Tender For maintenance of Various Colonies Under Nazul Account - Ii Dwarka Zone. Sh:- Rewiring And Compound Lighting Of Community Hall At Bindapur Block E Dwarka & Providing 9 Mtr Street Light G.I. Octagonal Poles Along With Fittings And Other Access
Tender Overview
Project Description
Tender for maintenance of Various Colonies Under Nazul Account - Ii Dwarka Zone. Sh:- Rewiring And Compound Lighting Of Community Hall At Bindapur Block E Dwarka & Providing 9 Mtr Street Light G.I. Octagonal Poles Along With Fittings And Other Accessories To Remove Dark Spots In Front Of Gate No. 10 & 11 Of Yashobhoomi Convention Centre Dwarka.
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 08-Sep-2026 | Corrigendum | Date | 14-Sep-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Rewiring for light point/ fan point/ exhaust fan point/call bell point with 1.5 sq.mm FRLS/HFFR PVCinsulated copper conductor single core cable and 1.5sq.mm FRLS/HFFR PVC insulated copper conductorsingle core cable as earth wire in existing surface/recessed steel/PVC conduit including dismantling asrequired. Group C |
| 2 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required.a)3 x 4 sq. mm (Circuit wiring and Power wiring) |
| 3 | b)2 X 6 sq. mm + 1 X 6 sq. mm earth wire for submain wiring (Excluding conduit) |
| 4 | Supplying and fixing following piano type switch/socket on the existing switch box/cover i/c connections etc as reqd.a) 5/6 A Switch |
| 5 | b)3 pin 5/6 A socket outlet |
| 6 | c)15/16 A switch |
| 7 | d)6 pin 15/16 A socket outlet |
| 8 | Supplying and fixing of minimum 3mm thick phenolic laminated sheet cover i/c cutting for fixing switch , socket , drilling holes etc as required. surface or recess on different size of metal boxes etc as reqd. |
| 9 | Supplying and fixing following way, single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earthbar, din bar, interconnections, powder painted includingearthing etc. as required. (But without MCB/RCCB/Isolator)8 way , Double door |
| 10 | Supplying & fixing 5 AMP to 32 AMP rating 240 /415 volt 'C' curve MCB sutiable for inductive road of following poles in the existing MCB DB complete with connections testing and commisoning etc as reqd.a) Single pole |
| 11 | b) Double pole |
| 12 | Supplying and replacement of 1200 mm sweep size ceiling fan i/c connection, testing etc complete as reqd. |
| 13 | Supplying and installation of 300 mm sweep extra size exhaust fan i/c connection, testing etc complete as reqd. |
| 14 | Supplying and fixing of following sizes of PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as req 20 mm |
| 15 | Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends,CCT 3000°K / 4000°K / 5700°K /6000°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm)18- 22 Watt |
| 16 | Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminum body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP 66,IK-10, CRI >80, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C) 90 Watt |
| 17 | Supplying and fixing of MS pipe of 50 mm dia having 1.5 mtr length to mount the LED fixture i/c clamping , fixing and connection etc, as required, |
| 18 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.3 x 1.5 sq. mm |
| 19 | Supplying of following size of XLPE insulated aluminium Conductor having stranded wire armourd power cable of 1.1 KV grade i/c making, connection testing etc. as reqd.a) 2C x 16 sq.mm |
| 20 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. a) Upto 35 sq.mm |
| 21 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.a) Upto 35 sq. mm |
| 22 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. i) 63 mm dia (OD- 63 mm & ID-51 mm nominal) |
| 23 | Providing boring and laying of HDPE pipes (ISI marked) confirming to IS:4984 with pressure rating of 6kg/Sq.cm by trench less technology with no dig. method by making bore hole in horizontal direction across the road with boring equipment a) 90 mm (outer dia) |
| 24 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 25 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 26 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required |
| 27 | Providing and laying in position, M25 reinforced cement concrete foundation of size 500 mm (L) x 500 mm (W) and 1400 mm (D) i/c excavation of earth, providing cutting, bending and placing in position reinforcement of cold twisted bar of 12 mm dia. 1400 mm long (approx.) – atleast 8 Nos. and reinforcement ring of cold twisted bar of 10 mm dia. 1800 mm long (approx.)- atleast 10 Nos. (with 150 mm spacing) i/c supplying of 4 Nos. M-24 x 700 mm long (150 mm top threaded & 250 mm top galvanized portion) M.S foundation bolt (EN 8-grade) with 3 Nos. nuts and 2 Nos. washer, bolt along with 2 Nos. templates/Anchor plate of size 260 mm x 260 mm x 4 mm thick having 4 Nos. 24 mm dia. holes to match with PCD of poles base plate with positioning of foundation bolts and providing 63 mm (OD) 2 Nos. DWC pipe for cable entry/exit, plastering & painting the foundation above the ground level etc complete as required. |
| 28 | Supplying, replacement, testing and commissioning of HOT Dip galvanized octagonal steel pole of 9 mtr height and made of 3 mm thick sheet, having bottom 155 mm OAF & top 70 mm OAF provided with welded base plate of size 260 mm x 260 mm x 16 mm thick inbuilt control box 1.0 mtr above the base plate, complete with 250mm wide 3 mm thick hot dip galvanised MS strip in octagonal shape welded permanenty around on window cover/junction box i/c providing L-hook in opposite side of control box just below the M.S. strip provided on juncion box/cover box of suitable projection from the pole shaft to prevent the movable junction/cover box going down to the base plate and making a suitable size of hole on above the L-hook (600 mm approx) to hold the junction/cover box during the maintenance i/c covering with MS cover arrangement the hole to prevent entry of rain water through it, complete as per drawing & technical specifications attached & providing following accessories with mounted inbuilt control box having flush cover with 2 nos. mounting strips with tapped holes on existing RCC foundation with bolt and nuts, making connections, interconnections with suitable size of copper wire with thimble/lugs in the connector box, earthing, marking/ numbering of pole etc. complete as per drawing & technical specifications attached including following accessories with mounted inbuilt control box.(a). 6mm thick phenolic laminated/Bakelite sheet inside the window mounted on the existing mounting strips inside the flush door.(b). 1 no. 63 Amp terminal block suitable for following conductor / cable, fixed on DIN channels i/c providing and fixing DIN channel of suitable length – on the existing phenolic laminated / Bakelite sheet.(i) 10 sq mm conductor – 2 nos. (incoming and outgoing looping) (ii) Terminal suitable for 6 SWG GI wire / 2.5 sq mm wire.(c). 6 Amp, SP MCB,10 KA, ‘C’ Series – 1 no. including mountings on DIN channel, Earth stud 2 Nos. welded at suitable height i/c washers, springs washers & nuts etc. (d) Suitable arrangement for saddling of incoming / outgoing cables. Note- Agency will remove existing LED lights from old poles/bracket & will refix thesame on newly installed pole/bracket. |
| 29 | Supplying & fixing of hot dip Galvanized minimum 1000 mm long Bracket (to be installed at 9 mtr height) made out of suitable sized round pipe B-Class on octagonal pipe (3.60 mm Thick), 48 mm outer dia with 400 mm long galvanized overhang with tightening bolts etc. as reqd. Tilt angle shall be around 10 degree.a) Single arm bracket |
| 30 | Supplying & fixing of hot dip Galvanized minimum 1000 mm long Bracket (to be installed at 9 mtr height) made out of suitable sized round pipe B-Class on octagonal pipe (3.60 mm Thick), 48 mm outer dia with 400 mm long galvanized overhang with tightening bolts etc. as reqd. Tilt angle shall be around 10 degree.a) Double arm bracket |
| 31 | Supplying, installation, testing & commissioning of floor mounted free standing type L.T. cubical main feeder pillar (outdoor type) with 200 Amps4 strips Al. bas bars, cable alleys , IP:54 rating dust and varmin proof duly compartmentalized suitable to accommodate the incoming and outgoing switch gears, made out of 2mm thick MS CRCA sheet i/c providing 40 mm x 40 mm x 5 mm thick MS angle iron frame work all around for mounting 4 nos. x 750 mm long 40 mm x 40 mm x 5 mm thick angle iron legs suitably grouting in CC foundation of 1:2:4 ( 1 Cement : 2 Coarse sand : 4 graded stone aggregate 20 mm nominal size with 750 mm deep ( 450 mm in ground and 300 mm above ground level and foundation size exceeding 150 mm on all sides of feeder pillar baseand connections, inter connections with suitable rating copper wires/strips, thimbles/lugs, earthing the body, painting etc complete with following switchgears and accessories as required a) 100 A,30KA,FPMCCB - 1 No (in comer) & 63 amp , 30KA ,FPMCCB - 3 No (out comer) b) Compartment having space for DISCOM energy meter with 6mm thick Bakelite sheet for mounting energy meter.c) Volt meter (0-500V) 96 Sq.mm with selector switch – 1 Setd) Amp-meter (0-100A) 96Sq.mm with selector switch & 100/5 Amp ratio CT's – 1 Sete) Indication Lamp (RYB) with control MCB - 1 set.f) 20/32 amp DP MCB,’C’ Series 10 KA, (out going circuit)- 9 Nos.g) 6 amp SP MCB – 1 No.h) Power contactor, 3 pole, 110 Amp. -1 No. i) Astronomical Timer switch – 1 No.j) Auto/Manual toggle switch – 1 No.k) 200 amp, 4 strip aluminium busbar – 1 Setl) Danger Notice plate – 1 No.m) 6 Pin 15 A Switch / Socket outlet - 1 Set n) Lighting inside the feeder pillar Note: Foundation shall be made as per site requirement for which nothing extra shall be paid. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
TodayBid Submission Deadline
Online submission via eProcurement portal.
TodayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 1 dayTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender