Tender For Special Repair / Replacement Internal Electrification Of Various Bldgs In Domsetic Area At Afs Phalodi.

Issued by Statutory Bodies & Commissions/Committees · Jodhpur, Rajasthan
Tender Value
Ref. Documents
Estimated cost
Bid Submission
26 Sep 2026
14 days left
EMD
53960
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Jodhpur → Rajasthan
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Special Repair / Replacement Internal Electrification Of Various Bldgs In Domsetic Area At Afs Phalodi.

BOQ

Name of Work:- SPECIAL REPAIR / REPLACEMENT INTERNAL ELECTRIFICATION OF VARIOUS BLDGS IN DOMSETIC AREA AT AFS PHALODI.
Sl. No. Item Description
1Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: Garrison Engineer (AF), Air Force Station, Phalodi Name of Work : SPECIAL REPAIR / REPLACEMENT INTERNAL ELECTRIFICATION OF VARIOUS BLDGS IN DOMSETIC AREA AT AFS PHALODI. Contract No: GE (AF) PHALODI/ OF 2026-27 Serial Page No. Bidder Name : SCHEDULE 'A'(BOQ)(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT TEXT # NUMBER TEXT NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER NUMBER # TEXT Srl.No. Item Description Item Code / Make Approx No of Units reqd Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words
2Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc complete all as specified and directed.
3Dismantling unserviceable main switch/DBs including wooden board and deposit to MES store yard including making good disturbed surface of wall complete all as specified and directed.
4Taking down sub main wiring of any size/capacity complete all as specified and making good disturbed sufaces to match with the existing surfaces complete all as specified and directed.
5M&L for Concealed Point wiring for One light point controlled by one, one way switch with PVC insulated unsheathed stranded copper conductor cable of size 1.5 Sqmm, with PVC insulated unsheathed stranded copper conductor cable FRLS of size 1.5 Sqmm stranded for earth continuity wire, to be drawn in and including, PVC conduit not less then 20 mm dia with metal sunken box including all necessary wall cutting and making good disturbed surface complete all as specified and directed. Note : Cutting chases, plastering and making good to match with the adjoining surface shall be included in the unit rate.
6M&L for Concealed Point wiring for One ceiling /exhaust fan point controlled by one switch, with PVC insulated unsheathed stranded copper conductor cable of size 1.5 Sqmm, with PVC insulated unsheathed stranded copper conductor cable FRLS of size 1.5 Sqmm stranded for earth continuity wire, to be drawn in and including, PVC conduit not less then 20 mm dia with metal sunken box including all necessary wall cutting and making good disturbed surface complete all as directed and specified . .Note : Cutting chases, plastering and making good to match with the adjoining surface shall be included in the unit rate. Note : - Rate shall be included for connection of ceiling rose to fan by using 3 core flexible copper wire in white colour complete all as directed and specified.
7M&L for Concealed Point wiring for One 3 pin 5 amp socket out point on the same board with other switches with PVC insulated unsheathed stranded copper conductor cable of size 1.5 Sqmm, with PVC insulated unsheathed stranded copper conductor cable FRLS of size 1.5 Sqmm stranded for earth continuity wire, to be drawn in and including, PVC conduit not less then 20 mm dia with metal sunken box including all necessary wall cutting and making good disturbed surface complete all as specified and directed. Note : Cutting chases, plastering and making good to match with the adjoining surface shall be included in the unit rate.
8M&L for Concealed Point wiring for One 3 pin 5 amps socket out let point on independent board with PVC insulated unsheathed stranded copper conductor cable of size 1.5 Sqmm, with PVC insulated unsheathed stranded copper conductor cable FRLS of size 1.5 Sqmm stranded for earth continuity wire, to be drawn in and including, PVC conduit not less then 20 mm dia with metal sunken box including all necessary wall cutting and making good disturbed surface complete all as specified and directed. Note : Cutting chases, plastering and making good to match with the adjoining surface shall be included in the unit rate.
9M&L for Concealed Point wiring for One light point controlled by two, two way switch with PVC insulated unsheathed stranded copper conductor cable of size 1.5 Sqmm, with PVC insulated unsheathed stranded copper conductor cable FRLS of size 1.5 Sqmm stranded for earth continuity wire, to be drawn in and including, PVC conduit not less then 20 mm dia with metal sunken box including all necessary wall cutting and making good disturbed surface. complete all as specified and directed. Note : Cutting chases, plastering and making good to match with the adjoining surface shall be included in the unit rate.
10All as per same in item No 4 above but for one socket outlet 15 amp on independent board with 2.5 Sq. mm cable and 2.5 Sq.mm. earth wire complete all as specified and directed.
11S&F in repair modular Switch one way 6 Amps, 1 module 240 V complete all as specified and as directed.
12S&F in repair modular Switch one way 16 Amps, 1 module 240 V complete all as specified and as directed.
13S&F in repair modular Switch two way 6 Amps, 1 module 240 V complete all as specified and as directed.
14S&F in repair modular socket 3 pin 5 Amps 240 V, combined 2 module flush type complete all as specified and as directed.
15S&F in repair Modular socket 6 pin 15 Amps 240 V, 2 module flush type complete all as specified and as directed.
16S&F in repair 6A one-way SP bell push - 1 module SP switch - 1 module complete all as specified and directed.
17S&F bell, AC, 230 Volts, single pole complete all as specified and directed.
18S&F in repair of 6A, 250V high quality robust surface/flush type polycarbonate/PVC ceiling rose, conforming to IS: 371- 1979, having 2/3 terminals and outside diameter not less than 63.5 mm complete all as specified and directed
19S&F in repair of Lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings complete all as specified and directed
20S & F Modular Fan step regulator, 120W - 2 module complete all as specified and directed.
21S&F in repair modular metal flush box 12 module complete all as specified and directed.
22S&F in repair modular metal flush box 8 module complete all as specified and directed.
23S&F in repair modular metal flush box 6 module complete all as specified and directed.
24S&F in repair modular metal flush box 4 module complete all as specified and directed.
25S&F in repair modular metal flush box 3 module complete all as specified and directed.
26S&F in repair modular metal flush box 2 module complete all as specified and directed.
27S&F in repair modular metal flush box 1 module complete all as specified and directed.
28S&F in repair modular White cover plate with frame 12 module complete all as specified and directed.
29S&F in repair modular White cover plate with frame 8 module complete all as specified and directed.
30S&F in repair modular White cover plate with frame 6 module complete all as specified and directed.
31S&F in repair modular White cover plate with frame 4 module complete all as specified and directed.
32S&F in repair modular White cover plate with frame 3 module complete all as specified and directed.
33S&F in repair modular White cover plate with frame 2 module complete all as specified and directed.
34S&F in repair modular White cover plate with frame 1 module complete all as specified and directed.
35S&F in repair of Modular AC Box With 20A SP MCB, Metal Enclosure & Unbreakable Heavy Duty With ISI Plug Top complete all as specified and directed
36Material and Labour for Concealed Sub main wiring power/circuit using FRLSH PVC insulated unsheathed, stranded copper conductor cable 2 runs of size 6.00 Sqmm, earth continuity conductor of size 6.00 Sqmm to be drawn through and including PVC conduit 20 mm dia concealed in walls/roof/floors complete all as specified and directed. Notes:- (i)Two wires of 6.00 sqmm and one wire of 6.0 sqmm and one run of PVC conduit shall be measured as one unit.
37Material and Labour for Concealed Sub main wiring power/circuit using FRLSH PVC insulated unsheathed, stranded copper conductor cable 2 runs of size 4.00 Sqmm, earth continuity conductor of size 4.00 Sqmm to be drawn through and including PVC conduit 20 mm dia concealed in walls/roof/floors complete all as specified and directed. Notes:- (i)Two wires of 4.00 sqmm and one wire of 4.0 sqmm and one run of PVC conduit shall be measured as one unit.
38Material and Labour for Concealed Sub main wiring power/circuit using FRLSH PVC insulated unsheathed, stranded copper conductor cable 2 runs of size 1.5 Sqmm, earth continuity conductor of size 1.5 Sqmm to be drawn through and including PVC conduit 20 mm dia concealed in walls/roof/floors complete all as specified and directed.Notes:- (i)Two wires of 1.5 sqmm and one wire of 1.5 sqmm and one run of PVC conduit shall be measured as one unit.
39S&F in replacement of Decorative Light, Tube light, 40-watt LED Batten/ Tube light | Star Bright Compact 4-ft Decorative Modern LED Wall Tube light for Living Room & Bedroom | Cool Day Light, aesthetic - Sleek, Bright LED Light, Compact LED, Energy Efficient, Eye-Friendly, Bulb Shape Size T5 ½, T5 ½, GU10 complete with fixing arrangements on wall complete all as specified and directed.
40S&F in renewal of 20 watt surface/wall mounted LED batten having high efficiency long life LED chips with luminous efficacy of > 100 lumen/W, independent isolated SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS : 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in polycarbonate housing and white coloured ABS and caps having input voltage 220-240V, input frequency 50-60 Hz, PF > 0.95, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed
41S&F in renewal of 10 watt surface/wall mounted LED batten having high efficiency long life LED chips with luminous efficacy of > 100 lumen/W, independent isolated SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS : 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in polycarbonate housing and white coloured ABS and caps having input voltage 220-240V, input frequency 50-60 Hz, PF > 0.95, including electrical connection with 3 core flexible Copper conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed
42S & F in repair of decorative LED light fitting 1x9W/1X10W bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed
43S&F in replacement building security light with high power LED as light source and electronic driver of capacity 35 watt complete with mounting bracket made of 32 mm dia GI pipe (not less than 550 mm long) bent to the shape at 120 degree angle complete with clamps & nuts, washers and bolts complete all as specified and directed Note :- The rate of supply of bracket of 32 mm dia GI pipe is included in quoted rates.
44Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed.
45Material and labour for taking down carefully and keeping it in safe custody and deposit to MES store and Supply and fix exhaust fan, steel body AC single Phase. 230V of size 300 mm sweep with, blades, and frame and louvers, including suitable size of wooden frame with circular opening for mounting exhaust fan in the ventilation opening complete all as specified and as directed.
46Material and labour for taking down carefully and keeping it in safe custody and deposit to MES store and Supply and fix exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 250 mm, including suitable size of wooden frame with circular opening for mounting exhaust fan in the ventilation opening complete all as specified and as directed.
47Material and labour for taking down of old serviceable ceiling fans from site and Painting of ceiling fans complete, in situ with synthetic enamel paint by spraying including filling cavities with filler, one coat after cleaning all dust etc.and refixing the same ceiling fan and connecting up including provision of cable from ceiling rose or connector to fan complete all as specified and directed.
48Material and labour for making hole in brick wall for exhaust fan opening of 300 mm sweep and Cutting upto a depth of 2.5cm into concrete/brick walls and trimming surface as required, girth exc. 30cm complete with plaster and finishing complete all as specified and directed.
49S&F in replacement of single pole & neutral 12 way DB (double door), conforming to IEC 61439- 3, suitable for flush mounting with 100 A insulated & shrouded copper busbar for each phase, fully insulated & shrouded neutral bar, earth bar, wire set and cable ties for cable management, IP 43 & IK 09 protection with reversible metal door with provision for DP MCB as incomer and SP MCBs as outgoing, all complete as specified and directed. NOTES: (i) MCBs shall be measured and paid in separate items.
50S&F in replacement of single pole & neutral 8 way DB (double door), conforming to IEC 61439- 3, suitable for flush mounting with 100 A insulated & shrouded copper busbar for each phase, fully insulated & shrouded neutral bar, earth bar, wire set and cable ties for cable management, IP 43 & IK 09 protection with reversible metal door with provision for DP MCB as incomer and SP MCBs as outgoing, all complete as specified and directed. NOTES: (i) MCBs shall be measured and paid in separate items.
51S&F in replacement of single pole & neutral 4 way DB (double door), conforming to IEC 61439- 3, suitable for flush mounting with 100 A insulated & shrouded copper busbar for each phase, fully insulated & shrouded neutral bar, earth bar, wire set and cable ties for cable management, IP 43 & IK 09 protection with reversible metal door with provision for DP MCB as incomer and SP MCBs as outgoing, all complete as specified and directed. NOTES: (i) MCBs shall be measured and paid in separate items.
52S&F in replacement of triple pole & neutral DB, 4 way (double door), conforming to IEC 61439- 3, suitable for flush mounting with 100 A insulated & shrouded copper busbar for each phase, 2 fully insulated & shrouded neutral bar, 2 earth bar, wire set and cable ties for cable management, IP 43 & IK 09 protection with reversible metal door with provision for 4 Pole MCB as incomer and TP/SP MCBs as outgoing, all complete as specified and directed. NOTES: (i) MCBs & MCCBs shall be measured and paid in separate items.
53S&F in replacement of Vertical triple pole & neutral DB, double door, vertical DB,4 way conforming to IEC 61439- 3, suitable for flush mounting with 250 A insulated & shrouded copper busbar for each phase, 2 fully insulated & shrouded neutral bar, 2 earth bar, wire set and cable ties for cable management, IP 43 & IK 09 protection with reversible metal door with provision for 4 Pole MCCB 160 Amps 16 KA as incomer and TP/SP MCBs as outgoing, all complete as specified and directed.NOTES: (i) MCBs & MCCBs shall be measured and paid in separate items.
54Supply and fixing of MCCB 4 Pole, 415 V, Adjustable type, 100 amps with breaking capacity 16 KA, complete all as specified and directed.
55Supply and fixing MCB TPN 440 Volts, 'B' series, breaking capacity 10 KA of rating 63-100 Amps complete all as specified and as directed.
56Supply and fixing MCB TP 440 Volts, 'B' series, breaking capacity 10 KA of rating 32 Amps complete all as specified and as directed.
57Supply and fixing amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of Double poles (DP) and current carrying capacity 40 Amps in the MCB DB complete with connection testing and commissioning. complete all as specified and as directed.
58Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles (SP) and current carrying capacity 6 to 32 AMP, in the MCB DB Complete with connection testing and commissioning.complete all as specified and as directed.
59Supply and fixing of 1.5 Ton energy efficient inverter AC hi wall split units indoor/outdoor complete with cordless remote control unit and , cooling capaicty of 5.28 kW (18000 Btu/h), R-32 eco-friendly refrigerant, copper condenser coils, 3D airflow, 5 star ISEER rating 5.70, Power supply 230 V / 50 Hz / 1 Phase, Ambient Operation: Up to 52°C, Condenser Coil: 100% Copper, Noise Level (Indoor): Low (around 39-45 dB), 3D air flow, PM 2.5 filter, dew clean technology, stabilizer free operation: Operates efficiently within a wide voltage range (typically 130-285V), compressor shall have minium 10 year warranty and PCB with minmum 5 year warranty and including MS brackets duly apinted with antirust paint powder coated to install outdoor units complete all as specified and directed.
60M&L for Earthing with galvanized steel earth plate electrode of size 600 mm x 600mm x 6.0 mm buried directly in ground (earth pit not less than 2.25 Mtr below normal ground level) connected to galvanized earth lead wire of 4 mm dia by means of bolts, buts, check nuts and washers of galvanized iron on steel including 40 mm dia light grade GI tubing for protection of earth lead, MS sheet m etal funnel with wire mesh, watering pipe medium grade 20 mm dia, charcoal or coke and common salt necessary excavation, earth work, in soil/loose soil and disposal of soil to a distance not exc 15 Mtr and necessary connection and testing complete all as specified and directed. Note: (i) Excavation, earthwork, charcoal, PCC pit is covered under this item.(ii) Contractor shall be produced the result of earth below 1 Ohm othrewise earthing will not be acceptable.
61Taking down of old unsv LT Panel and Supply, installing, testing and commissioning, factory made and tested (incl CPRI type test certified), LT feeder pillar box (KIOSK) of appropriate dimensions (as per Indian Electricity rules) to accommodate following components, indoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated Aluminium bus bars 250 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front & rear opening type, with aprons for cable entry, with double door shutter and locking arrangement, internal wiring with PVC insulated, multistranded copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 4 sqmm complete all as specified and directed. The scope of work includes the following COMPONENTS :-Incoming :(a) Aluminium bus bar of rating 250 Amps for four pole including PVC heat shrink sleeves (RYB & N ) : 01 Set (b) MCCB four pole 160 Amp ('C' Curve), 415 Volts, rupturing capacity- 36 kA, 415 Volts Adjustable Thermal & Fixed Magnetic type- 01 no Outgoing :- (a) MCCB Four Pole 100 Amps ('C' Curve), 415 Volts, rupturing capacity- 16 kA, 415 Volts Adjustable Thermal & Fixed Magnetic type- 01 nos(b) MCCB Four Pole 63 Amps ('C' Curve), 415 Volts, rupturing capacity- 16 kA, 415 Volts Adjustable Thermal & Fixed Magnetic type- 02 nos(c) On load changeover 4 pole 100 Amps -01 Nos (c) LED display Digital Type Voltmeter with CT - 01 No (d)LED Display Digital type Ammeter with CT - 01 No (e) LED indicators (RY&B) - 01 Set (Note :Necessary approval of drawings of LT feeder pillars to be taken from GE before placing order by the contractor)
62Supply & Laying XLPE insulated armoured PVC Sheathed LT (1100 Volts grade) cable with aluminium conductor of size 95 Sqmm 3.5 core in trench on wall/roof or passing through GI pipes including all fixing arrangements complete all as specified and as directed.Note:- (i) Cable may be laid in trenches, under road, across the Nallah, along poles/walls and ducts etc.(ii) Excavation, earthwork, sand cushioning, cable cover, pipe for cable protection to be measured and paid separately.
63Supply & Laying XLPE insulated armoured PVC Sheathed LT (1100 Volts grade) cable with aluminium conductor of size 25 Sqmm 4 core in trench on wall/roof or passing through GI pipes including all fixing arrangements complete all as specified and as directed.Note:- (i) Cable may be laid in trenches, under road, across the Nallah, along poles/walls and ducts etc.(ii) Excavation, earthwork, sand cushioning, cable cover, pipe for cable protection to be measured and paid separately.
64Excavation in trenches n.exc 1.50m wide and n exc 1.50m in depth for foundation etc n.exc 10 sqm on plan and getting out in soft & loose soil complete all as specified and directed. Note:- Any excavation in SDR/Loose soil/PCC/Hardstanding/Interlocking tiles/Bituminous pavement shall be carried out by manual mode only irrespective of Tech/Residential area. In case of mechanical excavation engaged by the contractor, any fault due to rupturing of communication/power/any other utility lines shall be rectified by appropriate joint as per direction of Engr-in-Charge/GE/Stn Auth as deemed fir and no extra cost will be paid in this respect.
65Returning, filling in including spreading, levelling, watering and well ramming excavated soil in layers not exceeding 25 cm thick each, back in trenches after cables have been laid and tested,poles, stays , struts have been erected and tested complete all as specified and directed.
66Removing excavated surplus (soil) obtained from excavation to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and directed.
67Material and labour for stone dust sand cushioning to under ground cable, provided with a layer 8 cm before and 15 cm after laying and stretching jointing and testing the cable all as specified and directed.[Note : Measurement will be done after punning]
68M & L for PCC cable cover of Class LV, Type I, flat, size 250mm x 150mm x 40mm to be laid over dry sand cushioning in trenches as protection to cable all as specified and directed.
69Material and labour for replacement of GI pipe 50 mm dia light grade for protection of LT Cable complete all as specified and as directed.
70Earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6mm as earthing lead buried directly in ground vertically to a depth not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to and including galvanised iron strip 25 X 4 mm as earthing lead by means of bolts, nuts, check nuts & washers etc made of GI and connected to earthing test point all as shown in electrical plate No. 5 of SSR Part I of 2009 & as specified or indicated and testing on completion including excavation/earth work in any type of strata PCC ( 1:3:6 ) type C1 earthing chamber, pre cast slab cover 50 mm thick in cement concrete ( 1: 2 : 4 ) type B 1 (reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg / Sqm), funnel with wire mesh, watering pipe of 20 mm bore medium grade, including galvanised iron strip 25X4 mm with GI protection pipe of 40 mm medium grade up to 7.5 meter length complete all as specified and directed.
71Taking down cement or cement lime plaster, any description on brick or stone walls, etc. incl raking out joints, hacking for key, scrubbing down with water etc complete all as specified and directed.
72M&L rendering 10mm thick in CM 1:6 on fair faces of brick or concrete surfaces all as specified and as directed.
73M&L for Preparation of new plastered surfaces and applying two coat of oil bound distemper over a coat of primer with 1.50 mm thick wall putty to achieve smooth finish complete all as specified and as directed.
74Complete removal of exisisting treatment on walls and applying two coat of oil bound distemper over a coat of primer with 1.50mm thick wall putty to achieve smooth finish complete all as specified and as directed. Total in Figures 0.0 23 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57244576
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE Ref. Documents
LAST DATE 26-09-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Special Repair / Replacement Internal Electrification Of Various Bldgs In Domsetic Area At Afs Phalodi.
Basic Detail
Tender No 8832/A/E8
Bidding Type Tender
Location
City Jodhpur
State Rajasthan
Key Dates
Publish Date 28 Aug 2026
Submission Date 26 Sep 2026
Open Date 28 Sep 2026
Finance
Tender Value Ref. Documents
Tender Fee 500
EMD 53960
Exemption Available
Document List
BOQ_881778.xls
f8854777-dad1-4bce-a2e8-1d6e53cfd874.html
tender.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 28, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 26, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 14 days
Sep 28, 2026

Bid Opening Date

Technical bids will be opened and evaluated.