Tender For repair maintenance E&M Services Installed Under Sub-Division M-2531 At Delhi Sachivalaya, New Delhi.(Sh: Misscellaneous electrical installation And Supply Installation Testing and Commissioning of Various Lights At Various Locations Of Del
Tender Overview
Project Description
Tender for repair maintenance E&M Services Installed Under Sub-Division M-2531 At Delhi Sachivalaya, New Delhi.(Sh: Misscellaneous electrical installation And Supply Installation Testing and Commissioning of Various Lights At Various Locations Of Delhi Sachivalaya As And When Required. )
BOQ
| Sl. No. | Item Description |
| 1 | Percentage BoQ BoQ_Ver3.0 Percentage Normal INR Only INR Select, At Par, Excess (+), Less (-) IOCL Tender Inviting Authority: Executive Engineer(E) PWD M-253 Name of Work:- RMO E&M Services installed under Sub-division M-2531 at Delhi Sachivalaya, New Delhi.(SH: Misscellaneous EI and SITC of various Lights at various locations of Delhi Sachivalaya as and when required. ) NIT No.:45/EE(E)/PWD M-253/2026-27 Estimated Cost:-22,26,266/- Name of the Bidder/ Bidding Firm / Company : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Sub Head Item Code / Make Quantity Units Estimated Rate inRs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Rs. P TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group C |
| 3 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.Group C |
| 4 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 3 x 1.5 sq. mm |
| 5 | 3 x 4 sq. mm |
| 6 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches on surface etc as required.3 Module (100 mmX75 mm) |
| 7 | 6 Module (200mmX75mm) |
| 8 | 12 Module (200mmX150mm) |
| 9 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch |
| 10 | 6 pin 15/16 amp socket outlet |
| 11 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 12 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 13 | Supplying, installation, testing and commissioning of decorative retrofit outdoor LED (18-24 watt) bollard light fitting of height not less than 1 metre, fixture size 385*225 mm (nominal) with hexagonal lantern top, fluted ornamental post and square decorative base, fixture mounted on aluminium die cast column with cast alum base, made of pressure die-cast aluminium with corrosion-resistant powder coated finish with PC/PUMMA diffuser, silicon filled complete having duly primar and painted, suitable for operation on 230V AC, 50Hz supply i/c making cement concerete foundation and painting as per OEM standard with the help of foundation bolt complete with necessary internal wiring, earthing terminal, and all accessories required for proper installation and operation as per site requirement and direction of Engineer-in-Charge.(Note: 18-24 W LED bulb included, CCT should be 4000°K ). |
| 14 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt )Supplying, Installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -50C to 400C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K /4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast /Extruded aluminium Body including trim 18 watt |
| 15 | LED Down lighter (COB Type) (System lumen efficacy ≥105 < 120 lm/Watt ). Supplying, installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) COB Type of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards. Manufactures Word Mark/Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast /Extruded aluminium Body including trim with Aluminium Reflector 18 watt |
| 16 | LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt)Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the equirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79& LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder Coated CRCA Sheet Body (Thickness > 0.50 mm) 36 watt |
| 17 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt).Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range-5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker shouldbe below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) 18- 22 Watt |
| 18 | Supplying,replacement, testing and commissioning of 36 to 40 watt surface/recess mounted 1x4 LED Luminaries housing made with white powder coated CRCA sheet metal and opal diffuser suitable for operation on 150 to 265V single phase A.C. supply, having system efficiency not less than 100 luman per watt. and colour temperature of 4000-6500 K, CRI >80 with APFC driver having power factor > 0.90, including connection with 1.5 sq. mm. PVC insulated copper conductor FRLS cable etc as per site requirement. |
| 19 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. |
| 20 | Supply & fixing of wireless remote door bell (230 V AC) with minimum 100 m wireless operating range, having multi selectable polyphonic tunes, complete with transmitter, receiver, mounting accessories with battery cell, complete as required |
| 21 | SITC of Instant Electric Water Geyser of suitable for operation on 230 V, 50 Hz AC supply, capacity 3 Litres, with ISI marked heating element, rust proof ABS body, safety valve and thermal cut-out protection, suitable for wall mounting, including all accessories complete as required. |
| 22 | Supplying, Installation, Testing and Commissioning of following size LED display (LED monitor) industrial grade with 3840x2160 resolution or better, USB playback, bluetooth and miracast connectivity, 4X HDMI 2.0, DP 1.2, HDR 10/10+, brightness: 500-nits or better, Video wall mode should be available, contrast ratio: 1200:1, OPS slot, viewing angle (H/V):170°/ 170°, response time less than 12ms, Display control shall be on monitor screen and programmable with remote (remote shall be supplied with system), Key Board, Optical Mouse, etc. as required. 55 inch or larger |
| 23 | SITC of 2000 Watt Room Heater Blower suitable for operation on 230V AC supply, complete with thermostat, thermal overload protection, power cord, plug top, testing and commissioning, as required. |
| 24 | SITC of Oil Heater of minimum 2500 Watt capacity with 13 fins, suitable for operation on 230V AC supply, complete with adjustable thermostat, multiple heat settings, thermal overload protection, castor wheels, power cord with plug top, testing and commissioning, as required. |
| 25 | Supplying, installation, testing and commissioning of cove light of 5 mtr length having minimum 240 leds per meter i/c 5A, 12 volt driver suitable for operation on 220 to 240 Volt and colour temperature of 4000 K, Median useful life 30000 hours etc i/c connection with 1.5 sq. mm. PVC insulated copper conductor FRLS cable complete as required. |
| 26 | Credit of old dismentleAssorted wire |
| 27 | PVC Sheet 3/6/12 |
| 28 | Assorted downlighter |
| 29 | Assorted COB Lights |
| 30 | Assorted batten |
| 31 | Assorted 1x4 light |
| 32 | Assorted remote bell/buzzer Total in Figures 2226266.0 23 Twenty Two Lakh Twenty Six Thousand Two Hundred & Sixty Six Only Quoted Rate in Figures Select 0.0 0.0 INR Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 4 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 4 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender