Tender For Laying Of 11 Kv Ht Line And Establishment Of Outdoor Substation At Lp7 Area And Providing Main Power Supply Including Light And Power Points To Bioenergy Facility At Lp7 Area, South C Us, Iit Mandi.Note:-1. Quoted Rate Should Be Inclusive
Tender Overview
Project Description
Tender for Laying Of 11 Kv Ht Line And Establishment Of Outdoor Substation At Lp7 Area And Providing Main Power Supply Including Light And Power Points To Bioenergy Facility At Lp7 Area, South C Us, Iit Mandi.Note:-1. Quoted Rate Should Be Inclusive Of All Applicable Taxes Including Gst (Nothing Extra Shall Be Payable).2. All Statutory Deduction Will Be Made As Per Prevailing Rates.
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell Group C point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 2 | Wiring for circuit/ submain wiring along with earth wire with the 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 3 | Wiring for circuit/ submain wiring along with earth wire with the 2 X 4 sq. mm + 1 X 4 sq. mm earth wire of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 4 | Wiring for circuit/ submain wiring along with earth wire with the 4 X 6 sq. mm + 2 X 6 sq. mm earth wire sq. mm earth wire of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 5 | Wiring for circuit/ submain wiring along with earth wire with the 4 X 10 sq. mm + 2 X 6 sq. mm earth wire sq. mm earth wire of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 6 | Supplying and fixing of 25 mm of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 7 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 8 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 9 | Supplying and fixing 5A to 32A Rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of Single pole in the existing MCB DB complete with connections, testing and commissioning etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 10 | Wiring for group C group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS/HFFRPVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 11 | Providing and fixing 125 A,25KA, FPMCCB rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 12 | Supplying and fixing 6 way (4 + 18), Double door way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required.as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. (But without MCB/RCCB/ Isolator) as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 13 | Supplying and fixing 5A to 32A Rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of Single pole in the existing MCB DB complete with connections, testing and commissioning etc. as required. as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 14 | Supplying and fixing 40 A rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 15 | Supplying and fixing 40 A rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 16 | Supplying and fixing of 8 way (4 + 24), Double door surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 17 | Supplying and fixing Triple pole 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of Single pole, in the existing MCB DB complete with connections, testing and commissioning etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 18 | Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 30 A \\"C\\" curve, FPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 19 | Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enamelled white on both sides, and with inscription in single red colour on front side as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 20 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 21 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 22 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 23 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 24 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of Above 35 sq. mm and up to 95 sq. mm in the existing RCC/ HUME/ METAL pipe as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 25 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of Above 35 sq. mm and up to 95 sq. mm in the existing masonry open duct as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 26 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of Above 185 sq. mm and up to 400 sq. mm in the existing masonry open duct as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 27 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of Above 35 sq. mm and up to 95 sq. mm (clamped with 25x3mm MS flat clamp) on Wall Surface as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 28 | Supplying and making end termination with brass compression gland and aluminium lugs for 3½ X 50 sq. mm (35mm) of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 29 | Supplying and making end termination with brass compression gland and aluminium lugs for 3½ X 95 sq. mm (45mm) of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 30 | Supplying and making end termination with brass compression gland and aluminium lugs for 3½ X 300 sq. mm (70mm) of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 31 | Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for 3½ X 300 sq. mm of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 32 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of up to 120 sq. mm in the existing masonry open duct as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 33 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for 95/120 sq. mm of 3 core, XLPE aluminium conductor cable of 11 KV grade as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 34 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for 95/120 sq. mm of 3 core, XLPE aluminium conductor cable of 11 KV grade as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 35 | Erection of steel tubular or rail pole strut in cement concrete 1:3:6 (1 cement: 3 coarse sand: 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling and secured with holding clamps, bolts, nuts, etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 36 | Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) cross arm for 2 wire overhead line complete with clamps, bolts, nuts and washer etc including drilling of holes for insulator pins etc (as per drawing) and painting with primer and finished paint as required as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 37 | Erection of angle iron/ channel iron cross arm on wood/ RCC/ PCC/ steel tubular/ rail pole etc. as required. as required as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 38 | Erection of ACSR conductor of 7/2.11 mm to 7/3.00 mm diameter including binding etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 39 | Erection of G.I. Wire No. 8 SWG including binding etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 40 | Supplying and erection of galvanised stay set for 11 KV overhead lines complete with 19/ 20 mm dia X 1.8 metres long stay rod, anchor plate of size 45 cm X 45 cm X 7.5 mm thick, thimble, stay clamps, turn buckle ( 20 mm X 600 mm ), 7/ 4.00 mm dia G.I. stay wire and 11 KV strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 41 | Supplying and erection of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) pole top bracket/ cross arm for single 11 KV overhead line conductor complete with 50 mm X 6mm flat iron clamp, bolts, nuts and washers including drilling holes for insulator pins, bolts and nuts etc and painting with primer and finish paint as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 42 | Supplying and erection of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) cross arm for two 11 KV overhead line conductors complete with 50 mm X 50 mm X 6 mm (angle iron bracket welded to the channel iron and complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 43 | Supplying and erection of two lengths of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) double pole cross arm for three wire 11KV overhead line conductors complete with through bolts and nuts for clamping to the poles, 50 mm X 6 mm M.S. flats welded on one side to the channel iron and with bolts and nuts on the other side for tying the cross arms together, including drilling holes for insulator pins/ fittings, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 44 | Supplying and erection of a set of cross bracing frame work for 11 KV overhead line double pole structure having four members fabricated out of 50 mm X 50 mm X 6 mm angle iron to form a rectangle of minimum size 1400 mm width X 2500 mm height , complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts and nuts etc (as per drawing) and painting with primer and finish paint as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 45 | Supplying and erection of 11 KV pin insulator complete with large steel head G.I. pin, nuts, washers etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 46 | Supplying and erection of 11 KV disc insulator for 11 KV overhead lines with galvanised insulator fittings, ball and socket type and complete with galvanised strain clamps, bolts, nuts, washers etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 47 | Erection of disc/ pin insulator for 11 KV overhead lines as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 48 | Supplying and erection of three-piece nonlinear resistor type lightning arrestor suitable for 3 wire, 11 KV overhead lines with rated voltage 9 KV (rms) with a nominal discharge current rating of 5 KA and complete with galvanised clamping arrangement, G.I. bolts, nuts, washers etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 49 | Supplying and laying of 63 mm dia (OD-63 mm & ID-51 mm nominal) DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. Direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 50 | Clearing jungle including uprooting of rank vegetation, grass, wood, trees and saplings of girth up to 30 cm measured at a height of above 1 mand removal of rubbish up to a distance of 50 m outside the periphery of the area cleared. |
| 51 | Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead up to 50 m and lift up to 1.5 m, all kinds of soil as directed by Engineer-in charge. |
| 52 | Providing and laying in 1:3:6 (1 Cement: 3 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 53 | Providing and laying in 1:4:8 (1 Cement: 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 54 | Centering and shuttering including strutting, propping etc. and removal of form for foundations, footings, bases of columns, etc. for mass concrete as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 55 | Thermo-mechanically treated bars of grade fe-500D or more Steel reinforcement for r.c.c. work including straightening, cutting, bending, placing in position and binding all complete above plinth level as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 56 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the Concrete of M25 grade with minimum cement content of 330 kg /cum grades of concrete ( All works up to plinth level ) Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 1.10 times of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 57 | Dry stone pitching 22.5 cm thick including supply of stones and preparing surface complete as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 58 | Applying priming coat: With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel galvanised iron/ steel works as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 59 | Painting with aluminium paint of approved brand and manufacture to give an even shade. Two or more coats on new work as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 60 | Providing and fixing G.I. chain link fabric fencing of required width in mesh size 25x25 mm made of G.I. wire of dia 3 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. |
| 61 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 62 | Painting on G.S. sheet with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade. New work (two or more coats) including a coat of approved steel primer but excluding a coat of mordant solution as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 63 | Supplying of ACSR 6/1/2.59 (30 mm²) Weasel conductor as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 64 | Supplying of 11-Meter-long Steel Tubular Poles (Working Load > 227 kgf/m²) as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 65 | Supplying and fixing of Barbed Wire on poles for safety purpose etc. as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 66 | Supplying of 8 SWG GI wire as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 67 | Supplying and installation of Eye Hook for earth wire etc. as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 68 | Supply and installation of GO AB Switch Unit (11kV, 400A, 25 KA) Tripple pole O/D type as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 69 | Supplying of 3 Core x 95 Sq. mm of 6.6 kv (UE)/11 KV (E) HT cables, Stranded Compacted Circular Aluminium Conductor, Conductor Screen with Extruded Semi Conducting Compound, XLPE Insulated, Insulation Screening with Extruded Semi Conducting Compound in Combination with Copper Tape, Cores Laid Up, Inner sheath of PVC, Galvanised Steel Flat Strip Armoured, & Overall PVC Sheathed Cable Conforming to IS 7098 (Part-2) 2011 with up to Date Amendments as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 70 | Supply and erection of Drop Out fuse unit for 11KV/0.415 KV 400 KVA Transformer unit complete as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 71 | Supply, installation, testing and commissioning of 11/0.440 kV, 250 kVA, 3-phase, 50 Hz oil immersed, naturally cooled (ONAN) outdoor type distribution transformer, having vector group Dyn11, with off-load tap changer of ±5% in steps of 2.5% on HV side, conforming to IS 1180 (Part-1): Latest amendment.The transformer shall be complete with copper windings, CRGO core, conservator with oil level indicator, silica gel breather, Buchholz relay, magnetic oil level gauge, winding temperature indicator (WTI), oil temperature indicator (OTI), explosion vent, pressure relief device, HV & LV bushings, marshalling box, earthing terminals (2 nos.), lifting lugs, rollers, rating and diagram plate.The transformer shall be filled with high quality insulating oil conforming to IS 335 and suitable for outdoor installation.The work includes all necessary accessories, first filling of oil, filtration of oil (if required), foundation alignment, erection, testing at site, and commissioning.The transformer shall be complete in all respects and ready for safe and efficient operation as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 72 | SITC of outdoor type distribution feeder panel suitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system, fabricated in compartmentalized (preferably) design from CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 630 Amp capacity extensible type TPN aluminium alloy bus bars of hight conductivity, DMC / SMC bus bars of high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 31 MVA for 1 Sec., bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring of required size, PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half, i/c providing following switch gears :-(I) Incoming :Incomer - 1 Nos 400 Amps 50 KA four pole MCCB With thermomagnetic releases and all required accessories(a) Independent manual spring closing mechanism- 1 No.(b) Digital type Voltmeter (0-500 V), with selector switch & back up HRC fuses/MCBs-1 set (c) Digital type Ammeter (0-400 Amp), with selector switch and one set of 3 nos. CT’s of ratio 400/5A Class I accuracy and 15VA burden- 1set.(d) 3 Nos. Phase indication LED lamps with 2 Amp back up HRC fuse, breaker ‘ON’ indicating light with 2 A HRC fuse, test terminal block set, fuses, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.Outgoings - 400 A, 50 ka FP MCCB - 1200 A, 36 ka FP MCCB - 2125 A, 30 ka FP MCCB - 363 A,16 ka FP MCB - 5 as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 73 | Supplying of 3.5 Core x 300 Sq. mm of 1.1 KV aluminium conductor XLPE Insulated, PVC inner-sheathed armoured, Extruded PVC Type ST2 Outer Sheathed, 650 V/1100 V Grade as per IS 7098 (Part 1) 1988 with up to Date Amendments as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 74 | Supplying of 3.5 Core x 95 Sq. mm of 1.1 KV Aluminium conductor XLPE Insulated, PVC extruded inner-sheathed armoured, Extruded PVC Type ST2 Outer Sheathed, 650 V/1100 V Grade as per IS 7098 (Part 1) 1988 with up to Date Amendments.) with latest amendments as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 75 | SITC of outdoor type distribution feeder panel suitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system, fabricated in compartmentalized (preferably) design from CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 200 Amp capacity extensible type TPN aluminium alloy bus bars of hight conductivity, DMC / SMC bus bars of high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 31 MVA for 1 Sec., bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring of required size, PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half, i/c providing following switch gears :-(I) Incoming:1 Nos 200 Amps 25 KA four pole MCCB with thermomagnetic releases and all required accessories.(a) Independent manual spring closing mechanism- 1 No.(b) Digital type Voltmeter (0-500 V), with selector switch & back up HRC fuses/MCBs-1 set (c) Digital type Ammeter (0-200 Amp), with selector switch and one set of 3 nos. CTs of ratio 200/5A Class I accuracy and 15 VA burden- 1setd) Digital kWh Meter (energy meter), suitable for 3-phase supply, with necessary CT/PT connections, complete with wiring and accessories – 1 No. (e) 3 Nos. Phase indication LED lamps with 2 Amp back up HRC fuse, breaker ‘ON’ indicating light with 2 A HRC fuse, test terminal block set, fuses, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.Outgoings - 125A,25 ka FP MCCB - 263 A, 10 ka FP MCB - 340 A, 10 ka FP MCB - 3 as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 76 | Supplying and fixing Triple pole 63 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of Triple pole, in the existing MCB DB complete with connections, testing and commissioning etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 77 | Supplying and fixing MCB Enclosure suitable for 63 Amp FP MCB as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 78 | Supplying of 3.5 Core x 50 Sq. mm of 1.1 KV Aluminium conductor XLPE Insulated, PVC extruded inner-sheathed armoured, Extruded PVC Type ST2 Outer Sheathed, 650 V/1100 V Grade as per IS 7098 (Part 1) 1988 with up-to-Date Amendments.) with latest amendments as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
| 79 | Supplying and installation of 50 W Flood light luminaire, CCT 5700 K with polycarbonate optics, pressure die-cast housing along with IP66 ingress protection. 4kV in-built surge protection, 120 lm/W, etc. as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 11 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 13 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender