Tender For Special Repair/Replacement Of Lt Services In Basistha Area Under Ge Guwahati
Tender Value
Ref. Documents
Estimated cost
Bid Submission
15 Sep 2026
18 days left
EMD
77600
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Kamrup Metro → Assam
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Special Repair/Replacement Of Lt Services In Basistha Area Under Ge Guwahati
BOQ
| Sl. No. | Item Description |
| 1 | Supply, installation, testing and commissioning of floor mounted LTOUTDOOR feeder pillar box AC 415V,50 HZ 3 Phase 4 wire of suitable size for accomodating the following accessories totally enclosed self supporting structure /cubicle, fully compartmentalized type (separate compartment for I/C, each O/G and cable alley) I/P and O/P terminal of suitable capacity, suitable for outdoor use, with bottom cable entry with suitable cable glands structure made out of 3.15mm thick with CPRI approved CRCA steel sheet of suitable size with angle iron frame work and legs of ISA 50X50X5 mm, with four legs grouted to PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for copper bus bars of suitable capacity i.e 600 Amps, hinged doors at front with suitable locking arrangment, provision of louvers at sides, structure treated under 8-tank metal treatment process and duly powder coated, minimum box dimension :1800 X1600 X800 mm (HXWXD) complete all as specified and as directed.INCOMER :-(a) MCCB 400 Amp, 4 pole 415 Volts with adjustable thermal and magnetic settings of breaking capacity 36 KA with adjustable thermal magnetic setting-01 No.Item continued below as srl item No.1.10 |
| 2 | Item continued from srl item No.1.00 here-in-aboveOutgoing:- (i) MCCB 100 Amp, 4P, 25KA - 2 Nos(ii) MCCB 250 Amp, 4P,25KA -2 NosBUSBAR :-(Outgoing)(i) Copper Bus-bar 600 Amps , supported on non hygroscopic fibres and brass screws for mounting - 04 Nos Note: (a) Internal Incomer MCCB and Outgoing MCCB Connected through solid Copper bus bar.INDICATING DEVICES:(i) S&F LED indicating lamps for main supply indicating R, Y, B - 03 Nos(ii) S&F multifunction meter alongwith suitable capacity of CT(iii) MCB 6A, SP, 10 KA for protection and controlling (Set of 3 Pcs) |
| 3 | Supply, installation, testing and commissioning of floor mounted LTOUTDOOR feeder pillar box AC 415V,50 HZ 3 Phase 4 wire of suitable size for accomodating the following accessories totally enclosed self supporting structure /cubicle, fully compartmentalized type (separate compartment for cable alley) I/P and O/P terminal of suitable capacity, suitable for outdoor use, with bottom cable entry with suitable cable glands structure made out of 3.15mm thick with CPRI approved CRCA steel sheet of suitable size with angle iron frame work and legs of ISA 50X50X5 mm, with four legs grouted to PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for copper bus bars of suitable capacity i.e 600 Amps, hinged doors at front with suitable locking arrangment, provision of louvers at sides, structure treated under 8-tank metal treatment process and duly powder coated, minimum box dimension :20250 X1900 X600 mm (HXWXD) complete all as specified and as directed.INCOMER :-(a) MCCB 400 Amp, 4 pole 415 Volts with adjustable thermal and magnetic settings of breaking capacity 36 KA with adjustable thermal magnetic setting-01 No.Item continued below as srl item No.2.10 |
| 4 | Item continued from srl item No.2.00 here-in-aboveOutgoing:- (i) MCCB 63 Amp, 4P, 25KA - 09 Nos(ii) MCCB 100 Amp, 4P, 25KA - 01 Nos(ii) MCCB 16 Amp, 4P, 25KA - 01 No(iv) MCCB TPN 16 Amp 4P, 25KA-02 NosBUSBAR :-(Outgoing)(i) Copper Bus-bar 600 Amps , supported on non hygroscopic fibres and brass screws for mounting - 04 Nos Note: (a) Internal Incomer MCCB and Outgoing MCCB Connected through solid Copper bus bar.INDICATING DEVICES:(i) S&F LED indicating lamps for main supply indicating R, Y, B - 03 Nos(ii) S&F multifunction meter alongwith suitable capacity of CT(iii) MCB 6A, SP, 10 KA for protection and controlling (Set of 3 Pcs) |
| 5 | Supply, install, testing and commissioning LT Panel board, TPN 415 Volts, 50 Hz, out door cubical type floor mounted CPRI approved factory made, double door dust and vermin proof IP-54, fabricated out of CRCA sheet not less than 3.15 mm thick with 2mm thick for internal compartment duly powder coated fixed on angle iron pedestal made out of 50x50x6 mm with cable chamber for individual feeders for incomming and outgoing connections, one set of LED indicator lamp RYB with switch and fuse and the panel board shall be provided with proper ventillation including suitable size of cable alley copper bus bar suitable for carrying of current 400 Amps duly insulated and colour coded heat shrinkable sleeve and shall be rigidly mounted on suitable size of bridge insulator including necessary PCC foundation of minimum 0.50 m height positioned and fixed with suitable nut, bolts, washers etc to the MC pedestal complete all as specified and directed comprising of the following :- INCOMER :-(a) MCCB 250 Amp, 4 pole 50 Hz, 415 Volts with fixed thermal and magnetic release having rupturing capacity 25 KA - 01 No incoming(b) 3 Ph digital multi function meter model A class 1 5A with relay vega series - 01 No(c) Indicating lamp 240 volts LED type - Set of threeItem continued below as srl item No.3.10 |
| 6 | Item continued from srl item No.3.00 here-in-aboveOutgoing:- (i) MCCB 63 Amp, 4P, 25KA - 04 Nos(ii) MCCB 100 Amp, 4P, 25KA - 01 Nos(ii) MCCB 16 Amp, 4P, 25KA - 01 No(iv) MCCB TPN 16 Amp 4P, 25KA-02 NosBUSBAR :-(Outgoing)(i) Copper Bus-bar 400 Amps , supported on non hygroscopic fibres and brass screws for mounting - 04 Nos Note: (a) Internal Incomer MCCB and Outgoing MCCB Connected through solid Copper bus bar.INDICATING DEVICES:(i) S&F LED indicating lamps for main supply indicating R, Y, B - 03 Nos(ii) S&F multifunction meter alongwith suitable capacity of CT(iii) MCB 6A, SP, 10 KA for protection and controlling (Set of 3 Pcs) |
| 7 | Supply and fixing / Laying, connecting, testing and commissioning of LT under ground cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric cable (heavy duty) with multistranded aluminium conductor of the following sizes, 1100 Volts grade in trenches/on wall/poles laid in ducts/inside protection pipe including cable glands, lugs and suitable size of MS saddle clips (where ever cable laid in ceilings / walls without cable duct) including taking down old cable complete all as specified and as directed for the following cross sectional area :-. |
| 8 | (a) 10 sq mm 2 core |
| 9 | (b) 16 sq mm 4 core |
| 10 | (c) 25 sq mm 3½ core |
| 11 | (d) 50 sq mm 3½ core |
| 12 | (e) 70 sq mm 3½ core |
| 13 | (f) 95 sq mm 3½ core |
| 14 | (g) 120 sq mm 3½ core |
| 15 | (h) 185 sq mm 3½ core |
| 16 | (j) 240 sq 3½ core |
| 17 | (k) 300 sq mm 3½ |
| 18 | (l) 500 sq mm 3½ core |
| 19 | M&L for earthing complete with galvanised steel earth plate 600mm x 600mm x6mm thick elecrode and 32mm x 6mm galvanised iron strip as earthing lead burried directly in ground vertically (earth pit not less than 2.25mtr deep below ground level) with top edge of the plate not less than 1.5mtr below normal ground level, the earth plate surrounded by adequate quantity of charcoal dust and common salt to a packed thickness of 15 cm on all sides connected to GI strip 32mm x 6mm as earth lead by means of bolts, nuts, check nuts and washers (including welding) of galvanised iron or steel and connected to main switch board / panel/ test point at the other including necessary earth work in any type of soil, returning filling in and removal of surplus soil, concrete pit in PCC (1:3:6) type C1, pre cast RCC 1:2:4 type BI cover slab 54cm x 54cm x 5cm reinforce with 8mm dia bar TMT @150mm centre to centre both ways with one handle for lifting made out 8mm dia MS bar with wire mesh funnel, 20mm GI tubing medium grade for watering and 40mm GI tubing light grade for protection, test point, testing on completion all as shown in Electrical Plate No 3 of SSR Part-I complete all as specified and directed. |
| 20 | Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr deep for taking out / laying of under ground cable, pole or stay and getting out in soft soil strata complete all as specified and as directed. |
| 21 | Returning filling in including spreading leveling watering and well ramming in layers not exceeding 25cms spread any type of soil complete all as specified and as directed. |
| 22 | Removing excavated materials not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and as directed. |
| 23 | Supply and lay for dry river sand filling for cable protection with a layer of 8cm deep before laying and 15cm covering above the top edge of cable after laying complete all as specified and as directed. (Note : Punned thickness shall be measured). |
| 24 | M&L in tranches bricks common burnt un clay, building brick, sub class B designation 75 for cable protection complete all as specifieed and as directed. |
| 25 | Boring/drilling (horizontally) hole manually under existing road, pavement, hard standing (maximum 10mtr in width) suitable for passing GI tubing of 40 to 150mm bore dia complete all as specifieed and as directed. |
| 26 | M&L for replacement of galvanised tubing light grade of 80 mm dia laid in trenches or fixed to pole and / or laid under road in any position with necessary clamp nut and bolt complete all as specifieed and as directed. |
| 27 | Supply and fixing in replacement Cable Junction Boxes IP 66 “halogen free and weather proof” for outdoor installation (with metric knockouts for cable entry - Black Colour) size 200 x 160 x 98 mm all as suitable for 16/25 sqmm fixed to pole /wall with suitable FI clamp 20X3 mm nuts , bolts and washers incl provision of 01 No miniature circuit breaker (MCBs) single pole, 240 volts 10 KA 6 Amps and incl suitable capacity Copper bus bar complete all as specified and as directed. |
| 28 | Supply and fixing in replacement PVC insulated and PVC round sheathed, copper conductor industrial cable (confirming to IS 694:2010) 1.5 sqmm, Three core of copper conductor for connection of street light/Flood light / post top lanterns/garden lights etc. fittings on pole / wall / pillar from over head conductor / junction box / DB including termination clip etc complete in all respect including through GI tubing of size 15mm/20mm dia complete all as specified and as directed. |
| 29 | Supply and fixing in replacement for 40mm bore GI protection pipe light grade for cable protection incl all fittings laid in trenches or fixed on pole/walls with mild steel clamps, bolts, nuts and washers complete all as specified and as directed. NOTE : Earth work reqd shall be measured and paid separately. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 25, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 15, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 18 daysSep 17, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 20 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender