Tender for Replacement Of Life Expired, Power Supply Distribution Panel, Feeder Pillars & Cables At Sanchar Colony, Indira Nagar In Dehradun Oa.
BOQ
| Sl. No. | Item Description |
| 1 | SITC of Powder Coated Double Door , free standing , Weather proof , Cubical type made of 16 SWG MS sheet , back closed Feeder Pillar (Power Distribution panel) suitable for operation on 415V, 3 Phase ,50Hz AC supply ,consisting of following and as per specification and drawing for Power distribution Panel attached I/c interconnection with suitable size pvc insulated copper conductor cable .The Panel shall for suitable for Out door Installation with suitable shade to restrict entry of rain water i/c louvers on both sides to provide cross ventilation for air cooling and grouted the same on existing angle irom from etc as required . |
| 2 | INCOMING |
| 3 | (a) 400 A Rating 4 Pole MCCB with Breaking Capacity 50 KA , Ics=50% of Icu and thermal magnetic release range 320-400 A and Separator Terminals complete as reqd. - 1 nos. Make (L&T/ Schneider Electric / Siemens) |
| 4 | OUTGOING |
| 5 | a250 Amp 4 pole MCCB ,Ics=100% Icu Breaking capacity 36KA at 415 V and thermal magnetic release range 200-250 A and Separator Terminals Complete as reqd = 03 Nos. Make (L&T/ Schneider Electric / Siemens) |
| 6 | a) 125 Amp 4 pole MCCB with Breaking capacity 10KA ,Ics=100% Icu and thermal magnetic release at 415 V and Separator Terminals = 01 Nos. Make (L&T/ Schneider Electric / Siemens) |
| 7 | (b) Digital Voltmeter size 96mmx96mm square flush LED display with inbuilt selector switch suitable for work on 415 V 3 phase AC supply class 1 accuracy etc -1 No |
| 8 | c) 22.5 mm dia LED type Indication lamp suitable for 230V AC Supply -7 No |
| 9 | d) 4 strip 400 Amp Alu bus bar-1 Set |
| 10 | 1.Note Drawing for the panel shall be got approved from Engineer-in-charge before fabrication of panel. The panel shall be fabricated as per specification attached and shall be offered for inspection at factory before dispatch to site. |
| 11 | 2.The ITC of panel shall be carried out as per direction and as per convenience of Site In charge to ensure minimum interruption in AC power supply . |
| 12 | SITC of Powder Coated Double Door , free standing , Weather proof , Cubical type made of 16 SWG MS sheet , back closed Feeder Pillar (Power Distribution panel) suitable for operation on 415V, 3 Phase ,50Hz AC supply ,consisting of following and as per specification attached I/c interconnection with suitable size pvc insulated copper conductor cable .The Panel shall for suitable for Out door Installation with suitable shade to restrict entry of rain water i/c louvers on both sides to provide cross ventilation for air cooling and grouted the same on existing angle iron frame etc as required . |
| 13 | INCOMING |
| 14 | (a) 250 A Rating 4 Pole MCCB with Breaking Capacity 36 KA , Ics=50% of Icu and thermal magnetic release range 200-250 A and Separator Terminals complete as reqd. - 1 nos. Make (L&T/ Schneider Electric / Siemens) |
| 15 | OUTGOING |
| 16 | a) 100 Amp 4 pole MCCB with Breaking capacity 10KA ,Ics=100% Icu and thermal magnetic release at 415 V and Separator Terminals = 07 Nos. Make (L&T/ Schneider Electric / Siemens) |
| 17 | b) 22.5 mm dia LED type Indication lamp suitable for 230V AC Supply -3 No |
| 18 | c) 4 strip 1.00 Mtr long 250 amp alu bus bar-1 Set |
| 19 | 1.Note -Drawing for the panel shall be got approved from Engineer-in-charge before fabrication of panel. The panel shall be fabricated as per specification attached and shall be offered for inspection at factory before dispatch to site. |
| 20 | 2.The ITC of panel shall be carried out as per direction and as per convenience of Site In charge to ensure minimum interruption in AC power supply . |
| 21 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). |
| 22 | 4 way (4 + 12), Double door |
| 23 | S/F of 6 W Surface mounting LED panel square flush model suitable for work on 230 V etc as reqd (Make -Philips /Crompton/Havells /Bajaj/Wipro ). |
| 24 | SITC of 30 Watt Energy Efficient LED type Road Light luminaire with pressure die cast aluminum with mid power LED's as light sources & Heat Resistant toughened glass with frame cover and integral electronic driver complete with IP 65 protection ,min. system efficacy 100 lm/Watt suitable for work on 140-270 V AC Supply i/c ixing on existing GI bracket / Pole and connection i/c removing of existing faulty light etc as reqd (Make -Philips /Crompton/Havells Endura omniplus /Bajaj/Wipro ). |
| 25 | S/F of ABS make moulded weather proof ,shocked proof ,fire retartand ,Compound light control gear box of size 250mmx200mm x100mm suitable for pole mounting and cable entry from bottom side with side hinges door i/c S/F of 6 Amp \\"C \\" Curve SP MCB on Din channel and two no 16A neutral Link i/c dismantling of existing faulty/unserviceable M S Box I/c connection testing etc as reqd (Make SINTEX or SS ) |
| 26 | Supplying and fixing of 10-40A capacity three phase Electronic Energy meter with LCD Display in polycarbonate housing with class 1 accuracy i/c fixing the same ,connection i/c dismantling of existing faulty unit(if reqd) etc as reqd ( Make L&T /HPL/or SS) |
| 27 | Supplying and fixing of 5-30A capacity Single phase Static Energy meter with LCD Display in polycarbonate housing with class 1 accuracy i/c fixing the same ,connection i/c dismantling of existing faulty unit(if reqd) etc as reqd ( Make L&T /HPL/or SS) |
| 28 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 29 | Above 35 sq. mm and upto 95 sq. mm Meter |
| 30 | Above 95 sq. mm and upto 185 sq. mm |
| 31 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required |
| 32 | Above 35 sq. mm and upto 95 sq. mm Meter |
| 33 | Above 95 sq. mm and upto 185 sq. mm |
| 34 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required |
| 35 | Above 35 sq. mm and upto 95 sq. mm Meter (clamped with 25x3mm MS flat clamp) |
| 36 | Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
| 37 | Supplying and making end termination with brass compression gland and aluminum lugs for following size of PVC insulated and PVC sheathed / XLPE aluminum conductor cable of 1.1 KV grade as reqd |
| 38 | 4 x16 Sq.mm.(28mm) |
| 39 | 3 1/2 x35 sqmm (32mm) |
| 40 | 3 1/2 x50 sqmm (35mm) |
| 41 | 3 X 95 sq. mm (38mm) |
| 42 | 3 X 120 sq. mm (45mm) |
| 43 | 3 X 185 sq. mm (57mm) |
| 44 | Providing and fixing Powder coated painted profile sheets of of 0.45mm thick of size 10 ft x 3.5 ft epoxy primer on both side of the sheet .The sheet shall be fixed using self-drilling /self-tapping screws of size (5.5x 55 mm) with EPDM seal, complete including cutting to size and shape wherever required. |
| 45 | Providing steel Structural fabrication work bolted or welded in built up sections, and framed work, for Shed of Panel to protect from rain water made out of following sections i/c fixing in position and applying a priming coat including painting with synthetic enamel paint al least two coats all complete. |
| 46 | 35mmx35mmx5 mm thick angle iron |
| 47 | 50mmx50mmx5 mm thick angle iron Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 31, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 14, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
TodaySep 15, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 1 dayTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender