Tender For Provn Of Water Heating Arrangements For Troops Under Age E/M-V Of Ge (N) Bathinda At Bathinda Mil Stn
Tender Value
43.20 Lakhs
Estimated cost
Bid Submission
10 Sep 2026
9 days left
EMD
86400
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Bathinda → Punjab
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provn Of Water Heating Arrangements For Troops Under Age E/M-V Of Ge (N) Bathinda At Bathinda Mil Stn
BOQ
| Sl. No. | Item Description |
| 1 | Supplying, installation , testing & commissioning of Heat pumps system of 450-500 Litre capacity for hot water using heat energy source from ambient air to Hot water, of High efficiency and energy saving operation, capable of heating water at 55⁰ to 60⁰ C with silent operation (the sound level should not exceed 65 dB). The Heat Pump shall have LCD display control panel with built in diagnostic and troubleshooting information and an inbuilt cycle for defrosting in case icing occurs on evaporator including all other mounting, fitting and controls, all interconnecting wiring/cabling between heat pump and electric panel etc including hot water storage tank complete in all respect with but not limited to following specifications. Power Supply V/Ph/Hz : 400V~440V, three Phase, 50Hz. Suggested Maximum output water temperature in 0C: >55 ⁰C, ambient temperature range in 0C: -5 ⁰C~45 ⁰C , Type of Fan : Low Noise axial fan , Suggested Noise level: dB <65 , COP: 3.0 to 4.0. Hot Water Storage Tank consisting of GI/MS/SS cylindrical shape clarifier tank. (inlet temperature of hot water storage tank >550C) suitable for minimum 4 Kg /Sq.cm working pressure. Tank shall be provided with water flow meter, inlet /outlet, overflow, drain connection with cover, 6 mm thick tank, pressure relief valves, pressure gauge at inlet / outlet with isolation cock, thermometer at inlet / outlet, ball Valve, safety valve,check valve etc and capacity of the tank shall be for 03 Hr rated output. The complete system to be tested to a pressure of 10 Kg/cm2 complete in all respects including temperature indicators, thermostat and other required accessories. Tank shall be insulated with 100 mm thick crown 150 grade & 50 mm rock wool pads of approved quality and cladded with 24 SWG aluminium sheet cladding complete all as specified and directed. CAT part No AO Smith CAHP 3.0-120 or equivalent. |
| 2 | Supply, installation, testing and commissioning of Booster Pump, 1 HP capacity, suitable for operation on single phase AC supply, 180–260 Volts, 50 Hz, having discharge capacity of 21–60 LPM at rated head, complete with TEFC motor, pump and motor mounted on common base frame, suction and delivery connections, isolation valves, non-return valve, pressure gauge, flexible connections, foundation bolts and anti-vibration pads. Including construction of PCC platform of size 600 mm × 600 mm × 250 mm in PCC (1:2:4) or as specified, with necessary excavation, centering, curing and finishing, complete. Including all interconnecting piping, electrical wiring/cabling from existing supply point, glands, lugs, earthing, testing, commissioning and all accessories required for satisfactory operation, complete all as specified and directed. |
| 3 | Supply and installation of rotational moulded polyethylene water storage tank of 1000 litre capacity, triple-layer, UV-stabilized, IS:12701 marked, suitable for potable water storage, complete with cover and suitable locking arrangement. Including hoisting and placing the tank at terrace level of G+2 building, making necessary holes for inlet, outlet, overflow and washout connections, providing all necessary fittings, connections, supports, sealing, fixing and making good disturbed surfaces, complete all as specified and directed. |
| 4 | Supply and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, SDR-11, conforming to relevant IS standards, suitable for hot and cold water supply, of 40 mm nominal outside diameter, complete with all CPVC plain and brass threaded fittings, specials, unions, elbows, tees, reducers, sockets and adaptors as required. Including cutting, threading wherever required, jointing with approved one-step CPVC solvent cement, fixing to wall or ceiling with approved CPVC/MS clamps and screws at intervals not exceeding 1.00 m, making all joints, testing the pipeline for leaks under working pressure, and making good disturbed surfaces, complete all as specified and directed. |
| 5 | Supply and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, SDR-11, conforming to relevant IS standards, suitable for hot and cold water supply, of 25 mm nominal outside diameter, complete with all CPVC plain and brass threaded fittings, specials, unions, elbows, tees, reducers, sockets, adaptors and accessories as required. Including cutting, jointing with approved one-step CPVC solvent cement, fixing the pipe on wall or ceiling with approved CPVC/MS clamps and screws at intervals not exceeding 1.00 m, testing the complete pipeline and joints for leakage under working pressure, and making good disturbed surfaces, complete all as specified and directed. |
| 6 | Making connection of G.I. distribution branch pipe with existing G.I. main pipe of 25 mm to 40 mm nominal bore by providing and fixing suitable G.I. tee, including cutting, threading and fitting of G.I. pipes, applying approved jointing materials, tightening, alignment, leak testing and making good the disturbed surfaces, complete with all necessary fittings and accessories, all as specified and directed. |
| 7 | Supply and fixing of CPVC ball valve of 25 mm nominal outer diameter, suitable for hot and cold water supply system, complete with CPVC connections, necessary adaptors, fittings, jointing materials and accessories. Including cutting, fitting, alignment, making joints with approved CPVC solvent cement/threaded connections as applicable, testing for leakage and making the installation complete in all respects, all as specified and directed. |
| 8 | Supply and fixing of CPVC ball valve of 40 mm nominal outer diameter, suitable for hot and cold water supply system, complete with CPVC connections, necessary adaptors, fittings, jointing materials and accessories. Including cutting, fitting, alignment, making joints with approved CPVC solvent cement/threaded connections as applicable, testing for leakage and making the installation complete in all respects, all as specified and directed. |
| 9 | Supply and fixing of CPVC tank union of 40 mm nominal outer diameter, suitable for hot and cold water supply system, complete with all necessary CPVC components, washers, nuts, adaptors, jointing materials and accessories. Including making connection to water storage tank, cutting and fitting as required, jointing with approved CPVC solvent cement/threaded connections, testing for leakage and making the installation complete in all respects, all as specified and directed. |
| 10 | Supply and fixing of CPVC union of 40 mm nominal outer diameter, suitable for hot and cold water supply system, complete with all necessary CPVC components, threaded ends, washers, jointing materials and accessories. Including cutting, fitting, alignment, jointing with approved CPVC solvent cement/threaded connections as applicable, testing for leakage and making the installation complete in all respects, all as specified and directed. |
| 11 | Supply and fixing of CPVC union of 25 mm nominal outer diameter, suitable for hot and cold water supply system, complete with all necessary CPVC components, threaded ends, washers, jointing materials and accessories. Including cutting, fitting, alignment, jointing with approved CPVC solvent cement/threaded connections as applicable, testing for leakage and making the installation complete in all respects, all as specified and directed. |
| 12 | Material and labour for circuit/submain wiring using FRLS/HFFR PVC insulated copper conductor single core cables of size 4 × 6.0 sq.mm phase/neutral conductors + 2 × 6.0 sq.mm earth continuity conductors, drawn in surface or recessed medium class PVC conduit as required, including supply and fixing of PVC conduits, bends, junction boxes, saddles, spacers, draw wires, cable pulling, termination with suitable lugs, glands, insulation tape and all necessary accessories. Including testing of insulation resistance, continuity, polarity and earth continuity, complete in all respects as specified and directed by Engineer-in-Charge. |
| 13 | Material and labour for circuit/submain wiring using FRLS/HFFR PVC insulated copper conductor single core cables of size 2 × 2.5 sq.mm phase/neutral conductors + 1 × 2.5 sq.mm earth continuity conductor, drawn in surface or recessed medium class PVC conduit as required, including supply and fixing of PVC conduits, bends, junction boxes, saddles, spacers, draw wires, cable pulling, termination with suitable copper lugs, glands, insulation tape and all necessary accessories. Including testing of insulation resistance, continuity, polarity and earth continuity, complete in all respects as specified and directed by Engineer-in-Charge. |
| 14 | Supply and fixing of metal enclosed plug socket outlet, single pole and neutral, complete with two pin and earth plug arrangement, suitable for 230 V AC supply, provided with 1 No. 20 Ampere SP MCB of 'C' series characteristics, IP-43 protected enclosure, complete with all necessary accessories including base plate, cover, terminals, connectors, fixing screws and hardware. Including connection of incoming and outgoing cables, testing for proper operation, insulation resistance, polarity and earth continuity, complete all as specified and directed. |
| 15 | Supply and fixing of double door type SPN Distribution Board (DB), 4 Way, 240 V, complete with 200 Ampere copper busbar for each phase, metal enclosure with double door arrangement having IP-54 ingress protection and IK-09 impact protection, suitable for housing MCBs. The DB shall be complete with neutral link, earth bar, DIN rail, detachable gland plates, cable entry arrangement, powder coated enclosure, fixing accessories and all necessary hardware. Including making connections, dressing of cables, testing of insulation resistance, polarity, continuity and earth continuity. MCB DB shall be concealed in wall wherever possible, including cutting of wall, fixing, making good the surface and finishing to match the surrounding colour, complete all as specified and directed by Engineer-in-Charge. |
| 16 | Providing and fixing 100 Ampere, 16 kA, TPN MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board, suitable for operational voltage up to 690 V AC, having service short circuit breaking capacity (Ics) equal to 100% of ultimate short circuit breaking capacity (Icu). Including drilling/cutting of required holes in cubicle panel, mounting and fixing of MCCB, providing terminal spreaders, making incoming and outgoing cable connections with suitable lugs, glands and hardware, tightening, testing for proper operation, insulation resistance, continuity and tripping characteristics, complete in all respects as specified and directed by Engineer-in-Charge. |
| 17 | Material and labour for supplying, laying, connecting and testing of XLPE insulated, screened, PVC bedded, galvanized steel strip/wire armoured electric power cable (heavy duty), ISI marked, 1100 Volt grade, with stranded aluminium conductor, size 25 sq.mm, 4 core, laid in trenches, under floors/roads or on walls, on existing or new route as required. Including excavation wherever required, laying of cable with proper bending radius, providing sand cushioning/protection where applicable, fixing on walls with clamps/supports, jointing and termination with suitable glands, lugs, cable tags, identification ferrules and all necessary accessories. Including testing of insulation resistance, continuity, phase identification and commissioning, complete in all respects as specified and directed by Engineer-in-Charge. |
| 18 | Excavation in trenches in soft/loose soil not exceeding 1.5 m width and 1.5 m depth, including setting out, excavation to required line, level and gradient, getting out excavated earth, dressing the sides and bottom of trenches, protection of excavation where necessary and all incidental works, complete with all labour, tools and tackles, all as specified and directed. |
| 19 | Returning filling in trenches/depressions with excavated earth of approved quality, including spreading, levelling and well ramming/compaction in layers not exceeding 25 cm thickness each, watering wherever required, dressing and finishing the filled surface to required levels, complete with all labour, tools and tackles, all as specified and directed. |
| 20 | Removing surplus excavated earth/material from site within a lead not exceeding 50 metres from the starting point and depositing the same at the place directed, including loading, carrying, unloading, spreading and levelling the deposited material, with height of deposit not exceeding 1.5 metres above the starting point, complete with all labour, tools and tackles, all as specified and directed. |
| 21 | Material and labour for filling trenches with clean, dry, unwashed sand for cable protection, including supply, transportation, spreading and filling of sand around and over cables in layers, gently punning/compacting by hand without causing damage to cables, complete in all respects as specified and directed.Note: Only the compacted (punned) thickness of sand filling shall be measured for payment. |
| 22 | Material and labour for providing old size well burnt bricks laid flat for protection of underground cables, including supply of bricks, laying flat over cable route with proper alignment, jointing/filling with suitable mortar where required, handling, dressing and all incidental works necessary for complete cable protection, all as specified and directed. |
| 23 | Supply and fixing of chromium plated cast copper alloy bib tap, 15 mm nominal bore, fancy type, suitable for connection to iron pipe/brass ferrule, screwed down pattern, complete with crutch or butterfly handle, including necessary fittings, washers, jointing materials and accessories. Including fixing, alignment, making connection, testing for leakage and making the installation complete in all respects, all as specified and directed by Engineer-in-Charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 27, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 10, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 9 daysSep 12, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender