Tender Overview
Project Description
Tender for Comprehensive Maintenance Of Water Cooled Ac Plant At Certain Locations And Replacement Of Filter Unsv Control Valves, Ms Pipes Insulation Of Chilled Water Pipe, Ducts, Control Panel, Starter, Rewinding Of Motor At Site A2 Of Naval Base Karwar
BOQ
| Sl. No. | Item Description |
| 1 | M & L for disconnecting condenser for descaling & Plugging them & providing of 15 mm tee out let for local circulation of mild acid solution in the condenser (separate container and small pump set to circulate diluted acid solution to be used) PH value of solution to be circulated & to be kept 4 and checking frequently i.e. every one hour during the operation Scalgun WS solution to be used for descaling purpose after 2 to 3 hours of cleaning if ph value remains less than 7 flush with fresh water mixed with sodium carbonate tubes and cleaning with nylon brush after closing the end covers, circulating diluted acid solution as specified above & PH value to be maintained as above & flushing the same with fresh water including recharging of stored refrigerant up to required pressure complete all as specified & directed by EIC of for 30 TR at WED/NSD/Ware House. |
| 2 | Pumping down the plant to preserve the existing refrigerant gas & leak testing chiller plant by charging of Nitrogen gas in to entire plant & monitoring for 24 hrs to find the leakages rectification of leak by brazing/ Capping leaked tubing & replacement of necessary gasket packing as wherever required including copper tubes of suitable size vacuumising of the plant by vacuum pump & keeping 24 hrs for testing including rectification of leakages if any finally recharging of existing refrigerant gas to the plant and and topping up of refrigerant if required to maintain the standard pressure complete testing of the plant for smooth functioning complete. |
| 3 | (a) 30 TR chiller unit at WED/NSD |
| 4 | (b) 7.5 TR chiller unit at BGRP |
| 5 | (c ) 26 TR Chiller Unit at Ware House |
| 6 | M & L for taking out the centrifugal pump motor and transporting to work shop, split opeing the motor removing the u/s burnt winding wire, cleaning the slots, re winding with super enameled copper conductor wire of suitable size including insulating materials, varnishing and drying and reassembling and transporting back to site , coupling with pump testing and commissioning all as directed for the following capacities of motors : - |
| 7 | (a) 25 Hp |
| 8 | (b) 7.5 Hp |
| 9 | (c) 5 Hp |
| 10 | (d) 3 Hp |
| 11 | Repairing /servicing and overhauling the centrifugal pump by dismantling the pump coupled with induction motor, opening the pump, inspecting for defects and replacing the worn out parts like gland bush, bearings, gland bolts and nuts,gland packing, gasket, water seal etc including repairs to pump shaft by remetalling, grinding, polishing and reassembling the same and replacing the rusted nuts, bolts, washers etc and coupling with motor testing complete for the following capacity of pumps complete all as specified and as directed. |
| 12 | (a) 5 hp at WED/NSD/ Ware House |
| 13 | (b) 3 hp at BGRP |
| 14 | (c ) 7.5 HP at Ware House |
| 15 | Taking out old unserviceabe scroll compressor 13 TR capacity from the unit after disconnecting electrical wiring and piping connections , nuts and bolts etc and Supply and fixing new scroll compressor 13 TR capacity and connecting pipe line for existing piping brazing and electric connection etc complete all as specified and directed. |
| 16 | Supply & charge refrigerant (R - 22) gas as per requirement complete all as specified and as directed. |
| 17 | Supply & charge refrigerant (R 407 C) gas as per requirement complete all as specified and as directed |
| 18 | Topping up / Replacement of compressor oil with new compressor oil of approved Make complete all as specified and as directed. |
| 19 | Supply and replacing the following defective / worn out spares / controls for the chiller Plant of make Kirloskar/ Voltas/ Blue Star all as specified and as directed |
| 20 | (a) Water Flow Switch complete all as directed . |
| 21 | (b) Moisture liquid indicators complete all as directed. |
| 22 | (c ) Single phase preventor for compressor /Motor for SM 101 GIC or eqv complete all as specified and as directed. |
| 23 | (d) Strip type 3 KW Heaters |
| 24 | (e) Strip type 2.0 KW Heaters |
| 25 | (f) Pressure gauge 0-300 PSI . |
| 26 | (g) Pressure gauge 0-150 PSI |
| 27 | (h) Filter drier core for 30/22 TR Central AC Plant |
| 28 | (j) LP/HP cut out switch for 30/22 TR Central AC Plant |
| 29 | (k) LP/HP cut out switch For 26 TR Central AC Plant |
| 30 | (l) Filter Drier 5/8'' Flarring type For 26 TR AC Plant |
| 31 | (m) Float Valve for 25 mm |
| 32 | (n) Cooling tower fins of size 4'x6' |
| 33 | (o) Supply and replace the worn out 'V' belts of blower motor. (Make : Make : Eco drive / fenner / reenolds rubber) |
| 34 | (p) Mercury in glass industrial type thermometer |
| 35 | M&L for applying one coat of synthetic enamel paint as per colour code with spray machine on surfaces of 3x30 TR central AC plant comprising compressor motor, Pump, water pipe lines etc by filling cavities if any with filler including preparation of surfaces & indication markings all as specified and directed. WED/NSD/Ware house |
| 36 | M&L for applying one coat of synthetic enamel paint as per colour code with spray machine on surfaces of 3x7.5 TR central AC plant comprising compressor motor, Pump, water pipe lines etc by filling cavities if any with filler including preparation of surfaces & indication markings all as specified and directed. BGRP |
| 37 | Taking down motor, blower fan assembly from cooling Tower, removing unserviceable fins , & providing new PVC fins of size 4\\"x6\\" ,after cleaning of Louvers, drift eleminators fill surface by moderate pressure water nozzle to remove all surface impurities incl removal of rust/scale, scrapping down the hard water deposited from bottom tray with chemical and preparing the surfaces and painting with one coat of anticorrosive paint to match with existing colour, servicing of fan and motor assembly including removal of dust, oil, scale of motor body and replacing of unserviceable nozzle,bearings , painting with anti corrosive paint, draining and filling of bearing housing with new SAE 20 grade mineral oil, greasing of bearing with IOCL mobilux etc , & reassembling complete of following cooling towers |
| 38 | (a) FRP Cooling tower capacity 131 USGPM Make Paharpur AT WED/NSD |
| 39 | (b) FRP Cooling tower capacity 130 USGPM Make Paharpur at Ware House |
| 40 | (c) FRP Cooling tower capacity 30 USGPM Make Paharpur AT BGRP |
| 41 | Supply and fix in repair Pressure sensor as per exiting complete all as specified and directed by engineer- in- charge |
| 42 | Supply and fix in repair Temprature sensor as per exiting complete all as specified and directed by engineer- in- charge |
| 43 | Removing old unserviceable insulation of chilled water pipe line and cleaning the surface & applying one coat of TPRA coat & M & L for wrapping on MS Chilled water pipe line with 50/40 mm thick fiber glass wool moulded to shape the thermal insulation in selection of 50 mm crown wrapped with chicken mesh wire netting 20 SWG and 20mm mesh & aluminium cladding with 24 SWG aluminum sheet on 150/100 mm dia MS chilled water pipe line complete all as specified & directed |
| 44 | Supply Erecrtion testing and commissioning in repair 19 mm thick thermal insulation O closed cell elastomeric nitrile rubber with aluminum foil laminated on oneside, having thermal Temperaturte, of 20 c as per EN 12667, moisture diffusion resistance factor or u Value of minium 7000 for base insulation material without the foil as per EN 12086, fire performance such that it passes Class 1 as per BS476 Part 7 for surface spread of flame and also fire performance of V0, HB as per UL 94, 1996, density without the foil between 40 to 55 KG/ Cum. the insulation material shall be FM ( factory Mutual) USA approved and dust & fiber free. the Aluminium foil shall be 60 microns thick and its weight shall be 193 gms as per EN ISO 2286-2, tensile strength 90 N/ 15 mm as per EN ISO 527-3 with elongation>10% as per EN ISO 527-3 complete all as specified and as directed. |
| 45 | Supply & Fix in repairs MS pipe heavy grade 80 mm dia including removing of unserviceable MS pipe medium grade of 80 mm dia all as specified & directed |
| 46 | Supply & Fix in repairs MS pipe heavy grade 100 mm dia including removing of unserviceable MS pipe medium grade of 100 mm dia all as specified & directed |
| 47 | Supply & Fix in repairs MS pipe heavy grade 50 mm dia including removing of unserviceable MS pipe medium grade of 50 mm dia all as specified & directed |
| 48 | Supply & Fix in repairs MS pipe heavy grade125 mm dia including removing of unserviceable MS pipe medium grade of 125 mm dia all as specified & directed |
| 49 | Supply & Fix in repairs MS pipe heavy grade 65 mm dia including removing of unserviceable MS pipe medium grade of 65 mm dia all as specified & directed |
| 50 | Supply & Fix in repairs butter fly valve 50 mm dia including removing of unserviceable butter fly valve of size 50 mm dia all as specified & directed. |
| 51 | Supply & Fix in repairs butter fly valve 80 mm dia including removing of unserviceable butter fly valve of size 80 mm dia all as specified & directed. |
| 52 | Supply & Fix in repairs butter fly valve 65 mm dia including removing of unserviceable butter fly valve of size 65 mm dia all as specified & directed. |
| 53 | Supply and fix in repair and replacement NRV of dia 80 mm suitable for condensing /chiller water line with ISI marked including jointing with proper gasket ,nut,bolts washer all as specified. |
| 54 | Supply and fix in replacement NRV of dia 50 mm suitable for condensing /chiller water line with ISI marked including jointing with proper gasket ,nut,bolts washerall as specified. |
| 55 | M&L for disconnecting and removing oid unserviceable AHU dranage line of MS pipe, S & F of new dranage line of 50/25 mm dia UPVC Pipe includind all fittings and necessary clamping all as specified and directed by Engineer-in-charge. |
| 56 | Supply and fixing in repair expansion valve for 22TR/30 TR AC plant as per exisiting make complete all as specified and directed. |
| 57 | Supply and fixing in repair expansion valve for 26 TR AC plant as per exisiting make complete all as specified and directed. |
| 58 | Supply and fixing in repair expansion valve for 7.5 TR AC plant as per exisiting make complete all as specified and directed. |
| 59 | S&F in replacement of double fitted polymer fabric HDPE fresh air filter(Filter class-G3 as per EN 779) washable/cleanable type having efficiency 95% to 99% down to particle size of 10 micron, fabricated out of CRCA sheet metal duly painted with two coat of grey hammer tone spray painted over two coats of red oxide primer, with lifting handle, Box/flanged type, aluminium spacer etc, complete all as specified and as directed by engr-in-charge of following sizes :- |
| 60 | (a) 600x600x50 mm |
| 61 | (b) 600x500x50 mm |
| 62 | (c)600x400x50 mm |
| 63 | (d)500x400x50 mm |
| 64 | S&F in replacement of double fitted polymer fabric HDPE fresh air filter(GL-type) washable/cleanable type having efficiency 95% to 99% down to particle size of 5 micron, fabricated out of CRCA sheet metal duly painted with two coat of grey hammer tone spray painted over two coats of red oxide primer, with lifting handle, Box/flanged type, aluminium spacer etc, including taking down complete all as specified and as directed by engr-in-charge of following sizes :- |
| 65 | (a)600x600x300 mm |
| 66 | (b)600x500x300 mm |
| 67 | (c)600x400x300 mm |
| 68 | (d)500x400x300 mmm |
| 69 | S&F in replacement of double fitted polymer fabric HDPE fresh air filter(Filter class-G3 as per EN 779) washable/cleanable type having efficiency 95% to 99% down to particle size of 10 micron, fabricated out of CRCA sheet metal duly painted with two coat of grey hammer tone spray painted over two coats of red oxide primer, with lifting handle, Box/flanged type, aluminium spacer etc, complete all as specified by engr-in-charge of following sizes :- |
| 70 | (a) 610x610x50 mm |
| 71 | (b) 600x305x50 mm |
| 72 | S&F in replacement of filter \\"HEPA\\"(EN-1882) with fibre glass paper filtering media capacited 1000 CFM efficiency 99.97% down to particle size of 0.3 to 0.5 micron aluminium frames box type of size 600x600x300mm including taking down complete all as specified and as directed. |
| 73 | S&F in replacement of filter \\"HEPA\\"(EN-1882) with fibre glass paper filtering media capacited 1000 CFM efficiency 99.97% down to particle size of 0.3 to 0.5 micron aluminium frames box type of size 450x450x300mm including taking down complete all as specified and directed |
| 74 | M&L in repair duct insulations with resin bonded fiber glass wool density 24 Kg/Cum with laminated aluminium barriers thick 50 mm and including following :-(a) Cleaning the duct surface.(b) Applying rubber based adhesive CPRX compound.(c) Ceiling all joints and circular cover laps including alumunium foil taps 50 mm size 12/50 mm maximum intervals 1.2 mtrs. |
| 75 | Removing side panel of AHU of any capacity, dismantling of AHU carefully removing unserviceable blower bearings and removing motor and blower assembly , replacement of AHU blower bearings after machining of shafts, cleaning bottom tray of AHU and refixing electric motor and top side panel in origial position with new bolts washers and shafts keys and bottom of tray and checking the shafts balancing and testing for smooth running all as specified and directed. |
| 76 | Supply & Fixing in repairs monoblock pump set of capacity 3HP,C.I,M.S,SS , Head 12 to 36 Mtrs ,LPS 2 to 5 LPS suitable for three phase 50 Cycle, 433V, AC Supply complete all as specified and directed by Engr-in-charge. |
| 77 | Supply & Fixing in repairs aluminium busbar of rated capacity 200A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection complete all as specified and directed. |
| 78 | Supply & Fixing in repair LED phase indicators (Red, Yellow, Blue) omplete all as specified and directed. |
| 79 | Supply & Fixing in repair Digital multi function meter with 63/5 CT capable of measuring V, A, F, PF, W/VA, WH, Vah, Runhrs, Onhrs & interrups- complete all as specified and directed. |
| 80 | Supply & fixing in repair digital display thermo hygrometer measuring temp and RH to be installed in conditioned space, complete all as specified and as directed. |
| 81 | Supplying, fixing, testing and commissioning in repair of Y - Strainer of Ductile CI Body flanged ends with stainless steel strainer for chilled water circulation of size 80 mm, in the chilled/hot water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications complete all as specified and as directed. |
| 82 | Supply and fixing in repair in position Ball Valves 25 mm dia for makeup line as per specifications complete all as specified and as directed |
| 83 | Supplying, installing, testing and commissioning in repair of Fresh Air powder coated Anodized extruded aluminium construction fresh air louvers (50 mm deep) (Fresh air louver with VCD , bird screen & rattle-free) complete as per specification complete all as specified and as directed |
| 84 | Supplying ,laying , fixing in repair & testing of following sizes of XLPE insulated,armoured heavy duty electric cable with aluminium conductor,1100 volts grade complete as required and as directed |
| 85 | 4 core 10 sqmm |
| 86 | 4 core 6 sqmm |
| 87 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded,galvanized steel strip or wire armoured,electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 sq mm 3.5 core |
| 88 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded,galvanized steel strip or wire armoured,electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core |
| 89 | Supply and fixing in repair amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) SP of 6 to 32 Amps current rating complete with connection testing and commissioning. |
| 90 | Opening the LT Panel board cubical type for DG set located in DG room, cleaning the Bus Duct chamber, inspect the complete panel, tighten the all incoming, outgoing ACBs/MCCB s/ SFU of different capacity, nuts, bolts, bus bar insulator and replace with new one if required and heating up for removal of moisture, record its IR value with the help of 1.1KV megger and applying thick coating of Z931 strippex B and Z 955 Strippex (SL) of stanvac product for preventing from flush over and fire hazard, including replacement of 3mm thick gasket, closing of all holes and charging the same complete all as specified and as directed. |
| 91 | All as per item No. 50 but for main electric panel |
| 92 | All as per item No. 50 but for DG auxiliary panel. |
| 93 | All as per item No. 50 but for AC Plant panel. |
| 94 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded,galvanized steel strip or wire armoured,electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185 sq mm 3.5 core complete all as specifid and as directed |
| 95 | Excavation in trenches, not exc 1.5 mtr wide and not exc 1.5 mtr in depth for laying of pipe line in soft / loose soil and getting out in soft / loose soil complete all as specified. |
| 96 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm in soft/loose soil all as specified & directed |
| 97 | Removing excavated meterial to a distance n.exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point all as specified & directed by Engineer-in-Charge |
| 98 | M&L for natural dry river sand cushioning including spreading, levelling and hand punning to underground cable in trench all as specified and directed.Note : Punned thickness shall only be measured and paid. |
| 99 | M&L for brick protection with PCC cable cover class LV, type-I, flat size 250mmx150mmx40mm factory casted ISI marked all as specified and directed. |
| 100 | Supply and lay GI tubing, 'light grade' of size 80 mm ,with all fittings as in cable protection, laid in trenches all as specified and directed by Engineer-in-charge. |
| 101 | M&L for rectification of defects and making functional cold room,cool room of any capacity incl rectification of minor defect such as tripping of MCBs, replacement of MCBs labour only wherever necessary, rectifying loose electrical connections, making fresh connections in electric panel / connectorr etc, making functional of defective drain pipe blockage/leakage etc, checking of functionality of compressor of any capacity etc complete all as specified and directed. Make Blue starNote :- (i) Unit rate quoted shall include for maintaining proper record and obtain the signature of concerned user unit. (ii) Unit rate quoted shall include for sundry items / materials as required. |
| 102 | Cool room- 1 with capacity 4 ton reciprocating compressor |
| 103 | Cold room - 1 with capacity 9 ton reciprocating compressor |
| 104 | M&L for rectification of defects and making functional cold room,cool room of any capacity incl rectification of minor defect such as tripping of MCBs, replacement of MCBs labour only wherever necessary, rectifying loose electrical connections, making fresh connections in electric panel / connectorr etc, making functional of defective drain pipe blockage/leakage etc, checking of functionality of compressor of any capacity etc complete all as specified and directed. Make- carrierNote :- (i) Unit rate quoted shall include for maintaining proper record and obtain the signature of concerned user unit. (ii) Unit rate quoted shall include for sundry items / materials as required. |
| 105 | (a) Cool room -2 with capacity 4 ton reciprocating compressor |
| 106 | (b) Cold room- 2 with capacity 9 ton reciprocating compressor |
| 107 | Supply only R-134 A refrigerant gas in sealed container. |
| 108 | Supply only R-404(a) refrigerant gas in sealed container. |
| 109 | Labour only for gas charging with required quantity with R-134 a and R- 404 a refrigerant gas including all allied works such as vaccumising the complete system, soap leak test, nitrogen gas pressure test, replacement of copper filters, capillary, copper tubing of suitable size and required length, flux, flare nut, dead plug, dead cap, brazing etc including necessary welding work, testing and commissioning upto satisfactory performance for the following :-Note :- Qty of gas will be measured and paid separately. |
| 110 | Refrigeration circuit of cool room of capacity 4 Ton. |
| 111 | Refrigeration circuit of cold room of capacity 9 Ton. |
| 112 | S&F in repair as per existing new fan / blower motor, single end shaft, single phase, 240 volts, 2 HP metallic body including fan blade assembly suitable for 9 TR and 4 TR make- Alstom/Marthom for outdoor unit of complete all as specified and directed. |
| 113 | S&F in repair three phase preventer cum controller for operation of floor mounted AC of 3 Ton capacity. complete all as specified and directed. |
| 114 | S&F in repair HP/LP cut out for floor mounted AC of 3 Ton capacity complete all as specified and directed. |
| 115 | Supply and fixed in repairs cassette AC indoor PCB for 3 TR complete all as specified and directed. |
| 116 | Supply and fixed in repairs expansion valves thermostatical type for cold storage of capacity 9 ton compressor complete all as specified and directed. |
| 117 | Supply and fixed in repairs expansion valves thermostatical type for cool storage of capacity 4 ton compressor complete all as specified and directed. |
| 118 | Supply and fixed in repairs filter drier model DG -304 suitable for refrigerant 404 (a) for cold storage of capacity 9 ton compressor complete all as specified and directed. |
| 119 | Supply and fixed in repairs filter drier for cool room suitable for refrigerant 134 (a) of capacity 4 ton compressor complete all as specified and directed. |
| 120 | Supply only Condensor fan motor capacity of 4 TR along with leaf suitable for existing bracket of outdoor unit suitable for +4°C cool Room complete all as specified and as directed. |
| 121 | Supply only Condensor fan motor capacity of 9TR along with leaf suitable for existing bracket of outdoor unit suitable for -18°C to - 30°C cold Room complete all as specified and as directed |
| 122 | Supply only Evaporator fan motor capacity 4 TR along with leaf suitable for existing bracket of Indoor unit suitable for +4°C cool Room complete all as specified and as directed |
| 123 | Supply only Evaporator fan motor capacity of 9 TR along with leaf suitable for existing bracket of Indoor unit suitable for -18°C to - 30°C cold Room complete all as specified and as directed |
| 124 | Supply only liquid line drier ( Model 604) complete all as specified and as directed. |
| 125 | Supply only Oil Pressure Switch complete all as specified and as directed. |
| 126 | Supply only Solenoid Valve complete all as specified and as directed. |
| 127 | Supply only Cold Room Defrost Heater working on 230 V complete all as specified and directed. |
| 128 | Supply only Door handle suitable for temprature range -18 °C to -30 °C cold rooms complete all as specified and directed |
| 129 | Supply only Door handle suitable for temprature range +4°C cool rooms complete all as specified and directed |
| 130 | S&F in repair 3 phase Contactor Model No ( A-16-A-30-10-240Volt) suitable for 9TR compressor of Cold room complete all as specified and directed. |
| 131 | S&F in repair 3 phase Contactor Model No ( A-9-30-10-240 Volt ) suitable for 9TR compressor of Cold room complete all as specified and directed. |
| 132 | S&F in repair 3 phase Contactor Model No ( B-25-30-10-240 Volt ) Volt suitable for 9TR compressor of Cold room complete all as specified and directed. |
| 133 | S&F in repair 8 Pin Pla relay suitable for 4TR and 9 TR compressor of Cold room & Cool room complete all as specified and directed. |
| 134 | S&F in repair 3 phase Contactor Model No ( B-9-30-10-240V) suitable for 4TR compressor of Cool room complete all as specified and directed. |
| 135 | S&F in repair 3 phase Contactor Model No ( MNX-18-240) suitable for 4TR compressor of Cool room complete all as specified and directed. |
| 136 | Supply and fixing in repairs sub zero suitable for 4 TR and 9TR compressor complete all as specified and directed. |
| 137 | Supply and fixed in repairs overload relay for capacity 9 ton and 4 Ton compressor complete all as specified and directed. |
| 138 | Supply and fixed in repair and replacement of Reciprocatiing Compressor of capacity 9TR all as specified and directed by Engineer-in Charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 13 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 15 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender