Tender For Provn Of Af Share Of Works Services For Gw System At Deesa (File No. 89418/E8)
Tender Overview
Project Description
Tender for Provn Of Af Share Of Works Services For Gw System At Deesa (File No. 89418/E8)
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 12-Oct-2026 | 3rd date amendment in tender | Date | 24-Oct-2026 |
| 2 | 06-Oct-2026 | 2nd amendment in tender dates | Date | 19-Oct-2026 |
| 3 | 06-Oct-2026 | 2nd amendment in tender dates | Date | 19-Oct-2026 |
| 4 | 28-Sep-2026 | Amendment in tender date | Date | 13-Oct-2026 |
| 5 | 28-Sep-2026 | Amendment in tender date | Date | 13-Oct-2026 |
| 6 | 22-Oct-2026 | 5th amendment in date | Date | 05-Nov-2026 |
| 7 | 16-Oct-2026 | 4th amendment in tender dates | Date | 28-Oct-2026 |
| 8 | 16-Oct-2026 | 4th amendment in tender dates | Date | 28-Oct-2026 |
| 9 | 12-Oct-2026 | 3rd date amendment in tender | Date | 24-Oct-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | NOTE: Schedule ‘A’ Part I to XII under Ser No. 1.00 to 12.00 are prepriced by MES. Bidders shall insert their lumpsum amount in the green coloured field under Col-6 only. |
| 2 | Lump sum price worked out for BUILDINGS/ STRUCTURES as listed in Sch 'A' Part I. |
| 3 | Lump sum price worked out for Earthwork, Excavation, Site Clearance and development as listed in Sch 'A' Part II |
| 4 | Lump sum price worked out for Internal Electrification as listed in Sch 'A' Part III |
| 5 | Lump sum price worked out for Internal Water Supply as listed in Sch 'A' Part IV |
| 6 | Lump sum price worked out for Road/ Path/ Culvert as listed in Sch 'A' Part V |
| 7 | Lump sum price worked out for Sewage Disposal as listed in Sch 'A' Part VI |
| 8 | Lump sum price worked out for Area Drainage as listed in Sch 'A' Part VII |
| 9 | Lump sum price worked out for External Electric Supply as listed in Sch 'A' Part VIII |
| 10 | Lump sum price worked out for External Water Supply as listed in Sch 'A' Part IX |
| 11 | Lump sum price worked out for Fencing, Gate& Retaining Wall as listed in Sch 'A' Part X |
| 12 | Lump sum price worked out for Street Light as listed in Sch 'A' Part XI |
| 13 | Lump sum price worked out for Standby DG Set as listed in Sch 'A' Part XII |
| 14 | SCHEDULE 'A' PART - XIII MISCELLANEOUS ITEMS is not prepriced by MES and prepriced rates indicates 0.0 under column 5 signifies this fact only. Bidder shall insert their rates in Green filed under Col-6. |
| 15 | Internal Electrification |
| 16 | M & L for maintenance free Chemical earthing of technology with copper bonded steel rod 3 mtr long 25.0 mm dia with 250-micron Copper bonded coating and UL listed. There should be terminal for connection of 150 x 50 x 6 mm with 4 holes of 12 mm dia along with 2 bags of 25 Kgs each of earth enhancing compound. The chemical compound should be tested and certified by any NABL accredited laboratory with 95 percent carbon content. The testing laboratory should be an ISO 9001 and 14001 certified. The earth enhancing compound should be IEC 62321. The ph value of compound should be 7-8. Electrode should be duly tested and certified by CPRI, Govt of India for a min short circuit current of 25 kA rms for 1 Sec. including necessary boring of suitable dia upto required depth in any type of soil for inserting copper rod and filling of chemicals and Poly plastic pit cover of material- polymer body & cover dimensions- 308 mm (L) x 308 mm (W) x 214 mm (H) bearing capacity 7.5 Ton approved from NABL approved Lab complete all as specified and as directed. |
| 17 | Note:- (i) Earthing is to be done infront of the Engr-in-Charge. (ii) Test Results of earthing to be submitted by the contractor for all earthings. (iii) The Contractor shall have to give written guarantee for maintenance earth resistance of less than 1.0 Ohm for the period of 10 (Ten) Years after certified date of completion and shall bdeposited 2000/- per earthing as security deposit for a period of Ten (10) Years. (iv) Failing to maintain resistance of earthing less than 01.0 ohm , new earthing to be provided by the contractor with out any extra cost. (v) Necessary earth work, excavation shall be carried out in any type of soil strata, retuning, filling in and making good surronding area complete. |
| 18 | Road/ Path/ Culvert |
| 19 | Demolition/excavation of existing WBM & SDAC layer (not exceeding 45 cm in depth) for road, including getting out and disposal of excavated material to lead exceeding 50 cm but not exceeding 1.5Km and lift upto 1.5m all as specified and directed. Note: Before commencement of any excavation/demolition of existing WBM/Soiling on the road, the existing ground levels shall be jointly taken by MES and contractor at the interval of 6.25m (longitudinal) and at the interval of 2.375m (transverse). The recorded levels shall be used as the basis for fixing of L profile/transverse profile of the road and computation of excavated/earthwork. |
| 20 | Demolition/excavation of existing Soling/Sub base(not exceeding 30cm in depth) for road, including getting out and disposal of excavated material to lead exceeding 50m but not exceeding 1.5K and lift upto 1.5m all as specified and as directed. |
| 21 | M&L for 200mm (compacted thickness) Granular sub bas (GSB) stabilised using cement forming Cement Treated Sub Base (CTSB) using granite, basalt or trap stone coarse aggregates of grade IV grading as per MoRTH, Table 400-1, stabilised using cement OPC-43 Grade cement content @2%(Exact quantity of cement will be finalized during the design mix stage), mixed in mechanical mix plant at OMC arrived during the design mix stage deposited, spread in uniform layer with mechanical paver and levelled in layers not exceeding 200m thick , compacted using 8 to 12 tonne vibratory roller to achieved minimum 7 day UCS 1.5-3.0 Mpa desired density 98% density as per MoRTH Vth edition clause 401 complete all as specified & directed. (Note: Item is excluding Qty of Cement). |
| 22 | M&L for 150mm (Compacted thickness) Granular Base Course stabilised using cement forming Cement Treated Base (CTB) using granite, basalt or trap stone coarse aggregate grading as per MoRTH (5th Revision), Table 400-4, stabilised using cement OPC-43 Grade cement content @3% (Exact quantity of cement will be finalized during the design mix stage), mixed in mechanical mixer plant at OMC arrived during the design mix stage, deposited, spread in uniform layer with mechanical paver and levelled in layers not exceeding 150mm thick compacted using 8 to 12 tonne vibratory roller to achieve minimum 7 day UCS 4.5-7.0 Mpa desired density 98% density as per MoRTH Vth edition clause 401 complete all as specified & directed. (Note: Item is excluding Qty of Cement). |
| 23 | M&L for providing stress absorbing membrane interlayer (SAMI) in accordance to clause 517 of MoRTH over the CTB layer with elastomeric modified binder (PMB-76-10 conforming to IS-15462-2019) @ 1.2 Kg/Sqm as per IRC-37-2018and dy stone chipping of size 11.2mm sprayed @0.01cum/sqm using hydraulic chip spreader sweeping the surface for uniform spared of aggregate and rolled by pneumatic roller complete all as specified & as directed. |
| 24 | M&L for preparing bituminous surfaces of road and marking 2.5mm thick centre lines, stop lines, dashes, arrows etc and the like n.exe 10 cm wide on road pavements with hot applied thermo plastic road marking paint of approved colour conforming to BS 3262-1989 with special applicator machine all as per manufactures instruction complete all as specified and directed. |
| 25 | Providing and laying non-woven geo textile of 300 Gm/Sqm from high quality polypropylene stable fibres below dry stone on road side berms including fibres are mechanically bonded through needle-punching to from a strong, flexible and dimensionally stable fabric structure with optimum pore sizes and high permeability, resistant to chemical biological organisms, ultra violet radiation and stabilised against degradation having thickness @ 2Kpa, >/ 3.0 tensile strength >/16KN/Mtr, tensile elongation % >/50, CBR puncture resistance >/3000N and all incidental works complete all as specified as per manufactures instruction etc., complete all as specified & as directed. |
| 26 | Sewage Disposal |
| 27 | Laying & Jointing DWCPE (Double corrugated polyethylene) (SN8) pipes of 180mm nominal outer dia and 163 mm internal dia, SN-8 stiffness class, Conf to IS 16098 (part 2) or relevant standards, complete with all specials, rubber ring joints, jointing materials , testing and commissioning, including connection to manhole complete all as specified and as directed. |
| 28 | S&F on site LLDP sub ground structure septic tank of capacity 800 Litres in one single unit, anaerobic type of domestic/semi commercial unit of dia 1100mm, height1450mm with BOD reduction upto approx 70% of the incoming sewage rotationally moulded with moulded in lifting eyes for handling & installation with provisions of manholes covers flexible in and outlet pipe designed to carry sewage & sludge water, excavation in any type of soil, PCC 1:4:8 below foundation, vent shift, connection etc with up flow filter including media complete all as specified and directed as per manufactures the following features shall be follows:-a. Durableb. 100% eco friendlyc. Light weightd. Rust proof/leak proof/corrosion proof/ not prone to crackinge. Completely water & air tight. |
| 29 | M&L Soakage well including excavation in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M-25 concrete including interrupting chamber and screen chamber made of brick masonry in CM, RCC cover slab in M-25/SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size 2.4 mtr dia and 3.0 mtr effective depth complete all as specified & as directed. |
| 30 | S&F SFRC solid manhole cover with cover size 700x1200x70mm & clear opening 600mm with human weight load capacity complete all as specified and as directed. |
| 31 | Area Drainage |
| 32 | S&F Open precast RCC drain M-40 grade, of internal size 450x450m each piece of drain 02 meter long, jointed and pointed in Cm 1:3 complete all as shown on drawings as specified and directed. |
| 33 | External Electric Supply |
| 34 | Supply, installation, Testing and commissioning of Outdoor type (IP 54), 03 way RMU (Ring Main Unit) 11 KV, 630 Amps, 25kA-3 Sec, IP54 SF6 insulated, One side Extensible, consisting of One No (01) motorised vacuum circuit breaker (Incomer) and Two Nos (02) motorised vacuum circuit breaker (Outgoing) & Metering Panel Bus PT with Top LV, Battery & Battery charger, Ethernet switch & LIU (Configuration VVV+M) inside robotically welded stainless steel 304 (Non Ferrite non Magnetic Grade) tank having min thickness 2.5 +/- 0.5mm with IP 67 degree of protection and enhanced BIL of 75 kVp internally to manager voltage surges and Air Insulated Metering Module of Class-0.5. RMU should be provided with internal bus bars, as well as earthing bus bars of electrolytic grade copper, padlock provisions & complete with all accessories. The complete RMU must be type tested for internal arc 21KA for 1 sec with AFLR Classification for Gas tank & Cable Chamber as per IEC 62271-200. HT RMU shall preferably have on-site-repairability features such as site replaceable bushing/ coupling/ mechanism and gas refilling to have very less downtime in the event of bushing breakage and restoration can be done at site immediately without sending the RMU to OEM Works, the Vacuum Interrupter must RMU manufacturer's own make. The earthing bus bar shall be provided inside each cable compartment for solid earthing of cable shields. The outer hinged main door should cover entire front of switchgear including cable doors for providing fail-safe protection complete all as specified and as directed. The unit shall include the following with all necessary standard fitting as required at site- (for Bldg & Street Light)Make of RMU shall be limited to ABB/SIEMENS/SCHNEIDER INFRASTRUCTURE (Channel partner/System Integrator/Authorized Partner/License partner make RMU Shall not be accepted). |
| 35 | Vacuum Circuit Breaker consists of following accessories:- (i) Microprocessor based Numerical Protection Relay for Circuit Breakers – REF615, Feeder Protection and Control Relay, Protections 50, 51, 50N, 51N, 46, 49, 67, 67N, 32, 27, 59, 25, 81U, 81O, 95 Measurement for 3I, I0, 3U, U0, kW, kVA, PF, Hz, Kwh, 16 DI + 10 DO, One front RJ45 Port, One Rear RJ45 Port for IEC-61850 Protocol, Draw out Type with CT Shorting feature, Graphical LCD Display. (ii) Capacitive voltage indication fixed type system with LED for all feeder and FPI in all load break switch feeder. (iii) SF6 Gas pressure indicator on the gas tank. (iv) Operating sequence of VCB must be O-0.3 Sec-CO-3 Mins-CO and suitable for 10,000 mechanical operation. (v) CT shall be minimum 50-100/1A, 2.5VA, 5P10 – 3 Nos. for protection. (vi) CT shall be minimum 50-100/1A, 2.5VA, Class 0.5 – 3 Nos. for metering. (vii) Right angle boot to be provided in each module. (viii) 2 x 12 Volts, 26 AH Battery with Charger – 1 Set. (ix) Bus VT shall be 11KV/√3/110V/√3, 20VA, Class 0.5 – 3 Nos. for metering. (x) Auxiliary VT shall be 11KV/230, 500VA for AC supply input to Battery Charger. |
| 36 | (xi) Capacitive voltage indication fixed type system as per IE. (xii) Interlocked Cable box for front termination of the cable suitable upto 3 core 120 Sqmm, 11 KV XLPE cable (IP3X). Safety interlocked to prevent access to cable termination in live-condition. (xiii) Right angle boots (push on type). (xiv) Cable covers with self interlocking mechanism between doors, earth switch, disc-connector & VCB. (xv) Necessary interlocking arrangement for safety and operations. (xvi) One No. Operating Handle for Manual Operation and one No. manometer. (xvii) Safety Interlocks shall be provided as per relevant IEC/IS Standards and Manufacturer’s directions. (xviii) Above switchgear shall confirm to all relevant IEC/IS Standards. (xix) In addition to above each incomer and outgoing RMU shall have multifunction metre with RS 485 – 01 Nos. (xx) The RMU shall be including all standard metering/accessories and conforming to technical specifications and compatible SCADA/PLC system. (xxi) Breaker ON/OFF function shall be possible through SCADA, all energy measurements shall be available in relay. |
| 37 | S&F for cable route indicator/Marker made up of PCC Block in cement mortar 1:3:6 (20 mm graded aggregate) of size 900x300x100mm thick with DANGER/11KV CABLE/MES embossing on cable route indicator/marker including painting as per approved colour and buries in ground 45 cms including necessary earth work (as required/ordered at site) complete all as specified and as directed. |
| 38 | Supply, fabrication, installation and testing of LT Panel factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, Outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out 3.15 mm thick CRCA sheet of suitable size to accommodate accessories / fittings with front and back double door opening / lockable by the key from both side with IP 65 Protection and provn of suitable bus bar chamber and switch gear compartments for MCCB incoming & out going feeders etc with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC / Epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20 mm graded stone aggregate). All extension link / inter connection shall be insulated with heat shrinkable colour coated sleeves to accommodate and including the following accessories (for Transformer Main LT Panel): |
| 39 | INCOMING:(a) Copper strip bus bar of 320 amps rated capacity wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydro graphic insulators with nuts & bolts at both ends = 04 Nos.(b) MCCB 160 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links – 01 No (Outgoing).(c) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC – 01 set (set of three).(d) Digital Ammeter of range (0–500) Amps, flush mounting type with suitable CT’s of ratio and selector switch – 01 set.(e) Digital voltmeter of range (0–500) volts, flush mounting type with selector switch – 01 No. |
| 40 | OUT GOING:(a) MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links – 02 Nos (for APFC Panel & Spare).(b) MCCB 32 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links – 02 Nos (for High Mast light feeder & Spare).(c) MCB Triple pole & Neutral, 5 to 32 Amps, 415 Volts, 'C' curve, breaking capacity 10 KA with all fixing accessories for both ends spreader links – 08 Nos (for store, Parking shed, Driver’s Room & Security light, feeder & Spare).(d) Multifunctional Digital type Astronomical function time switch (Astro type having longitude and latitude of Indian cities memory) 240 volts AC Single Phase – 01 No.(e) Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm x 150 mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of LT Panel – 01 No.(f) Power contactor 63 Amps, 3 pole 415 volts – 01 No. Please Enable Macros to View BoQ information |
| 41 | OUT GOING:(a) MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links – 02 Nos (for APFC Panel & Spare).(b) MCCB 32 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links – 02 Nos (for High Mast light feeder & Spare).(c) MCB Triple pole & Neutral, 5 to 32 Amps, 415 Volts, 'C' curve, breaking capacity 10 KA with all fixing accessories for both ends spreader links – 08 Nos (for store, Parking shed, Driver’s Room & Security light, feeder & Spare).(d) Multifunctional Digital type Astronomical function time switch (Astro type having longitude and latitude of Indian cities memory) 240 volts AC Single Phase – 01 No.(e) Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm x 150 mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of LT Panel – 01 No.(f) Power contactor 63 Amps, 3 pole 415 volts – 01 No. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-3 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-4 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-5 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-6 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 11 daysCorrigendum-7 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 3 daysCorrigendum-8 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 3 daysCorrigendum-9 Issued
Clarifications on tender conditions and amendments issued.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 11 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 13 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender