Tender For special Repair /Replacement Of Lt Panel, Feeder Pillar, Xlpe Ug Cables And Connected Items Under Ge 859 Ews
Tender Overview
Project Description
Tender for special Repair /Replacement Of Lt Panel, Feeder Pillar, Xlpe Ug Cables And Connected Items Under Ge 859 Ews
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 03-Sep-2026 | BOQ Corrigendum | BOQ | 17-Sep-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Supply and Laying and connecting with appropriate lugs in replacement XLPE LT cable PVC insulated, heavy duty electric cables with Aluminum conductors,1100 volts grade, laid in trenches/on pole/in pipe /on wall ,using suitable clamps for fixing of cable complete all as specified and directed of following cross-sectional area including removing/ taking down of old unserviceable cables of any size :-size 10 Sqmm 2 Core. |
| 2 | All as per above item No-1 but size 16 Sqmm 2 Core. |
| 3 | All as per above item No-1 but size 25 Sqmm 3.5Core. |
| 4 | All as per above item No-1 but size 35 Sqmm 3.5 Core. |
| 5 | All as per above item No-1 but size 70 Sqmm 3.5 Core. |
| 6 | Excavation in trenches, n exc 1.5m wide and m exc 1.5m in depth, for foundation, etc or for shafts, wells, cess-pits, menholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5m in depth and getting out for soft/loose soil. |
| 7 | Removing excavated material n exc. 50 m and depositing where directed at a layers not exc 25 cm. for hard/dense soil. |
| 8 | Returning, filling in, including spreading, levelling, waterring and wall ramming in layers not exc 25 cm. for hard/dense soil. |
| 9 | S&F Double walled corrugated (DWC) Pipe conforming to IS 14930(Part-II) Pipes of Outer dia 50 mm and innder dia 38mm all as specified and as directed. |
| 10 | S&F Double walled corrugated (DWC) Pipe conforming to IS 14930(Part-II) Pipes of Outer dia 63 mm and innder dia 50mm all as specified and as directed. |
| 11 | M&L in replacement GI pipe light grade with all fittings complete grouted in ground all as specified for the 50 mm bore of pipe laid in trenches/fixed with poles/laid in road/plinth/floor for protection of cable including taking out old unserviceable pipe complete all as specified. |
| 12 | M&L in replacement GI pipe light grade with all fittings complete grouted in ground all as specified for the 40 mm bore of pipe laid in trenches/fixed with poles/laid in road/plinth/floor for protection of cable including taking out old unserviceable pipe complete all as specified. |
| 13 | M&L cutting the road hard standing & making good surface with PCC 1:2:4 B-1 Type Using 20 mm graded stone aggregate & removing the to distance n.exe 50mtr all as specified. |
| 14 | Supply and fix Off Load changeover switch side handle in sheet enclosure 415 V AC 50 Hz of Capacity 63 Amp 4 pole including taking out old unserviceable changeover switch all as directed by Engr- in- charge Make : Havells ,L&T,Legrand and its equivalent |
| 15 | Supply, installation, commissioning and testing in replacement powder coated factory made out door type double door panel board confirming to IP 66 protaction, of suitable size made of Robust steel sheet construction made from min 3.15 mm steel sheet with countersunk holes at bottom for base mounting brackets and sheet steel gland plates for cable entry, formed gasket arround doors, with provision of Lock inserts, earthing straps, door stay and grouted in ground by using angle iron frame of size 50mm x 50mm x 6mm, pedastal type and provided with four nos of angle iron supports duly embedded in foundation using PCC (1:2:4) type C-1 with 20mm graded stone aggregate.The panel will be prewired with suitable size PVC insulated copper conductor cable, multistranded housed with the following accessories:- (a) Al bus bar of suitable capacity for phase and neutral.(b) MCCB 4 pole 250 Amp 36 KA alongwith Spreader terminals with adjustable thermal setting – 01 Nos (Incomming)(c) MCCB 4 pole 125 Amp 25 KA alongwith Spreader terminals with adjustable thermal setting – 04 Nos (Out going)(d) Digital volt meter 0 to 500 volt with selector switch – 01 Nos(e) Digital Amp meter 0 to 500 Amp with CT of suitable ratio and selector switch – 01 Nos(f) Phase indicator lamp RYB-01 Set |
| 16 | Supply, installation, commissioning and testing in replacement powder coated factory made out door type double door Feeder panel board confirming to IP 66 protaction, of suitable size made of Robust steel sheet construction made from min 3.15 mm steel sheet with countersunk holes at bottom for base mounting brackets and sheet steel gland plates for cable entry, formed gasket arround doors, with provision of Lock inserts, earthing straps, door stay and grouted in ground by using angle iron frame of size 50mm x 50mm x 6mm, pedastal type and provided with four nos of angle iron supports duly embedded in foundation using PCC (1:2:4) type C-1 with 20mm graded stone aggregate.The panel will be prewired with suitable size PVC insulated copper conductor cable, multistranded housed with the following accessories:- (a) Al bus bar of suitable capacity for phase and neutral.(Incoming)(b) MCCB 4 pole 125 Amp 25 KA alongwith Spreader terminals with adjustable thermal setting – 01 Nos (Outgoing)(c) (i) MCCB 4 pole 100 Amp 25 KA alongwith Spreader terminals with adjustable thermal setting – 01 Nos (ii) MCB SPN 32 AMP - 06 Nos (iii) MCB SPN 40 to 63 AMP -02 Nos (d) Digital volt meter 0 to 500 volt with selector switch – 01 Nos(e) Digital Amp meter 0 to 500 Amp with CT of suitable ratio and selector switch – 01 Nos(f) Phase indicator lamp RYB-01 Set |
| 17 | M&L for in repair earthing complete with galvanised steel earth plate electrode 60cmX60cmX6mm thick, burried directly in ground (earth pit not less than 2.25 metres deep below ground level)with top edge of the plate not less than 1.5 metres below normal groundlevel, connected to galvanised earth lead strip 32x6mm by means of volts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No-3 of SSR Part-I connected to earthing test point all as specified or indicated including excavation and connected earth work in hard/dense soil, PCC 1:3:6 type C-1 as in pit, 20mm dia GI pipe medium grade for watering pipe, 15 mm bore GI medium grade earth lead protection pipe, 50 mm thick RCC 1:2:4 type B-1 cover slab of earth pit reinforced with 8 mm dia TMT bars @ 10 cm C/C both ways and with handle made out of 10 mm dia bars, funnel, strainer,charcoal and testing on completion all as specified and directed.. |
| 18 | M&L for in repair earthing complete with galvanised steel earth plate electrode 60cmX60cmX6mm thick, burried directly in ground (earth pit not less than 2.25 metres deep below ground level)with top edge of the plate not less than 1.5 metres below normal groundlevel, connected to galvanised earth lead strip 32x6mm by means of volts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No-3 of SSR Part-I connected to earthing test point all as specified or indicated including excavation and connected earth work in hard/dense soil, PCC 1:3:6 type C-1 as in pit, 20mm dia GI pipe medium grade for watering pipe, 15 mm bore GI medium grade earth lead protection pipe, 50 mm thick RCC 1:2:4 type B-1 cover slab of earth pit reinforced with 8 mm dia TMT bars @ 10 cm C/C both ways and with handle made out of 10 mm dia bars, funnel, strainer,charcoal and testing on completion all as specified and directed.. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 10 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 10 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender