Home Affairs Statutory Bodies & Commissions/Committees Closing in 3 days TDR #57222264

Tender For Construction Of Type- Ii/56 Nos (S+7) Separated Family Accommodation (Sfa) Residential Quarters In Delhi Ncr I.E. In The C Us Of 39Th Bn Itbp, Greater Noida (Up).

Issued by Statutory Bodies & Commissions/Committees · Ghaziabad, Uttar Pradesh
Tender Value
19.73 Crore
Estimated cost
Bid Submission
17 Sep 2026
3 days left
EMD
29.73 Lakhs
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Ghaziabad → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Construction Of Type- Ii/56 Nos (S+7) Separated Family Accommodation (Sfa) Residential Quarters In Delhi Ncr I.E. In The C Us Of 39Th Bn Itbp, Greater Noida (Up).

BOQ

Name of Work:- Construction of Type- II/56 Nos (S+7) Separated Family Accommodation (SFA) Residential Quarters in Delhi NCR i.e. in the c us of 39th Bn ITBP, Greater Noida (UP).
Sl. No. Item Description
1Earth work in excavation by mechanical means(Hydraulic excavator)/manual means over areas (exceeding 30cm in depth. 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50 m and lift upto 1.5 m ; disposed earth to be levelled and neatly dressed. All kinds of soil
2Extra for every additional lift of 1.5 m or part thereof in: excavation/banking excavated or stacked materials.(a) All Kinds of Soil
3Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth: consolidating each deposited layer by ramming and watering, lead upto 50 m and lift upto 1.5 m.
4Supplying and filling in plinth with Jamuna sand under floors, including watering, ramming, consolidating and dressing complete.
5Treatment of soil under existing floors using insecticide emulsion/solution @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor:
61:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)
7Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor,etc., up to floor five level, excluding the cost of centering, shuttering and finishing: 1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size)
8Providing and laying damp-proof course 50 mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources).
9Providing & applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7 kg per square metre on damp proof course after cleaning the surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil.
10Making plinth protection 50 mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75 mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth.
11Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing,finishing carriage for all leads; but excluding the cost of centering, shuttering and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete. Concrete of M30 grade with minimum cement content of 350 kg /cum. All works up to plinth level
12Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing,finishing carriage for all leads; but excluding the cost of centering, shuttering and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete. All works above plinth level upto floor V level. Concrete of M25 grade with minimum cement content of 330 kg /cum
13Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns,raft etc. for mass concrete.
14Centering and shuttering including strutting, propping etc. and removal of form for : Suspended floors, roofs, landings, balconies and access platform.
15Centering and shuttering including strutting, propping etc. and removal of form for : Lintels, beams, plinth beams, girders, bressumers and cantilevers.
16Centering and shuttering including strutting, propping etc. and removal of form for : Columns, Pillars, Piers, Abutments, Posts and Struts.
17Centering and shuttering including strutting, propping etc. and removal of form for : Chajja
18Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.Thermo-Mechanically Treated bars Upto plinth level.
19Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.Thermo-Mechanically Treated bars Above plinth level. Thermo-Mechanically Treated bars
20Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand)
21Brick work with non modular fly ash bricks conforming to IS:12894, class designation 10 average compressive strength in super structure above plinth level up to floor V level in : Above plinth level up to floor V level
22Half brick masonry with non modular fly ash bricks of class designation 10, conforming to IS : 12894, in super structure Cement mortar 1 : 4 (1 cement : 4 coarse sand) Above plinth level up to floor V level
2312 mm cement plaster of mix : 1:6 ( 1 cement : 6 coarse sand )
2415mm cement plaster on rough side of single or half brick wall of mix 1:6 (1 cement : 6 coarse sand )
256 mm cement plaster 1:3 ( 1 cement : 3 fine sand)
26Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. Double charge vitrified tile polished finish of size Size of Tile 600 x 600 mm
27Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. Double charge vitrified tile polished finish Size of Tile 600 x 600 mm
28Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily.Double charge vitrified tile polished finish Size of Tile 600 x 1200 mm
29Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. Glazed Vitrified tiles Matt/Antiskid finish of size Size of Tile 600 x 600 mm
30Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. (size of tile 600 x 600 mm)
31Providing and laying Vitrified tiles in different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS: 15622, of approved brand & manufacturer, in all colours and shade, in skirting, riser of steps, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS: 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately). Size of Tile 600x600 mm
32Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing of edges to give high gloss finish etc. complete at all levels. Granite stone slab of colour black, Cherry/Ruby red Area of slab over 0.50 sqm
33Extra for providing opening of required size & shape for wash basin/ kitchen sink in kitchen platform, vanity counter and similar location in marble/ Granite/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.
34Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in Charge. Granite work
35Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. Polished Granite stone slab of all colour and texture exceptBlack, Cherry/Ruby Red
36Providing and fixing wire gauge shutters using galvanized M.S. wire gauge of average width of aperture 1.4 mm in both directions with wire of dia 0.63 mm, for doors, windows and clerestory windows with hinges and necessary screws 35 mm thick shutters With ISI marked M.S.pressed butt hinges of required size Kiln seasoned and chemically treated hollock wood
37SS ball bearing of size 100 x89x3 mm
38Providing and fixing chromium plated brass 100 mm mortice latch and lock with 6 levers and a pair of lever handles of approved quality with necessary screws etc. complete.
39Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 250x10 mm
40Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete. Twin rubber stopper
41Providing and fixing 18 mm thick both sides Pre-laminated cement bonded wood particle board as per IS : 15786:2008 of approved brand and shade with suitable full threaded steel screws etc. in partitions, boxes, shelves, racks and cupboard, kitchen cabinet under kitchen counter etc. all complete as per direction of Engineer-in-charge (Note: Fittings to be paid separately). 18 mm thick
42Providing and fixing 6 mm thick both sides Pre-laminated cement bonded wood particle board as per IS : 15786:2008 of approved brand and shade with suitable full threaded steel screws etc. on the backing of racks, drawer, cupboard, kitchen cabinet under kitchen counter etc. all complete as per direction of Engineer-in-charge.
43Providing and fixing stainless steel fancy handle of approved make fixed with SS screws etc. complete as per direction of Engineer-in-charge. 200 mm
44Providing and fixing stainless steel soft closing spring hinges at 0 degree hinges (hydraulic type) of approved make/brand to cupboard shutters with full threaded steel screws including making necessary recess in board and finished etc. complete as per direction of Engineer-in-charge.
45Providing and fixing 2 mm thick 16 to 19 mm wide PVC edge binding tape of approved quality for cupboard/wardrobe shutters including necessary synthetic resin hot pressed to edges on binding machine etc. complete as per direction of Engineer- in-charge.
46Providing and fixing Pre-laminated flat pressed 3 layer (medium density) particle board or graded wood particle board IS : 3087 marked, with one side decorative and other side balancing lamination Grade I, Type II exterior grade IS : 12823 marked, in shelves with screws and fittings wherever required, edges to be painted with polyurethane primer (fittings to be paid separately). 18 mm thick
47Providing and fixing flat pressed three layer particle or graded plain wood board medium density exterior grade (Grade I) FPT-I, conforming and marked to frame, backing or studding with screws etc. complete (Frames, backing or studding to be paid separately): 18 mm thick
48Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face of shutters: 30 mm thick including ISI marked Stainless Steel butt hinges with necessary screws
49Providing PVC moulding / architrave for door frame made up of extruded solid foam PVC profile having homogenous fine cellular structure with smooth outer integral skin, minimum 30 mm width and minimum 12 mm thick suitable for fixing to frame. The molding shall be snap fitted in the groove provided in the frame & fixed with PVC solvent adhesive / cement and self tapping screws (of required size) complete as per direction of Engineer-in-Charge.
50Providing wooden moulding / architrave for door frame made up of kiln-seasoned hardwood or premium density fibreboard (MDF) profile having a straight, defect-free structure with a smooth surface finish, minimum 30 mm width and minimum 12 mm thick suitable for fixing to frame. The moulding shall be accurately mitred at joints, secret-nailed, or fixed into the frame rebate using premium wood adhesive and countersunk wood screws / lost-head nails (of required size) complete as per direction of Engineer-in-Charge.
51Providing & fixing of (0.1x0.1)m magic eye in front entry door.
52Providing wood work in frames of washroom doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length (hold fast lugs or dash fastener shall be paid for separately). Second class teak wood
53Providing and fixing glazed shutters for doors, windows and clerestory windows using 4 mm thick float glass panes (weight not less than 10 kg per sqm) fixing with ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws. Second class teak wood 30 mm thick
54Providing and fixing 37 mm thick factory made PVC Door shutter, styles and rails made of PVC hollow extruded printed and laminated section having overall dimension 115 mm x 37 mm with wall thickness 2 mm (± 0.2 mm) with inbuilt beading on one side, the styles and rails mitred cut and joint at corners by inserting 2 nos PVC profile reinforcement of size 75 mm x 200 mm long with cross section size of 28 mm x 30 mm having wall thickness 2 mm (± 0.2 mm). Styles, rails and reinforcements to be fusion welded together. Only hinge side vertical style to be reinforced with PVC profile reinforcement in full length. Printed and laminated PVC lock rail of size 110 mm x 37 mm having wall thickness 2 mm (± 0.2 mm) to be welded horizontally with the vertical styles after inserting PVC profile reinforcement as in styles and rails, providing with PVC snap fit beading, panels of 100 x 20 mm printed & laminated and inserting 2 nos 6 mm diabright steel rod horizontally with both side threaded and tightened with check nuts and washers complete, all as per manufacturer’s specification and direction of engineer-in-charge. 25 mm thick
55Providing and fixing 18 mm thick both sides Pre-laminated cement bonded wood particle board as per IS : 15786:2008 of approved brand and shade with suitable full threaded steel screws etc. in partitions, boxes, shelves and wardrobe etc. all complete as per direction of Engineer-in-charge (Note: Fittings to be paid separately).
56Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main “T” runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross “T” of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main “T” at 600 mm center to center to form a grid of 1200x600 mm and secondary cross “T” of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main “T” runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge. GI Metal Ceiling Lay in perforated Tegular edge global white color tiles of size 595x595 mm and 0.5 mm thick with 8 mm drop; made of GI sheet having galvanizing of 100 gms/sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC (Noise Reduction Coefficient ) of 0.5, electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation and backed with a black Glass fiber acoustical fleece.
57Steel work welded in built up sections/ framed work, including cutting,hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets,gates and similar works
58Providing & fixing of M.S. angle (size 50x50x5)mm for washbasin with fastner including necessary welding and applying a priming coat of approved primer on exposed surface etc. complete.
59Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved manufacturer and of required shade and colour all complete to achieve even shade and colour : New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC content less than 50 gram/litre
60Finishing walls with ready mixed Premium acrylic emulsion paint (Company Depot Tinted) having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade with silicon additives. New work (Two or more coats applied @ 1.43 litre/ 10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm.
61Painting with enamel paint of approved brand and manufacture of required colour to give an even shade : New work (two or more coats) including a coat of approved primer
62Providing and fixing factory made uPVC glazed/wire mesh windows/doors comprising of lead free uPVC multi-chambered frame, sash and mullion/coupler (where ever required) extruded profiles having minimum wall thickness of 1.70 mm for Series R1 and R2 profiles and 2.10 mm for Series R3 and R4 profiles conforming to EN: 12608 in any shape, colour and design duly reinforced with galvanized mild steel section made of required shape & size as per CPWD Specification, uPVC extruded glazing beads, interlocks and Inline sash adaptor (where ever required) of appropriate dimension, EPDM gasket, hardware, SS 304 grade fasteners of minimum 8 mm dia with countersunk head, comprising of matching polyamide PA6 grade sleeve for fixing frame to finished wall as per IS 1367 : Part 1 to 14, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame, sash & mullion (if required) shall be mitred cut and fusion welded/mechanically jointed duly sealed at all corners, including drilling of holes for fixing hardware and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of approved size and quality, all complete as per approved drawing conforming to CPWD specification & direction of Engineer-in-Charge. Section of steel reinforcement and cross sections of uPVC profiles to be as per design approved by Engineer-in-Charge. Wire mesh / Glazing of plain/ toughened/ laminated/ double glass unit with / without high performance coatings as per design requirements and conforming to IS: 3548 & IS: 16231 shall be paid separately. Note:- Structural design proof checked from a Government Engineering Institute, to be provided by the manufacturer for : (i) Sites with basic wind speed > 45 m/sec as per IS 875 – Part 3 (ii) Sites with structure height more than 20m for all wind speeds Three track three panels sliding window with Aluminium channel for roller track, wool pile, nylon rollers with SS 304 body. Using R3 series with frame (98 mm & above) x (40 mm & above) & sash (30 mm & above) x (55 mm & above) with zinc alloy (zamak) powder coated handle on two end panels along with multi-point locking system (Height upto 1.8 metre).
63Providing and fixing of aluminium curtain track ( with screw, runners, end caps etc ) in bedroom1' s slider and window, bedroom2 's slider and window, living and dining' windows of all flates.
64Supply of dust, damp and vermin proof cubicle free floor, indoor type factory built sheet steel enclosed modular bolted construction extendable Panel, suitable for operation on 415 ±10% volts, 50 Hz AC 3 phase 4 wire supply system fabricated out of Form 3b compartmentalized design and covered with CRCA sheet steel of 2mm thick for frame work and 1.6mm thick for doors/ covers, 3mm thick for gland plates i/c cleaning & finishing complete with 9 tank process for powder coating in approved shade, having extensible type TPN Aluminium bus bars of high conductivity, SMC bus bar supports, with short circuit with stand capacity of 35KA for 1 sec., bottom base channel of section not less than ISMC 75mm, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bus bar to switch gears with required size of Alum. bus bars and inter-connection with solid copper conductor wires/ aluminium strips, neutral links, including control wiring with 1.5sqmm. PVC insulated FRLS copper conductor Single Core cable for voltage & 2.5sq.mm for current circuits, cable alleys, cable gland plates in two half, danger notice plates, etc. necessary metering protections & indications and mounted with the following switch gears as per drawing and technical specifications etc. complete as required.
65Incomer
66250 Amps 4 Pole, 25 KA, MCCB with MP based releases.with 3 Nos. R,Y,B Indication Lamps with 2A back up SP MCB with ON indication.MCCB shall be provided with spreader link and direct rotary handle. 3 Nos. Phase indication LED lamps with 2 Amps back up MCB, breaker 'ON' 3 phase 4 wire Multifunction meter of class 0.5S accuracy with communication interface port RS 485 for recording V ( Between Phases and between each phase and neutral ), A ( In each Phase and neutral), KVA, KW, KWhr, KVAR, pf, 64 samples/cycle, Total harmonic distortion, with suitable rating CTs etc. complete with wiring , connections etc. 2 / Class C SPD- surge protection device.
67Busbar:
68TPN aluminium bus bars of minimum of 320 A 25 kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
69Outgoings
70Supplying and fixing following outgoing MCCB/MCB including connection, inter-connection etc. with suitable size of wires complete as required.(Each MCB/MCCB to be provided with ON OFF and RYB indiation with 2A backup SP MCB)125 Amp 4P MCCB '25 KA' - 3Nos.( 2 for meterboards) + 1 No. spare 63 Amp 4P MCCB '25 KA' - 3 Nos ( Lift panel , plumbing panel) + 1 No. spare
71panel described as above
72Design, fabrication, supplying, assembling, erecting, testing and commissioning of wall mounted /floor mounted cubical type compartmentalised dust, damp & vermin proof Metering Panel fabricated out of suitable sized angle iron and flats and covered with 2mm thick cold rolled CRCA sheet painting etc. complete with Al. bus bars, interconnection with solid/stranded copper conductor wires copper strips neutral links, etc. and mounted with 1 No 0-500V, Voltmeter, selector switch, 1 set (3 Nos) of phase indicating lamps, ammeter with CTs etc. as required. The Panel shall have IP-42 rating .The Panel will also include fabrication of energy meter box with SITC of single or three phase postpaid type electronic energy Meter as per Incoming/outgoing requirement or as per SLD with all necessary power wiring for dual metering with MS support for meter fixing , windows for meter reading including supply and fixing of MCB\\"s, main frame fabricated out of 2mm in cubical formation. 1 No. - 125 Amp. 16ka 4 pole Thermal release, MCCB (Ics=lcu) with O/L, S/C & modular earth fault protection. 3 Set of three phase R,Y,B indicating lamps along with 2A SP MCB backup protection. 2 / Class C SPD- surge protection device
73Bus Bars
74TPN aluminium bus bars of minimum of 160 A 16 kA capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
75Outgoing:-
76(Following MCB (Ics=Icu upto 433 V) thermal magnetic release with over current and short circuit releases, all indication, ) :- 14 Nos. 40A 4P MCB 'C' 10 kA breaking capacity. 4 Nos. 40A 4P MCB 'C' 10 kA breaking capacity.
77Panel Described as above.
78LIFT PANEL
79Incomer
801 No. - 63 Amps Four Pole , 16 KA (ICU=ICS), MCCB with thermal based release with o/c, s/c protection inbuilt E/F protection release all indication, front operating hand & door interlock with shunt trip relay
81Busbar:
82TPN aluminium bus bars of minimum of 80 A capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc.
83Outgoings
84Supplying and fixing following outgoing MCCB/MCB including connection, inter-connection etc. with suitable size of wires complete as required.(Each MCB/MCCB to be provided with ON indication with 2A backup SP MCB)
8540A Amp 4P MCCB '25 KA' - 4 Nos. 40 A Amp DP MCB '10 KA' - 2 Nos. 25A Amp DP RCCB '10 KA' - 2 Nos.
86Lift Panel as above
87Supplying, Installation, testing and commissioning of following sizes of 0.5 mm dia annealed tinned copper conductor PVC insulated and PVC sheathed unarmoured telephone cable on surface/ existing cable tray complete as required. 40 Pair
88Supplying and drawing co-axial TV cable following grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.RG-11
89Supplying, erection, testing and commissioning of following tap off / splitter as per specification in 1.6 mm thick CRCA sheet steel enclosure for CATV system. 4 Way splitter box
90Supplying of LED bracket light for wall with lumens110 per watt system power 12W the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P.F.≥0.95, IP20, CRI >80 System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).
91Supply of Heavy duty bulkhead reccess or surface type lighting fixture (ramp light) 10W made up of pressure die-cast aluminium housing and Polyster Powder coated die cast aluminium with High quality polycarbonate diffuser in opal finish for glare free light distribution.High efficiency long life LED module with SMD LED package mounted on MCPCB with lumen efficacy of >95 lm/W with system lumen 950. Powered by integral electronic LED driver with APFC with low THD Output short/open circuit Protection. CCT 5700, CRI>80, System Efficacy>90Lm/W, THD<15%, PF>.95, IP66,IK 10, Life class of 50,000 hrs @ L70, Operating Temperature:-10 TO +45 DEG.C; Input Supply Voltage Range:140-270 V, Frequency :50-60 HZ. DRIVER SAFETY REQUIREMENT STANDARDS :IS 15885-2-13, TEST REPORT TO BE SUBMITTED; DRIVER PERFORMANCE REQUIREMENTS: IS 16104, TEST REPORT TO BE SUBMITTED; PHOTO BIOLOGICAL SAFETY NORMS: IS 16108, TEST CERTIFICATE TO BE SUBMITTED; CERTIFICATION: LM 79 FOR LUMINAIRE LM 80 FOR LED SOURCE. As per approved makes
92Supply of 2ft mirror surface type lighting fixture 10W .High efficiency long life LED module with with lumen efficacy of >95 lm/W with system lumen 950. Powered by integral electronic LED driver with APFC with low THD Output short/open circuit Protection. CCT 5700, CRI>80, System Efficacy>90Lm/W, THD<15%, PF>.95, IP66,IK 10, Life class of 50,000 hrs @ L70, Operating Temperature:-10 TO +45 DEG.C; Input Supply Voltage Range:140-270 V, Frequency :50-60 HZ
93Supply of door decorative surface type lighting fixture .High efficiency long life LED module with with lumen efficacy of >95 lm/W. Powered by integral electronic LED driver with APFC with low THD Output short/open circuit Protection. ; Input Supply Voltage Range:140-270 V, Frequency :50-60 HZ
94Supply of Exhaust fan complete with louver and with 3 core flexible wire as required upto socket/ ceiling boxes as required, complete with cutting of wall, grouting of fan and making good of the wall.300 mm SWEEP EXHAUST FAN (1400 RPM)
95Supply of Metal Exhaust fan complete for kitchen and with 3 core flexible wire as required upto socket/ ceiling boxes as required, complete with cutting of wall, grouting of fan and making good of the wall.300 mm EXHAUST FAN
96SITC of 25 Litre Electric Storage Water Heater (Geyser): Supply, installation, testing and commissioning of 25 litre capacity storage type electric water heater complete with high grade enamel/glass lined steel tank, PUF insulation, copper/Incoloy heating element, 230V AC single phase 50Hz supply, 2–3 kW rating, adjustable thermostat with thermal cut-out, safety valve, pressure relief valve, non-return valve, drain valve, wall mounting brackets, inlet/outlet connections, necessary plumbing and electrical accessories, wiring, earthing, supports and all accessories required for complete operation. Make: Havells/Racold/AO Smith or equivalent approved make
97Supply of following size of 1.1 kv grade FRLS multicore aluminium / copper conductor XLPE insulated and PVC sheathed armoured cable as per IS: 7098:1988 (Part-I) with upto date amendments. 3-½ x 50 Sq.mm.
98Supply of following size of 1.1 kv grade FRLS multicore aluminium / copper conductor XLPE insulated and PVC sheathed armoured cable as per IS: 7098:1988 (Part-I) with upto date amendments. 4 x 25 Sq.mm.
99Supply of following size of 1.1 kv grade FRLS multicore aluminium / copper conductor XLPE insulated and PVC sheathed armoured cable as per IS: 7098:1988 (Part-I) with upto date amendments. 4 x 10 Sq.mm. copper
100Supply, installation, testing & commisioning of cable termination of above cables with copper lugs & flameproof brass compression glands on both the ends with inhibting compound etc. complete as required. 4 X 10 sq. mm (25mm)
101Providing and fixing \\"EXIT\\" Light with battery backup, suspended from ceiling or fixed to the walls with accessories as required and as directed at site etc. complete as required.
102Supply, Installation, Testing & Commissioning of 8 Passenger lift, electric traction SS door lift, machine room less having contract speed of 1.5 Meter per second serving different floors in the lift shaft of size as per drawing, 1700 mm pit depth and 4800 mm overhead as per detailed specifications attached and as under complete with all the equipment and accessories.
103Location of lift: ITBP Tower Stilt + First + 6 Floors = 8 Floors, Travel Height - 24Mtrs, No. Of Openings - 8 Stop & 8 Opening (all opening be on same side), Drive System & Control - Micro Processor based VVVF or Alternating Current Voltage Frequency (ACVF) with Closed Loop system with Gealess Motor, Automatic Rescue Device (ARD) compete with dry maintenance free batteries as required. Operation - Microprocessor based Duplex collective selective - (with/without -attendant)
104Passenger lift as described as above
105Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/FHHR PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS/FHHR PVC insulated copper conductor single core cable etc. as required. Group C
106Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS/FHHR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS/FHHR PVC insulated copper conductor single core cable etc. as required. Group C
107Wiring for light/ power plug with 2X4 sq. mm FRLS/FHHR PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No 4 sq. mm FRLS/FHHR PVC insulated copper conductor single core cable for loop earthing as required.
108Wiring for light/ power plug with 4X4 sq. mm FRLS/FHHR PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 2 Nos. 4 sq. mm FRLS/FHHR PVC insulated copper conductor single core cable for loop earthing as required.
109Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS/FHHR PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
110Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS/FHHR PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
111Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS/FHHR PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required 2 X 6 sq. mm + 1 X 6 sq. mm earth wire
112Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS/FHHR PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required 4 X 10 sq. mm + 2 X 10 sq. mm earth wire
113Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required
114Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required.
115Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
116Supplying & fixing of 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
117Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 Nos. 3 pin 5/6 amps modular socket outlet and 1 No. 6 amps modular switch, connection etc. as required.
118Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \\"C\\" curve DP MCB complete with connections, testing andcommissioning etc. as required.
119Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. (For ckt/submain wiring extra): 20 mm
120Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. (For ckt/submain wiring extra): 25 mm
121Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. (For ckt/submain wiring extra): 32 mm
122Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. (For ckt/submain wiring extra): 40 mm
123Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. Telephone socket outlet
124Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. TV antenna socket outlet
125Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 1 or 2 Module (75mm X 75mm)
126Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 4 Module (125mmX75mm)
127Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. 2 Pair
128Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required
129Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required
130Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. (For tel./ TV / Data wiring) 25 mm
131Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. (For tel./ TV / Data wiring) 32 mm
132Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 2 + 8 way, Double door
133Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 2 + 12 way, Double door
134Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way (4 + 24), Double door
135Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
136Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
137Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
138Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
139Location of lift: ITBP Tower Stilt + First + 6 Floors = 8 Floors, Travel Height - 24Mtrs, No. Of Openings - 8 Stop & 8 Opening (all opening be on same side), Drive System & Control - Micro Processor based VVVF or Alternating Current Voltage Frequency (ACVF) with Closed Loop system with Gealess Motor, Automatic Rescue Device (ARD) compete with dry maintenance free batteries as required. Operation - Microprocessor based Duplex collective selective - (with/without -attendant)
14018 watt
141Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 withdriver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P.F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till lifeends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)
14236 watt
143Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required
144Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor without remote , class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies,shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperaturerise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum)
145Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required
146Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.
147Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep
148Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes.
149Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required.
150Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required.
151Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run)
152Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run)
153Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc.complete as required.
154Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required.
155Online UPS - Input supply: Single Phase, Output Supply: Single Phase.Supplying, installation, Testing & Commissioning of following capacity at full load (Unity Power Factor) ON LINE Uninterrupted Power Supply (UPS) system suitable for Single Phase input, Single Phase output AC Supply. The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. The UPS systems shall be Microprocessor based Digital Control, using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter with PWM (Pulse Width Modulation) Technology. The quality of design, manufacturing and inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >95% at 100% non-linear loads. Current total harmonic distortion(ITHD)/ total demand distortion (TDD) on the input grid shall be < 5% at 100 %load. (The required LC filters shall be included in UPS cost), extreme power factor kit to be include to limit the input pf to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ) however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC single phase 160-270V 50 Hz and delivering output AC supply true sine wave single phase 220/230/240 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins and 150% for 1minute. Operating temperature 0 to 40 0C, Relative humidity 0-95% non condensing, noise level less than 60db at 1 meter distance, Protection for Under voltage, over voltage, abnormal output voltage, battery over charging, output over current, short circuit, battery deep discharge , 10 KV surge.Display for watt/VA,Amp and Voltage power parameters etc. UPS shall comply with low voltage electromagnetic compatibility (EMC) achieved asper EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI) type UPS (as per standard IEC 62040-1, 2 & 3) . The UPSshould be with IGBT Based Inverter Technology, Communication RS232/ RS485/ SNMP port open protocol for BMS integration as per approved byEngineering in charge. Required battery racks, DC breaker of suitable rating and interconnecting copper conductor cable of suitable size andconnectors and all required accessories are inclusive in the cost. The UPS should have QR code which should contain drawing, test report OEMmanual, Geo- Tag of manufacturing location etc
156Laying and fixing of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of following size on cable tray as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
157Above 35 sq. mm and upto 95 sq.mm (clamped with 25x3mm MS flat clamp)
158Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 50 sq. mm (35mm)
159Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 25 sq. mm (32mm)
160Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required 150 mm. Width x 50mm. Depth x 1.6mm. Thickness.
161Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required 150 mm. Width x 50mm. Depth x 1.6mm. Thickness.
162Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Tee\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required 150 mm. Width x 50mm. Depth x 1.6mm. Thickness.
163Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. (panels)
164Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. (lifts)
165Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
166Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
167Providing and fixing 25 mm X 5 mm copper strip onsurface or in recess for connections etc. as required.
168Providing and fixing 25 mm X 5 mm G.I. strip onsurface or in recess for connections etc. as required.
169Supplying Installation Testing and Commissioning of 2MP Fixed Lens IP IR Outdoor Bullet Camera having following specifications and features etc :-1) Signal System: PAL/NTSC, Signal to Noise Ratio: > 50 dB,Camera should display Camera title, Date & Time in live & recorded video 2)Image Sensor: 1/2.8\\" or better progressive Scan CMOS to get color image even at night condition(Minimum Illumination: 0.006 Lux@ F1.4, AGC ON, 0 lux with IR or better) True Day & Night High Performance Mechanical IR cut filter with auto switch, Integrated IR Source (Auto, Manual)- Inbuilt Smart IR LED's with effective distance upto 50 meter or better and 30 meter for colour view in night, Imaging: 1/3s to 1/30000s electronic shutter support, Auto Gain Control , White Balance- Auto, Back Light Compensation, Multi zone Privacy Masking, HLC, Digital Watermarking.3) Compression (Minimum):-Video:- H.265 or better, H.264H, H.264, Audio:- G.711U/A, G.711Mu, G.726,AAC, G.723 4) Wide Dynamic Range:- WDR (120db or more)5) Digital Noise Reduction:- DNR (3D) On/Off6) Video Streaming & Frame Rates :- Triple streaming, configurable(Main stream: 2MP (1920 × 1080)@25/30 fps Sub streams minimum: 720P@25/30 fps).7) Image Setting: Rotate Mode, saturation, brightness,contrast, sharpness adjustable through client software or web browser, Edge Analytics: Tripwire, Intrusion, Motion Detection8) Cyber Security: AES 256-bit Encryption, Configuration encryption, trusted execution, Digest,security logs, account lockout, syslog, videoencryption, IP/MAC filtering, HTTPS, trusted upgrade, trusted boot.9) Onboard Storage: Camera should support built-in Micro SD/SDHC/SDXC Card slot upto 512 GB. It should be supplied with minimum 128GB memoryCard. 10) Recording Management: Format SD, overwrite, storage management, video to NAS device
17011) Alarm Trigger : Motion/tampering detection; audio detection; network disconnection detection; IP conflict detection; memory card state detection; memory space detection12) Network Protocol: SFTP, IPv6, IPv4, DNS,RTCP, NTP, RTP, HTTP, HTTPS, SNMP TCP/IP, PPPoE, NFS, UDP, ICMP, SSL, DHCP, SMTP, RTSPS, unicast,13) System Capability: ONVIF, Camera shall support open source VMS 14) Ethernet: 1 RJ 45 10/100 Ethernet port15) Audio : It should support 1 x Built-In Mic and 1/1 Alarm In/ Out for External Mic. and Speakers as per site requirement.16) Power Input: The camera should support simultaneous dual power input—12 VDC (via power adapter) and PoE (802.3af)—to ensure continuous operation in the event of a failure in one power source.17) Power Requirement: 12VDC/24 VAC/PoE(802.3af)/ePoE18) Housing/ Enclosure:- IP67 weather proof, IK10,Metallic body19) Operating Condition:- Ambient Temperature:- (-)05°C to 50°C, humidity 95% (max) (non-condensing)20) IR life: 40000 hours or higher21) Video Bit rate: 32 KBPS - 8 MBPS or better22) Standards: BIS with ER, STQC Certified, CE, FCCand RoHS
1712MP @ 25/30fps@1080P (1920×1080) Outdoor Bullet Camera with 2.8/ 3.6mm fixed lens
17216 Channel Network Video Recorder (NVR) having display split :- Main screen: 1/4/8/9/16, 2nd screen: 1/4/8/9/16
173Supplying, Installation, Testing and Commissioning following capacity Serveillance grade Hard Disk with upto 256MB/s Transfer Rate, 256 MB Cache, 7200 RPM Disk Speed, 3.5 inch form factor, SATA Interface, BSMI, ICES-003/NNB-003, CE, FCC, KC, Maghreb, RCM, UKCA, VCCI, CB-Scheme, TUV, UL Certifications. 4TB (Terabytes)
174Supplying, drawing, Testing and commissioning of Cat6A UTP 4 pair, 23 AWG solid copper cable in existing conduit/ on surface, U/FTP, LSZH, Non-Plenum, Horizontal (solid) Cable suitable for high speed data networking application supporting upto 10Gbps over a 100 meter channel. The 4 Unshielded Twisted Pairs (UTP) cable with color coded insulationfor easy indentification should have FLAME PROPERTIES i.e. Flammability Test - IEC 60332-1, Smoke Density - IEC 61034, LSZH standardscompliance: ANSI/TIA-568 C.2, ISO/IEC 11801, IEEE 802.3an, RoHS. Delay Skew should be < 45NS. The outer Cable Diameter should be 7.5 + 2 mm. Cable should have been tested and verified by UL/ ETL etc. complete as required. 1 Run of cable
175Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 150 mm dia ID
176Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 300 mm dia ID
177Supplying, installation, testing & commissioning of manual call boxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required.
178Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required.
179Supplying, installation, testing & commissioning sector panel suitable for following zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities as per IS:2189 with mimic diagramfor all area/zone covered, complete with all connections, interconnections as required. 4 Zone
180Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS/HFFR outer sheath complete as required.
181Providing and fixing white vitreous china extended wall mounting water closet of size 780x370x690 mm of approved shape including providing & fixing white vitreous cistern with dual flush fitting, of flushing capacity 3 litre/6 litre (adjustable to 4 litre/8 litres), including seat cover, and cistern fittings, nuts, bolts and gasket etc Complete
182Providing and fixing G.I. inlet connection for flush pipe connecting with W.C. pan.
183Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:-(a) White Vitreous Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer
184Providing and fixing CP Brass 32 mm size Bottle Trap of approved quality & make and as per the direction of Engineer-in-charge.
18517.31 Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.
186Providing and fixing 600x120x5 mm glass shelf with edges round off, supported on anodised aluminium angle frame with C.P. brass brackets and guard rail complete fixed with 40 mm long screws, rawl plugs etc., complete.
187Providing and fixing toilet paper holder : C.P. brass
188Providing and fixing towel ring complete with brackets fixed with CP brass screws PVC sleeves etc. Complete. 450 mm long .Model No- ACN-1111 BNM ,
189Providing and fixing Health Faucet with 8mm Dia, 1.00 M long Flexible Tube & Wall hook arrangement Model No- ALD-573 ,
190Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931. 15 mm nominal bore
191Providing and fixing Braided hose with Two 15mm Nuts & Rubber washers without Nipple : Model No. ALD-805B 45 cm length
192Providing and Fixing Stainless Steel A ISI 304 Kitchen sink as Per IS 13983 with C.I brackets and stainless steel plug 40 mm including painting of fitting and brackets,cutting and making good the walls wherever required. Kitchen sink with drain board 510X1040 mm bowl depth 250mm
193Providing and fixing C.P. Brass kitchen sink mixer with swinging spout on upper side (wall mounted) with connecting legs and flangs as per model no. OPL-15165
194Providing, Fixing, Storage, Installing, testing and commissioning Shower in polished chrome with wall flange and shower arm, including Three Way Mixer Diverter: -Polished Chrome Finish single lever concealed mixer & diverter good the walls & floors slab wherever required
195Providing and fixing CP brass twin coat hooks fixed on toilet door/wall with CP brass screws, complete in all respect
196Providing, fixing, testing and commissioning of UPVC SWR pipe type 'B' conforms to IS : 13592-1992 with all fittings such as bends, tees, elbow, 'Y', offset, cleaning pipe door, clamps etc. conforming to IS:14735-1999 and steel structural supports etc. including cutting the floors, walls and making good the same in cement concrete 1:2:4 & cement mortar 1:4. The wall thickness of pipe and technical characteristic conforms to IS : 13592-1992 type 'B'. The fitting dimension conforming to IS : 14735-1999. The jointing to be completed with rubber ring joint/solvent weld joint as required (Toilet and Shaft). 110 OD
197Providing Fixing in position uPVC SWR floor trap conforming to IS:13592 including providing necessary steel support and as per Specification. Making proper connection cutting chase / hole in floors / slabs and bringing the same in proper condition and shape after placing the trap in right position complete as required. The hopper and trap shall be set in cement concrete mix 1:2:4 complete as required. 110 mm inlet and 110 mm outlet.
198Providing Fixing EXTENSION PIECE for 100 mm dia floor trap formed out of main pipe(Type A) with multiple side inlets, suitable for various dia pipes, side connections, including all fixtures and fittings as per site conditions and as per standard 100 mm diameter pipe
199Providing and fixing floor drain made out of 110x63 mm OD uPVC elbow connected to uPVC Pipe complete as per direction of Engineer-Incharge.
200Providing & fixing cockcroch trap S.S. grating of approved design for floor traps etc. including setting in floor with cement mortar. 100 mm dia
201Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete.40 mm dia Semi rigid pipe
202Providing and fixing P.V.C. waste pipe for floor drain including P.V.C. waste fittings complete.63 mm dia Semi rigid pipe
203Providing and. fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS: 13592 Type A, including jointing with seal ring conforming to IS: 5382, leaving 10 mm gap for thermal expansion, (i) Singk socketed pipes. 110 mm diameter
204.Providing and fixing Polyethelene-Aluminium- Polyethelene (PEALPE) Composite Pressure Pipes conforming to IS - 15450, U.V. stabilized with carbon black having thermal stability for hot & cold water supply, capable to withstand temperature up to 80°C, including all special fittings of composite material (engineering plastic blend and brass inserts wherever required) e.g. elbows, tees, reducers, couplers & connectors etc., with clamps at 1.00 metre spacing. This includes the costs of cutting chases and including testing of joints complete as per direction of the engineer in charge. CONCEALED WORK, including cutting chases and making good the wall etc 1216 (16 mm OD) pipe
205Providing and fixing, testing and commissioning of GI pipes Class-C and fittings conforming to IS:1239 (heavy class) complete with GI fittings (union and clamps including cutting holes in wall, makes chases in wall and making good the same in cement mortar 1 : 2 (1 cement : 2 coarse sand) as directed by Project Manager, complete in all respects for internal works) including pipe supports with galvanised MS slotted angle iron, clamps, spacers as required and making good where required. Internal work - Exposed on wall
20615 mm dia nominal bore
20720 mm dia nominal bore
20825 mm dia nominal bore
20932 mm dia nominal bore
21040 mm dia nominal bore
21150 mm dia nominal bore
21265 mm dia nominal bore
21380 mm dia nominal bore
214100 mm dia nominal bore
215Painting of exposed pipes with two or more coats of synthetic enamel paint of approved quality over a coat of red oxide zinc cromate primer including painting of legends in English with direction arrows.
21615 mm dia nominal bore
21720 mm dia nominal bore
21825 mm dia nominal bore
21932 mm dia nominal bore
22040 mm dia nominal bore
22150 mm dia nominal bore
22265 mm dia nominal bore
22380 mm dia nominal bore
224100 mm dia nominal bore
225Providing and Fixing, testing & commissioning of C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931. 15 mm nominal bore
226Providing and fixing C.P. Brass extension nipple (size 15 mm x 50 mm) of approved make and quality as per direction of Engineer-in-charge.
227Providing and fixing ball valve (brass) of approved quality, High or low pressure with plastic floats complete20 mm nominal bore
228The top slab shall be 150mm thick with RCC (1:2:4) including nominal reinforcement and 2 nos. heavy duty 560 dia SFRC manhole covers with frames as per IS:12592 (weight not less than 182 kg) shall be provided in the top slab. PVC encased 12mm dia 50 mm dia.
229The top slab shall be 150mm thick with RCC (1:2:4) including nominal reinforcement and 2 nos. heavy duty 560 dia SFRC manhole covers with frames as per IS:12592 (weight not less than 182 kg) shall be provided in the top slab. PVC encased 12mm dia 100 mm dia.
230Providing and fixing motorised butterfly valve with float type sensors suitable for 240 volts with working pressure rating of not less than 5 kg/cm2 with control panel and sensors to open valve when water level is low in tanks and to close when water level is high in water tanks including necessary cables, conduits, upto junction box etc., complete. 50 mm dia.
231Supply Installation testing and commissioning of Vertical/horizontal monoblock centrifugal transfer pumping set with SS-316 body and SS-316 impeller, SS-316 shaft mechanical seal, connected to a TEFC induction motor suitable for 415 volts ± 3% phase 50 cycles AC supply with a common suction header with valves on main connecting & pumps inlet and a common delivery header with valves, includingt water shock absorber, non return valves with MS galvanized supports and painting with one coat of primer and two coats of synthetic enamel paint including a 100mm dia pressure gauge, Vibration eliminating pads under foundation, all mounted on a common base plate of MS 80x40mm I section bolted to RCC foundation, including control panel complete in all respects. water transfer pumps for OHT filling No. of Pumps : 2( 1 Working + 1 Stand by) Capacity : app. 180 LPM each Head : 50 M approx as per current loaction in Ground Level Pump Room (complete set as mentioned above)
232Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5m including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50m Pipes, cables etc. exceeding 80mm dia. But not exceeding 300mm dia.
233Providing and laying non-pressure NP3 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete. 150 mm dia R.C.C/S.W. pipe
234Providing and laying non-pressure NP3 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete. 300 mm dia R.C.C/S.W. pipe
235Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 20 mm nominal size) up to haunches of S.W./RCC pipes including bed concrete as per standard design : 200 mm dia R.C.C/S.W. pipe
236Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 20 mm nominal size) up to haunches of S.W./RCC pipes including bed concrete as per standard design : 300 mm dia R.C.C/S.W. pipe
237Providing, laying and jointing glazed stoneware pipes class SP-1 with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete: 150 mm dia S.W. pipe
238Providing, laying and jointing glazed stoneware pipes class SP-1 with stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand) including testing of joints etc. complete: 200 mm dia S.W. pipe
239Providing and laying cement concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 20 mm nominal size) alround S.W./RCC pipes including bed concrete as per standard design: 150 mm diameter
240Providing and laying cement concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 20 mm nominal size) alround S.W./RCC pipes including bed concrete as per standard design: 200 mm diameter
241Providing and laying cement concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 20 mm nominal size) alround S.W./RCC pipes including bed concrete as per standard design: 300 mm diameter
242Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth 1.5m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5m, disposed earth to be leveled and neatly dressed. (For Manholes) All kinds of soil
243Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone- III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone- III) : 8 graded stone aggregate 40 mm nominal size),inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design Inside size 90 x 80 cm and 45 cm deep including C.I. cover with frame (light duty) 455 x 610 mm internal dimensions total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
244Extra depth for manholes: Size 90 x 80 cm (With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 )
245Constructing brick masonry road gully chamber of specified size with common burnt clay(non modular) bricks of class designation 7.5 in cement mortar 1:4 ( 1 cement : 4coarse sand) including precast R.C.C. horizontal grating with frame complete as per standard design: Chamber size 50x45x60 cm including precast R.C.C grating with frame 500x450 mm horizontal grating.
246Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design: 100x100 mm size P type With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
247Material & labour for constructing Silt trap of size 1000mm x 2000mm x 2000mm deep in brick masonry with bricks of class designation 7.5 in cement mortar 1:6 (1 cement: 6 coarse sand) including necessary excavation and foundation concrete 150mm thick in 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate of 40mm nominal size), inside plaster 12mm thick in cement mortar 1:4 (1 cement : 4 coarse sand) finished with a floating coat of neat cement, C.C. floor, RCC slab in mix 1:2:4 & RCC baffle wall including reinforcement, centering & shuttering etc. and SFRC manhole cover and frame 610 x 455 mm heavy duty HD 10 conforming to IS: 12592 complete in all respects as shown on drawing.
248Material and labour for Constructing Brick masonry percolation pit 2m dia and 4m deep with bricks of class designation 7.5 in cement mortar 1:6, base concrete 1:3:6 below the brick wall, including cost of necessary excavation in any type of soil, back filling as required in 20cm thick layers, dewatering if any, shuttering and shoring and disposal of surplus excavated material within the plot. 2 nos. 300mm dia borings to a depth of 50 metre (to be measured from the bottom of the percolation pit), provisioning and Fixing 160 O.D. PVC pipes, tested to 6kg/sqcm, in each bore and upto the height of 300mm above the RCC top slab. The PVC pipe shall be slotted except 3.0 metres at the top and 3.0 metres below from the bottom of the percolation pit, which shall be blind. Top of the PVC pipe shall be covered with PVC Socket & plug. Each bore around the PVC pipe shall be filled with pea gravels. The percolation pit shall be filled with river stone/pebbles as shown in drawings. The top slab shall be 150mm thick with RCC (1:2:4) including nominal reinforcement and 2 nos. heavy duty 560 dia SFRC manhole covers with frames as per IS:12592 (weight not less than 182 kg) shall be provided in the top slab. PVC encased 12mm dia steel bar Footrests shall be provided 300 centre to centre. The above shall be provided all as specified and shown on drawings. 300mm dia RCC pipe for inlet and overflow as shown on drawings shall be measured separately.
249Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m : All kinds of soil Pipes, cables etc, not exceeding 80 mm dia.
250Providing and laying S&S Centrifugally Cast (Spun)/Ductile Iron pipes confirming to is:8329: 100 mm dia Ductile Iron Class K-9 pipes
251Providing and fixing enclosed type water meter (bulk type) conforming to IS : 2373 and tested by Municipal Board complete with bolts, nuts, rubber insertions etc. (The tall pieces if required will be paid separately) 100 mm dia nominal bore
252Supplying, installation, testing and commissioning of Electric driven Terrace Pump suitable for automatic operation and consisting of following, complete in all respects, as required : (B) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS:1520. (C ) Suitable HP Squirrel cage induction motor, TEFC type suitable,for operationon 415 volts, 3 phase 50 Hz, AC supply with IP 55 classprotection for enclosure, horizontal foot mounted typewith Class-'F' insulation, conforming to IS-325. M.S. fabricated Common base plate, coupling, couplingguard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered with anti vibration pads. 900 lpm at 35 m Head
253Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required. 1.2 Meter high and 250 mm dia.
254Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal / Stainless Steel cap and chain as required : Single headed Gunmetal
255Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 40 m
256Supplying and fixing 63mm dia, 15 mtr long RRL hose pipe with 63mm dia male and female gun metal couplings duly binded with GI wire, rivets etc. confirming to IS 636 (type-A)as required. (Gun Metal)
257Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required (Gun metal)
258Supply & Fixing of Fire Man's Axe with heavy Insulated rubber tested up to 20 KV and confirming to IS ;926 as required.
259Providing & fixing 100mm dia bourden type, Stainless steel dial type pressure Gauge (0 - 16 Kg) range, 3 / 8\\" BSP bottom entry on Pump Delivery Line complete with Ball valve
260Providing and fixing M.S. fire hose door (Including door frame and all civil work and finishing) of size 2000mm High x 1200mm Wide x 100 mm Deep approx.Fabricated from 16 gauge M.S sheet.Provision for hole fasteners on both sides with double dore & frame with 2 nos locking arrangement with 2 nos tower bolts and Glazed with 4mm thick Float clear glass (glass panel to be fix in door panel - 700 mm from the bottom of the door and 100 mm from the top /sides of door panel) suitably marked on the outside with the letters \\"FIRE HOSE\\".all M.S. work to be stove in Enamled Fire Red Colour over appropriate primer (Front side P.O. Red Paint & inside white paint two coat).The width & height to depend upon the actual size of the fire shaft available.Contractor to make shop drawings and get it approved by Enginner -in-charge/Consultant before fabrication.(Cost shall be inclusive of providing break glass box containing key for the door)
261Providing laying, testing and commissioning of class 'C' heavy duty MS pipe confirming to IS 3589/1239 including fittings like elbows, tees, flanges, reducer, jointing with nuts bolts, gasket and welding etc. and supports, as required and painting with tow or more coats of synthetic enamel paiing of required shade complet as directed by Engineer-iin-charge.100 mm dia
262Providing laying, testing and commissioning of class 'C' heavy duty MS pipe confirming to IS 3589/1239 including fittings like elbows, tees, flanges, reducer, jointing with nuts bolts, gasket and welding etc. and supports, as required and painting with tow or more coats of synthetic enamel paiing of required shade complet as directed by Engineer-iin-charge.80mm dia
263Providing laying, testing and commissioning of class 'C' heavy duty MS pipe confirming to IS 3589/1239 including fittings like elbows, tees, flanges, reducer, jointing with nuts bolts, gasket and welding etc. and supports, as required and painting with tow or more coats of synthetic enamel paiing of required shade complet as directed by Engineer-iin-charge. 25 mm dia
264Providing and fixing inspection & testing assembly/drain assembly consist of following :- i) 25 mm dia Inspection Test Valve (Ball Valve) & Piping ii) Sight Glass iii) Union iv) 50 mm dia ball valve for drain with piping The arrangment shall be complete as per drawing and as per NBC provisions. The item will include all works from the sprikler header to the drain pipe.
265Providing & fixing double flanged Metallic expansion with M.S. fixed flanges (PN-1.6) joint (suitable for system test pressure) of standard length as per manufacturers specs including rubber gaskets, flanges, nuts, bolts and washers complete as required as per specifications. 150 mm dia
266Providing & fixing double flanged Metallic expansion with M.S. fixed flanges (PN-1.6) joint (suitable for system test pressure) of standard length as per manufacturers specs including rubber gaskets, flanges, nuts, bolts and washers complete as required as per specifications. 100 mm dia
267Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :2 way-100 mm dia M.S. Pipe
268Supplying and fixing air release valve made of 100 mm dia, required accessories, as required
269Providing and fixing fire extinguisher of carbon dioxide type consisting of brand new high pressure steel cylinder bearing IS: 7285 mark and having the approval of controller of explosives Nagpur, wheel type valve bearing IS:3224 mark internal discharge tube, 1 meter long high pressure discharge hose, non conducting horn, suspension bracket, fully charged bearing IS: making fixed to wall as directed. 4.5kg capacity cylinder.
270ABC type extinguisher with cylinder fully charged with 6 Kg. capacity.
271FIRE FIGHTING PANEL
272Fabrication, Supplying, Installation, Testing & Commissioning of Electrical Fire Motor Control Panel of cubical construction, wall mounted type, fabricated out of 2mm. thick CRCA sheet, compartmentalized with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 9 tank treatment process, cable alley, interconnection with solid aluminium strip / single core PVC insulated FRLS copper conductor cable, having suitable mountings for switchgears and accessories and internal control & power wiring with suitable rating PVC insulated FRLS copper conductor, earth terminals, numbering etc. complete in all respects, suitable for operation on 415 V, 3 phase 50 HZ AC supply with enclosure protection class IP 42 with 100 Amp aluminium bus bar etc complete as required.
273Incoming
274MCCB, 4 Pole, 63 A, 25 KA with microprocessor based and rotary handle (ICS= ICU= 16 KA upto 415 V) - 1 sets.
275Digital Ammeter (0 - 250 A), 96 mm. sq. CT operated with inbuilt selector switch with 3 Nos. CT's of ratio 250/5 A, 15 VA burden and accuracy of class 1.0 - 1 Sets
276Digital Volt Meter (0-500 V) 96 mm. sq. with inbuilt selector switch and control MCBs - 2 Sets
277Phase Indicating coloured LED (RYB) with control MCBs - 1 Sets
278Bus Bar :
279Electrolytic high conductivity aluminium three phase and neutral busbars rated at 415V, 300 amps, 50Hz, AC, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints.
280Outgoing Terrace pump
281Fully Automatic Star Delta Starter suitable for sprinkler Pump,Hydrant Pump,Diesel Pump motor of 15HP and (as per the recommendation of pump manufacturer) complete with over load protection, current sensing type single phase preventer complete with contactors, push button, indicators LED type Auto/manual selector switches all accessories and FRLS copper conductor wiring etc. as required - 2 Set
282Fire panel as above Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57222264
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 19.73 Crore
LAST DATE 17-09-2026
Authority
Authority Name Indo Tibetan Border Police Force
Work Description Tender for Construction Of Type- Ii/56 Nos (S+7) Separated Family Accommodation (Sfa) Residential Quarters In Delhi Ncr I.E. In The C Us Of 39Th Bn Itbp, Greater Noida (Up).
Basic Detail
Tender No 393-95
Bidding Type Tender
Location
City Ghaziabad
State Uttar Pradesh
Key Dates
Publish Date 27 Aug 2026
Submission Date 17 Sep 2026
Open Date 18 Sep 2026
Finance
Tender Value 19.73 Crore
Tender Fee Ref. Documents
EMD 29.73 Lakhs
Exemption Not Available
Document List
82883370-aca4-4903-8cf8-adf67d954e1d.html
BOQ_970776.xls
drawings.pdf
tenderform.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 27, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 17, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 3 days
Sep 18, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 4 days

Tender Documents

Download All (ZIP) ↓
html

82883370-aca4-4903-8cf8-adf67d954e1d.html

xls

BOQ_970776.xls

pdf

drawings.pdf

pdf

tenderform.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders