Tender For Provn Of Garages For Mil Vehicles At Malpur Under Ge (S) Akhnoor
Tender Overview
Project Description
Tender for Provn Of Garages For Mil Vehicles At Malpur Under Ge (S) Akhnoor
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 10-Oct-2026 | CorrNo02 | Date | 28-Oct-2026 |
| 2 | 30-Sep-2026 | CorrNo01 | Date | 17-Oct-2026 |
| 3 | 21-Oct-2026 | CorrNo03 | Date | 12-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Sch 'A' Part-I (Building Work):-This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as \\"Rs. 0.00\\" under col.5 signifies this fact only. |
| 2 | Construction of building block of Garrage for MHV 6x6 Gun Towing and Bus long Chassis 50/54 Seater 2x2, complete all as specified and as shown on drawings. |
| 3 | Construction of building block of Garrage for Lorry 3.5/7.5Ton 4x4, complete all as specified and as shown on drawings. |
| 4 | Total Amount of Sch 'A' Part - II (Site Clearance and Development Work) |
| 5 | Total Amount of Sch 'A' Part - III (Sec-I) (Internal Electric Supply Work) |
| 6 | Total Amount of Sch 'A' Part - IV (Area Drainage Work) |
| 7 | Total Amount of Sch 'A' Part -V (Road, Path and Culvert Work) |
| 8 | Total Amount of Sch 'A' Part - VI (Sec-I) (External Electric Supply Work) |
| 9 | Sch 'A' Part-III (Sec-II) (Internal Electric Supply Work):-This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as \\"Rs. 0.00\\" under col.5 signifies this fact only. |
| 10 | Point wiring complete with 1.5 sqmm PVC insulated, FRLSH type, ISI marked, conforming to IS-694/1990 unsheathed, multistranded, single core, copper conductor cable 1100 volts grade colour code cables drawn through and including PVC Conduit 20mm dia medium grade (MMS) and all accessories are concealed in walls / roofs / floors / ceiling etc; including modular metal flush box with top, bottom, side/back wall knockout for conduit entry from any direction made out of 1.60mm thick including modular top cover plate as per numbers of switch modules for fixing of modular switches, sockets, fan regulators, red colour indicator, blank plates etc. as approved colours and including 1.5 Sqmm PVC insulated multistranded FRLSH type unsheathed (Green colour), single core cable with copper conductor cable as earth continuity conductor and connecting to common earth dolly and including making good the disturbed surfaces to match with existing surface and colour coat including providing putty and white cement for smooth finishing of existing surface complete all as specified and directed for the following:- Note No1: All necessary accessories such as modular steel box, top cover plate, blank plate, screws, washers and all modular electrical fixtures are to be used of same make/brand only. Note No 2: Any cutting /leaving /forming holes, chases etc., in walls, floors and ceiling as required and making good the same, shall be deemded to be included in lump sum Sch 'A' Part-I as per para 10(b) in Sch 'A' BOQ Notes. |
| 11 | All as per Srl Item No. 7.01 here-in-above but one light/fan point exhaust fan point controlled by one switch |
| 12 | All as per Srl Item No. 7.01 here-in-above but one 3 pin, 5 amps socket point controlled by one switch |
| 13 | MCB, SPN, 16 Amps 10 KA,\\"C\\" series, AC, 240Volts, 50Hz, (ISI marked) complete all as specified and directed. |
| 14 | MCB, SP, 6 to 32 Amps 10 KA,\\"C\\" series, AC, 240Volts, 50Hz, (ISI marked) complete all as specified and directed. |
| 15 | Concealed sub main wiring of two run with 10 sqmm single core PVC insulated, FRLSH, flexible multi stranded copper conductor cable 1100 volts grade, drawn through and including PVC conduit 25mm dia , medium grade, ISI marked and fixed, including cutting /chasing as required and its accessories including one run of 10 Sqmm single core PVC insulated, FRLSH, multi stranded copper conductor cable as earth continuity conductor in green colour, connected to common earth dolly, complete all as specified and as directed. Note No. 1: Two run of 10 sqmm single core copper conductor cable and one run of 10 sqmm single core copper conductor cable as earth continuity and one run of PVC conduit shall be measured as one unit only.Note No 2: Any cutting /leaving /forming holes, chases etc., in walls, floors and ceiling as required and making good the same, shall be deemded to be included in lump sum Sch 'A' Part-I as per para 10(b) in Sch 'A' BOQ Notes. |
| 16 | Sch 'A' Part-VI (Sec-II) (Exaternal Electric Supply Work):-This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as \\"Rs. 0.00\\" under col.5 signifies this fact only. |
| 17 | LED street light fitting 35 Watt, 230 V, AC outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver, lamp bracket made to shape with GI pipe of 40mm dia, 1.5m length, made to shape and fixed on wall with impact and corrosion resistant including thermal management in multiple optics complete with IP 66 protection, complete all as specified and directed. |
| 18 | Sch 'A' Part - VII (Misc Items of work) Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as \\"Rs. 0.00\\" under col.5 signifies this fact only. |
| 19 | Earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6.0mm thick buried directly in ground ( earth pit not less than 2.25 mtr below normal ground level) with top edge plate not less than 1.5 metre below normal ground level connected to galvanized earth strip of size (32x6)mm as earthing lead by means of bolts, nuts, chuck nuts and washers of galvanized iron earth lead with 15 cm thick alternate layers of charcoal dust & common slat including PCC pit in PCC 1:2:4 type B-1, RCC cover made out of cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) reinforced with TMT steel bars 8 mm dia @150 mm c/c both ways with suitable handle and angle iron (40x40x5)mm frame, GI medium grade watering pipe 20mm bore and funnel with wire mesh, GI medium grade protection pipe 40mm bore up to main board complete as shown on electrical plate No 3 of MES Sch 2009 (Part-I) and testing on completion complete all as specified and directed. (Contd.../) |
| 20 | Note: (i) On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction.(ii) Supply and fix of the earth Pit chamber board for all earthing fixe in this project of 3.15mm thick mild steel sheet of size min 45cm x 30cm fixed with 12mm thick MS rod two Nos up to 90cm height by nut/bolts including spray painting with two coats of synthetic enamel black paint complete MS sheet both side including writing letters min 6cm height i.e; earth Pit No. location, earthinc test value and date and other letters complete all as specified and directed by Engr- in-Charge. |
| 21 | Earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of earth plate not less than 1.5m below normal ground level connected with galvanized iron earth lead wire 4mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel complete, 20mm dia GI medium grade watering pipe with funnel including charcoal, dust, salt, PCC M-15 type B1 in pit with angle iron (25x25x3)mm frame work with precast RCC 1:2:4 type B-1 cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways and 12mm dia MS fabricated handle, test point etc. in and including medium grade GI protection pipe 15mm bore up to 7.5m length for drawing in earth lead wire, all as shown in electric plate No. 3 of SSR Part-I complete with necessary earth work in any type of soil, removal of soil to a distance not exc. 50m, testing on completion complete all as specified and directed. (Contd.../) |
| 22 | Note:- (i) On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction.(ii) Supply and fix of the earth Pit chamber board for all earthing fixe in this project of 3.15mm thick mild steel sheet of size min 45cm x 30cm fixed with 12mm thick MS rod two Nos up to 90cm height by nut/bolts including spray painting with two coats of synthetic enamel black paint complete MS sheet both side including writing letters min 6cm height i.e; earth Pit No. location, earthinc test value and date and other letters complete all as specified and directed by Engr- in-Charge. |
| 23 | Supply, installation, commissioning and testing of cubical type LT panel, size 1.00 x1.00 x0.3m depth, weather proof panel board, factory made, dust and vermi proof, powder coated, outdoor type, IP 65, double door shutter, made out of CRCA 3.15mm thick sheet for outer and 1.6mm thick sheet for inner door with angle iron (50x50x6)mm and 'T' section with front openable double door shutter and rear opening complete with locking arrangements, floor mounting type with 200 amp rated Aluminium bus bar mounted on epoxi/porcelain insulators in totally enclosed chamber, suitable for 3 phase, 4 wire system, 50 Hz, AC supply, prewired system with suitable copper wire PVC insulated with all control accessories and suitable glands etc; including PCC work, 0.6 mtr above ground level grouting etc; complete all as specified and directed and space for provisioning followings:-Incoming: (a) MCCB four pole 32A, 415V, adjustable type, 32 Amps with breaking capacity 16KA, 01 No (Incommer feeder) Outgoing:(b) MCB, SPN, 16KA, 240V, fixed type, 16 Amps with breaking capacity 10KA, 02 No (02 No outgoing feeders for garages) (Contd..../) |
| 24 | (c) MCB, SPN, 16KA, 240V, fixed type, 16 Amps with breaking capacity 10KA - 01 No. (01 No. Standby) (d) Digital volt meter 0 to 500 volts with selecter switch-01 No. (e) Digital Ammeter 0 to 350 Amps with CTs of suitable Amps and selecter switch -01 No. (f) Indicator lamp RYB-01 Set.Note-:1) The pannel shall be front operatded with cable entry from the bottom with cable glands. The fault with standing Capacity shall be 50 KA & earth bus shall be part of the LT panel.(2) Earth work and construction of platform for panel, brick masonary in cement mortar 1:6 with foundation PCC 1:48 (type D-2) including plaster work, PCC coping 1:2.4 (20mm graded crushed stone aggregate). Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-3 Issued
Clarifications on tender conditions and amendments issued.