Tender For Special Repair/ Replacement Of Lt Panel And Allied Work At Various Location And Provision Of 3 Phase Power Supply With Allied Work For Auditorium Shed & Prepaid Electric Meter For Regimental Shops & High Mast Light At Mcte Under Ge (Mcte)
Tender Overview
Project Description
Tender for Special Repair/ Replacement Of Lt Panel And Allied Work At Various Location And Provision Of 3 Phase Power Supply With Allied Work For Auditorium Shed & Prepaid Electric Meter For Regimental Shops & High Mast Light At Mcte Under Ge (Mcte) Mhow
BOQ
| Sl. No. | Item Description |
| 1 | S&F in replacement LT Panel IP 54/65 Factory made Polyacrbonate LT Panel floor mounted with canopy with certificate. The LT Panel made of environment friendly polycarbonate PC-GFS, 1800 x 1950 x 530mm size, The enclosures must be suitable for outdoor installation - harsh environment and/or outdoor installation. Bottom parts, Glands Plate and lids of the boxes made from impact-resistant polycarbonate, halogen and silicone-free, transparent/ Opaque lid with quick action fasteners for tool operation. Maximum water absorption 10 mg in accordance with DIN 53473. The LT Panel should be Single door floor mounted with canopy and cable gland plate and cable glands. The enclosure should have mechanical strength individual enclosure equivalent to IK 08. The Enclosure having high grade internally embedded gasket made of Polyurethane (PUR). Panel should have UL. Lab. certified in accordance with IEC/EN 61439-2. Panel should have to manufactured and assembled by OEM only. Shall have Polycarbonate enclosure and panel manufacturer are the same. Fabrication/ Assembling from any system house & at site fitment will not be accepted. Shall have submit Panel drawing for approval on OEM Letterhead before supply at site. Fabrication/ Panel Builder drawing not accepted. The bidder should have to submit all relevant test certificate/ compliance in OEM letterhead during technical evaluation. The bidder should have to submit warranty format in OEM letterhead. The bidder should have to submit Routine test certificate in OEM letterhead. Protection Class II, totally insulated, IP65 (in accordance with IEC/EN60529), Glow Wire Test in accordance with IEC 60695-2-11 - 960° C. UL Subject 94: V-2, flame retardant & self-extinguishing, Should have Panel accessories Gland Plate ,Cable Glands loose supply, O/G Terminals installtion accessories etc. including taking down complete all as specified and directected. |
| 2 | Technical Details:-Enclosure : Thermoplastic Polycarbonate System Voltage : 415V, 50HZ, 4Wire +EFinish Shade : Enclosure & Accessories : RAL 7035Mounting Structure : RAL 7016Installation : OUTDOOR Floor Mounted with canopyIncoming - 400A FP 36kA MCCB - 1 Nos. - RYB Indication Lamp- Each - 1 Nos. - Fuse Terminal Block with fuse (2A) - 6 Nos.- Multifunction meter - 1 Nos.- 400/5A, 5VA, CL1, Current Transformer - 3 Nos. Bus Bar Rating - 400A (RYBN 40 x 10mm CU.), Outgoing - 200A, FP 25KA, MCCB - 1 Nos. - 100A, FP 25KA, MCCB - 3 Nos. Cat No. - HEN MI DB -1285-2026-2 |
| 3 | S&F in replacement of LT Panel IP 54/65 Factory made Polyacrbonate LT Panel floor mounted with canopy with certificate. The LT Panel made of environment friendly polycarbonate PC - GFS. The enclosures must be suitable for outdoor installation - harsh environment and/or outdoor installation. Bottom parts, Glands Plate and lids of the boxes made from impact-resistant polycarbonate, halogen and silicone-free, transparent/ Opaque lid with quick action fasteners for tool operation. Maximum water absorption 10 mg in accordance with DIN 53473. The LT Panel should be Single door floor mounted with canopy and cable gland plate and cable glands. The enclosure should have mechanical strength individual enclosure equivalent to IK 08. The Enclosure having high grade internally embedded gasket made of Polyurethane (PUR). Panel should have UL. Lab. certified in accordance with IEC/EN 61439-2. Panel should have to manufactured and assembled by OEM only. Shall have Polycarbonate enclosure and panel manufacturer are the same. Fabrication/ Assembling from any system house & at site fitment will not be accepted. Shall have submit Panel drawing for approval on OEM Letterhead before supply at site. Fabrication/ Panel Builder drawing not accepted. The bidder should have to submit all relevant test certificate/ compliance in OEM letterhead during technical evaluation. The bidder should have to submit warranty format in OEM letterhead. The bidder should have to submit Routine test certificate in OEM letterhead. Protection Class II, totally insulated, IP65 (in accordance with IEC/EN60529), Glow Wire Test in accordance with IEC 60695-2-11 - 960° C. UL Subject 94: V-2, flame retardant & self-extinguishing, Should have Panel accessories Gland Plate, Cable Glands loose supply, O/G Terminals installtion accessories etc, including taking down complete all as specified and directected. |
| 4 | Technical Details:-Enclosure : Thermoplastic Polycarbonate System Voltage : 415V, 50HZ, 4Wire +EFinish Shade : Enclosure & Accessories : RAL 7035Mounting Structure : RAL 7016Installation : OUTDOOR Floor Mounted with canopy Incoming - 400A FP 36KA MCCB - 1 Nos.- RYB Indication Lamp- Each - 1 Nos.- Fuse Terminal Block with fuse (2A) - 6 Nos.- Digital Multifunction Meter - 1 Nos.- 400/ 5A, 5VA, CL1, Current Transformer - 3 Nos. Bus Bar Rating - 400A (RYBN 40 x 10mm CU.). Outgoing - 200A, FP 25KA, MCCB - 2 NOS. - 100A, FP 25/30KA, MCCB - 3 Nos. . - 63A, FP 18/25KA, MCCB - 03 Nos. Terminals - 50 Sqmm Terminal Blocks - 12 Nos. 25 Sqmm Terminal Blocks - 12 Nos. Cat No. - HEN MI DB -1044-2026-3 Dimension in mm - 1800 x 1700 x 450mm |
| 5 | S&F in replacement of LT Panel IP 54/65 Factory made Polyacrbonate LT Panel floor mounted with canopy with certificate. The LT Panel made of environment friendly polycarbonate PC-GFS, 1500 x 1950 x 530mm size, The enclosures must be suitable for outdoor installation - harsh environment and/or outdoor installation. Bottom parts, Glands Plate and lids of the boxes made from impact-resistant polycarbonate, halogen and silicone-free, transparent/ Opaque lid with quick action fasteners for tool operation. Maximum water absorption 10 mg in accordance with DIN 53473. The LT Panel should be Single door floor mounted with canopy and cable gland plate and cable glands. The enclosure should have mechanical strength individual enclosure equivalent to IK 08. The Enclosure having high grade internally embedded gasket made of Polyurethane (PUR). Panel should have UL. Lab. certified in accordance with IEC/EN 61439-2. Panel should have to manufactured and assembled by OEM only. Shall have Polycarbonate enclosure and panel manufacturer are the same. Fabrication/ Assembling from any system house & at site fitment will not be accepted. Shall have submit Panel drawing for approval on OEM Letterhead before supply at site. Fabrication/ Panel Builder drawing not accepted. The bidder should have to submit all relevant test certificate/ compliance in OEM letterhead during technical evaluation. The bidder should have to submit warranty format in OEM letterhead. The bidder should have to submit Routine test certificate in OEM letterhead. Protection Class II, totally insulated, IP65 (in accordance with IEC/EN60529), Glow Wire Test in accordance with IEC 60695-2-11 - 960° C. UL Subject 94: V-2, flame retardant & self-extinguishing, Should have Panel accessories Gland Plate, Cable Glands loose supply, O/G Terminals installtion accessories etc, including taking down complete all as specified and directected. |
| 6 | Technical Details:-Enclosure : Thermoplastic Polycarbonate System Voltage : 415V, 50HZ, 4Wire +EFinish Shade : Enclosure & Accessories : RAL 7035Mounting Structure : RAL 7016Installation : OUTDOOR Floor Mounted with canopy Incoming- - 400A FP 36KA MCCB - 2 Nos, - Changeover Switch 400A FP - 1 Nos. - RYB Indication Lamp - Each 1 Nos.- Fuse Terminal Block with fuse (2A) - 6 Nos. - Digital Multifunction meter - 1 Nos.- 400/5A, 5VA, CL1, Current Transformer - 3 Nos. Bus Bar Rating - 400A (RYBN 40 x 10mm CU.), Outgoing - 100A FP 25/30KA MCCB - 1 Nos. - 63A, FP 25/30KA, MCCB - 5 Nos. Cat No. - HEN MI DB - 1285-2026-4 |
| 7 | S&F in replacement of LT Panel IP 54/65 Factory made Polyacrbonate LT Panel floor mounted with canopy with certificate. The LT Panel made of environment friendly polycarbonate PC-GFS, 1500 x 1950 x 530mm size, The enclosures must be suitable for outdoor installation - harsh environment and/or outdoor installation. Bottom parts, Glands Plate and lids of the boxes made from impact-resistant polycarbonate, halogen and silicone-free, transparent/ Opaque lid with quick action fasteners for tool operation. Maximum water absorption 10 mg in accordance with DIN 53473. The LT Panel should be Single door floor mounted with canopy and cable gland plate and cable glands. The enclosure should have mechanical strength individual enclosure equivalent to IK 08. The Enclosure having high grade internally embedded gasket made of Polyurethane (PUR). Panel should have UL. Lab. certified in accordance with IEC/EN 61439-2. Panel should have to manufactured and assembled by OEM only. Shall have Polycarbonate enclosure and panel manufacturer are the same. Fabrication/ Assembling from any system house & at site fitment will not be accepted. Shall have submit Panel drawing for approval on OEM Letterhead before supply at site. Fabrication/ Panel Builder drawing not accepted. The bidder should have to submit all relevant test certificate/ compliance in OEM letterhead during technical evaluation. The bidder should have to submit warranty format in OEM letterhead. The bidder should have to submit Routine test certificate in OEM letterhead. Protection Class II, totally insulated, IP65 (in accordance with IEC/EN60529), Glow Wire Test in accordance with IEC 60695-2-11 - 960° C. UL Subject 94: V-2, flame retardant & self-extinguishing, Should have Panel accessories Gland Plate, Cable Glands loose supply, O/G Terminals installtion accessories etc,. including taking down complete all as specified and directected. |
| 8 | Technical Details:-Enclosure : Thermoplastic Polycarbonate System Voltage : 415V, 50HZ, 4Wire +EFinish Shade : Enclosure & Accessories : RAL 7035Mounting Structure : RAL 7016Installation : OUTDOOR Floor Mounted with canopy Incoming-- 400A FP 36KA MCCB - 1 Nos.- RYB Indication Lamp - Each 1 Nos. - Fuse Terminal Block with fuse (2A) - 6 Nos.- Digital Multifunction Meter - 1 Nos.- 400/5A, 5VA, CL1, Current Transformer - 3 Nos. Bus Bar Rating - 400A (RYBN 40 x 10mm CU.), Outgoing - 250A, FP 25KA MCCB - 1 Nos. - 100A, FP 25/30KA, MCCB - 3 Nos. - 32A, SP 10KA MCB - 07 Nos. |
| 9 | M&L for earthing with galvanized steel earth plate electrode 600 x 600 x 6.0mm thick buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to galvanized iron 32 x 6mm strip as earthing lead protected by GI pipe light grade 40mm bore for protection of GI earth strip and 20mm dia GI pipe medium grade for watering with alternate layers of charcoal/ coke and salt including all accessories like nut, bolts, reducer, nipple, wire meshed/ screened funnel and making brick masonry finished chamber of internal size 300mm x 300mm x 300mm with concrete base, covered with a cast Iron hinged cover resting over the cast iron frame painted with black bitumastic paint which shall be embedded in the block masonry including excavation works, refilling, connected to main switch/ MCB DB for feeding the electric supply complete including dismantling of old unsv earthing complete all as specified and as shown in electrical plate No. 3 of SSR Part-I and testing of earth resistance as required.Note:- 7.5 RM strip wire upto 7.5 RM including unit rate. |
| 10 | M&L for boring under road horizontely of 80/50mm bore of GI pipe for passing of cable in road in hard/ soft/ loose soil complete all as specified and directed. |
| 11 | Supply & laying cable 50 Sqmm 3.5 core XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor using lugs bothe end of cable & wrapping pvc tape over XLPE insulation cable and testing complete all as specified and directed. (Note:- Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid seperately) |
| 12 | Supply & laying cable 16 Sqmm 4 core XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor using lugs bothe end of cable & wrapping pvc tape over XLPE insulation cable and testing complete all as specified and directed. (Note:- Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid seperately) |
| 13 | Excavation in trenches in any type of soil not exceeding 1.5 M wide and not exceeding 1.5 Mtr deep and getting out including filling bottom surface to required level or slope for laying of pipes/ cables complete all as specified and directed. |
| 14 | Removing excavated surplus soil not exceeding 50 Mtr and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and directed. |
| 15 | Returning filling including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in soft soil complete all as specified and directed. |
| 16 | Supply and laying sub class 'B' bricks laid dry and flat across the length of cable for protection of cable including taking down old/ broken bricks complete all as specified and directed. |
| 17 | M&L for sand cushioning with dry local sand for cable protecting under ground cable (8 cm before laying the cable and 15 cm after laying the cable) in trenches including punning the sand upto 18 cm thick and consolidated complete all as specified and directed.Note : Punned thickness 18 cm shall be measured only. |
| 18 | S&F for 50mm dia GI pipe 'light grade' ISI marked including fittings such as bends, tees, sockets etc fixed on wall/ pole or laid in trenches under road crossing/ hard standing complete all as specified and directed.Note:- Excavation and earth work shall be measured & paid separately. |
| 19 | Supply, installation, testing and commissioning of LT Panel including taking down old unserviceable LT Panel out door type factory made CPRI Approved, water and vermin proof protection of size 2500mm x 1500mm x 800mm (over all dimension) made out of 3.00mm thick CRCA sheet dully supported with mild steel angle iron of size 50 x 50 x 6mm vertical frame and legs with mild steel flat iron 50 x 50 x 6mm in horizontal sides of the frame with front and back side openable, single hinged door/ shutter with locking arrengement and powder coated finish both internal and external steel surfaces after necessary preparation of steel surfaces including providing PCC (1:3:6) type C2 foundation of suitable size and connections of all outgoing/ incomming cable inclusive of necessary excavation and earthwork as required including the following fitment accessories and also complete all as specified and directed. Note:- Rate of earth work and PCC work are deemed to be inclusive in this item. |
| 20 | INCOMING:- (a) Copper strip busbar of size 1200 Amps rated capacity wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends - 04 Nos.(b) 4 pole MCCB 400 Amps with rotary handle, adjustable thermal magnetic release type 415 Volts, Ics = 100% Icu, breaking capacity 35 KA including all fixing accessories with both ends spreader links - 01 Nos.(c) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three).(d) Digital Ammeter of range (0-500) Amps, flush mounting type with CT's of ratio 400/5 and selector switch - 01 Set. (e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch - 01 Nos.OUTGOING(a) 4 Pole MCCB 400 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 36 KA breaking capacity including all fixing accessories with both ends spreader links - 02 Nos.(b) 4 Pole MCCB 250 Amps with rotary handle, adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics = 100% Icu, 36 KA breaking capacity including all fixing accessories with both ends spreader links - 02 Nos.(c) 4 Pole MCCB 100 Amps with rotary handle, adjustable thermal magnetic release type, 4 poles, 415 Volts, Ics =100% Icu, 16 KA breaking capacity including all fixing accessories with both ends spreader links - 02 Nos.(d) Enamelled iron danger notice plate of 1.60mm thick mild steel sheet of size 200mm x 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of JB for LT - 01. |
| 21 | M&L for earthing with galvanized steel earth plate electrode 600 x 600 x 6.0mm thick buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to galvanized iron 32 x 6mm strip as earthing lead protected by GI pipe light grade 40mm bore for protection of GI earth strip and 20mm dia GI pipe medium grade for watering with alternate layers of charcoal/ coke and salt including all accessories like nut, bolts, reducer, nipple, wire meshed/ screened funnel and making brick masonry finished chamber of internal size 300mm x 300mm x 300mm with concrete base, covered with a cast Iron hinged cover resting over the cast iron frame painted with black bitumastic paint which shall be embedded in the block masonry including excavation works, refilling, connected to main switch/ MCB DB for feeding the electric supply complete all as specified and as shown in electrical plate No. 3 of SSR Part-I and testing of earth resistance as required.Note:- 7.5 RM strip wire upto 7.5 RM including unit rate. |
| 22 | M&L for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6mm thick directly buried in ground (earth pit not less than 2.25 m deep below ground level) with top edge of earth plate not less than 1.5m below the ground level connected to GI earth wire 4mm dia by means of bolts nuts check nuts and washers of galvanised iron at 2 points & GI pipe 15mm bore light grade for protection of earthing wire PCC chamber 1:3:6 (type C-1) using 20mm graded stone aggregate, watering pipe 20mm bore light grade, funnel with wire mesh, 50mm thick cover of RCC 1:2:4 type B-1 using 20mm graded stone aggregate reinforced with 8mm MS bars at 150mm centre to centre both ways and charcoal dust and common salt all as shown in electrical plate No. 3 of MES SSR Part-I and including excavation & earth work & connecting the earthing point/ equipment and testing complete all as specified and directed. |
| 23 | S&F doubel door MS metal enclosure for DB when MCBs to be used TPNL, 4 way, 415 Volts (horizontal type) with 200 Amp rated busbar IP 43-IK 09 suitable for TPN MCB/ 4 pole isolator fixed properly on in concealed position and to provide required size of flexible conduit at any open surfaces near DBs for cable/ wire complete all as specified and directed. |
| 24 | S&F for MCB TPN 63 Amps, 415 Volts, 'B' series, 10 KA breaking capacity & connection complete all as specified and directed.. |
| 25 | S&F MCB SP 240 volts 6 to 32 Amps, 'B' series, 10 KA breaking capacity & connection complete all as specified and directed. Please Enable Macros to View BoQ information |
| 26 | S&F MCB SP 240 volts 6 to 32 Amps, 'B' series, 10 KA breaking capacity & connection complete all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 19 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender