Tender for As And As Of External Power Supply At Old Guard Room Area At installation Kalinga Under Ge (P) (N) Kalinga
BOQ
| Sl. No. | Item Description |
| 1 | Dismantling of 4 Pole Structure and any type of cable disconnected with jummper and GOD and Any type of Channel and any type insulator and all frame work of following complete and loading transporting as directed by Engr-in -charge.Note :-(i) All XLPE Cable Any Type disconnected and Carefully complete.(ii) All Channel are Dismantling and safely removing to Insulator etc.(iii) 4 Pole Structure are removing below ground level .(iv) Structure supporting Guy Removing ground level complete. (v) Jummper and connected accesories complete.(vi) HT electrical panel / Transformer / RMU and cable etc as required to disconnected at site all as specified and directed. |
| 2 | Excavation in trenches not exc.1.5m wide and not exceeding 1.5 m depth and getting out hard / dense soil for laying of under ground cable and including taking out of cable, cable cover complete all as specified and directed. |
| 3 | Excavation in trenches not exc.1.5m wide and not exceeding 1.5 m depth and getting out soft / loose soil for laying of under ground cable and including taking out of cable, cable cover complete all as specified and directed. |
| 4 | Returning and filling in soils and including spreading, levelling, watering and well ramming in layers each not exceeding 25 cm thick complete all as specified and directed. |
| 5 | Removing excavated soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed. |
| 6 | Supply and laying reinforced precast concrete cable cover class HV type 1, flat size 300 x 180 x 40 mm complete all as specified and directed. |
| 7 | Supply and spread clean dry river sand as cable cushioning for protection of cable to be laid in trenches / transformer yard / two pole structure complete all as specified and directed.Note: Punned thickness shall be measured. |
| 8 | Labour charges for re-laying of serviceable bricks of any size and type recovered during taking out of old cable , over newly laid or re-laid cables complete all as specified and directed. |
| 9 | Supplying, laying and testing HT UG cable [earthed], XLPE insulated, screened, steel strip armoured and pressure extruded PVC bedded, 11000 Volts grade [heavy duty] with aluminium conductor of size 3 Core 185 Sqmm laid in trenches / ducts, passing through pipes and connecting up complete all as specified and as directed. |
| 10 | S & F Cable Jointing Kit for 11 KV (earthed) grade XLPE cable for straight through joint heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm including testing after jointing complete all as specified and as directed. |
| 11 | S & F Cable Jointing Kit for HT 11 KV (earthed) grade XLPE cable for outdoor end termination heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm including testing after jointing complete all as specified and as directed. |
| 12 | Earthing complete with Galvanized steel earth plate electrode of size 600x600x6mm thick buried directly in ground with earth pit not less than 2.25m deep below the normal ground level with top edge of plate not less than 1.5m below normal GL connected to galvanised earth strip of size 32x6mm as earth lead by means of bolts, nuts, check nuts and washers of Galvanized iron or steel all as shown in electrical plate No. 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on ompletion including taking out old earthing and as directed.[Note: The unit rate shall be deemed to include for excavation & earth work in any type of soil, PCC (1:3:6) type C1 chamber, MS angle iron frame 40x40x6mm, RCC 1:2:4 type B-1 cover 40mm thick with 8mm dia steel reinforcement bars at 150mm c/c both ways, MS handle 12mm dia, CI funnel and wire mesh, GI watering pipe 20mm dia medium grade for watering, GI protection pipe light grade 40mm dia, earthing lead upto 7.5m including providing charcoal or coke and common salt in alternate layers of 15cm compacted thickness all around the electrode complete all as specified in preambles of SSR Part-II and as shown in plate No. 3 of SSR Part-I.] |
| 13 | Supply and replace of GI strip 32 mm x 6 mm complete with with porcelain insulator saddles 1.5 spacing and fixing screws for fitting the strip fixed on wall, floor or roof all as directed. |
| 14 | Supplying, Installing, Testing & Commissioning of 8 way RMU (2 incoming + 6 outgoing), 12KV, 630 Amps, outdoor, extensible type, SF6 Insulated, consisting of 02 Nos 630 Amps VCB, fixed, non draw out type as incoming and 06 Nos 630 Amps VCB as outgoing complete all specified and as directed comprising of the following:- |
| 15 | [A] RMU shall be floor mounted, 12 KV, 630 Amps, 21 kA for 3 Seconds, SF6 Insulated, Motorized, Outdoor extensible type, RMU with Air Insulated Bus Connected Metering unit, Type tested in line with latest IEC Standards, suitable for operations at a height up to 1000m above sea level and Ambient Temperature range from 5ºC to 50ºC without any de-rating, Switchgear and Busbar shall all be contained in a Stainless Steel Enclosure [Minimum 2.0mm thick SS 304 Grade] filled with SF6 at 0.3 Bar [300 hPa] Relative Pressure, RMU Tank shall provide Full Insulation and Switchgear shall be insensitive to the environment with Degree of Protection of IP67, Switchgear Operating Mechanism shall have an IP2X Protection and Cable Chamber shall have IP3X Protection, Outer Enclosure shall be IP 54 type tested, Powder Coated with Pure Polyester Based Paint, suitable for the site installation conditions, Accidental Overpressure due to an Internal Arc is limited by the opening of the safety valve, at the bottom of the metal enclosure, away from the operator, Plug in type of extensibility must be provided and coupling busbar should not be exposed to air to avoid oxidation of busbars. Extension of cubicle shall require 450mm to handle and the gap between the coupled RMU’s must be within 10mm. |
| 16 | [B] Each Vacuum Circuit Breaker [VCB] shall be comprising of the following: [i] 11 KV, 630 Amps, 21 kA/ 3s, 3 Pole Motorised VCB (Non draw out type) with 3 pole manual disconnector and 3 pole manual earth switch, Motorized Spring Assisted Mechanism and Series Trip Coil – 1 No. [ii] Self Powered Relay with auxiliary supply arrangement with O/C, S/C, E/F Protection. Relay shall have a Front USB for Laptop Interface, LCD Display, 10 Event Records, 5 Fault Records, min 2 setting group and keypad for setting parameters for the relay with Zero time delay for I>>, I>>>, I0>> & I0>>> setting groups - 1 No[iii] Resin Cast ring core Protection CT, Plate mounted type : 100-50/1+1A, 0.5,5P10, 2.5 VA-01 Set.[iv] Live Cable Indicator with indications at the Front and Three Inlets to check the Synchronization of Phases – 1 No[v] Making capacity - 52.5 kAp[vi] Cable Termination Bushing suitable for up to 1 Run, 3 Core, 240 Sq.mm, XLPE Cable – 1 Set[vii] Cable Termination Cover Boots [Push on type] – 1 Set |
| 17 | [viii] Circuit Breakers shall have Two Positions: Open or Disconnected and Closed. A separate and independent 3 Position Earthing Switch and disconnector shall be fitted to open and earth the cables in such way that interlocks prevent all unauthorised operations. An operating mechanism shall be used to manually close the circuit breaker and charge the mechanism in a single movement. An independent mechanism shall be fitted for the 3 Positions Earthing Switch and Disconnector Circuit breaker shall be fitted with a local system for manual tripping by an Integrated Push Button. There shall be no automatic reclosing. Circuit Breaker shall have a min of 2000 Mechanical and Electrical Operations. |
| 18 | [C] Air Insulated Bus Connected Metering Unit comprising the folloing:[i] Air Insulated Enclosure with necessary Bus Connection – 1 No[ii] PT 11KV / √3 / 110V / √3, 50 VA, Class-1.0 – 1 Set[iii] Multi Function Meter, Digital Type [Displaying A, V, PF, Hz, KVA, KW, KVAR, KWH, KVARH etc. Class 1.0 / 0.5] with RS485 Port for Communication in Modbus Protocol. - 01 Set[iv] R / Y / B Indicating Lamps – 1 Set[v] 11 KV / 230V AC, Class 1, 500VA Control Transformer fitted with surge suppressor– 1 No[vi] Battery and Battery Charger, 12 Ah, [I/P-230V AC, O/P - 24V DC] – 1 No |
| 19 | Notes:[a] An operator situated in front, lateral and rear [A-FLR 21 kA – 1 Sec, Downwards Exhaust, for Tank as well as Cable Compartment] of the RMU Switch board during an internal fault shall not be exposed to the effects of Arcing. Internal ARC Type Test Report for IAC AFLR 21 kA for 1 Sec for both Tank & Cable Box shall be submitted.[b] All operations shall be from front of the RMU, including access to cable bushings. Bushings along the sides or the rear of the RMU are not acceptable.[c] Construction of Plinth / Foundation for 11KV RMU should be as per site / manufacturer instructions / recommendations. The rate quoted by the tenderer shall deemed to inclusive of foundation.[d] The rate quoted is also deemed to be including the cost of disconnection of HT Cables up to 3 Core, 240 Sq.mm from existing 2 Pole / 4 Pole Structures, removing of cable loop and reconnection to RMU complete all as specified and as directed by the Engineer-in-Charge. |
| 20 | [e] End termination joints shall be measured and paid separately.[f] There should be electrical interlock established between both incomers ensuring one incomer only switched on at any time. In addition pad locking facility to be provided in both incomers. Rate includes pad lock (2 lock & 1 key)[g] The make of RMU/ VCB/ vacuum interrupter/ Relays/ FRTU offered shall be of same make. Different makes shall not be accepted. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 31, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 21, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 10 daysSep 28, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 17 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender