantling and removing cement concrete including stacking of the materials for reuse and removing the debris within 50 meter lead. Per 1 Cum Ground Floor Academic Building |
| 184 | Providing average 25mm thick grading Concrete in C.C ( 1:2:2 ) using 6mm size crusher broken black hard granite chips using 2% water proofing cement compound of approved quality over top of Roof, Terrace, including cost of scaffolding, scraping and cleaning the roof surface and finishing smooth to proper slope and gradient including cost of all materials, conveyance, , and sundries,T&P watering and curing by ponding water over terrace slab etc. complete as per the direction of the Engineer-in-charge.First FloorAcademic Building |
| 185 | Providing average 25mm thick grading Concrete in C.C ( 1:2:2 ) using 6mm size crusher broken black hard granite chips using 2% water proofing cement compound of approved quality over top of Roof, Terrace, including cost of scaffolding, scraping and cleaning the roof surface and finishing smooth to proper slope and gradient including cost of all materials, conveyance, , and sundries,T&P watering and curing by ponding water over terrace slab etc. complete as per the direction of the Engineer-in-charge.First FloorLAB 4 NOS & CANTEEN BUILDING |
| 186 | Providing two coats of Water proofing painting with 100% Dr. Fixit MR and sika Guard -625 exterior grade with melamine polish and A1 thineer of approved make & shade manufactured of approved shade to make an even finished surface in all floor and heights with all scaffolding and staging charges including cost conveyance,taxes of all materials,coast of all labours,T&P,Sundries etc as requird for the work complet in all respect as per direction of Engineer-in-charge.First FloorLAB 4 NOS & CANTEEN BUILDING |
| 187 | Supplying fitting and fixing of Chequerred tiles in floors off approved make laid on 20 mm thick cement mortar (1:4) (1 cement :4 course sand) and filling joints with white cement of approved quality including cost of all materials, labour T&P etc are required for the work all complete as per direction of Engineer-in-Charge. (For New work only)Car Parking Shed |
| 188 | Loosening,leveling and compacting original ground supporting embankment to facilitate placement of first layer of embankment, scarified to a depth of 150 mm mixed with water at OMC and then compacted by Vibratory Road Roller so as to achive minimum dry density to meet the requirement of Table-300.2 and as per Clause 305 of MoRT&H Specifications for Road & Bridge works(4th Revision) including cost, conveyance, Royalities, Taxes of all materials,all labours,hire and running charges of all machineries,T&P ,sundries etc. complete as per spcification and direction of Engineer-in-Charge.Area Development |
| 189 | Construction of GSB by providing close graded GSB grading-VI materials as per Table 400-1, spreading in uniform layers with mortar grader on prepared surface mixing by mix in place method with rotavator at OMC and compacting with V.R.R to achieve the desired density complete as epr clause No.401 of MORT&H specification for road & Bridge work (4th revision)Area Development |
| 190 | Supplying and fixing of Pre cast kerb stone of size 600mm x 300mm x 150mm of M-30 grade of approved make, design, colour and size made by Block making machine with proper compaction fixed in required pattern etc. complete in all respect conforming to IS 5758:1984.Area Development |
| 191 | Supplying and fixing of 60mm thick cement concrete interlocking paver block of M-30 grade of approved make, design, colour and size made by Block making machine with proper compaction laid in required pattern etc. complete in all respect conforming to IRC SP-63:2018. Area Development |
| 192 | Painting on concrete surface Providing and applying 2 coats of water based cement paint to unplastered concrete surface after cleaning the surface of dirt, dust, oil, grease, efflorescence and applying paint @ of 1 litre for 2 sqm. Area Development |
| 193 | Priming one coat with approved Wood Primer on wood work in Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 194 | Priming one coat with approved Red Oxide Primer on Steel work in Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 195 | Painting two coats with approved Enamel Paint on wood work and Steel work in Ground Floor'Entrance Gate With Security Post With Cow Catcher. |
| 196 | Supplying, fitting & fixing Vetrified industrial floor Tile of premium grade having thickness 8mm to 10mm confirming to IS 4457 of size 300mmx300mm of with veilcraft (VC/FT ) shield( Scratch free/stain free) with water absorption limit between 0.08% to 3% and conforming to IS : 15622:2006 (Group B Ib). laid on 20 mm thick cement mortar (1:4) (1 cement : 4 course sand) and filling joints with white cement of approved quality including cost of all materials, labour T&P etc. required for the work all complete as per direction of the Engineer-in-charge (for New Work only )'Entrance Gate With Security Post With Cow Catcher. |
| 197 | Providing & Fixing Granite Tiles of Above 0.10 Sqm & up to 0.4 Sqm (10mm.thick) wall tiles in Dados skirting and risers of steps on 12 mm thick cement plaster (1:3) Jointed with Neat cement slurry mixed with pigments to match the shade of the tiles including rubbing and polishing complete as per the direction of Engineer-In-Charge.'Entrance Gate With Security Post With Cow Catcher. |
| 198 | Providing & Fixing of WPC boards of sizes as mentioned below along with 3D letters inlay on the same with the required letters to be approved by the Architect/ EIC. Samples have to be approved by the concernd before execution. The rate is inclusive of the WPC board with fixing of the same along with Rates, Taxes, T&P all inclusive. 'Entrance Gate With Security Post With Cow Catcher. |
| 199 | Distempering 2-coat to walls with distemper of approved shade on old/new work to give on even shade excluding cost of distemper.Car Parking Shed |
| 200 | ELECTRICAL WORKSINTERNAL ELECTRICAL WorksRecessed wirring to light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor of ISI marked Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/Vguard with 20 mm dia HMS FRLS PVC conduit ISI marked Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal 6A modular type ( flame retradant type) switch ISI marked Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) and ceiling rose ISI marked of modular type G.I box with metallic cover plate (both side) Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) of suitable size, modular box with 1.5 sq. Mm FRLS PVC insulated single core multistandard copper conductor as earth wire including all accessories and connection as per direction of Engineer -in -Charge. . All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials.NB:All the electrical,Fire fighting,HVAC,ELV drawings, Technical Data Sheets & make will be approved by SE R& B Electrical circle & CE Building ,Odisha ,Bhubaneswar prior to execution of the work. GROUP-ALABORATORY |
| 201 | Recessed wirring to light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor of ISI marked Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/Vguard with 20 mm dia HMS FRLS PVC conduit ISI marked Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal 6A modular type ( flame retradant type) switch ISI marked Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) and ceiling rose ISI marked of modular type G.I box with metallic cover plate (both side) Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) of suitable size, modular box with 1.5 sq. Mm FRLS PVC insulated single core multistandard copper conductor as earth wire including all accessories and connection as per direction of Engineer -in -Charge. . All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials.NB:All the electrical,Fire fighting,HVAC,ELV drawings, Technical Data Sheets & make will be approved by SE R& B Electrical circle & CE Building ,Odisha ,Bhubaneswar prior to execution of the work. GROUP-AACADEMIC BUILDING |
| 202 | Recessed wirring to light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor of ISI marked Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/Vguard with 20 mm dia HMS FRLS PVC conduit ISI marked Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal 6A modular type ( flame retradant type) switch ISI marked Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) and ceiling rose ISI marked of modular type G.I box with metallic cover plate (both side) Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) of suitable size, modular box with 1.5 sq. Mm FRLS PVC insulated single core multistandard copper conductor as earth wire including all accessories and connection as per direction of Engineer -in -Charge. . All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials.NB:All the electrical,Fire fighting,HVAC,ELV drawings, Technical Data Sheets & make will be approved by SE R& B Electrical circle & CE Building ,Odisha ,Bhubaneswar prior to execution of the work. GROUP-AEntrance Gate With Security Post & Car Parking |
| 203 | Recessed wirring to light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor of ISI marked Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/Vguard with 20 mm dia HMS FRLS PVC conduit ISI marked Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal 6A modular type ( flame retradant type) switch ISI marked Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) and ceiling rose ISI marked of modular type G.I box with metallic cover plate (both side) Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) of suitable size, modular box with 1.5 sq. Mm FRLS PVC insulated single core multistandard copper conductor as earth wire including all accessories and connection as per direction of Engineer -in -Charge. . All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials.NB:All the electrical,Fire fighting,HVAC,ELV drawings, Technical Data Sheets & make will be approved by SE R& B Electrical circle & CE Building ,Odisha ,Bhubaneswar prior to execution of the work. GROUP-BLABORATORY |
| 204 | Recessed wirring to light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor of ISI marked Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/Vguard with 20 mm dia HMS FRLS PVC conduit ISI marked Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal 6A modular type ( flame retradant type) switch ISI marked Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) and ceiling rose ISI marked of modular type G.I box with metallic cover plate (both side) Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) of suitable size, modular box with 1.5 sq. Mm FRLS PVC insulated single core multistandard copper conductor as earth wire including all accessories and connection as per direction of Engineer -in -Charge. . All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials.NB:All the electrical,Fire fighting,HVAC,ELV drawings, Technical Data Sheets & make will be approved by SE R& B Electrical circle & CE Building ,Odisha ,Bhubaneswar prior to execution of the work. GROUP-BACADEMIC BUILDING |
| 205 | Recessed wirring to light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor of ISI marked Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/Vguard with 20 mm dia HMS FRLS PVC conduit ISI marked Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal 6A modular type ( flame retradant type) switch ISI marked Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) and ceiling rose ISI marked of modular type G.I box with metallic cover plate (both side) Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) of suitable size, modular box with 1.5 sq. Mm FRLS PVC insulated single core multistandard copper conductor as earth wire including all accessories and connection as per direction of Engineer -in -Charge. . All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials.NB:All the electrical,Fire fighting,HVAC,ELV drawings, Technical Data Sheets & make will be approved by SE R& B Electrical circle & CE Building ,Odisha ,Bhubaneswar prior to execution of the work. GROUP-BEntrance Gate With Security Post & Car Parking |
| 206 | Recessed wirring to light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor of ISI marked Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/Vguard with 20 mm dia HMS FRLS PVC conduit ISI marked Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal 6A modular type ( flame retradant type) switch ISI marked Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) and ceiling rose ISI marked of modular type G.I box with metallic cover plate (both side) Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) of suitable size, modular box with 1.5 sq. Mm FRLS PVC insulated single core multistandard copper conductor as earth wire including all accessories and connection as per direction of Engineer -in -Charge. . All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials.NB:All the electrical,Fire fighting,HVAC,ELV drawings, Technical Data Sheets & make will be approved by SE R& B Electrical circle & CE Building ,Odisha ,Bhubaneswar prior to execution of the work. GROUP-CLABORATORY |
| 207 | Recessed wirring to light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor of ISI marked Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/Vguard with 20 mm dia HMS FRLS PVC conduit ISI marked Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal 6A modular type ( flame retradant type) switch ISI marked Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) and ceiling rose ISI marked of modular type G.I box with metallic cover plate (both side) Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) of suitable size, modular box with 1.5 sq. Mm FRLS PVC insulated single core multistandard copper conductor as earth wire including all accessories and connection as per direction of Engineer -in -Charge. . All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials.NB:All the electrical,Fire fighting,HVAC,ELV drawings, Technical Data Sheets & make will be approved by SE R& B Electrical circle & CE Building ,Odisha ,Bhubaneswar prior to execution of the work. GROUP-CACADEMIC BUILDING |
| 208 | Recessed wirring to light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor of ISI marked Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/Vguard with 20 mm dia HMS FRLS PVC conduit ISI marked Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal 6A modular type ( flame retradant type) switch ISI marked Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) and ceiling rose ISI marked of modular type G.I box with metallic cover plate (both side) Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) of suitable size, modular box with 1.5 sq. Mm FRLS PVC insulated single core multistandard copper conductor as earth wire including all accessories and connection as per direction of Engineer -in -Charge. . All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials.NB:All the electrical,Fire fighting,HVAC,ELV drawings, Technical Data Sheets & make will be approved by SE R& B Electrical circle & CE Building ,Odisha ,Bhubaneswar prior to execution of the work. GROUP-CEntrance Gate With Security Post & Car Parking |
| 209 | Supplying ,fixing of 6A Plug on the same board in existing switch board with complete fitting by 01 no of 6A switch & socket (modular type) & other required accessories of ISI marked as approved as per direction of Engg. -in -Charge. Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) .All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials.LABORATORY |
| 210 | Supplying ,fixing of 6A Plug on the same board in existing switch board with complete fitting by 01 no of 6A switch & socket (modular type) & other required accessories of ISI marked as approved as per direction of Engg. -in -Charge. Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) .All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials.ACADEMIC BUILDING |
| 211 | Supplying ,fixing of 6A Plug on the same board in existing switch board with complete fitting by 01 no of 6A switch & socket (modular type) & other required accessories of ISI marked as approved as per direction of Engg. -in -Charge. Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) .All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials.Entrance Gate With Security Post & Car Parking |
| 212 | Supplying,fixing of 6A Plug on the separate board with complete fitting by 01 no of 6A switch & socket(modular type) with suitable size modular box & cover including supplying of all required accessories of ISI marked as approved as per direction of engg-in-charge..Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) .All the switches & sockets should be warrantied for a period of 2 years against manufacturing defects against which ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials.LABORATORY |
| 213 | Supplying,fixing of 6A Plug on the separate board with complete fitting by 01 no of 6A switch & socket(modular type) with suitable size modular box & cover including supplying of all required accessories of ISI marked as approved as per direction of engg-in-charge..Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) .All the switches & sockets should be warrantied for a period of 2 years against manufacturing defects against which ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials.ACADEMIC BUILDING |
| 214 | Supplying,fixing of 6A Plug on the separate board with complete fitting by 01 no of 6A switch & socket(modular type) with suitable size modular box & cover including supplying of all required accessories of ISI marked as approved as per direction of engg-in-charge..Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) .All the switches & sockets should be warrantied for a period of 2 years against manufacturing defects against which ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials.Entrance Gate With Security Post & Car Parking |
| 215 | Supplying,fixing of 1x16A Plug on the separate board with complete fitting by 01 no of 16A switch & socket(modular type) with suitable size modular box & cover including supplying of all required accessories of ISI marked as approved as per direction of engg-in-charge.. Make-Schneider(Zencelo)/legrand( Myrius)/Panasonic (vision) (For equipement power)All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials.LABORATORY |
| 216 | Supplying,fixing of 1x16A Plug on the separate board with complete fitting by 01 no of 16A switch & socket(modular type) with suitable size modular box & cover including supplying of all required accessories of ISI marked as approved as per direction of engg-in-charge.. Make-Schneider(Zencelo)/legrand( Myrius)/Panasonic (vision) (For equipement power)All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials.ACADEMIC BUILDING |
| 217 | Supplying,fixing of 1x16A Plug on the separate board with complete fitting by 01 no of 16A switch & socket(modular type) with suitable size modular box & cover including supplying of all required accessories of ISI marked as approved as per direction of engg-in-charge.. Make-Schneider(Zencelo)/legrand( Myrius)/Panasonic (vision) (For equipement power)All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials.Entrance Gate With Security Post & Car Parking |
| 218 | Supply and fixing of ISI marked modular type 2nos 6Amp socket with switch on suitable size of metal box and modular cover in front on surface or recess including all conection as per direction of E.I.C. All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials. (Make :Legrand(Myrius)/-Schneider(Zencelo)/PANASONIC(VISION)LABORATORY |
| 219 | Supply and fixing of ISI marked modular type 2nos 6Amp socket with switch on suitable size of metal box and modular cover in front on surface or recess including all conection as per direction of E.I.C. All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials. (Make :Legrand(Myrius)/-Schneider(Zencelo)/PANASONIC(VISION)ACADEMIC BUILDING |
| 220 | Supply and fixing of ISI marked modular type 2nos 6Amp socket with switch on suitable size of metal box and modular cover in front on surface or recess including all conection as per direction of E.I.C. All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials. (Make :Legrand(Myrius)/-Schneider(Zencelo)/PANASONIC(VISION)Entrance Gate With Security Post & Car Parking |
| 221 | Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/V Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge. 2 nos single core 1.5 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor. In 20 mm dia non metallic heavy duty conduit (LDB to LSB/LIGHT CKT)LABORATORY |
| 222 | Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/V Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge. 2 nos single core 1.5 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor. In 20 mm dia non metallic heavy duty conduit (LDB to LSB/LIGHT CKT)Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/V Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge. 2 nos single core 1.5 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor. In 20 mm dia non metallic heavy duty conduit (LDB to LSB/LIGHT CKT)ACADEMIC BUILDING |
| 223 | Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/V Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge. 2 nos single core 1.5 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor. In 20 mm dia non metallic heavy duty conduit (LDB to LSB/LIGHT CKT)Entrance Gate With Security Post & Car Parking |
| 224 | Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI V Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.2 nos single core 2.5 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor in 20 mm dia non metallic heavy duty conduit.(BDB to LSB/LIGHT CKT/5A PLUG/UPS POINT ) LABORATORY |
| 225 | Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI V Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.2 nos single core 2.5 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor in 20 mm dia non metallic heavy duty conduit.(BDB to LSB/LIGHT CKT/5A PLUG/UPS POINT ) |
| 226 | Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI V Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.2 nos single core 2.5 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor in 20 mm dia non metallic heavy duty conduit.(BDB to LSB/LIGHT CKT/5A PLUG/UPS POINT ) Entrance Gate With Security Post & Car Parking |
| 227 | Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEIV Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.2 nos single core 4 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor in 20 mm dia non metallic heavy duty conduit .(PDB to PSB/ POWER POINT/AC POINT) LABORATORY |
| 228 | Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEIV Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.2 nos single core 4 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor in 20 mm dia non metallic heavy duty conduit .(PDB to PSB/ POWER POINT/AC POINT) ACADEMIC BUILDING |
| 229 | Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEIV Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.2 nos single core 4 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor in 20 mm dia non metallic heavy duty conduit .(PDB to PSB/ POWER POINT/AC POINT) Entrance Gate With Security Post & Car Parking |
| 230 | Receass wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/V Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.2 nos single core 6 sq. mm copper wire for phase and neutral and 01 nos of single core 4 sq. mm copper wire for earth continuty conductor in 25 mm dia non metallic heavy duty conduit.LABORATORY |
| 231 | Receass wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/V Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.2 nos single core 6 sq. mm copper wire for phase and neutral and 01 nos of single core 4 sq. mm copper wire for earth continuty conductor in 25 mm dia non metallic heavy duty conduit.ACADEMIC BUILDING |
| 232 | Receass wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/V Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.2 nos single core 6 sq. mm copper wire for phase and neutral and 01 nos of single core 4 sq. mm copper wire for earth continuty conductor in 25 mm dia non metallic heavy duty conduit.Entrance Gate With Security Post & Car Parking |
| 233 | Receass wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/V Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.4 nos single core 6 sq. mm copper wire for phase and neutral and 02 nos of single core 4 sq. mm copper wire for earth continuty conductor in 32 mm dia non metallic heavy duty conduit.LABORATORY |
| 234 | Receass wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/V Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.4 nos single core 6 sq. mm copper wire for phase and neutral and 02 nos of single core 4 sq. mm copper wire for earth continuty conductor in 32 mm dia non metallic heavy duty conduit.ACADEMIC BUILDING |
| 235 | Receass wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI /V Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.4 nos single core 10 sq. mm copper wire for phase and neutral and 02 nos of single core 6 sq. mm copper wire for earth continuty conductorin 32 mm dia non metallic heavy duty conduit .LABORATORY |
| 236 | Receass wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI /V Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.4 nos single core 10 sq. mm copper wire for phase and neutral and 02 nos of single core 6 sq. mm copper wire for earth continuty conductorin 32 mm dia non metallic heavy duty conduit .ACADEMIC BUILDING |
| 237 | Supplying and installation of AC Point having 16-20A DP MCB, C series with enclosure, Schneider/Siemens/Legrand/ABB of suitable size as required as per direction of Engg.-in-Charge .All the Components should be warrantied for a replacement period of 1 year against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials.LABORATORY |
| 238 | Supply and fixing CALL bell (Ding dong type) /Buzzer on the existing switch box/cover.Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) as required as per direction of Engg.-in-Charge.All the Components should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials.LABORATORY |
| 239 | Sub-Head II (Light fitting Fixture & Fan)Supplying, installation, testing and commssioning of 1200 mm sweep white/milky colour BLDC copper winding ceiling fan with aluminium blades having wattage not more than 28W and air delivery 215m3/min Make-Crompton Energion Groove /Havells Efficiencia Neo/Usha Technix/Bajaj Turbo Pro 12DC5 ) including wiring the down rod of standard length (upto 30 cm) with 1.5 sq mm PVC insulated, copper conductor, single core cable etc. as required as per direction of Engg.-in-Charge,Replacement Warranty will be 4 years.(With fan Regulator) LABORATORY |
| 240 | Supplying, installation, testing and commssioning of 1200 mm sweep white/milky colour BLDC copper winding ceiling fan with aluminium blades having wattage not more than 28W and air delivery 215m3/min Make-Crompton Energion Groove /Havells Efficiencia Neo/Usha Technix/Bajaj Turbo Pro 12DC5 ) including wiring the down rod of standard length (upto 30 cm) with 1.5 sq mm PVC insulated, copper conductor, single core cable etc. as required as per direction of Engg.-in-Charge,Replacement Warranty will be 4 years.(With fan Regulator) ACADEMIC BUILDING |
| 241 | Supplying, installation, testing and commssioning of 1200 mm sweep white/milky colour BLDC copper winding ceiling fan with aluminium blades having wattage not more than 28W and air delivery 215m3/min Make-Crompton Energion Groove /Havells Efficiencia Neo/Usha Technix/Bajaj Turbo Pro 12DC5 ) including wiring the down rod of standard length (upto 30 cm) with 1.5 sq mm PVC insulated, copper conductor, single core cable etc. as required as per direction of Engg.-in-Charge,Replacement Warranty will be 4 years.(With fan Regulator) Entrance Gate With Security Post & Car Parking |
| 242 | Supplying, installation, of exhaust fan of heavy duty 300 mm sweep 1400 rpm with louvers (Make- Havells/Crompton/Usha/Orient/Bajaj ) of exhaust fan in the existing wall, including fixing & conntection as required as per direction of Engg.-in-Charge. Replacement Warranty will be 2 years.ACADEMIC BUILDING |
| 243 | SITC Of 4Ft surface mounted/suspended Single Piece Constructed CRCA LED TUBE BATTEN required pre-wired terminal one side with body earthing provision - along with mounting of 1No.s Essential Glass T8 Base Tube 2200Lumen Pack,Efficacy >110Lm/W, 20Watt,CRI >=80, PF >0.9, CCT 4K, IP20, 25K Burning Hours Temp -20To45Degree,CE marking RoHS compliance KEMA Keur certificate.(Make: Panasonic/LT/Havells /Philips((TMC502 1xT-LED 22W))/Wipro /Crompton/Bajaj).The luminaire should be Replacement Warranty will be 2 years.for all Hostel Room & Corrider.LABORATORY |
| 244 | SITC Of 4Ft surface mounted/suspended Single Piece Constructed CRCA LED TUBE BATTEN required pre-wired terminal one side with body earthing provision - along with mounting of 1No.s Essential Glass T8 Base Tube 2200Lumen Pack,Efficacy >110Lm/W, 20Watt,CRI >=80, PF >0.9, CCT 4K, IP20, 25K Burning Hours Temp -20To45Degree,CE marking RoHS compliance KEMA Keur certificate.(Make: Panasonic/LT/Havells /Philips((TMC502 1xT-LED 22W))/Wipro /Crompton/Bajaj).The luminaire should be Replacement Warranty will be 2 years.for all Hostel Room & Corrider.ACADEMIC BUILDING |
| 245 | SITC Of 4Ft surface mounted/suspended Single Piece Constructed CRCA LED TUBE BATTEN required pre-wired terminal one side with body earthing provision - along with mounting of 1No.s Essential Glass T8 Base Tube 2200Lumen Pack,Efficacy >110Lm/W, 20Watt,CRI >=80, PF >0.9, CCT 4K, IP20, 25K Burning Hours Temp -20To45Degree,CE marking RoHS compliance KEMA Keur certificate.(Make: Panasonic/LT/Havells /Philips((TMC502 1xT-LED 22W))/Wipro /Crompton/Bajaj).The luminaire should be Replacement Warranty will be 2 years.for all Hostel Room & Corrider.Entrance Gate With Security Post & Car Parking |
| 246 | Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as requiredas required as per direction of Engg.-in-Charge .(Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)of ISI mark as approved.LABORATORY |
| 247 | Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as requiredas required as per direction of Engg.-in-Charge .(Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)of ISI mark as approved.ACADEMIC BUILDING |
| 248 | Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as requiredas required as per direction of Engg.-in-Charge .(Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)of ISI mark as approved.Entrance Gate With Security Post & Car Parking |
| 249 | S/F of 5 step type Modular electronic Fan Regulator ISI Marked with all connection complete in all respect as per direction of Engineer in charge ( Make-Schneider(Zencelo)/legrand( Myrius)/Panasonic (vision) LABORATORY |
| 250 | S/F of 5 step type Modular electronic Fan Regulator ISI Marked with all connection complete in all respect as per direction of Engineer in charge ( Make-Schneider(Zencelo)/legrand( Myrius)/Panasonic (vision) ACADEMIC BUILDING |
| 251 | S/F of 5 step type Modular electronic Fan Regulator ISI Marked with all connection complete in all respect as per direction of Engineer in charge ( Make-Schneider(Zencelo)/legrand( Myrius)/Panasonic (vision) Entrance Gate With Security Post & Car Parking |
| 252 | Supplying and fixing 32 amps, 240 volts, SPN, industrial type socket outlet, with 2 pole+E-DP plug & socket DB with 32A DP MCB,C series,10ka as per IEC-61439-3 ,suitable for flush & surface mounting,supplied with neutral link with provission for mounting modular devices as per direction of Engg.-in-Charge. Make-Legrand/ Siemens/Schneider/ABBLABORATORY |
| 253 | Supplying and fixing of Energy efficient surface /recess mounted square /round shape 18 W LED luminaire of dimension of consists of white powder coated , die-cast Alluminium housing with high quality frosted diffuser for glare-free uniform lighting distribution with wattage not more than 18 watt and lumen output of 1800 lumens, , CRI not less than 80,CCT of 6000 degree K,THD less than 10%, with electronic driver, internal surge protection of 3 KV , L70 B50: 50000 hrs and all other accessories suitable for operation on 220 V to 240 V supply as required as per direction of Engg.-in-Charge. (Make: Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj).The luminaire should be Replacement Warranty will be 2 years.To be used in corridor, rooms, toilet areaACADEMIC BUILDING |
| 254 | Supplying and fixing of Energy efficient surface /recess mounted square /round shape 18 W LED luminaire of dimension of consists of white powder coated , die-cast Alluminium housing with high quality frosted diffuser for glare-free uniform lighting distribution with wattage not more than 18 watt and lumen output of 1800 lumens, , CRI not less than 80,CCT of 6000 degree K,THD less than 10%, with electronic driver, internal surge protection of 3 KV , L70 B50: 50000 hrs and all other accessories suitable for operation on 220 V to 240 V supply as required as per direction of Engg.-in-Charge. (Make: Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj).The luminaire should be Replacement Warranty will be 2 years.To be used in corridor, rooms, toilet areaEntrance Gate With Security Post & Car Parking |
| 255 | SITC of Sleek LED 10 watt mirror light fitting with extruded polycarbonate housing,High optically efficient diffuser,above wash basin complete with all accessoriesetc. directly on wall, including connection with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required as per direction of Engg.-in-Charge. (Make: Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj)The luminaire should be Replacement Warranty will be 2 yearsACADEMIC BUILDING |
| 256 | BDBS,DB,AC DB,FLOOR PANELS,MCBSSupplying and fixing of following mentioned way, three pole/single pole and neutral, sheet steel,double door MCB distribution board, 415 volts/240 volts shall be as per IEC 61439-3,integrated door earthing system offering additional safety to the user,High quality polyurethane Gasket,the box and cover shall be fabricated to withstand IK09,the DB should be properly pre-treated with 7 tank process and duly powder coated, phosphatized with powder coated finish, on surface/recess, complete with terminal blocks,with suitable size FR PVC insulated copper conducter up to terminal blocks, tinned copper busbar, neutral busbar, earth bar, din bar. Make-LEGRAND-Ekinox3 DB/ Siemens-Betaguard/ Schneider- Acti 9/ABB Itus as per direction of Engg.-in-Charge. The Distribution boards should be Replacement Warranty will be 3 years4 Way(8+12) Way TPN MCB DD DB Horizontal Type as per IEC 61439-3 suitable for Flush mounting and Surface mounting with 100A Copper Bus Bar for each phase, with neutral Bus bar, Earth Bar & Cable ties for cable management, prefitted masking sheet, IP43-IK09 with metal door Warranty on DB is 3 years.2 Nos For PDB & ACDB, 1Nos For UPS DB LABORATORY |
| 257 | BDBS,DB,AC DB,FLOOR PANELS,MCBSSupplying and fixing of following mentioned way, three pole/single pole and neutral, sheet steel,double door MCB distribution board, 415 volts/240 volts shall be as per IEC 61439-3,integrated door earthing system offering additional safety to the user,High quality polyurethane Gasket,the box and cover shall be fabricated to withstand IK09,the DB should be properly pre-treated with 7 tank process and duly powder coated, phosphatized with powder coated finish, on surface/recess, complete with terminal blocks,with suitable size FR PVC insulated copper conducter up to terminal blocks, tinned copper busbar, neutral busbar, earth bar, din bar. Make-LEGRAND-Ekinox3 DB/ Siemens-Betaguard/ Schneider- Acti 9/ABB Itus as per direction of Engg.-in-Charge. The Distribution boards should be Replacement Warranty will be 3 years4 Way(8+12) Way TPN MCB DD DB Horizontal Type as per IEC 61439-3 suitable for Flush mounting and Surface mounting with 100A Copper Bus Bar for each phase, with neutral Bus bar, Earth Bar & Cable ties for cable management, prefitted masking sheet, IP43-IK09 with metal door Warranty on DB is 3 years.2 Nos For PDB & ACDB, 1Nos For UPS DB ACADEMIC BUILDING |
| 258 | Supply and fixing of 12 way DD single pole and neutral sheet steel MCB distribution board 250V on surface/recess complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, detachable gland plate, interconnections, phosphatized and powder painted including earthing etc. as required (but with out MCB/ RCCB/ Isolator) Warranty on DB is 3 years. FOR LDB & UDBLABORATORY |
| 259 | Supply and fixing of 12 way DD single pole and neutral sheet steel MCB distribution board 250V on surface/recess complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, detachable gland plate, interconnections, phosphatized and powder painted including earthing etc. as required (but with out MCB/ RCCB/ Isolator) Warranty on DB is 3 years. FOR LDB & UDBACADEMIC BUILDING |
| 260 | Supplying and fixing 6-32 Amps rating, C series,10KA breaking capacity,SP, 240 volts, MCB . Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge. .. The MCB should be Replacement Warranty will be 1 year..LABORATORY |
| 261 | Supplying and fixing 6-32 Amps rating, C series,10KA breaking capacity,SP, 240 volts, MCB . Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge. .. The MCB should be Replacement Warranty will be 1 year..ACADEMIC BUILDING |
| 262 | Supplying and fixing 6-32 Amps rating, C series,10KA breaking capacity,SP, 240 volts, MCB . Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge. .. The MCB should be Replacement Warranty will be 1 year..Entrance Gate With Security Post & Car Parking |
| 263 | Supplying and fixing 40 Amps rating,C series,10KA breaking capacity, 2P, 415 volts, RCCB 30mA . Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB FB 200 in the existing MCB DB complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge. . The RCCB should be Replacement Warranty will be 1 yearLABORATORY |
| 264 | Supplying and fixing 40 Amps rating,C series,10KA breaking capacity, 2P, 415 volts, RCCB 30mA . Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB FB 200 in the existing MCB DB complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge. . The RCCB should be Replacement Warranty will be 1 yearACADEMIC BUILDING |
| 265 | Supplying and fixing 40 Amps rating,C series,10KA breaking capacity, 2P, 415 volts, RCCB 30mA . Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB FB 200 in the existing MCB DB complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge. . The RCCB should be Replacement Warranty will be 1 yearEntrance Gate With Security Post & Car Parking |
| 266 | Supplying and fixing 63Amps 4P 415 volts MCB Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB in the existing MCB DB complete with connections as per direction of Engg.-in-Charge..Warranty on MCB is 1 year.LABORATORY |
| 267 | Supplying and fixing 63Amps 4P 415 volts MCB Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB in the existing MCB DB complete with connections as per direction of Engg.-in-Charge..Warranty on MCB is 1 year.ACADEMIC BUILDING |
| 268 | Supplying and fixing 63Amps 4P 415 volts RCCB 30 mA Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB FB 200 in the existing MCB DB complete with connections as per direction of Engg.-in-Charge..The RCCB should be Replacement Warranty will be 1 year.LABORATORY |
| 269 | Supplying and fixing 63Amps 4P 415 volts RCCB 30 mA Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB FB 200 in the existing MCB DB complete with connections as per direction of Engg.-in-Charge..The RCCB should be Replacement Warranty will be 1 year.ACADEMIC BUILDING |
| 270 | Supplying and fixing 63Amps DP 230 volts,10KA C series MCB Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB in the existing MCB DB complete with connections as per direction of Engg.-in-Charge. The MCB should be Replacement Warranty will be 1 yearsLABORATORY |
| 271 | Supplying and fixing 63Amps DP 230 volts,10KA C series MCB Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB in the existing MCB DB complete with connections as per direction of Engg.-in-Charge. The MCB should be Replacement Warranty will be 1 yearsACADEMIC BUILDING |
| 272 | Supplying and fixing 32Amps DP 230 volts,10KA C series MCB Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB in the existing MCB DB complete with connections as per direction of Engg.-in-Charge. The MCB should be Replacement Warranty will be 1 yearsLABORATORY |
| 273 | Supplying and fixing 32Amps DP 230 volts,10KA C series MCB Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB in the existing MCB DB complete with connections as per direction of Engg.-in-Charge. The MCB should be Replacement Warranty will be 1 yearsACADEMIC BUILDING |
| 274 | 2+4 way MCB Enclosure DB (GLAZED door)(only each EM. CONNECTION UPS LOAD)Warranty on DB is 3 years Entrance Gate With Security Post & Car Parking(EARTHING) INSTALLATION |
| 275 | Supplying,installation,testing & commissioning of materials and installation of GI earth plate 600mmx600mmx6mm thick ISI marked with G. I. nut bolts & washers including cost of burnt wood charcoal, salt, foreign soil, water pouring arrangements, brick masonary enclosure on top with removable RCC cover complete with labour for excavation of pit in all kinds of soil & rock as required and as per direction of Engineer-in-charge.LABORATORY |
| 276 | Supplying,installation,testing & commissioning of materials and installation of GI earth plate 600mmx600mmx6mm thick ISI marked with G. I. nut bolts & washers including cost of burnt wood charcoal, salt, foreign soil, water pouring arrangements, brick masonary enclosure on top with removable RCC cover complete with labour for excavation of pit in all kinds of soil & rock as required and as per direction of Engineer-in-charge.ACADEMIC BUILDING |
| 277 | Supplying,installation,testing & commissioning of materials and installation of GI earth plate 600mmx600mmx6mm thick ISI marked with G. I. nut bolts & washers including cost of burnt wood charcoal, salt, foreign soil, water pouring arrangements, brick masonary enclosure on top with removable RCC cover complete with labour for excavation of pit in all kinds of soil & rock as required and as per direction of Engineer-in-charge.Entrance Gate With Security Post & Car Parking |
| 278 | Providing and fixing 25mm x 5 mm GI strip on surface or in recess for connections etc. as required as per direction of Engg.-in-Charge. LABORATORY |
| 279 | Providing and fixing 25mm x 5 mm GI strip on surface or in recess for connections etc. as required as per direction of Engg.-in-Charge. ACADEMIC BUILDING |
| 280 | Providing and fixing 25mm x 5 mm GI strip on surface or in recess for connections etc. as required as per direction of Engg.-in-Charge. Entrance Gate With Security Post & Car Parking |
| 281 | Providing and fixing 50mm x 6 mm GI strip on surface or in recess for connections etc. as required as per direction of Engg.-in-Charge. LABORATORY |
| 282 | Providing and fixing 50mm x 6 mm GI strip on surface or in recess for connections etc. as required as per direction of Engg.-in-Charge. ACADEMIC BUILDING |
| 283 | Providing and fixing 50mm x 6 mm GI strip on surface or in recess for connections etc. as required as per direction of Engg.-in-Charge. Entrance Gate With Security Post & Car Parking |
| 284 | CABLING AND END TERMINATION MAIN AREASupplying of one number PVC insulated armoured and PVC sheathed XLPE property AL. conductor power cable of 1.1 KV grade Make- Finolex/Polycab/HAVELLS/RR KABLE/KEI/Gloster of following size cables as per direction of Engg.-in-Charge. 3.5core x 70 sq mmLABORATORY |
| 285 | Supplying of one number PVC insulated armoured and PVC sheathed XLPE property AL. conductor power cable of 1.1 KV grade Make- Finolex/Polycab/HAVELLS/RR KABLE/KEI/Gloster of following size cables as per direction of Engg.-in-Charge. 3.5core x 70 sq mmACADEMIC BUILDING |
| 286 | Supplying of one number PVC insulated armoured and PVC sheathed XLPE property AL. conductor power cable of 1.1 KV grade Make- Finolex/Polycab/HAVELLS/RR KABLE/KEI/Gloster of following size cables as per direction of Engg.-in-Charge. 3.5core x 35 sq mmLABORATORY |
| 287 | Supplying of one number PVC insulated armoured and PVC sheathed XLPE property AL. conductor power cable of 1.1 KV grade Make- Finolex/Polycab/HAVELLS/RR KABLE/KEI/Gloster of following size cables as per direction of Engg.-in-Charge. 3.5core x 35 sq mmACADEMIC BUILDING |
| 288 | Supplying of one number PVC insulated armoured and PVC sheathed XLPE property AL. conductor power cable of 1.1 KV grade Make- Finolex/Polycab/HAVELLS/RR KABLE/KEI/Gloster of following size cables as per direction of Engg.-in-Charge. 4core x 16 sq mm LABORATORY |
| 289 | Supplying of one number PVC insulated armoured and PVC sheathed XLPE property AL. conductor power cable of 1.1 KV grade Make- Finolex/Polycab/HAVELLS/RR KABLE/KEI/Gloster of following size cables as per direction of Engg.-in-Charge. 4core x 16 sq mm ACADEMIC BUILDING |
| 290 | Supplying of one number PVC insulated armoured and PVC sheathed XLPE property AL. conductor power cable of 1.1 KV grade Make- Finolex/Polycab/HAVELLS/RR KABLE/KEI/Gloster of following size cables as per direction of Engg.-in-Charge. Entrance Gate With Security Post & Car Parking |
| 291 | LAYING OF CABLELaying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 25 SQ. MM direct in ground in the trench in one horizental formation including excavation ,sand coushing protection covering and refilling the trench etc as required as per direction of Engg.-in -charge.LABORATORY |
| 292 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 25 SQ. MM direct in ground in the trench in one horizental formation including excavation ,sand coushing protection covering and refilling the trench etc as required as per direction of Engg.-in -charge.ACADEMIC BUILDING |
| 293 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 25 SQ. MM direct in ground in the trench in one horizental formation including excavation ,sand coushing protection covering and refilling the trench etc as required as per direction of Engg.-in -charge.Entrance Gate With Security Post & Car Parking |
| 294 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size exceeding 25 SQ. MM but not exceeding 120 SQ. MM direct in ground in the trench in one horizental formation including excavation ,sand coushing protection covering and refilling the trench etc as required as per direction of Engg.-in -charge.LABORATORY |
| 295 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size exceeding 25 SQ. MM but not exceeding 120 SQ. MM direct in ground in the trench in one horizental formation including excavation ,sand coushing protection covering and refilling the trench etc as required as per direction of Engg.-in -charge.ACADEMIC BUILDING |
| 296 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 25 SQ. MM in surface with shaddle and screw etc as required as per direction of Engg.-in -charge.LABORATORY |
| 297 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 25 SQ. MM in surface with shaddle and screw etc as required as per direction of Engg.-in -charge.ACADEMIC BUILDING |
| 298 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 25 SQ. MM in surface with shaddle and screw etc as required as per direction of Engg.-in -charge.Entrance Gate With Security Post & Car Parking |
| 299 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 120 SQ. MM From 25 SQ. MM in surface with shaddle and screw etc as required as per direction of Engg.-in -charge.LABORATORY |
| 300 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 120 SQ. MM From 25 SQ. MM in surface with shaddle and screw etc as required as per direction of Engg.-in -charge.ACADEMIC BUILDING |
| 301 | Supplying and making end termination with double brass compression gland and aluminium lugs for following mentioned size cable.as per direction of Engg.-in-Charge. 4 core x16sq mmLABORATORY |
| 302 | Supplying and making end termination with double brass compression gland and aluminium lugs for following mentioned size cable.as per direction of Engg.-in-Charge. 4 core x16sq mmACADEMIC BUILDING |
| 303 | Supplying and making end termination with double brass compression gland and aluminium lugs for following mentioned size cable.as per direction of Engg.-in-Charge. 3.5 core x35 sq mmLABORATORY |
| 304 | Supplying and making end termination with double brass compression gland and aluminium lugs for following mentioned size cable.as per direction of Engg.-in-Charge. 3.5 core x35 sq mmACADEMIC BUILDING |
| 305 | Supplying and making end termination with double brass compression gland and aluminium lugs for following mentioned size cable.as per direction of Engg.-in-Charge. 3.5 core x70sq mmLABORATORY |
| 306 | Supplying and making end termination with double brass compression gland and aluminium lugs for following mentioned size cable.as per direction of Engg.-in-Charge. 3.5 core x70sq mmACADEMIC BUILDING |
| 307 | Providing,fixing and laying of following dia G.I. pipe (medium class) in ground complete with G.I fitting incl. trenching(75 mm depth)and refilling as per direction of Engg.-in-Charge. 50 mm diaLABORATORY |
| 308 | Providing,fixing and laying of following dia G.I. pipe (medium class) in ground complete with G.I fitting incl. trenching(75 mm depth)and refilling as per direction of Engg.-in-Charge. 50 mm diaACADEMIC BUILDING |
| 309 | Providing,fixing and laying of following dia G.I. pipe (medium class) in ground complete with G.I fitting incl. trenching(75 mm depth)and refilling as per direction of Engg.-in-Charge. 50 mm diaEntrance Gate With Security Post & Car Parking |
| 310 | Providing,fixing and laying of fallowing dia HDPE pipe (medium class) in ground complete with fitting incl. trenching(75 mm depth)and refilling as per direction of Engg.-in-Charge. 200 mm diaLABORATORY |
| 311 | Providing,fixing and laying of fallowing dia HDPE pipe (medium class) in ground complete with fitting incl. trenching(75 mm depth)and refilling as per direction of Engg.-in-Charge. 200 mm diaACADEMIC BUILDING |
| 312 | PANELS MAIN CONTROL PANEL S/I/T&Commissioning of Main LT indoor floor mounted CPRI Tested cubical type Main panel made out by 2mm CRCA steel sheet duly derusted & painted by simens grey powder cote paint is designed as G.A drawing.as per direction of Engg.-in-Charge. Warrentee period of replacement of panel & accessories must be 1 year & compelete test certificate must be submitted along with panel board including component list. 40X10MM Separate Aluminium Earth bus bar should be installed.All the incomers shall have 65 kA 3P+N type 1+2 SPD with 63 A 4P MCB, C series, 10 kA. Mandatory provision of cable alley is to be given. ON/OFF/TRIP indication shall be given for all the feeders.LABORATORY |
| 313 | S/I/T&Commissioning of Main LT indoor floor mounted CPRI Tested cubical type Main panel made out by 2mm CRCA steel sheet duly derusted & painted by simens grey powder cote paint is designed as G.A drawing.as per direction of Engg.-in-Charge. Warrentee period of replacement of panel & accessories must be 1 year & compelete test certificate must be submitted along with panel board including component list. 40X10MM Separate Aluminium Earth bus bar should be installed.All the incomers shall have 65 kA 3P+N type 1+2 SPD with 63 A 4P MCB, C series, 10 kA. Mandatory provision of cable alley is to be given. ON/OFF/TRIP indication shall be given for all the feeders.ACADEMIC BUILDING |
| 314 | In commer-1-01 number of 200A 4P Icu=100%Ics,50Ka LSIG MCCB with micro processor based release ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider-CVS/ ABB FormulaBusbar- 04 numbers of 300Amps aluminium busbar with 1A/SQ.MM current carring capacity. busbar duly sleeved by color coated PVC sleeve & supported by suitable size DMC insulator. Out going- 04 numbers of 63A 4P MCCB,25Ka MCCB withTMR based release with adjustable overload ,Icu=100%Ics( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ABB FORMULA)DG In commer-2- 01 no of 63A 4P onload changeover switch(Make-ABB/Siemens/Schneider/LK/C&S)Out going- 1 numbers of 63A rating,10 KA breaking capacity,C series, 4P MCB(Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9//ABB SB 200) Out going- 6 numbers of 40A rating,10 KA breaking capacity,C series, DP MCB(Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9//ABB SB 200) Instrument- (i) 03 numbers phase indicating lamp with toggle switch & HRC fuse.(ii) 01 set of digital type multifunction meter with CT for voltage,current,frequency,PF,THD indication with RS 485 COMPACTIVITY FOR bms data.1 no. 3P+N 65kA type 1+2 SPD with 63A rating,10KA breaking capacity ,4P MCB (Make-LEGRAND/ Siemens/ Schneider/ABB/OBO/DEHN) (iii) All the MCCB outgoing feeders shall have digital ammeter with class 1 CT of suitable rating. Make-Legrand/ABB/Siemens/Schneider(iv) All the incoming and outgoing feeders shall have ON/OFF/TRIP indication. UPS SYSTEM (10KVA)Supply ,installation ,testing & commissioning of 10 KVA UPS SYSTEM WITH IGBT based inverter system, true online double conversion system, inbuilt isolation transformer & automatic phase sequence corrector of 3ph in put to 1 ph output,415V, with built in BMS with battery back up up to 30 minutes with MS Rack for battery Housing, DC cable 7 Mtr with SFU and links for installation (Battery required: 12V, 42AH, 20 No.s) protection for fault by OL,UV,EF,GF,OC,Ph. (Make:Numeric/APC/ Vertiv/) , as per direction of Engg.-in-Charge. Warranty period of all accessories & component & system must be 2 years & complete test certificate must be submitted along with ups including component list & SLD.LABORATORY |
| 315 | In commer-1-01 number of 200A 4P Icu=100%Ics,50Ka LSIG MCCB with micro processor based release ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider-CVS/ ABB FormulaBusbar- 04 numbers of 300Amps aluminium busbar with 1A/SQ.MM current carring capacity. busbar duly sleeved by color coated PVC sleeve & supported by suitable size DMC insulator. Out going- 04 numbers of 63A 4P MCCB,25Ka MCCB withTMR based release with adjustable overload ,Icu=100%Ics( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ABB FORMULA)DG In commer-2- 01 no of 63A 4P onload changeover switch(Make-ABB/Siemens/Schneider/LK/C&S)Out going- 1 numbers of 63A rating,10 KA breaking capacity,C series, 4P MCB(Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9//ABB SB 200) Out going- 6 numbers of 40A rating,10 KA breaking capacity,C series, DP MCB(Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9//ABB SB 200) Instrument- (i) 03 numbers phase indicating lamp with toggle switch & HRC fuse.(ii) 01 set of digital type multifunction meter with CT for voltage,current,frequency,PF,THD indication with RS 485 COMPACTIVITY FOR bms data.1 no. 3P+N 65kA type 1+2 SPD with 63A rating,10KA breaking capacity ,4P MCB (Make-LEGRAND/ Siemens/ Schneider/ABB/OBO/DEHN) (iii) All the MCCB outgoing feeders shall have digital ammeter with class 1 CT of suitable rating. Make-Legrand/ABB/Siemens/Schneider(iv) All the incoming and outgoing feeders shall have ON/OFF/TRIP indication. UPS SYSTEM (10KVA)Supply ,installation ,testing & commissioning of 10 KVA UPS SYSTEM WITH IGBT based inverter system, true online double conversion system, inbuilt isolation transformer & automatic phase sequence corrector of 3ph in put to 1 ph output,415V, with built in BMS with battery back up up to 30 minutes with MS Rack for battery Housing, DC cable 7 Mtr with SFU and links for installation (Battery required: 12V, 42AH, 20 No.s) protection for fault by OL,UV,EF,GF,OC,Ph. (Make:Numeric/APC/ Vertiv/) , as per direction of Engg.-in-Charge. Warranty period of all accessories & component & system must be 2 years & complete test certificate must be submitted along with ups including component list & SLD.ACADEMIC BUILDING |
| 316 | CABLE TRAY /RACE WAY FOR DISTRIBUTION OF POWERSupplying,fixing of perforated cable trays with horizental & vertical bends,reducers ,tees,crossover,brakets & other accessories ar requited confirming to IS-IEC -61537 ,the cable tray shall be galvanised for corrosion protection confirming to DIN EN 10346/ISO 1461. Size 60mm(H) x 200mm(W) of MAKE- Profab/OBO/Neidax.The Load bearing capacity of the Cable Trays should be minimum of 104.8Kg/meter at the span of 1.5Meter as per UL specifications as required as per direction of Engg.-in-Charge.LABORATORY |
| 317 | Supplying,fixing of perforated cable trays with horizental & vertical bends,reducers ,tees,crossover,brakets & other accessories ar requited confirming to IS-IEC -61537 ,the cable tray shall be galvanised for corrosion protection confirming to DIN EN 10346/ISO 1461. Size 60mm(H) x 200mm(W) of MAKE- Profab/OBO/Neidax.The Load bearing capacity of the Cable Trays should be minimum of 104.8Kg/meter at the span of 1.5Meter as per UL specifications as required as per direction of Engg.-in-Charge.ACADEMIC BUILDING |
| 318 | Supplying,fixing of perforated cable trays with horizental & vertical bends,reducers ,tees,crossover,brakets & other accessories ar requited confirming to IS-IEC -61537 ,the cable tray shall be galvanised for corrosion protection confirming to DIN EN 10346/ISO 1461. Size 60mm(H) x 300mm(W) of MAKE-Profab/OBO/Neidax.The Load bearing capacity of the Cable Trays should be minimum of 104.8Kg/meter at the span of 1.5Meter as per UL specifications as required as per direction of Engg.-in-Charge.LABORATORY |
| 319 | Supplying,fixing of perforated cable trays with horizental & vertical bends,reducers ,tees,crossover,brakets & other accessories ar requited confirming to IS-IEC -61537 ,the cable tray shall be galvanised for corrosion protection confirming to DIN EN 10346/ISO 1461. Size 60mm(H) x 300mm(W) of MAKE-Profab/OBO/Neidax.The Load bearing capacity of the Cable Trays should be minimum of 104.8Kg/meter at the span of 1.5Meter as per UL specifications as required as per direction of Engg.-in-Charge.ACADEMIC BUILDING |
| 320 | Lightning Protection For both Building:-Supply of 8 mm Aluminum Round Conductor.Tested as per IEC 62561. as per direction of engineer in charge.Make-OBO/Dehn/ABB |
| 321 | Supply of Roof conductor holder for parapet- Polyamide Conductor holder:With M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder.Weather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder @ 1 meter distance.Tested as per IEC 62561. as per direction of engineer in charge.Make-OBO/Dehn/ABB |
| 322 | Supply of Polyamide roof cable holder for flat roof: DIN 48829 Form B1. Closed form with bottom. Filling weight 1Kg (frost-resistant concrete). Sleeve from polyethylene, black @ 1 meter distance. Tested as per IEC 62561. Make-OBO/Dehn/ABB |
| 323 | Supply of Connector: For T cross and parallel connectors. Quickinstallation using hexagonal bolt M10X30 high-grade hot dipgalvanised. Tested as per IEC 62561.(2nos/expansion piece ).Make-OBO/Dehn/ABB |
| 324 | Supply of 1 mtr vertical air terminal with mounting accessorieson the flat surface to meet the requirements of IS/IEC 62305.Tested for Electrical , mechanical and chemical as per IEC62561. Tested for 100kA lightning current. Make-OBO/Dehn/ABB |
| 325 | Supply of Vertical air terminal with accessories:Providing of Air terminalsas per IS-IEC -62305 part-3Nominal size Ø10/16 mm aluminium rod:2 Mtr Airterminal: semi-hard (E-AlMgSiO5 corresponds to DIN48801) Suitable for high wind load.Tested as per IEC 62561. Make-OBO/Dehn/ABB |
| 326 | Supply for Providing of Stand for Fang Fix system 16 kg with base andclamp ,made up of frost resistant concrete and clamp testedupto 100KA lightning current . Make-OBO/Dehn/ABB |
| 327 | Supply for Providing of Stand for Fang Fix system 16 kg made up of frostresistant concrete. Make-OBO/Dehn/ABB |
| 328 | Supply of Test Joint (Folding Clamp) suitable to connect 8mmround conductor and max by 30x3 mm GI strip as specified indrawing and directed by Engineer.Tested for 100kA lightning current. Make-OBO/Dehn/ABB |
| 329 | Supply of IP 66 Poly Propylene Junction Box. Installation at 1Mtr HeightFor Test Joint .Internal dimensions: 100x100x48 mm Make-OBO/Dehn/ABB |
| 330 | Supply of Galvanised Steel Flat 30X3 mm thickness from earthelectrode directly in ground as required. Flat conductor HotDipped Galvanized. Tested as per IEC 62561. Make-OBO/Dehn/ABB |
| 331 | Supply for Providing of Cross connector for Flat: Suitable for 30mm Galvanised steel strip. Installed with 4 nos of hexagonal plate. Tested for 100kA lightning current. Make-OBO/Dehn/ABB |
| 332 | Supply of flat conductor holder- Fit: FL 30, With mounting hole6.2 x 22 mm, With 2 cylinder bolts M6 x 16 and over-piece fromhot-dip galvanised steel, Bottom section from polyamide, black.Tested as per IEC 62561. Make-OBO/Dehn/ABB |
| 333 | Supply for Providing of Plastic Corrosion Protection strip: Approx 1.1 mm thick. Width 50mm. Made of petrolatum- coated chemical fibre fabric. Make-OBO/Dehn/ABB |
| 334 | Supply of UL Listed maintenance free ,Low carbon coppercoated earth rod of 3 metre electrode having diameter of 17.2mm with copper coating thickness of 250micron tested as perIEC 62561-2 Make-OBO/Dehn/ABB |
| 335 | Supply of universal clamp made of SS to connect rod with flatconductor Make-OBO/Dehn/ABB |
| 336 | Supply of Earth conductivity enhancing mineral compound shall be of 25kg/pit tested as per IEC 62561-7,TCLP tested Make-OBO/Dehn/ABB |
| 337 | Supply of The above arrangements shall be provided with Heavy dutyearth champer of 5000kg load bearing capacity to ensure thesafety of earthing system Make-OBO/Dehn/ABB |
| 338 | Lightnig counter - To count no of lightning strike & it can record the date and time of the lightning incident also tested as per IEC 62561-6. Make-OBO/Dehn/ABB |
| 339 | Installation of The above arrangements including all accessories as per Direction of Engg. In charge. |
| 340 | FIRE FIGHTINGPUMPS AND APPURTENANCESSupplying, installation, testing and commissioning of Electric Motor Driven Pressurization Terrace Pump having discharge of 450 LPM at 35 Mtr head complete with Pump Set, Electric Motor suitable for operation on 415 V ,3 ph, 50 c/s AC supply , Base Frame.Make-Wilo/KSB/Kirloskar/Grundfoss |
| 341 | Supply, installation, testing and commissioning of Floor/Wall mounted sectionalised, front operated top entry dust and vermin proof M.V.Panel Boards suitable for operation at 415V, 3 phase, 4 wire, 50Hz distribution system fabricated out of 2.0 mm thick CRCA sheet, insulated busbar with heat shrienkable PVC sleeve, base frame, complete with all accessories including interconnections, earth bus etc as required comprising of One (1)- 63 Amp, 10 KA,TPN (Class-C) MCB with 3 Nos Phase indicating lamps with control fuse/ MCB, Digital Voltmeter with selector switch. DOL starter with O/L and Single Phasing Preventor suitable for 7.5 HP motor. ON/OFF indication lamps, Auto manual switch and ON/OFF push button.as per direction of engineer in charge Control panel for fire pumps for auto action.make-Legrand/schneider/Siemens/ABB |
| 342 | 1100 V GRADE POWER/CONTROL CABLES :SITC of FRLS,PVC outer sheateh, steel armoured, aluminium, 1100v grade power cables with glands etc. The minimum size of the cables shall as mentioned below as per direction of engineer in charge.Make-Polycab/Havels/KEI/RR KABEL/FINOLEX/GLOSTER |
| 343 | PIPE & VALVES ETC.Supplying, installation testing and commissioning of the following-: C class MS Pipe as per IS1239 for underground/over ground pipes with welded / flanged connection with saddles, supports (all with screwed/welded joints) as required including pipe of shorter lengths, tapering connecting pieces, short or long bends, specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. Complete to make the system operative as required by LFA / TAC authorities the pipes will have to be laid and fixed in trenches. The work includes excavation in all types of soils and back filling, dewatering, etc., making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for overheads pipes and providing and fixing pyp kote (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping for underground piping (wrapping should have overlap of 15 to 20 mm) etc.Complete as per ASTM standards/IS: 10221 for corrosion protection of pipes for the underground installation.Note: The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable codes & standard before applying paint or pipe coating or wrapping etc. complete. Make-TATA/JINDAL/SAIL100mm NB |
| 344 | Supplying, installation testing and commissioning of the following-: C class MS Pipe as per IS1239 for underground/over ground pipes with welded / flanged connection with saddles, supports (all with screwed/welded joints) as required including pipe of shorter lengths, tapering connecting pieces, short or long bends, specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. Complete to make the system operative as required by LFA / TAC authorities the pipes will have to be laid and fixed in trenches. The work includes excavation in all types of soils and back filling, dewatering, etc., making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for overheads pipes and providing and fixing pyp kote (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping for underground piping (wrapping should have overlap of 15 to 20 mm) etc.Complete as per ASTM standards/IS: 10221 for corrosion protection of pipes for the underground installation.Note: The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable codes & standard before applying paint or pipe coating or wrapping etc. complete. Make-TATA/JINDAL/SAIL80mm NB |
| 345 | Supplying, installation testing and commissioning of the following-: C class MS Pipe as per IS1239 for underground/over ground pipes with welded / flanged connection with saddles, supports (all with screwed/welded joints) as required including pipe of shorter lengths, tapering connecting pieces, short or long bends, specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. Complete to make the system operative as required by LFA / TAC authorities the pipes will have to be laid and fixed in trenches. The work includes excavation in all types of soils and back filling, dewatering, etc., making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for overheads pipes and providing and fixing pyp kote (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping for underground piping (wrapping should have overlap of 15 to 20 mm) etc.Complete as per ASTM standards/IS: 10221 for corrosion protection of pipes for the underground installation.Note: The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable codes & standard before applying paint or pipe coating or wrapping etc. complete. Make-TATA/JINDAL/SAIL25mm nb |
| 346 | Providing, fixing, testing and commissioning of following size manually operated hand lever type cast iron double flanged slim seal wafer type Butterfly valves with EPDM iron disc as per IS-13095 having pressure ratting PN -1.60 including fixing the same with supply of required jointing materials like rubber insertion, MS nuts & bolts, paint etc. and testing the joints with required water pressure etc. all complete as per specification & direction of E.I.C. Make-Zoloto/AUDCO/Leader |
| 347 | Providing, fitting & fixing of following size cast iron double flanged type dual plate Non return Valve as per IS- 5312 (Part 1): 2004 with ISI mark of pressure ratting PN-1.60 including fixing the same with supply of required jointing materials like flanges, rubber insertion, MS nuts & bolts, paint etc. and testing the joints with required water pressure etc. all complete as per specification & direction of Engineer-in-charge. Make-Zoloto/AUDCO/Leader |
| 348 | Supply,Installation,Testing & Commissioning of Pressure gauge of 0-16 Kgf/sq.cm. range with cut-off bronze ball valves of suitable size with all accessories as per direction of Engineer-in-charge.Make-H.Guru/G.Guru |
| 349 | Supply,Installation,Testing & Commissioning of Pressure Switch with cut-off bronze ball valves with integral strainer & flare nut (mixed ends) of suitable size with all accessories as per direction of Engineer-in-charge.Make-Danfoss/Indfoss/Grundfoss |
| 350 | Supply,Installation,Testing & Commissioning of stainless steel strainer fabricated out of 1.6 mm thick stainless steel sheet Y Stainer with 3 mm dia hloes with stainless steel flange as required. Make-Zoloto/AUDCO/Leader |
| 351 | DOWN COMER SYSTEMSupply,Installation,Testing & Commissioning of Stainless steel Hydrant Valve / Landing valve, of 63 mm NB size, type-A, single headed , oblique type, as per IS :5290/93 and as per direction of Engineer-in-charge.Make-Newage/Minimax/Fireshield |
| 352 | Supply,Installation,Testing & Commissioning of SS short branch pipe with 63 mm male inlet and 19 mm outlet nozzle, as per IS:903 and as per direction of Engineer-in-charge. Make-Newage/Minimax/Fireshield |
| 353 | Supply,Installation,Testing & Commissioning of 63 mm NB and 15meter long RRL Fire Hose fitted with 63mm intstantaneous stainless steel male & female SS coupling, complete by GI wire binding for Internal Hydrant as per direction of Engineer-in-charge. Make-Newage/Minimax/Fireshield |
| 354 | Providing supply & fixing of MS Hose Box for of suitable size(750X600X250mm) to accomodate 2 nos. of 15/ 1 no of 30 mtr long fire hose and a branch pipe, wall mounted type as per direction of Engineer-in-charge. Make-Newage/Minimax/Fireshield |
| 355 | Supply,Installation,Testing & Commissioning of Swinging pattern wall fixing first aid hose reel made from MS sheet and waterways and moving parts with rubber hose of 20 mm dia. and 30 mtrs. long with ABS(Plastic) shut-off nozzle as per IS: 444/IS: 12585 Type-I., complete with all accessories as per direction of Engineer-in-charge. Make-Newage/Minimax/Fireshield |
| 356 | Providing, fitting and fixing of C.I. 25 MM single air relief valve with stop cock confirming to IS:14845/2000 with ISI mark for water works purpose including fixing the same with hydrant riser including testing & commissioning the system etc. all complete as per approved specification & direction of Engineer-in-charge. |
| 357 | Providing, fitting & fixing of 2-Way GM fire brigade connection consisting of 63 mm dia instantaneous type male couplings with built-in check valves, 150mm dia flanged outlet complete with bolts, nuts and rubber insertions confirming to IS:904 with ISI mark including testing & commissioning the system etc. all complete as per apporoved specification & direction of EIC. Make-Newage/Minimax/Fireshield |
| 358 | EXTINGUISHER SYSTEMProviding and fixing carbon-di-oxide type fire extinguishers consisting of welded M.S cylindrical body, squeeze lever dischange valve fitted with pressure indicating gauge internal discharge tube, 30cms long high pressure discharge hose, discharge nozzle, suspension bracket, conforming to IS : 2878 finished externally with red enamel paint and fixed to wall with brackets complete with internal charge. Make- Safex/ Fireshield/Kanex/ Ceasefire/Flameklog.4.5 kg capacity |
| 359 | FIRE EXTINGUISHERS :- Providing and fixing ABC type fire extinguishers consisting of welded M.S cylindrical body, squeeze lever dischange valve fitted with pressure indicating gauge internal discharge tube, 30cms long high pressure discharge hose, discharge nozzle, suspension bracket, conforming to IS finished externally with red enamel paint and fixed to wall with brackets complete with internal charge.Make- Safex/ Fireshield/Kanex/ Ceasefire/Flameklog 6 kg capacity |
| 360 | Supplying and installing at approved location approved make fire buckets at 24 gauge galvanized stseel sheet, standard 9 liters capacity and of round bottom shape, painted white inside and red outside and black on the bottom, inscribed with letter \\"FIRE\\" in black and gold. Cost shall be inclusive of Providing MS stand duly painted over a coat of primer (one stand shall be suitable for hanging 5 buckets. |
| 361 | SIGNAGES: SITC flexyl of Photoluminescent based Glow-in-the-dark sheeting with luminious properties enclosed in a weather-proof UV stabilized film with UV screen printing by imported inks pasted over 3 mm Thick Cast Acrylic Sheet with the Protection of 3 mm Thick Cast Acrylic from Front side with stud type mirror screw with lifespan of 5 years, visible upto 4-6 hrs in total darkness for floor indication, fire exit, hydrant, hose reel, fire extinguisher, MCP, fire alarm panel, in case of fire, lift, alarm valve signages |
| 362 | Aerosol based Automatic Fire ExtinguisherSupply & Installation of 60 gm Portable Aerosol based Automatic triggering through linear heat detection cable/electrical initiation Fire Extinguisher (Coverage: 0.6 m3) , EN 15276-1:2019 and EN 15276-2:2019 ,ISO 15779:2011 approved ,capable for extinguishing Class A, B, C & E fire, non-corrosive, non-conductive, non-toxic, activation temperature 70 deg-180 deg Celcius including all accessories as per the direction ofEngineer-in-Charge. The triggering device should be compatible with linear heat detector to detect heat and should use industrial lithium ion battery with 10 yrs service life to supply electrical power in order to activate the aerosol module. Replacement warranty on the product shall be 3 years and shell-life of 10 years. Make-Pyrogen/Genefire/Stat-x/Equivalent |
| 363 | Supply & Installation of 20 gm Portable Aerosol based Automatic Fire Extinguisher (Coverage: 0.2 m3), EN 15276-1:2019 and EN 15276-2:2019 ,ISO 15779:2011 approved ,capable for extinguishing Class A, B, C & E fire, non-corrosive, non-conductive, non-toxic, activation temperature 70 deg-180 deg Celcius including all accessories as per the direction of Engineer-in-Charge. Replacement warranty on the product shall be 3 years and shell-life of 10 years. Make-Pyrogen/Genefire/Stat-x/Equivalent |
| 364 | Supply and installation of linear heat detection cable compatible with aerosol based fire extinguisher as per the direction of Engineer-in-charge. Make-Pyrogen/Genefire/Stat-x/Equivalent |
| 365 | PH WORKSInternal PH WorksSupplying all materials, labour, T&P and providing and fixing to wall or ceiling and floor CPVC/upvc pipes and pipe fittings of the following nominal bore with clamps including making good the wall, ceiling and floor all complete as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)In ground floor20mm dia CPVC pipe |
| 366 | Supplying all materials, labour, T&P and providing and fixing to wall or ceiling and floor CPVC/upvc pipes and pipe fittings of the following nominal bore with clamps including making good the wall, ceiling and floor all complete as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)In ground floor25mm dia CPVC pipe |
| 367 | Supplying all materials, labour, T&P and providing and fixing to wall or ceiling and floor CPVC/upvc pipes and pipe fittings of the following nominal bore with clamps including making good the wall, ceiling and floor all complete as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)In ground floor25mm dia PVC ASTM (Sch-80) Pipes |
| 368 | Supplying all materials, labour, T&P and providing and fixing to wall or ceiling and floor CPVC/upvc pipes and pipe fittings of the following nominal bore with clamps including making good the wall, ceiling and floor all complete as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)In ground floor32mm dia PVC ASTM (Sch-80) Pipes |
| 369 | Supplying all materials, labour, T&P and providing and fixing to wall or ceiling and floor CPVC/upvc pipes and pipe fittings of the following nominal bore with clamps including making good the wall, ceiling and floor all complete as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)In ground floor40mm dia PVC ASTM (Sch-80) Pipes |
| 370 | Supplying all materials, labour, T&P and providing and fixing to wall or ceiling and floor CPVC/upvc pipes and pipe fittings of the following nominal bore with clamps including making good the wall, ceiling and floor all complete as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)In first floor20mm dia CPVC pipe |
| 371 | Supplying all materials, labour, T&P and providing and fixing to wall or ceiling and floor CPVC/upvc pipes and pipe fittings of the following nominal bore with clamps including making good the wall, ceiling and floor all complete as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)In first floor25mm dia CPVC pipe |
| 372 | Supplying all materials, labour, T&P and providing and fixing to wall or ceiling and floor CPVC/upvc pipes and pipe fittings of the following nominal bore with clamps including making good the wall, ceiling and floor all complete as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)In first floor25mm dia PVC ASTM (Sch-80) Pipes |
| 373 | Supplying all materials, labour, T&P and providing and fixing to wall or ceiling and floor CPVC/upvc pipes and pipe fittings of the following nominal bore with clamps including making good the wall, ceiling and floor all complete as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)In first floor32mm dia PVC ASTM (Sch-80) Pipes |
| 374 | Supplying all materials, labour, T&P and providing and fixing to wall or ceiling and floor CPVC/upvc pipes and pipe fittings of the following nominal bore with clamps including making good the wall, ceiling and floor all complete as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)In first floor40mm dia PVC ASTM (Sch-80) Pipes |
| 375 | Supplying all materials, labour, T&P and providing and fixing to wall or ceiling and floor CPVC/upvc pipes and pipe fittings of the following nominal bore with clamps including making good the wall, ceiling and floor all complete as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)In second floor50mm dia PVC ASTM (Sch-80) Pipes |
| 376 | Supplying all materials, labour, T&P and cutting holes through existing brick work including making good the damages in cement mortar ( 1:4) for taking GI pipes and fittings/ PVC pipes and fittings etc all complete as per PH specification and direction of the Engineer in charge.Ground Floor |
| 377 | Supplying all materials, labour, T&P and cutting holes through existing brick work including making good the damages in cement mortar ( 1:4) for taking GI pipes and fittings/ PVC pipes and fittings etc all complete as per PH specification and direction of the Engineer in charge.First Floor |
| 378 | Supplying all materials, labour, T&P and cutting grooves in pucca floors and walls for taking GI/PVC pipes and making good the damages as per the direction of the Engineer in chargeGround Floor |
| 379 | Supplying all materials, labour, T&P and cutting grooves in pucca floors and walls for taking GI/PVC pipes and making good the damages as per the direction of the Engineer in chargeFirst Floor |
| 380 | Supplying all materials, labour, T&P and cutting holes through existing brick or laterite masonry wall for taking HCI pipes and fittings including making good the damages etc all complete as per PH specification and direction of the Engineer in charge250mm to 375mm thick wall Ground Floor |
| 381 | Supplying all materials, labour, T&P and cutting holes through existing brick or laterite masonry wall for taking HCI pipes and fittings including making good the damages etc all complete as per PH specification and direction of the Engineer in charge250mm to 375mm thick wall First Floor |
| 382 | Supplying all materials,labour,T&P and fixing Rotational moulded polyethylene cylindrical vertical water storage tanks conforming to IS : 12701--1996 including cutting holes through the tank and fixing mild steel tubes and fittings and providing extra sockets and jam nuts, fixing ball valve etc, including hoisting upto a height of 5 metres above ground level and placing the tank to the required position and providing 1st class K.B brickwork in cement mortar (1:6) of 0.46m height in staging and in circular protection wall to support the tank, 12mm thick cement plaster (1:6) over brickwork, R.C.C slab of size 1.60mx1.60m and 0.10m thick, R.C.C beam of 0.25mx0.30m and 2.60m average length in cement concrete(1:2:4) using 12mm size h.g chips including centering and shuttering, watering, curing, conveyance of all materials to worksite etc all complete as per specification and direction of the Engineer in charge(3 layer)Fixing 1500 Ltr Roto-moulded water storage tanks-On the roof of second floor. |
| 383 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materials complete as per specification and direction of the Engineer in charge(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG).15mm dia Bib Cock (Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG) |
| 384 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materials complete as per specification and direction of the Engineer in charge(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG).15mm dia. C.P angle stop cock (Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG) |
| 385 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materials complete as per specification and direction of the Engineer in charge(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG).20mm dia CP concealed stop cock(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG) |
| 386 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materials complete as per specification and direction of the Engineer in charge(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG).15mm dia CP Pillar cock (Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG) |
| 387 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materials complete as per specification and direction of the Engineer in charge(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG).15mm dia PVC Health faucet(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG). |
| 388 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materials complete as per specification and direction of the Engineer in charge(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG).15mm dia Two way Bib Cock (Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG) |
| 389 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materials complete as per specification and direction of the Engineer in charge(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG).25mm dia C-PVC ball valve |
| 390 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materials complete as per specification and direction of the Engineer in charge(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG).32mm dia C-PVC ball valve |
| 391 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materials complete as per specification and direction of the Engineer in charge(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG).40mm dia C-PVC ball valve |
| 392 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materials complete as per specification and direction of the Engineer in charge(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG).50mm dia C-PVC ball valve |
| 393 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materials complete as per specification and direction of the Engineer in charge(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG).15mm dia CP Flange |
| 394 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materials complete as per specification and direction of the Engineer in charge(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG).15mm dia CP Extention Nipple |
| 395 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materials complete as per specification and direction of the Engineer in charge(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG).125mm CP grating |
| 396 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materials complete as per specification and direction of the Engineer in charge(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG).25mmx600mm long CP towel rail |
| 397 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materials complete as per specification and direction of the Engineer in charge(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG).CP ring towel rail |
| 398 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materials complete as per specification and direction of the Engineer in charge(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG).CP soap holder |
| 399 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materials complete as per specification and direction of the Engineer in charge(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG).15mm dia PVC inlet connection pipe 0.45m long |
| 400 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materials complete as per specification and direction of the Engineer in charge(Plaza/Aquatic/Amber/Cera/Kerovit/Hydro/Somany/AKG).32mm dia PVC waste pipe with brass coupling nut |
| 401 | Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No. 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)110mm dia U-PVC SWR pipe |
| 402 | Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No. 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)Construction of 50 users RCC septic tank- 1 No |
| 403 | Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No. 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)110mm U-PVC door Tee |
| 404 | Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No. 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)110mm dia U-PVC Plain Tee |
| 405 | Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No. 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)110mm U-PVC door bend |
| 406 | Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No. 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)110mm U-PVC plain bend |
| 407 | Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No. 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)110mm dia U-PVC plain shoe bend |
| 408 | Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No. 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)110mm dia U-PVC offset without ear |
| 409 | Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No. 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)110mm dia U-PVC 'P' trap |
| 410 | Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No. 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)110mm dia U-PVC cowl |
| 411 | Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No. 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)Construction of 50 users RCC septic tank- 1 No |
| 412 | Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No. 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)PVC clamp suitable for 50mm to 110mm dia pipe |
| 413 | Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No. 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)75mm dia U-PVC SWR pipe(Supreme/Ashirvad/Oriplast) |
| 414 | Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No. 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)75mm dia U-PVC Plain Tee |
| 415 | Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No. 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG)75mm U-PVC plain bend |
| 416 | Supplying all materials, labour, T&P and fixing the following vitreous china Wash Down Water Closet (European type W.C pan) with integral P or S trap to the floor with wooden plug and chromium plated pedestal screws including jointing the trap with soil pipe in cement mortar (1:1), fixing plastic seat and cover for wash down water closet with chromium plated brass hinges and rubber buffers including polishing etc all complete as per specification and direction of the Engineer in charge. European water closet with S trap plain (Parryware/Hendware/Cera/Somany/Kerovit) |
| 417 | Supplying all materials , labour, T&P and fixing Vitreous china water closet ,squatting pan ( Indian type W.C. pan / Orissa pattern squatting pan ) duly embedded in cement concrete 1:5:10 using hard granite metal 4cm nominal size including fixing a pair of vitreous china 250mmx130mmx30mm foot rest, fixing 100mm dia hci 'P' or 'S' trap for water closet squatting pan including jointing the trap with pan in cement mortar (1:1), cutting the floor and mending good the damages etc. all complete as per P.H. specification and direction of Engineer-in-charge. 580mmx440mm size Orissa pan ((Parryware/Hendware/Cera/Somany/Kerovit) |
| 418 | Supplying all materials, labour, T&P and fitting and fixing 10 litres capacity low level flushing cistern with a pair of cast iron or M.S brackets complete with fittings such as siphonic arrangements 15mm nominal size brass/pvc ball valve with polythene float CP brass handle, unions and couplings for connection with inlet, outlet and overflow pipes,32mm dia CP flush bend,15mm dia pvc inlet connection pipe including cutting holes and making good the same and connecting the flush bend with cistern and closet and connecting the inlet pipe with supply main etc all complete as per specification and direction of the Engineer in charge. 10 litres capacity pvc low level cistern with 32mm dia CP long flush bend Slimline white (Parryware/Hendware/Cera/Somany/Kerovit) |
| 419 | Matrix Set -1 (WB 65 x 35 with one pair mounting brackets, EWC & Cistern complete with fittings & seat cover, one no hinged rail 76 cm and five nos of grab rails 60 cm) (head)70002 |
| 420 | Supplying all materials, labour, T&P and fixing bowl pattern urinal conforming to IS:771-part-3-1985 of the following sizes including connecting the urinal with 32mm dia pvc waste pipe 910mm long by means of white lead mixed with chopped hemp, fixing 32mm dia CP dome waste, 15mm dia CP spreader including cutting holes in walls and making good the damages with supply of wooden plugs, screws and cement etc all complete as per specification and direction of the Engineer in charge. Half stall urinal (Jaquar/Parryware / Hindware make). URS-WHT-13253N Urinal (Back Inlet) |
| 421 | 15mm dia urinal spreader |
| 422 | 32mm dia C.P. dome waste |
| 423 | Supplying all materials , labour, T&P and fixing Vitreous china water closet ,squatting pan ( Indian type W.C. pan / Orissa pattern squatting pan ) duly embedded in cement concrete 1:5:10 using hard granite metal 4cm nominal size including fixing a pair of vitreous china 250mmx130mmx30mm foot rest, fixing 100mm dia hci 'P' or 'S' trap for water closet squatting pan including jointing the trap with pan in cement mortar (1:1), cutting the floor and mending good the damages etc. all complete as per P.H. specification and direction of Engineer-in-charge. Squatting URINAL pan (Parryware/Hinware/Sanituf) |
| 424 | Supplying all materials, labour, T&P and fixing wash basins with hole for pillar taps conforming to IS:2556-part-4-2004 with cast iron or M S brackets painted white including cutting holes in walls and making good the damages with supply of wooden plugs, screws and cement etc, fixing pedestal for wash basin recessed at the back for the reception of pipes and fittings, fixing PVC waste pipe of 32mm nominal diameter for wash basin including brass check nut complete, fixing pillar taps capstan head screw down high pressure lettered Hot and Cold with long screws, shanks and back nuts of 15mm dia nominal bore(Plaza make), fixing 15mm dia PVC inlet connection pipe and making connection with pillar cocks and supply mains for wash basin, fixing 32mm dia CP brass waste(Plaza make), etc all complete as per specification and direction of the Engineer in charge |
| 425 | Supplying all materials, labour, T&P and fixing mirror of superior glass conforming to IS:3438-1996 mounted on 6mm thick A.C sheet or plywood sheet and fixed to wooden plugs with CP screws and washers complete as per specification an direction of the Engineer in chargeDesign mirror(Parryware) |
| 426 | Supplying all materials,labour ,T&P and filling in foundation and plinth with sand well watered and rammed including cost, conveyance of all materials to work site ,payment of royalty,taxes etc. all complete as per direction of the Engineer-in -chargeIn ground floor |
| 427 | Construction of 50 users RCC septic tank- 1 No |
| 428 | Supplying all materials, labour, T&P and providing cement concrete (1:3:6) with 4cm size hard granite metal including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge. Ground Floor |
| 429 | Construction of 50 users RCC septic tank- 1 No |
| 430 | Supplying all materials, labour, T&P and providing cement concrete (1:2:4) with 12mm size crusher broken hard black granite chips including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge. Ground floor |
| 431 | Supplying all materials, labour, T&P and providing cement concrete (1:2:4) with 12mm size crusher broken hard black granite chips including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge. Ground floorFirst floor |
| 432 | Construction of 50 users RCC septic tank- 1 No |
| 433 | Supplying all materials, labour, T&P and providing 12mm thick cement plaster (1:4) on brickwork including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in chargeGround floor |
| 434 | Supplying all materials, labour, T&P and providing 12mm thick cement plaster (1:4) on brickwork including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in chargeIn first floor |
| 435 | Construction of 50 users RCC septic tank- 1 No |
| 436 | Supplying the waterproofing material Pidifin 2K of Dr.fixit on equivalent water proofing material and appling in two coat over the concrete floor and dado upto 1\\"-6\\" in wall including cleaning,applying and mending as per specification including all labour charges as per direction of Engineer-in-charge.In first floor |
| 437 | Supplying all materials, labour, T&P and providing ceramic tiles in floors, treads and landing on 25mm thick bed of cement mortar 1:1 (1 cement:1 sand) joined with neat cement slurry mixed with pigment to match the shades of the tiles including rubbing and polishing complete as per direction of the Engineer in charge. Kajaria / Somany / Johnson to be pre-approved 300 x 300mm of size-In. Ground Floor |
| 438 | Supplying all materials, labour, T&P and providing ceramic tiles in floors, treads and landing on 25mm thick bed of cement mortar 1:1 (1 cement:1 sand) joined with neat cement slurry mixed with pigment to match the shades of the tiles including rubbing and polishing complete as per direction of the Engineer in charge. Kajaria / Somany / Johnson to be pre-approved 300 x 300mm of size-In. First floor |
| 439 | Supplying all materials, labour, T&P and fixing porcelain glazed tiles in dados skirting on 12mm thick cement plaster (1:3) jointed with neat cement slurry mixed with pigments to match the shades of the tiles including rubbing and polishing complete as per direction of the Engineer in charge. Kajaria / Somany 30cm x45 cm size of Ground Floor;- |
| 440 | Supplying all materials, labour, T&P and fixing porcelain glazed tiles in dados skirting on 12mm thick cement plaster (1:3) jointed with neat cement slurry mixed with pigments to match the shades of the tiles including rubbing and polishing complete as per direction of the Engineer in charge. Kajaria / Somany 30cm x45 cm size of First Floor |
| 441 | Supplying all materials, labour, T&P and fixing Granite tiles in dados skirting on 12mm thick cement plaster (1:3) jointed with neat cement slurry mixed with pigments to match the shades of the tiles including rubbing and polishing complete as per direction of the Engineer in chargeGround floor |
| 442 | Supplying all materials, labour, T&P and fixing Granite tiles in dados skirting on 12mm thick cement plaster (1:3) jointed with neat cement slurry mixed with pigments to match the shades of the tiles including rubbing and polishing complete as per direction of the Engineer in chargeIn , First floor |
| 443 | Finishing wall surface of walls with Acrylic wall putty (Water based ) of approved make and finished smooth and even surface to receive painting including cost of scaffolding staging charges with cost of all materials taxes, labour T&P etc complete.GroundFloor |
| 444 | Finishing wall surface of walls with Acrylic wall putty (Water based ) of approved make and finished smooth and even surface to receive painting including cost of scaffolding staging charges with cost of all materials taxes, labour T&P etc complete.First floor |
| 445 | Supplying all materials, labour, T&P and providing cement washing 2 coats including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge.Ground Floor |
| 446 | Supplying all materials, labour, T&P and providing cement washing 2 coats including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge.First floor |
| 447 | Supplying all materials, labour, T&P and distempering two coats to walls with distemper of approved shade on new work to give an even shade etc all complete as per specification and direction of the Engineer in charge.Ground Floor |
| 448 | Supplying all materials, labour, T&P and distempering two coats to walls with distemper of approved shade on new work to give an even shade etc all complete as per specification and direction of the Engineer in charge.First floor |
| 449 | Factory made Solid WPC door frame of size 95mmx55mm fabricated .The door frame consist of four segments which are provided with plug-in-socket arrangement in-situ in the mould. The segments are plugged in and are joined together by means of screw. The WPC frame shall be provided with The material and process for manufacturing the door frames shall conform to Relavent I.S.specification. The finish of door frame will be plain colour white/ Ivory/ Beige/ Light grey/ Golden brown/Mahogany/ Teak wood/sand stone/Champagne/Pastel blue or any other colour using high quality pigments complete in all respect as per specification and direction of the Engineer in charge |
| 450 | Factory made single leaf Solid WPC (Wood polymer) composite door shutter of 25mm thickcompacted with wood grain finish structural foam panel of 29mm thickness and a density of 20kg/cu.mtr shall be used as core material for fitting the metal fittings such as tower bolts, aldrops, handles etc shall be provided. A structural adhesive compatible with (EPS) foam shall be used for bending the core material, The material and process for manufacturing the door shutters shall conform to RV-TIFAC composites Design Centre's standards and specifications and the door shutters Conforming to relevant I.S.specification. The finish of door shutter will be plain colour white/ Ivory/ Beige/ Light grey/ Mahogany/ Teak wood or any other colour using high quality pigments. Three heavy whight mild steel butt hinges type-I(ISI marked) size 100mm are to be fitted on one side of shutter. |
| 451 | Supplying all materials, labour, T&P and constructing gully trap chamber of the following inside size with 8cm thick R.C.C precast cover slab in cement concrete (1:2:4) mix using 12mm size h.g chips, foundation concrete (1:4:8) using 40mm size hard granite metal on bed and around trap, KB brickwork in cement mortar (1:6) in F&P and inside 12mm thick cement plastering (1:3) finished with a floating coat of neat cement including fixing 100mmx100mm size HCI gully trap,150mmx150mm size CI grating etc all complete as per approved drawing, specification and direction of the Engineer in charge |
| 452 | Supplying all materials, labour, T&P and constructing inspection chamber of the following size with cement concrete(1:3:6) using 40mm size hard granite metal on bed, 1st class KB brickwork in cement mortar(1:6), moulding and shaping the channel inside and benching with cement concrete (1:2:4) using 12mm size h.g chips, 12mmthick cement plaster (1:3) with punning to inside, cement flush pointing (1:3) to outside, RCC cover slab in (1:2:4) using 12mm size h.g chips with RCC man hole cover, earthwork in excavation in all kinds of soil and refilling the cavity around the chamber including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per approved specification and direction of the Engineer in charge |
| 453 | R.C.P.C Cover |
| 454 | Supplying all materials, labour, T&P and constructing man hole chamber of the following size with cement concrete(1:3:6) using 40mm size hard granite metal on bed, 1st class K.B brickwork in cement mortar(1:6), moulding and shaping the channel inside and benching with cement concrete (1:2:4) using 12mm size h.g chips,12mmthick cement plaster (1:3) with punning to inside, cement flush pointing (1:3) to outside, R.C.C cover slab in (1:2:4) using 12mm size h.g chips with RCC man hole cover, earthwork in excavation in all kinds of soil and refilling the cavity around the chamber including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per approved specification and direction of the Engineer in charge |
| 455 | R.C.P.C Cover |
| 456 | Supplying all materials, labour, T&P and constructing soakway pit of the following size with dry brick walling from bottom upto invert of inlet pipe and 1st class K.B brickwork in cement mortar (1:6) for the remaining height at top, cement concrete (1:4:8) using 40mm size hg chips on bed, 12mm thick cement plaster (1:4) inside and outside over masonry brickwork, gravel backing in the rear of well steining, RCC cover slab in cement concrete (1:2:4) using 12mm size hg chips fitted with iron lifting handles including earthwork in open well excavation in all kinds of soil and refilling of cavity around the pit & painting the iron works, watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per approved specification and direction of the Engineer in charge |
| 457 | Supplying all materials, labour, T&P and laying in trenches (to level or slope) unplasticized PVC pipes conforming to IS: 4985/2000 of the following outside dia for class 3(0.60mpa) including jointing with supply of approved solvent cement by non-heat application method/as per manufacturer s specification, providing and laying in trench cement concrete (1:4:8) with 40mm size hard granite metal in the Type C-1 standard bedding surrounding or encasing including concrete for bedding and curing etc all complete as per PH specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG).110mm dia alround concrete |
| 458 | Supplying all materials, labour, T&P and laying in trenches (to level or slope) unplasticized PVC pipes conforming to IS: 4985/2000 of the following outside dia for class 3(0.60mpa) including jointing with supply of approved solvent cement by non-heat application method/as per manufacturer s specification, providing and laying in trench cement concrete (1:4:8) with 40mm size hard granite metal in the Type C-1 standard bedding surrounding or encasing including concrete for bedding and curing etc all complete as per PH specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast/AKG).160mm dia alround concrete |
| 459 | Construction of 50 users RCC septic tank- 1 NoEarth work in excavation of foundation in all kinds of soil within 50m initial lead and 1.5m initial lift including rough dressing & breaking clods to maximum 5cm to 7cm and laying in layers not exceeding 0.30m in depth and as per direction of the Engineer-in-Charge. |
| 460 | Extra lifts of 1.50 mtr or part thereof over the initial lift of 1.5 mtr in all kinds of embankments and road works and ordinary earthwork in general. |
| 461 | Excavation of foundation in laterite rock or any hard rock (other than granite or disintegrated rock) removed by chiselling including dressing and levelling the bed not exceeding 1.50 mtr. in depth and depositing the soil within initial lead of 50 mtr. and as per specification approved by the Department. |
| 462 | Supplying all materials, labour, T&P and providing 6mm thick cement plaster (1:4) on RCC work including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge |
| 463 | Supplying all materials, labour, T&P and providing cement punning including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge |
| 464 | Supplying all materials, labour, T&P and providing rigid and smooth centering and shuttering for R.C.C works including false work and dismantling them after casting including conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in chargeR.C.C floor and roof slabs up to 4.30m height |
| 465 | Supplying all materials, labour, T&P and providing rigid and smooth centering and shuttering for R.C.C works including false work and dismantling them after casting including conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in chargeR.C.C beams,columns,girder and bressmer etc. |
| 466 | Supplying all materials, labour, T&P and providing M.S reinforcement for R.C.C work including cutting, bending, binding, and tying the grills and placing in position including cost of binding wire 18 to 20 gauge, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge |
| 467 | Supplying all materials, labour, T&P and providing cement concrete (1:1.5:3) with 12mm size hard broken granite chips for R.C.C works including hoisting, laying, watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge |
| 468 | Supplying all materials, labour, T&P and providing brick work with Fly ash bricks having crushing strength not less than 75kg/cm² with dimensional tolerance ± 8 percent in cement mortar (1:4) including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge |
| 469 | Supplying all materials, labour, T&P and making MS step iron in 20mm diameter MS steel bars and fixing into walls of man hole/septic tank duly embedded in cement concrete (1:3:6) complete as per specification and direction of the Engineer in charge. |
| 470 | Filling in foundation and plinth with excavated materials, moorum including watering and ramming as directed by the Engineer in charge |
| 471 | Supplying all materials, labour,T&P and providing 25mm thick grading concrete (1:2:2) on roof slab with 6mm size hard granite chips on new work including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge |
| 472 | Supplying all materials, labour, T&P and providing shoring and shuttering foundation trenches, pits etc with close wooden planks or sheets shuttering etc all complete as per direction of the Engineer in charge. |
| 473 | Dewatering with 5 H.P diesel engine pump during excavation |
| 474 | Supplying all materials, labour, T&P and providing, fitting and fixing U-PVC SWR Tee in wall including filling the recess with cement concrete (1:3:6) with 12mm size h.g chips all complete including watering, curing, conveyance of all materials to worksite, payment of royalty all complete as per specification and direction of the Engineer in charge160mm U-PVC plain Tee |
| 475 | Supplying all materials, labour, T&P and constructing vent base as per P.H.D specification etc all complete. |
| 476 | Sinking of 2 dia large Tube well(1 No.)Labour for drilling a perfectly vertical bore hole of specified dia for a specified depth below ground level through consolidated and unconsolidated rock with down the hole hammer drilling rig or combination rig as required to suit the site condition as per the direction of the Engineer in charge including use of own rig with its accessories, tools and plant and consumables etc for lowering of 200mm/150mm dia G.I/P.V.C/M.S casing pipes for housing fitted with socket and with or without well screen as per the necessity for soft, medium, hard and boulder formation(G.I/P.V.C/M.S casing pipes if required to prevent collapse of overburden is to be provided by the contractor including lowering and withdrawing after completion of the tube well), 200mm dia to 400mm dia in overburden portion including packing of gravel supplied by the contractor for 400mm dia bore.Labour for Drilling of 200 mm dia bore 0mtr to 120mtr |
| 477 | Sinking of 2 dia large Tube well(1 No.)Labour for drilling a perfectly vertical bore hole of specified dia for a specified depth below ground level through consolidated and unconsolidated rock with down the hole hammer drilling rig or combination rig as required to suit the site condition as per the direction of the Engineer in charge including use of own rig with its accessories, tools and plant and consumables etc for lowering of 200mm/150mm dia G.I/P.V.C/M.S casing pipes for housing fitted with socket and with or without well screen as per the necessity for soft, medium, hard and boulder formation(G.I/P.V.C/M.S casing pipes if required to prevent collapse of overburden is to be provided by the contractor including lowering and withdrawing after completion of the tube well), 200mm dia to 400mm dia in overburden portion including packing of gravel supplied by the contractor for 400mm dia bore.Labour for Drilling of 150 mm dia bore 0mtr to 120mtr |
| 478 | Lowering the following size of G.I/P.V.C/M.S housing pipes with or without slotted pipes as per the necessity from ground level up to 45.00m depth and fitted and fixed up in perfectly vertical position including cutting and threading of pipes and slotted pipes and supplying and fixing all jointing materials, tools and plant etc all complete and keeping the top of casing pipe threaded including plugging tube wells to prevent entry of foreign materials.Lowering of 200 mm dia GI/P.V.C/MS casing pipes 0 mtr to 30 mtrs |
| 479 | Lowering the following size of G.I/P.V.C/M.S housing pipes with or without slotted pipes as per the necessity from ground level up to 45.00m depth and fitted and fixed up in perfectly vertical position including cutting and threading of pipes and slotted pipes and supplying and fixing all jointing materials, tools and plant etc all complete and keeping the top of casing pipe threaded including plugging tube wells to prevent entry of foreign materials.Lowering of 200mm dia GI/P.V.C/MS casing pipes 31 mtr to 45 mtrs |
| 480 | Lowering the following size of G.I/P.V.C/M.S housing pipes with or without slotted pipes as per the necessity from ground level up to 45.00m depth and fitted and fixed up in perfectly vertical position including cutting and threading of pipes and slotted pipes and supplying and fixing all jointing materials, tools and plant etc all complete and keeping the top of casing pipe threaded including plugging tube wells to prevent entry of foreign materials.Cost of 200 mm dia ASTM-D-1785/89 P.V.C schedule-80 pipe |
| 481 | Cleaning and developing the tube well with supply of compressor worked till clear and adequate discharge is obtained from the tube well including supply and use of all necessary equipment and labour as per direction of the Engineer in charge |
| 482 | By DTH Supplying submerssible pump with sqirrel cage induction type submersible type submerssible electric motor to run on 3 phase/1 phase line voltage ranging from 320 volt to 450 volt conforming to IS: 8034 - 2002 with following specificationsSupplying submerssible pump with sqirrel cage induction type submersible type submerssible electric motor to run on 3 phase/1 phase line voltage ranging from 320 volt to 450 volt conforming to IS: 8034 - 2002 with following specificationsSubmerssible Pump Set 1 H.P three phase 3 stage head range 30 to 54 metres, discharge 155 to 6110 L.M.P with outlet dia of 32 mm. |
| 483 | By DTH Supplying submerssible pump with sqirrel cage induction type submersible type submerssible electric motor to run on 3 phase/1 phase line voltage ranging from 320 volt to 450 volt conforming to IS: 8034 - 2002 with following specificationsDOL control panel |
| 484 | By DTH Supplying submerssible pump with sqirrel cage induction type submersible type submerssible electric motor to run on 3 phase/1 phase line voltage ranging from 320 volt to 450 volt conforming to IS: 8034 - 2002 with following specifications2.50 sqmm cable |
| 485 | By DTH Supplying submerssible pump with sqirrel cage induction type submersible type submerssible electric motor to run on 3 phase/1 phase line voltage ranging from 320 volt to 450 volt conforming to IS: 8034 - 2002 with following specifications32mm dia steel short piece |
| 486 | By DTH Supplying submerssible pump with sqirrel cage induction type submersible type submerssible electric motor to run on 3 phase/1 phase line voltage ranging from 320 volt to 450 volt conforming to IS: 8034 - 2002 with following specifications32 mm dia HDPE Pipe |
| 487 | By DTH Supplying submerssible pump with sqirrel cage induction type submersible type submerssible electric motor to run on 3 phase/1 phase line voltage ranging from 320 volt to 450 volt conforming to IS: 8034 - 2002 with following specificationsBore Cap |
| 488 | By DTH Supplying submerssible pump with sqirrel cage induction type submersible type submerssible electric motor to run on 3 phase/1 phase line voltage ranging from 320 volt to 450 volt conforming to IS: 8034 - 2002 with following specificationsC.I.Bracket |
| 489 | By DTH Supplying submerssible pump with sqirrel cage induction type submersible type submerssible electric motor to run on 3 phase/1 phase line voltage ranging from 320 volt to 450 volt conforming to IS: 8034 - 2002 with following specificationsRope Wire |
| 490 | Labour charges for lowering of submesible pumpset with pipes and cables etc. with testing and commissioning at site. |
| 491 | Supply all materials,labours,T&P and construction bore well protection chamber of the inside size 650x650x1000 height with cement concrete ( 1;3;6) using 40 mm size hard granite metal on foundation,1st class fly ash brickwork incement motar(1:3),with base cement concrete (1:2:4) useing 12 mm size h.g chips ,12 mm thick cement plaster (1:4) inside and out site ,R CC cover slab in (1:1.5:3) using 12 mm size h.g chips earthwork in excavation in all kinds of soil and refiling the cavity around the chamber including watering ,curing,convayance of all materials to worksite,payment of royalty,taxes etc all complete as per approved specification and direction of the engineer-in -charge. Bore well protection chamber. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Sep 02, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 21, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 5 daysSep 22, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 6 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender