Tender For Repair / Maintenance Of Security Lights , Garden Lights, Solar Lights And Other Maintenance Works In The Aor Of Age E/M Division Under Ge (Nw) Mankhurd.
Tender Value
Ref. Documents
Estimated cost
Bid Submission
17 Sep 2026
21 days left
EMD
94000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Mumbai Suburban → Maharashtra
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair / Maintenance Of Security Lights , Garden Lights, Solar Lights And Other Maintenance Works In The Aor Of Age E/M Division Under Ge (Nw) Mankhurd.
BOQ
| Sl. No. | Item Description |
| 1 | Excavation in trenches not exceeding 1.50 m wide and n.exc 1.5 m in depth for foundation of poles, cable etc, not exc 10 sqm on plan and getting out in soft/loose soil including taking out brick protection etc complete all as specified and directed. |
| 2 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25cm thick complete all as specified and directed. |
| 3 | Removing excavated materials (soils) not exc. 50m and depositing where directed at a level not exc. 1.5m above the starting point complete all as specified and directed. |
| 4 | M & L for sand cushioning by spreading in trenches fine crush sand by gently by punning down manually as in cable protection all as specified and as directed by Engineer -in-charge. |
| 5 | Supply and laying in repairs un-reinforced precast concrete cable cover class LV, type-I, flat size 250mm x 150mm x 40mm laid in trenches all as specified. Make: MEHTAB /NATIONAL TILES |
| 6 | Laying only un-reinforced precast concrete cable cover class LV, type-I, flat size 250mm x 150mm x 40mm laid in trenches all as specified. Note :- Serviceable cable cover obtained here-in-after shall be reused. |
| 7 | Dismantling only in repairs of PCC foundation / pole coping from ground level all as per specified. |
| 8 | M & L in repairs for PCC 1:2:4, type B-1, (using 20mm graded stone aggregate) as in coping including necessary use & waste of form work complete all as specified and directed. |
| 9 | Supply and Laying in repairs or fixing or passing through pipe, XLPE insulated ISI marked, armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 16 Sqmm 4 core including necessary connection and providing cable lugs as required including disconnection/taking down of existing cable all as specified. Make: Polycab/ Havell's/ KEI/ Gloster |
| 10 | -Ditto- all as per item No 9 above here-in-before but 10 Sqmm 4 Core complete all as specified & directed. Make: Polycab/ Havell's/ KEI/ Gloster/ Universal |
| 11 | M & L for earthing in repairs complete with Copper earth plate electrode 600x 600x 3 mm buried directly in ground with top edge of the plate not less than 1.5 mtrs below normal gound level and connected to earth test point by means of copper Strip of size 20x3 mm all as specified and shown in electric plate No 3 of MES SSR Part-I 2009 including earthwork, PCC chamber, CI cover, protection and watering pipe, funnel, mesh etc all as required at site and all as directed and including taking down of old earthing materils |
| 12 | S & F in repairs copper 20x3 mm earth continuity strip fixed to walls on batten or recess or chases or buried in ground or drawn in conuit / pipe or fixed to poles or any other indicated situation for earthing, etc. as fixed / laid in repairs complete all as specified and directed by the Engineer-in-charge |
| 13 | M & L in repairs for reinforced cement concrete nominal mix M-20 (using 20mm graded stone aggregate) for foundations, including rafts, footings, foundation beams, plinth beams, bases for column etc and mass concrete, complete all as specified and directed. |
| 14 | M & L in repairs for TMT bars of Fe-500 D grade conforming to IS: 1786, 10 mm dia & over, including cutting to length, bent to shape required, cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with clips etc, complete all as specified and directed. |
| 15 | M & L in repairs for TMT bars of Fe-500 D grade conforming to IS: 1786, 8mm dia bars as in binders, spacers, strippus including cutting to length, bent to shape required, cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with clips etc, complete all as specified and directed. |
| 16 | M & L in repairs for use and waste of formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams , side and soffits (if any) of foundation and plinth beams and similar work, vertical or to batter, for rough finished surfaces of concrete, complete all as specified and directed. |
| 17 | Dismantling only in repairs of old UNSV/rusted steel tubular poles 9 mtr long necessary disconnecting cables/over head condcutor and removing unserviceable pole from site complete all as specified and directed. |
| 18 | Supply, Fixing and connection of hot dip galvanised octagonal poles of height 8.5 mtr with 130 mm bottom A/F & 70mm top A/F made up of 3mm thick HT sheet along with base plate of size 200 x 200 x 12mm thick including 4 nos of M20 x 600 long J type foundation bolts and 1 mtr long hot dip galvanised single arm standard bracket, including MCB of 6 Amps, with connector 4 way to be provided as termination point complete all as specified and directed. |
| 19 | Preparing surfaces in repairs of steel tubular swaged pole LT with scraping out old paint by emmery paper, wire brush complete and painting with two coats of aluminium paint and numbering of poles with white paint on black paint background and stripping with black and yellow synthetic enamel paint (100 mm each stripe) 3 Nos at equal distance from bottom (above PCC coping) upto a height of 1200 mm complete. Make:- Paint:- ASIAN/ NEROLAC/ BERGER, Primer:- Best available ISI Brand in Market |
| 20 | M & L in repairs for preparation of old painted surfaces of pre-stressed concrete pole upto 11/9 mtr long by scarping old paint and applying two coats of cement base paint including numbering of pole with black synthetic enamel paint painting the base of the pole in alternate black and yellow stripes each 30 Cm apart up to 1.5mtr height all as directed by Engineer in Charge. Make:- Paint:- ASIAN/ NEROLAC/ BERGER, Primer:- Best available ISI Brand in Market |
| 21 | Supply and fix in repair of Cable junction box IP 66/69 \\"weather proof\\" (with knockouts for cable entry) box of size 155 x 210 x 92 mm with connector/terminal, Din Rail, GI clamps made out of GI flat of size 25 mm X 3 mm channel including providing cable gland plate and including cable glands as required at size and making connections all as specified and directed by Engineer –in –Charge. Make - National/ Sintex/ Hensel |
| 22 | Supply and fix in repair of Cable junction box IP 66/69 \\"weather proof\\" (with knockouts for cable entry) box of size 130 x 180 x 77 mm with connector/terminal, Din Rail, GI clamps made out of GI flat of size 25 mm X 3 mm channel including providing cable gland plate and including cable glands as required at size and making connections all as specified and directed by Engineer –in –Charge. Make - National/ Sintex/ Hensel |
| 23 | Supply & Fixing LT, Air Circuit Breaker, operational voltage 660 Volts, insulation voltage 1000 Volts, AC, 50 cycles, 3 phase, 4 pole, Manual draw out type, rated current rating 630 amps and of breaking capacity 50 KA with quick make, quick break with manual operating mechanism complete with Triple mound current transformer, Microprocessor based over current stop less release and static trip release, adjustable short circuit release, earth fault release with shunt trip with indication under voltage release and wired for indicating \\"Trip Healthy Circuit\\" ancillary switch etc complete over load release 400 to 600 Amps complete all as specified and directed. Make - Legrand/ L&T/ Schneider/ABB/C&S/Siemens |
| 24 | M&L for cutting existing road/hard standing not exc 30x60 cm in wide & depth getting out excavated material for laying GI tube including returning filling & well rammaing watering finish suraface and provision of 10 cm concrete using PCC 1:3:6 type C2 from Top', including removal of surplase soil all as directed. |
| 25 | S & F in repairs/ replacement of GI steel tubing medium grade 40 mm dia for laying in ground, along the pole in coping, road crossing etc for cable protection including necessary fittings , clamps for supports, etc all as directed by Engineer in charge. Make- TATA/ JINDAL/ ZENITH/ SURYA |
| 26 | M&L for taking down old unsv and supply & lay 3 Core 1.5 Sq mm size multistranded FRLS copper conductor PVC unsheathed 650 / 1100 Volt Grade As per IS 694 with and including 20 mm dia PVC conduit with necessary saddle, clamps, bolts & nuts, all for interconnection of cable looping box to Street Light Fitting, Post Top Lantern etc all as Directed. Make :- POLYCAB / KEI / HAVELLS/ BENLO |
| 27 | Dismantling and taking down the existing defective street light fitting/Garden lights/Building security light of any type and any capacity from steel tubular pole, opening the street light fitting, checking the serviceability of spare parts including replacement of defective parts such as electric drivers and remove the carbon after repairing including refixing on pole including connecting & testing complete all as directed by Engr-in-Charge. [Note:- Electronic drivers and LED will be measured and paid separately on respective item of Sch 'A' here-in-after]. |
| 28 | Supply and fix in repairs flood light luminaire with polycarbonate optics pressure die cast housing IP 66 ingress protection, 4 KV in-built and 10 KV external SPD, having efficiency not less than or equal to 150 lm/watt, CCT 5700oK in buildings etc the fitting shall be of LED type 150 Watts complete all as specified. Make : Bajaj/ Jaguar/ Wipro/ Benlo/ Havells/ Crompton |
| 29 | S&F in repair of building Security light fitting made up of pressure die cast alluminium body with mid power 60 Watt LED luminaire, with IP 66 protection, 4 KV in-built and 10 KV external large protection having luminuous efficiencies not less than 110 lm/watt CCT 5700K as lighting sources and PC cover having Top opening seperate driver compartment with IP66 protection Including fixing arrangements and taking down old rusted bracket fittings complete all as per directed by Engr- in – charge. Make : Bajaj/ Wipro / Havells /Jaguar /Benlo |
| 30 | Dismantling complete old Bolard light fitting and Supply & Fix 8/9 watts LED Bollard Garden light fittings with efficient high output LED, Pressure die cast powder coated housing with PC diffuser , driver nuts, bolt, washers, base plate, foundation 0.3 Meter x 0.3 Meter x 0.3 Meter by PCC 1:2:4 type B-1 using 20 mm graded stone aggregates of size including excavation and earthwork, provision of GI bend of size 50 mm dia in the PCC for cable entry complete. Make:- Havells / Bajaj/ Crompton/ Jaguar/ Benlo/ Wipro Please Enable Macros to View BoQ information |
| 31 | Dismantling complete old Bolard light fitting and Supply & Fix 8/9 watts LED Bollard Garden light fittings with efficient high output LED, Pressure die cast powder coated housing with PC diffuser , driver nuts, bolt, washers, base plate, foundation 0.3 Meter x 0.3 Meter x 0.3 Meter by PCC 1:2:4 type B-1 using 20 mm graded stone aggregates of size including excavation and earthwork, provision of GI bend of size 50 mm dia in the PCC for cable entry complete. Make:- Havells / Bajaj/ Crompton/ Jaguar/ Benlo/ Wipro Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 27, 2026
11:30 IST
Tender Published
Tender notice published.
TodaySep 17, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 21 daysSep 19, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 23 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender