Tender For Repair / Replacement / Maintenance Of Street / Security Lights, Cables, Lt Poles, Acsr Conductor, Painting Of Panel Boards, Poles And Misc E/M Works At Mic&S Under Ge(S) Ahilyanagar
Tender Value
46 Lakhs
Estimated cost
Bid Submission
18 Sep 2026
2 days left
EMD
92000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Ahmednagar → Maharashtra
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair / Replacement / Maintenance Of Street / Security Lights, Cables, Lt Poles, Acsr Conductor, Painting Of Panel Boards, Poles And Misc E/M Works At Mic&S Under Ge(S) Ahilyanagar
BOQ
| Sl. No. | Item Description |
| 1 | Earth work in excavation in trenches in all kind of soil by mechanical means (Hydraulic excavator) / manual means, in foundation trenches not exceeding 1.5 m in width including dressing of sides and ramming of bottoms, for lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil, within a lead of 50 m complete all as specified and as directed. |
| 2 | Earth work in excavation in trenches in all kind of soil by mechanical means (Hydraulic excavator) / manual means, in foundation trenches not exceeding 1.5 m in width, exceeding 1.50 m and not exceeding 3m in depth including dressing of sides and ramming of bottoms and lift upto 3m, including getting out the excavated soil and disposal of surplus excavated soil, within a lead of 50 m complete all as specified and as directed. |
| 3 | Returning, filling in excavated material (soil) including spreading, levelling, watering and well ramming in layers not exc 25 cm all as specified and as directed. |
| 4 | Supply and laying Double Walled Corrugated (DWC) HDPE pipe of nominal bore 50mm including 90 degree bends with coupler and rubber ring, conforming to IS :16205 Part 24 Type 450N, laid in trenches for cable protection complete, all as specified and as directed. |
| 5 | Supply and laying Double Walled Corrugated (DWC) HDPE pipe of nominal bore 63mm including 90 degree bends with coupler and rubber ring, conforming to IS :16205 Part 24 Type 450N, laid in trenches for cable protection complete, all as specified and as directed. |
| 6 | Supply and laying Double Walled Corrugated (DWC) HDPE pipe of nominal bore 120mm including 90 degree bends with coupler and rubber ring, conforming to IS :16205 Part 24 Type 450N, laid in trenches for cable protection complete, all as specified and as directed. |
| 7 | Supply and laying in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 240 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete including taking out old unserviceable cable from trenches/poles etc, alongwith protection covers all as specified and as directed. |
| 8 | Supply and laying in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 185 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete including taking out old unserviceable cable from trenches/poles etc, alongwith protection covers all as specified and as directed. |
| 9 | Supply and laying in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 150 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete including taking out old unserviceable cable from trenches/poles etc, alongwith protection covers all as specified and as directed. |
| 10 | Supply and laying in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 120 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete including taking out old unserviceable cable from trenches/poles etc, alongwith protection covers all as specified and as directed. |
| 11 | Supply and laying in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 95 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete including taking out old unserviceable cable from trenches/poles etc, alongwith protection covers all as specified and as directed. |
| 12 | Supply and laying in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 70 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete including taking out old unserviceable cable from trenches/poles etc, alongwith protection covers all as specified and as directed. |
| 13 | Supply and laying in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 50 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete including taking out old unserviceable cable from trenches/poles etc, alongwith protection covers all as specified and as directed. |
| 14 | Supply and laying in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 35 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete including taking out old unserviceable cable from trenches/poles etc, alongwith protection covers all as specified and as directed. |
| 15 | Supply and laying in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 25 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete including taking out old unserviceable cable from trenches/poles etc, alongwith protection covers all as specified and as directed. |
| 16 | Supply and laying in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 16 Sqmm, 4 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete including taking out old unserviceable cable from trenches/poles etc, alongwith protection covers all as specified and as directed. |
| 17 | Supply and laying in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 10 Sqmm, 2 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete including taking out old unserviceable cable from trenches/poles etc, alongwith protection covers all as specified and as directed. |
| 18 | S&F in replacement 80 mm bore galvanised steel tubing, light grade, ISI marked, for protection of under ground cable on pole/wall/under road including clamps where reqd and taking out old unserviceable pipe complete all as specified and as directed. |
| 19 | S&F in replacement 50 mm bore galvanised steel tubing, light grade, ISI marked, for protection of under ground cable on pole/wall/under road including clamps where reqd and taking out old unserviceable pipe complete all as specified and as directed. |
| 20 | S&F in replacement 40 mm bore galvanised steel tubing, light grade, ISI marked, for protection of under ground cable on pole/wall/under road including clamps where reqd and taking out old unserviceable pipe complete all as specified and as directed. |
| 21 | M&L for heat shrinkable straight through cable joint kit suitable for 10 to 16 Sqmm 4 core LT XLPE cable 1100 Volts grade complete with jointing material and accessories and testing including necessary excavation / earth work complete all as specified and as directed. |
| 22 | M&L for heat shrinkable straight through cable joint kit suitable for 25 to 50 Sqmm 3.5 core LT XLPE cable 1100 Volts grade complete with jointing material and accessories and testing including necessary excavation / earth work complete all as specified and as directed. |
| 23 | M&L for heat shrinkable straight through cable joint kit suitable for 70 to 120 Sqmm 3.5 core LT XLPE cable 1100 Volts grade complete with jointing material and accessories and testing including necessary excavation / earth work complete all as specified and as directed. |
| 24 | M&L for heat shrinkable straight through cable joint kit suitable for 150 to 185 Sqmm 3.5 core LT XLPE cable 1100 Volts grade complete with jointing material and accessories and testing including necessary excavation / earth work complete all as specified and as directed. |
| 25 | M&L for heat shrinkable straight through cable joint kit suitable for 240 Sqmm 3.5 core LT XLPE cable 1100 Volts grade complete with jointing material and accessories and testing including necessary excavation / earth work complete all as specified and as directed. |
| 26 | Supply, install in replacement and testing out door wheather proof bus bar chamber of size 100 cm x 60cm x 30cm made out of 3.15mm CRCA MS sheet having one side openable hinged door shutter with locking arrangement/provn of two nos 80cm long 40x40x6mm anlge iron legs welded and 04 nos Aluminium bus bar of 200Amp rating including provn of one MCCB TPN 100 Amp 25 KA for controlling Electric supply complete erected on ground with necessary PCC 1:3:6 type C2 foundation complete bus bar chamber painted with two coats of approved enamel paints over one coat of primer including making cable connection with necessary gland , lugs/thimbles complete all as specified and as directed. |
| 27 | Supply and erection in replacement steel tubular swaged poles with MS base plate 6 mm thick of size 300 x 300 mm, finial tapper plug, bolts, nuts & screws as specified type 410 SP-31, 9.00 Mtr long, made out of ERW MS tubing conforming to IS-2713 Part II including drilling holes of required size for fixing cross arms etc erected in true vertical position, including one coat of red-oxide zinc chrome primer and two coats of aluminium paint on surfaces exposed to view and making 30cm wide strips (total 5 Nos) with yellow and black paint alternately on external surface above PCC benching and painting with bituminous paint internally including writing the pole number in white letters on black background complete and externally for portion embedded in PCC, complete all as specified and as directed. Note:- Excavation & earthwork and PCC in foundation of poles,coping etc shall be measured and paid under respective item. |
| 28 | M & L PCC 1:3:6 type C2 using 40 mm graded stone aggregate for foundation of pole/stays complete all as specified and as directed by Engineer-in-Charge. |
| 29 | M&L for PCC 1:2:4, type B1, using 20 mm graded stone aggregates as in coping of pole and similar work etc including necessary formwork and finishing even and smooth without using extra cement complete all as specified and as directed. |
| 30 | M& stay assembly comprising of 16 mm dia stay rod, 1800 mm long, loop type insulator of size 65 mm x 90 mm, galvanised stay plate 6 mm thick of size 250 x 250 mm and stay bow & dismantling of old Stay assembly complete all as specified and directed & as shown in Electrical Plate No. 1 of SSR Pt I complete all as specified and as directed. Note : Excavation/earth work PCC shall be measured and paid seperately. |
| 31 | M&L for Galvanised stay strand 7/3.15 mm complete all as specified and directed by Engr in Charge. |
| 32 | M&L in repairs/replacement earthing complete with galvanized steel earth plate electrode 60 cm X 60 cm X 6.0 mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below ground level, connected to and including galvanized earth strip 25mmx4mm upto 7.5 m by means of bolts, nuts, check nuts and washers made of galvanised iron and protected by light grade 32mm dia GI pipe connected to main control board, including provision of concrete pit in PCC (1:2:4) type B-1 using 20 mm graded stone aggregates with 40 mm thick RCC (1:2:4) cover with reinforced with XPM (weight not less than 4 Kg / Sqm) and frame of angle iron 25mm X 25 mm X 3mm with lugs 2 Nos and with 6 mm dia MS bar handle made to shape, GI light grade 20 mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, 15cm thick alternate layers of common salt and charcoal filling all around the plate, test point made out of phosphorus bronze with fixing arrangement, funnel, wire mesh and earth work in hard/dense soil, returning filling in and removal of surplus soil to a distance not exceeding than 50 mtr, all as per electric plate No 3 of SSR Part I 2009 and connection to earth test point all as specified including testing on completion. |
| 33 | Disconnecting of electric supply from over head line and removing existing binding wire and ACSR conductor and restringing of ACSR conductor including binding of conductor on insulator with new binding wire & reconnecting the electric supply complete all as specified and as directed by Engr-in-charge. |
| 34 | S&F line separators for two conductors complete all as specified and as directed. |
| 35 | S&F line separators for three conductors complete all as specified and as directed. |
| 36 | S&F line separators for four conductors complete all as specified and as directed. |
| 37 | S&F in repairs cross arms, bracings, support channel, backplate hooks etc fabricated from structural steel sections (MS angle, Channel) of required size and shape including nuts, bolts, washers, welding, bending, cutting cold or hot, drilling holes for inserting bolts as indicated and directed including painting with one coat of red oxide primer and two coats of silver aluminium paint complete all as specified and as directed by Engr-in-Charge. |
| 38 | S&F in repairs pin type porcelain vitreous brown/white insulator with approved make including one galvanised MS spindle two GI washers and GI nut of size 100 mm height and 65 mm dia 1100 Volt grade including taking out old unserviceable insulator complete all as specified and as directed. |
| 39 | S&F in repair shackle type porcelain vitreous brown/white insulator with approved make including galvanised MS strip washers, insulated bolts, washers nut of size 75 mm height 90 mm dia for 1100 volt grade including taking out of old unserviceable insulator complete all as specified and as directed. |
| 40 | S&F in repairs aluminium conductor steel reinforced, any size, (Weasel/ Ferret/ Squirrel as required) including stringing, binding, jointing, jumpering etc on insulators or on poles with minimum sag including dismantling old ACSR conductor from LT pole complete all as specified and as diercted. |
| 41 | Material and labour for preparation of surfaces for LT pole painting by scrapping damaged paint and painting with two coats of silver aluminium paint and alternate painted strip of 30 cm width of colour as approved by Accepting officer upto 1.5 meter height from bottom of the pole and writing pole No with black paint on yellow circuit complete all as specified and as directed by Engineer-in-Charge. |
| 42 | Trimming of tree branches touching to the LT/HT over head line or near to the LT/HT over head line as per the direction of AGE E/M/JE incharge complete including removing the tree branches from site complete all as specified and directed.Note : (i) Written shut down shall be obtained from concerned JE/AGE (E/M) before taking the trimming work in hand by contractor. (ii) Span from one pole to next pole (30 to 50 RM) will be considered as a one Job.(iii) Any damage caused due to negligence of workmen shall be rectified by thecontractor without any extra payment.(iv) T & P such as ladder, rope, cutter, axes and other related materials shall be provided by the contractor. |
| 43 | M&L for surface dressing n.exc 15 cm deep and removing rubbish to distance n.exc 50m including cleaning of bushes/small plants up to root level, around and surrounding area of E/M installations (i.e two pole / four pole structures, out door substation yards & misc E/M installations) complete all as specified and as directed by Engr-in-charge. |
| 44 | M&L for disconnecting burnt LT cable from MCCB/Main switch/OH line etc and cleaning the bus bar and removing carbon and rusted nut bolts etc complete and reconnecting the LT cable after replacement of aluminium lugs, glands etc for LT under ground cable of size 16 sqmm 3.5 core complete all as specified and as directed. |
| 45 | M&L for disconnecting burnt LT cable from MCCB/Main switch/OH line etc and cleaning the bus bar and removing carbon and rusted nut bolts etc complete and reconnecting the LT cable after replacement of aluminium lugs, glands etc for LT under ground cable of size 25 sqmm 3.5 core complete all as specified and as directed. |
| 46 | M&L for disconnecting burnt LT cable from MCCB/Main switch/OH line etc and cleaning the bus bar and removing carbon and rusted nut bolts etc complete and reconnecting the LT cable after replacement of aluminium lugs, glands etc for LT under ground cable of size 35 sqmm 3.5 core complete all as specified and as directed. |
| 47 | M&L for disconnecting burnt LT cable from MCCB/Main switch/OH line etc and cleaning the bus bar and removing carbon and rusted nut bolts etc complete and reconnecting the LT cable after replacement of aluminium lugs, glands etc for LT under ground cable of size 50 sqmm 3.5 core complete all as specified and as directed. |
| 48 | M&L for disconnecting burnt LT cable from MCCB/Main switch/OH line etc and cleaning the bus bar and removing carbon and rusted nut bolts etc complete and reconnecting the LT cable after replacement of aluminium lugs, glands etc for LT under ground cable of size 70 sqmm 3.5 core complete all as specified and as directed. |
| 49 | M&L for disconnecting burnt LT cable from MCCB/Main switch/OH line etc and cleaning the bus bar and removing carbon and rusted nut bolts etc complete and reconnecting the LT cable after replacement of aluminium lugs, glands etc for LT under ground cable of size 95 sqmm 3.5 core complete all as specified and as directed. |
| 50 | M&L for disconnecting burnt LT cable from MCCB/Main switch/OH line etc and cleaning the bus bar and removing carbon and rusted nut bolts etc complete and reconnecting the LT cable after replacement of aluminium lugs, glands etc for LT under ground cable of size 120 sqmm 3.5 core complete all as specified and as directed. |
| 51 | M&L for disconnecting burnt LT cable from MCCB/Main switch/OH line etc and cleaning the bus bar and removing carbon and rusted nut bolts etc complete and reconnecting the LT cable after replacement of aluminium lugs, glands etc for LT under ground cable of size 150 sqmm 3.5 core complete all as specified and as directed. |
| 52 | M&L in repairs to LT panel boards complete with necessary welding works to doors, replacement of unserviceable hinges and aldrop bolt complete and painting with one coat of synthetic enamel paint of approved colour internally and externally complete all as specified and as directed by Engr-in-charge. |
| 53 | M&L for replacement of damaged sheet of panel board of size not less than 0.6m x 0.75m made of 14 SWG MS powder coated sheet to match to existing including bending, cutting, pressing to required size and shape complete all as specified and as directed by Engr-in-charge. |
| 54 | M&L for MCCB TPN 63 amps capacity, breaking capacity 16 KA at 415 volt 50 Hz AC supply including necessary modification in panel board if required to fix the MCCB complete with replacement of incoming and out going cable connection with lugs, aluminium conductor cable of proper size, nuts bolts including taking out old unserviceable MCCB TPN from existing LT panel board complete all as specified and as directed by Engr-in-charge. |
| 55 | M&L for MCCB TPN 100 amps capacity, breaking capacity 16 KA at 415 volt 50 Hz AC supply including necessary modification in panel board if required to fix the MCCB complete with replacement of incoming and out going cable connection with lugs, aluminium conductor cable of proper size, nuts bolts including taking out old unserviceable MCCB TPN from existing LT panel board complete all as specified and as directed by Engr-in-charge. |
| 56 | M&L for MCCB TPN 160 amps capacity, breaking capacity 25 KA at 415 volt 50 Hz AC supply including necessary modification in panel board if required to fix the MCCB complete with replacement of incoming and out going cable connection with lugs, aluminium conductor cable of proper size, nuts bolts including taking out old unserviceable MCCB TPN from existing LT panel board complete all as specified and as directed by Engr-in-charge. |
| 57 | M&L for MCCB TPN 400 amps capacity, breaking capacity 36 KA at 415 volt 50 Hz AC supply including necessary modification in panel board if required to fix the MCCB complete with replacement of incoming and out going cable connection with lugs, aluminium conductor cable of proper size, nuts bolts including taking out old unserviceable MCCB TPN from existing LT panel board complete all as specified and as directed by Engr-in-charge. |
| 58 | S&F in repairs 415V MCB TPN 100 Amps 10 KA 'C' complete with connection, testing and commissioning complete all as specified and as directed. |
| 59 | Supply, install, testing and commissioning in replacement, factory made and tested (including CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted, compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated aluminium bus bars 250 amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 50x50x6mm angle iron , powder coated, Front and rear opening type with aprons for cable entry with double door shutter and locking arrangement with including cable gland, lugs, jointing material etc and jointing, connecting, testing and commissioning and including following items. (Notes :The rate quoted shall include for Cost of dismantling/ taking down old unserviceable LT feeder piller, earth work & excavation for angle iron frame for foundation of panel board upto 0.50 m below GL in any type of soil & PCC (1:4:8), D2 filling in foundation the ground clearance of panel board shall be 0.40 m GL to the bottom of panel board ). |
| 60 | Incoming: (a) MCCB 160 amps, 4 pole, 36 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 No. (b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 250 Amp, 4 pole, not less than 60cm long mounted on insulators for incoming supply-01 No (c) Digital volt and ammeter with selector switch and CT's set - 01Set. (d) Neon indicating lamps (R, Y & B) -01 Set Outgoing: (a) MCCB 100 amps, 4 pole, 16 KA with adjustable thermal release, 50 Hz, 415 volts grade - 1 No.(b) MCCB 63 amps, 4 pole, 16 KA with adjustable thermal release, 50 Hz, 415 volts grade - 4 No. |
| 61 | Supply, install, testing and commissioning in replacement, factory made and tested (including CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted, compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated aluminium bus bars 150 amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 50x50x6mm angle iron , powder coated, Front and rear opening type with aprons for cable entry with double door shutter and locking arrangement with including cable gland, lugs, jointing material etc and jointing, connecting, testing and commissioning and including following items. (Notes :The rate quoted shall include for Cost of dismantling/ taking down old unserviceable LT feeder piller, earth work & excavation for angle iron frame for foundation of panel board upto 0.50 m below GL in any type of soil & PCC (1:4:8), D2 filling in foundation the ground clearance of panel board shall be 0.40 m GL to the bottom of panel board ). |
| 62 | Incoming: (a) MCCB 100 amps, 4 pole, 25 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 No. (b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 150 Amp, 4 pole, not less than 60cm long mounted on insulators for incoming supply-01 No.(c) Digital volt and ammeter with selector switch and CT's set - 01Set. (d) Neon indicating lamps (R, Y & B) -01 Set Outgoing: (a) MCCB 32 amps, 4 pole, 16 KA with adjustable thermal release, 50 Hz, 415 volts grade - 10 No. |
| 63 | Supply, install, testing and commissioning in replacement, factory made and tested (including CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted, compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated aluminium bus bars 300 amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 50x50x6mm angle iron , powder coated, Front and rear opening type with aprons for cable entry with double door shutter and locking arrangement with including cable gland, lugs, jointing material etc and jointing, connecting, testing and commissioning and including following items. (Notes :The rate quoted shall include for Cost of dismantling/ taking down old unserviceable LT feeder piller, earth work & excavation for angle iron frame for foundation of panel board upto 0.50 m below GL in any type of soil & PCC (1:4:8), D2 filling in foundation the ground clearance of panel board shall be 0.40 m GL to the bottom of panel board ). |
| 64 | Incoming: (a) MCCB 250 amps, 4 pole, 36 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 No. (b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 300 Amp, 4 pole, not less than 60cm long mounted on insulators for incoming supply-01 No.(c) Digital volt and ammeter with selector switch and CT's set - 01Set. (d) Neon indicating lamps (R, Y & B) -01 Set Outgoing: (a) MCCB 160 amps, 4 pole, 16 KA with adjustable thermal release, 50 Hz, 415 volts grade - 1 No.(b) MCCB 100 amps, 4 pole, 16 KA with adjustable thermal release, 50 Hz, 415 volts grade - 3 No. |
| 65 | Supply and fixing Cable route indicator made out cast iron and embedded LT Cable on the plate of size 80 mm dia 5 mm thick with angle iron legs of 0.3 metre and grouting leg in PCC 1:3:6 foundation of suitable size complete all as directed and directed by Engineer in Charge. |
| 66 | S&F in replacement, manual change over switch, 415 Volt, sheet metal enclosure, 4 Pole of capacity 63 Amps with connecting acessories complete all as specified and as directed . |
| 67 | S&F in replacement, manual change over switch, 415 Volt, sheet metal enclosure, 4 Pole of capacity 100 Amps with connecting acessories complete all as specified and as directed . |
| 68 | S&F in replacement, manual change over switch, 415 Volt, sheet metal enclosure, 4 Pole of capacity 200 Amps with connecting acessories complete all as specified and as directed . |
| 69 | S&F in repairs, 4 Pole Power Contactor having AC-1 Rating 200 Amps suitable for operation on 415 Volts 50 Hz, AC supply complete all as specified and as directed. |
| 70 | M&L for disconnecting and taking down unserviceable street light fittings/gate lights & garden lights of any type/rating from pole or wall dismantling the same for necessary repair or replacment of unserviceable spares complete and refixing, connecting and testing the same complete all as specified and as directed.Notes:- (i) Spares/accessories required for replacement shall be measured and paid seprateley as supply only under respective items of BoQ. (ii) The cost of T&P required for repair/ mantenance such as ladder, vehicle like crane, manpower etc, shall deemed to be included in the unit rate quoted. |
| 71 | Supply only LED drivers compatible with industrial & outdoor LED fixtures/Sign boards as per existing make and model suitable for 30 Watt LED fitting complete all as specified and as directed. |
| 72 | Supply only LED drivers compatible with industrial & outdoor LED fixtures/Sign boards as per existing make and model suitable for 50 Watt LED fitting complete all as specified and as directed. |
| 73 | Supply only LED drivers compatible with industrial & outdoor LED fixtures/Sign boards as per existing make and model suitable for 60 Watt LED fitting complete all as specified and as directed. |
| 74 | Supply only LED drivers compatible with industrial & outdoor LED fixtures/Sign boards as per existing make and model suitable for 90 Watt LED fitting complete all as specified and as directed. |
| 75 | Supply only LED drivers compatible with industrial & outdoor LED fixtures/Sign boards as per existing make and model suitable for 120 Watt LED fitting complete all as specified and as directed. |
| 76 | Supply only LED drivers compatible with industrial & outdoor LED fixtures/Sign boards as per existing make and model suitable for 150 Watt LED fitting complete all as specified and as directed. |
| 77 | S&F in replacement PVC insulated and over all PVC sheathed, stranded copper conductor wire 1.5 sqmm x 3 core, ISI marked complete from light fitting to pole junction box complete all as specified and as directed. |
| 78 | Supply and fixing GI pipe bracket light grade of 40mm dia ISI marked duly bent to shape with an angle including clamps, nuts, bolts, washers etc complete and taking out of existing old u/s brackets ofcomplete all as specified and directed by Engineer-in-Charge. (Note: - The total length of the bracket shall be 1.5m) |
| 79 | Supply and fixing GI pipe bracket light grade of 50mm dia ISI marked duly bent to shape with an angle including clamps, nuts, bolts, washers etc complete and dismantling of existing old u/s brackets of complete all as specified and directed by Engineer-in-Charge. (Note: - The total length of the bracket shall be 1.5m) |
| 80 | S&F 1100 volts grade heavy duty cable, 4 sqmm 2 core, PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections twin core cable flat stranded conductor including taking down old unserviceable cable complete all as specified and directed. |
| 81 | S&F 1100 volts grade heavy duty cable, 6 sqmm 2 core, PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections twin core cable flat stranded conductor including taking down old unserviceable cable complete all as specified and directed. |
| 82 | S&F 1100 volts grade heavy duty cable, 10 sqmm 2 core, PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections twin core cable flat stranded conductor including taking down old unserviceable cable complete all as specified and directed. |
| 83 | S&F in replacement PVC weather proof, hinged door, junction box with aluminium bus bar, 240V, neutral link and 1No MCB SP of 6 Amps, necessary fixing arrangement such as clamps, nut, bolts etc complete all as specified and as directed. |
| 84 | M&L for repair of Unserviceable street light timer controller panel including reconnecting and testing complete all as specified and directed. Note:- Spares/accessories required for replacement shall be measured and paid seperately under respective item of BoQ. |
| 85 | Supply only digital type timer single phase, 230 Volts, 50 Hz of rating 20 Amps complete all as specified and as directed. |
| 86 | Supply only contactor 2 pole 40 Amps main pole confugration 230 volts fixing with existing box by suitable size of copper cable with suitable size of lugs complete all as specified and as directed. |
| 87 | Supply only contactor 3 pole 40 Amps main pole confugration 415 volts fixing with existing box by suitable size of copper cable with suitable size of lugs complete all as specified and as directed. |
| 88 | Supply only 415V MCB TPN 63 Amps 10 KA 'C' complete with connection testing and commissioning complete all as specified and as directed. |
| 89 | M&L in repairs for lowering of high mast lantern carriage for disconnecting and taking down unserviceable high mast light fittings of any type/rating, dismantling the same for necessary repair or replacment of unserviceable spares and refixing, connecting, testing including raising high mast lantern carriage to its original position complete all as specified and as directed.Notes:- (i) Spares/accessories required for replacement shall be measured and paid seperately under respective item of BoQ. (b) Cost of T&P required for repair/ maintenance such as ladder, vehicle, manpower etc, shall deemed to be included in the unit rate quoted. |
| 90 | Supply only 200 watt LED flood light, energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP65 flood light with high power LEDs as light source, suitable for highlighting architectural facade highmast and general purpose lighting complete all as specified and as directed. |
| 91 | Supply only stainless steel wire rope of 6mm dia (7/19 construction) complete all as specified and as directed. |
| 92 | Supply only flexible copper cable 2.5 Sqmm 5 core complete all as specified and as directed. |
| 93 | Supply only starter suitable for 3.0 HP motor, three phase, 415 V , AC supply with forward/ reverse switch for High mast raising and lowering of lantern carriage with its supporting stand. |
| 94 | M&L for repairing of highmast light panels complete with necessary welding works to doors, replacement of unserviceable including wiring, fixing of timer, contactor & MCB etc complete all as specified and as directed. Notes:- (i) Spares/accessories required for replacement shall be measured and paid seperately under respective items of BoQ. (ii) Cost of T&P required for repair/ mantenance such as ladder, vehicl, manpower, welding cutting arrangement etc, shall deemed to be included in the unit rate quoted. |
| 95 | Supply and fix in replacement of 170 watt LED flood light, energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP65 flood light with high power LEDs as light source, suitable for highlighting architectural facade highmast and general purpose lighting. |
| 96 | Supply and fix in replacement 60 watt LED street light of new generation energy saving and environmental friendly long life, made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP opening seperate driver compartment with IP66 protection and impact resistance of IK07, suitable upto 40 mm mounting pipe as directed. Make: LUKER, Cat No. LST-60 or equivalent model of makes specified. |
| 97 | Supply and fix in replacement 90 watt LED street light of new generation energy saving and environmental friendly long life, made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP opening seperate driver compartment with IP66 protection and impact resistance of IK07, suitable upto 40 mm mounting pipe as directed by engineer-in-charge. Make: LUKER, Cat No. LST-90 or equivalent model of makes specified. |
| 98 | S&F in replacement of post top lantern light decorative type post top for 360 degree indirect light IP 65 protection resistant to impact and corrosion, Glare-free and better uniformity 20 watt LED 230 V 50 Hz including necessry fitting accessories complete all as per directed by engineer-in-charge. |
| 99 | Supply, install, testing and commissioning in replacement, factory made and tested (including CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted, compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated aluminium bus bar 300 amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 50x50x6mm angle iron , powder coated, Front and rear opening type with aprons for cable entry with double door shutter and locking arrangement with including cable gland, lugs, jointing material etc and jointing, connecting, testing and commissioning and including following items. (Notes :The rate quoted shall include for Cost of dismantling/ taking down old unserviceable LT feeder piller, earth work & excavation for angle iron frame for foundation of panel board upto 0.50 m below GL in any type of soil & PCC (1:4:8), D2 filling in foundation the ground clearance of panel board shall be 0.40 m GL to the bottom of panel board ). |
| 100 | Incoming: (a) MCCB 200 amps, 4 pole, 25 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 No. (b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 300 Amp, 4 pole, not less than 60cm long mounted on insulators for incoming supply-01 No.(c) Digital volt and ammeter with selector switch and CT's set - 01Set. (d) Neon indicating lamps (R, Y & B) -01 Set Outgoing: (a) MCB TPN 63 amps, 4 pole, 10 KA with adjustable thermal release, 50 Hz, 415 volts grade - 07 Nos.(b) MCB SPN 40 amps, 10 KA with adjustable thermal release, 50 Hz, 230 volts grade - 1 No. |
| 101 | S & F in repairs 10 Watt decorative type garden path lights bollard type Housing made up of aluminium pipe UV protected pure polyster powder coated with high efficiency long life LED module with SMD LED package and including necessary Concrete foundation fixed by 3 nos M 10 bolts complete as specified and as directed by Engr-in-Charge. Make: HAVELLS Cat No TURINBLS10WLED857PSYMTOPC or equivalent model of makes specified. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 29, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 18, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 2 daysSep 21, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 5 daysTender Documents