Tender For Repair/ Maintenance Of Conversion Of Overhead Lt/Ht Line To Ug Cable And Related Items At Faridkot Mil Station
Tender Overview
Project Description
Tender for Repair/ Maintenance Of Conversion Of Overhead Lt/Ht Line To Ug Cable And Related Items At Faridkot Mil Station
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 02-Sep-2026 | Corrigendum No 1 | Date | 19-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Supply and laying XLPE insulated armoured heavy duty electric cable with aluminium conductor Multi standard cable 1100 volts grade in trenches ducts, pipe on walls, poles including suitable size of thimbles, nuts and bolts of following size, complete all as specified and directed.(a) 240 Sqmm 3.5 core |
| 2 | 120 Sqmm 3.5 core |
| 3 | 95 Sqmm 3.5 core |
| 4 | 70 Sqmm 3.5 core |
| 5 | 35 Sqmm 3.5 core |
| 6 | 25 Sqmm 4 core |
| 7 | 16 Sqmm 4 core |
| 8 | 10 Sqmm 4 core |
| 9 | Supply, install testing and commissioning CPRI approved weather and vermin proof LT feedar pillar box (Panel board) factory fabricated outdoor type totally enclosed made out of 3.15 mm thick sheet metal enclosure of suitable size, with angle iron frame of MS angle 40 X 40 X 6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 Hz system, with hinged panel doors (covers) on both two sides with handles, bottom gland plate and locking arrangement consisting suitable and sufficient nos circular cable entry holes at bottom only with suitable PVC/rubber bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated (15 micron) grey hammer tone with one coat of including connecting with LT armoured incoming and outgoing cables with suitable size of cable lugs and angle iron stand stand of height not less then 2.5 Feet from AGL with earth work, PCC fountation and other connected items complete all specified and directed and consisiting of following :-(a) Aluminium bus bar of 600 Amp current rating capacity, length as actually required at site for 3 phase and neutral, mounted on epoxy/FRP bus bar insulator(b) MCCB 315 Amps 4 Pole 36 KA, 415 V - 01 No for incoming.(c) MCCB 100 Amps 4 pole 16 KA, 415 V - 05 for outgoing .(d) MCCB 63 Amps 4 pole 16 KA, 415 V - 04 for outgoing .(e) TPN 40 Amp 16 KA 415 Volt -01 Nos(f) SPN 32 Amp 10 KA 415 Volt 4 Pole -01 Nos(g) 3 phase digital timer switch with contactors for auto switch on-off of street lights- 01 Set(h) Digital mutifunction meter for indicating of current, voltage etc with necessary CTs - 01 No (j) LED type indicator lamp Red/Yellow/Blue colour-01 set(k) Necessary internal wiring with copper conductor incl lugs and thimbles. |
| 10 | Supply, install testing and commissioning CPRI approved weather and vermin proof LT feedar pillar box (Panel board) factory fabricated outdoor type totally enclosed made out of 3.15 mm thick sheet metal enclosure of suitable size, with angle iron frame of MS angle 40 X 40 X 6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 Hz system, with hinged panel doors (covers) on both two sides with handles, bottom gland plate and locking arrangement consisting suitable and sufficient nos circular cable entry holes at bottom only with suitable PVC/rubber bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated (15 micron) grey hammer tone with one coat of including connecting with LT armoured incoming and outgoing cables with suitable size of cable lugs and angle iron stand stand of height not less then 2.5 Feet from AGL with earth work, PCC fountation and other connected items complete all specified and directed and consisiting of following :-(a) Aluminium bus bar of 600 Amp current rating capacity, length as actually required at site for 3 phase and neutral, mounted on epoxy/FRP bus bar insulator(c) MCCB 200 Amps 4 pole16 KA, 415 V - 01 for outgoing .(c) MCCB 63 Amps 4 pole 16 KA, 415 V - 04 for outgoing .(e) TPN 32 Amp 10 KA 415 Volt 4 Pole -01 Nos(f) 3 phase digital timer switch with TPN , contactors for auto switch on-off of street lights- 01 Set(g) Digital mutifunction meter for indicating of current, voltage etc with necessary CTs - 01 No (h) LED type indicator lamp Red/Yellow/Blue colour-01 set(j) Necessary internal wiring with copper conductor incl lugs and thimbles. |
| 11 | Supply, install testing and commissioning CPRI approved weather and vermin proof LT feedar pillar box (Panel board) factory fabricated outdoor type totally enclosed made out of 3 mm thick sheet metal enclosure of suitable size, with angle iron frame of MS angle 40 X 40 X 6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 Hz system, with hinged panel doors (covers) on both two sides with handles, bottom gland plate and locking arrangement consisting suitable and sufficient nos circular cable entry holes at bottom only with suitable PVC/rubber bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated (15 micron) grey hammer tone with one coat of including connecting with LT armoured incoming and outgoing cables with suitable size of cable lugs and angle iron stand stand of height not less then 2 Feet from AGL with earth work, PCC fountation and other connected items complete all specified and directed and consisiting of following :-(a) Aluminium bus bar of 200 Amp current rating capacity, length as actually required at site for 3 phase and neutral, mounted on epoxy/FRP bus bar insulator having agrrangement for 03 outgoing LT cables(b) MCCB 100 Amps 4 Pole 16 KA, 415 V - 01 No. for incoming.(c) Digital mutifunction meter for indicating of current, voltage with necessary CTs etc - 01 No (d) LED type indicator lamp Red/Yellow/Blue colour-01 set(e) Necessary internal wiring with copper conductor incl lugs and thimbles. |
| 12 | Supply and fix in replacement three phase of 5 KW automatic street light switch using Street light timer switch multi functional digital for automatic switching on & off of street lights at a preset time along with suitable three phase power contactor of 32 to 40 amps current rating, incomming MCB TPN and outgoing TPN MCBs of 32 to 40 Amps and, size of circuit should be multistranded FRLS min size of 6 Sqmm, selection operation should be enclosed in a pole/wall mounted enclosure with clamp , nut , bolts etc made of rust proof, electric shock proof termite proof and FR grade special mounting compound conforming to IP 54 complete all as specified and directed. |
| 13 | Supply, install testing and commissioning CPRI approved weather and vermin proof LT feedar pillar box (Panel board) factory fabricated outdoor type totally enclosed made out of 3.15 mm thick sheet metal enclosure of suitable size, with angle iron frame of MS angle 40 X 40 X 6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 Hz system, with hinged panel doors (covers) on both two sides with handles, bottom gland plate and locking arrangement consisting suitable and sufficient nos circular cable entry holes at bottom only with suitable PVC/rubber bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated (15 micron) grey hammer tone with one coat of including connecting with LT armoured incoming and outgoing cables with suitable size of cable lugs and angle iron stand stand of height not less then 2.5 Feet from AGL with earth work, PCC fountation and other connected items complete all specified and directed and consisiting of following :-(a) Aluminium bus bar of 600 Amp current rating capacity, length as actually required at site for 3 phase and neutral, mounted on epoxy/FRP bus bar insulator(b) MCCB 200 Amps 4 pole16 KA, 415 V - 01 for incoming .(c) MCCB 160 Amps 4 pole 16 KA, 415 V - 01 for outgoing .(d) MCCB 63 Amps 4 pole 16 KA, 415 V - 02 for outgoing .(e) TPN 40 Amp 10 KA 415 Volt 4 Pole -01 Nos(f) 3 phase digital timer switch with TPN , contactors for auto switch on-off of street lights- 01 Set(g) Digital mutifunction meter for indicating of current, voltage etc with necessary CTs - 01 No (h) LED type indicator lamp Red/Yellow/Blue colour-01 set(j) Necessary internal wiring with copper conductor incl lugs and thimbles. |
| 14 | Supply, install testing and commissioning CPRI approved weather and vermin proof LT feedar pillar box (Panel board) factory fabricated outdoor type totally enclosed made out of 3.15 mm thick sheet metal enclosure of suitable size, with angle iron frame of MS angle 40 X 40 X 6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 Hz system, with hinged panel doors (covers) on both two sides with handles, bottom gland plate and locking arrangement consisting suitable and sufficient nos circular cable entry holes at bottom only with suitable PVC/rubber bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, duly powder coated (15 micron) grey hammer tone with one coat of including connecting with LT armoured incoming and outgoing cables with suitable size of cable lugs and angle iron stand stand of height not less then 2.5 Feet from AGL with earth work, PCC fountation and other connected items complete all specified and directed and consisiting of following :-(a) Aluminium bus bar of 600 Amp current rating capacity, length as actually required at site for 3 phase and neutral, mounted on epoxy/FRP bus bar insulator(b) MCCB 315 Amps 4 Pole 36 KA, 415 V - 01 No for incoming.(c) MCCB 160 Amps 4 pole16 KA, 415 V - 03 for outgoing .(c) MCCB 63 Amps 4 pole 16 KA, 415 V - 02 for outgoing .(e) TPN 32 Amp 10 KA 415 Volt 4 Pole -01 Nos(f) 3 phase digital timer switch with TPN , contactors for auto switch on-off of street lights- 01 Set(g) Digital mutifunction meter for indicating of current, voltage etc with necessary CTs - 01 No (h) LED type indicator lamp Red/Yellow/Blue colour-01 set(j) Necessary internal wiring with copper conductor incl lugs and thimbles. |
| 15 | Disconnecting, dismantling and taking down carefully ACSR conductor from poles of LT any size and setting a side complete all as specified and as directed. |
| 16 | Dismantling/ taking down old cross arms, clamps, braces etc of any section from pole including nuts, bolts, washers complete all as specified and as directed. |
| 17 | Dismantling insulators any type, any size complete all as specified & directed. |
| 18 | Excavation in trenches n.exc 1.5m wide and n.exc 1.5m in depth for laying pipes and getting out in soft/loose soil all as specified and directed. |
| 19 | Returning filling in including spreading levelling watering and well ramming in layers n.exc 25cm all as specified and directed. |
| 20 | Removing the excavated soil from the trench n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point all as specified and directed. |
| 21 | Excavation in trenches by mechanical means (Hydraulic excavator )n.exc 1.5m wide for laying cables, DWCP pipes etc and getting out in soft/loosse soil incl dressing of sides, ramming of bottom, getting out the excavated soil, returning filling and disposal of surplus excvated soil as directed within a lead of 50m, making good disturbed surfaces of interlocking tiles, road ect all as specified and directed. |
| 22 | Supply and laying double wall corrugated pipe (DWC), non-metallic, Resistance to Compression : Type 450, Resistance to Impact: Normal, Resistance to Bending : Pliable, Resistance to External Influence: Ingress Protection : IP 67, Resistance against Corrosion : Without Protection, Resistance to Flame Propagation : Non Flame Propagating, Nominal outside diameter 77 mm, minimum inside dia 63 mm conforming to IS 16205 (Part 24) : 2017 complete all as specified and as directed. |
| 23 | Supply and laying double wall corrugated pipe (DWC), non-metallic, Resistance to Compression : Type 450, Resistance to Impact: Normal, Resistance to Bending : Pliable, Resistance to External Influence: Ingress Protection : IP 67, Resistance against Corrosion : Without Protection, Resistance to Flame Propagation : Non Flame Propagating, Nominal outside diameter 120 mm, minimum inside dia 103 mm conforming to IS 16205 (Part 24) : 2017 complete all as specified and as directed. |
| 24 | M&L Earthing complete with galvanised mild steel earth plate electrode 600x600x6.0mm thick, burried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using GI strip 32 x 6 mm as earth strip electrode bolted or rivetted to earth plate at one end and connected to equipments at another end 20 dia bore GI pipe 'light grade' as water pipe from earth chamber to upper edge of earth plate, test point , GI funnel with wire mesh fixed on water pipe and PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1 complete all as specified and directed and testing on completion. |
| 25 | Supply and fixing of hot press moulded SMC (Sheet Moulding Compound) junction box of inside dimention 210 mm x 190mm x 95mm including 4 Nos aluminium stud terminal of suitable size and fixed on pole with clamps, bolts and nuts with pole complete as provided by manufacturer all as specified and directed. |
| 26 | S&F PVC insulated multi stranded copper conductor cable 1.5 sqmm two core and making connections of street light complete all as specified and directed. |
| 27 | S&F in replacement LED street light 60 watt with aluminium housing toughned glass IP-66 weather protection complete all as specified and directed. |
| 28 | S&F GI Pipe 80mm bore light grade and including GI Fitting in Trenches/on Wall or Laying in floors complete all as specified and directed . |
| 29 | S&F GI Pipe 40mm bore light grade and including GI Fitting in Trenches/on Wall or Laying in floors complete all as specified and directed . |
| 30 | Material and labour for cable route path indicators made out of precast PCC mark LT cable 1100 V having PCC pillar of size 700mmx220mmx80mm, embedded 300 mm below ground level with PCC 1:3:6 (Type C1 using 20mm above ground level incl colour paint and written as per electricity rule above ground level incl excavation and earth work complete all as specified& directed. |
| 31 | Material for labour for drilling / boring of holes (horizondal ) under main road pavment hard standing or any other situation by trenchless technology mean for accommodate 100mm bore GI tube (light grade) in the drilling holes,including returniong filling in the end working space including removal of surplus soil and making good the surface complete all as specified and as directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 61 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 61 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 63 daysTender Documents