Defence Statutory Bodies & Commissions/Committees Closing in 4 days TDR #57199898

Tender For Repair/Maintenance Of Point Wiring Fixtures With Fittings & Sub Main Wiring,Mcb,Dbs,Ceiling Fan,Exhaust Fan,Bldg Security Lights And Other Connected Works To Various Md Accn And Certain Units And Repair/Maintenance Of Hot Water Apparatus(G

Issued by Statutory Bodies & Commissions/Committees · Tinsukia, Assam
Tender Value
37.40 Lakhs
Estimated cost
Bid Submission
15 Sep 2026
4 days left
EMD
75000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Tinsukia → Assam
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair/Maintenance Of Point Wiring Fixtures With Fittings & Sub Main Wiring,Mcb,Dbs,Ceiling Fan,Exhaust Fan,Bldg Security Lights And Other Connected Works To Various Md Accn And Certain Units And Repair/Maintenance Of Hot Water Apparatus(Geyser) Including Solar Water Heater,Ceiling Fans,Wall Mounted Fans,Air Circulator And Exhaust Fan And Connected Works At Out Pockets Under Ge Dinjan No.2

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 08-Sep-2026 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 15-Sep-2026

BOQ

Name of Work:- REPAIR/MAINTENANCE OF POINT WIRING FIXTURES WITH FITTINGS & SUB MAIN WIRING,MCB,DBs,CEILING FAN,EXHAUST FAN,BLDG SECURITY LIGHTS AND OTHER CONNECTED WORKS TO VARIOUS MD ACCN AND CERTAIN UNITS AND REPAIR/MAINTENANCE OF HOT WATER APPARATUS(GEYSER) INCLUDING SOLAR WATER HEATER,CEILING FANS,WALL MOUNTED FANS,AIR CIRCULATOR AND EXHAUST FAN AND CONNECTED WORKS AT OUT POCKETS UNDER GE DINJAN NO.2
Sl. No. Item Description
1Taking down carefully unserviceable aluminium/copper point wiring (light, fan, socket or power) complete, including unserviceable fitting such as switches, ceiling roses, pendants, regulators, sockets, etc removing material to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions seperately) and making good the disturbed surfaces of wall/floor or ceiling to match with existing surface and finishing the surfaces with distemper/white washing/colour washing as per existing complete all as specified and directed.
2Taking down carefully (copper/aluminum) unsv sub main wiring complete of any type (batten/surface conduit or concealed) complete for taking credit and making good the disturbed surfaces of wall/floor or ceiling to match with existing surface and finishing the surfaces with distemper/white washing/colour washing as per existing complete all as specified and directed.
3M & L for Point Wiring with 1.5 Sqmm (Nominal Area) PVC insulated unsheathed fire retardant low smoke and halogen (FR-LSH),1100 Volts Grade Copper conductor single core multi stranded copper cable must conform to IS 14927 (Part 1 & 2): 2001 using approved colour code for phase and neutral as per IS code (Red Colour Cable for Phase and Black Colour Cable for Neutral), laid in and including PVC Casing and Capping size of casing and caping as per actual site requirement in accordance with clause No 19.125 of SSR Part I (ISI marked) with accessories including 1.50 Sqmm PVC insulated Stranded Cpper Conductor Cable (Green Colour) as Earth Continuity Conductor and connected to Common Earth Dolly or as directed and PVC terminal box (sunken type) switch board (For normal/modular switch socket) fixed with suitable sizes cadmium plated iron screws and washers etc. for mounting switches, sockets, regulators etc, with 1.2 mm thick PVC cover fixed on wall complete for one light/ceiling fan/Exhaust fan point controlled by one, one way switch complete all as specified and directed.
4Description all as per item no 3 here -in-before but for one 5 Amps, 3/5 pin socket outlet contolled by one switch on the same board.
5Description all as per item no 3 here -in-before but for One bell /Buzzer point controlled by one, one way switch/bell push.
6Description all as per item no 3 here -in-before but for one Socket Outlet Point, 5 Amp on independent board with 2.5 Sqmm copper cable complete all as specified and directed.
7Description all as per item no 3 here -in-before above but for one Socket Outlet Point 5 or 6 Pin, 15 Amp controlled by one switch on independent board complete all as specified and as directed.
8Description all as per item no 3 here -in-before above but for one 3 pin socket outlet 15 Amps for AC Point with 4.00 sqmm copper cable complete all as specified and as directed.
9M & L for Point wiring with 1.5 sqmm PVC insulated and unsheathed fire retardant low smoke and halogen (FR-LSH) copper conductor single core multi stranded copper cable confirming to IS:694 (2010) using approved colour code for phase and neutral as per IS code drawn through non metallic PVC rigid concealed conduit medium mechanical stress (MMS) grade in accordance with IS:9537 (Part 3) having wall thickness not less than 2.0 mm thick and minimum 20 mm external dia but shall be increased as per actual site requirement in accordance with clause No 19.125 of SSR Part I (ISI marked) including conduit accessories like bends, tees, junction boxes etc fixed concealed with all accessories suitable for modular type fitment, provision for fixing of modular flush boxes of appropriate size and dimensions for fixing of piano switches/modular switches/sockets/regulator etc including PVC insulated and unsheathed FRLSH 1.5 sqmm multi stranded copper conductor cable (green color) as continous earth lead wire connected to common earth and earth dolly for one light point/fan point controlled by one switch complete all as specified and directed by Engr-in-Charge. Make of Wire : Havells/RR Kabel/FinolexMake of Coduit : Anchor/Precision/Astral
10Description all as per item no 9 here -in-before but for One 5 Amps, 3/5 pin socket outlet contolled by one switch on the same board.
11Description all as per item no 9 here -in-before but for One bell /Buzzer point controlled by one, one way switch/bell push
12Description all as per item no 9 here -in-before but for one Socket Outlet Point, 5 Amp on independent board with 2.5 Sqmm copper cable complete all as specified and directed.
13Description all as per item no 9 here -in-before but for one Socket Outlet Point 3 or 5 Pin, 15 Amp controlled by one switch on independent board with 2.5 sqmm copper cable complete all as specified and as directed.
14Description all as per item no 9 here -in-before but for one 3 pin socket outlet 15 Amps for AC Point with 4.00 sqmm copper cable complete all as specified and as directed.
15M & L for Sub main wiring with two runs of 6 sqmm single core cable FRLSH PVC insulated multistranded, unsheathed, copper conductor cables 1100 Volts grade drawn through PVC casing capping, thickness not less than 1.2 mm dia with all fittings and accessories (like Tee, bend etc) etc including 6 sqmm (nominal area) single core, FRLSH PVC casing insulated multistranded, unsheathed copper conductor as earth wire and duly connected to common earth point fixed on wall with all accessories complete all as specified and as directed by Engr-in-charge.Note: (a) Rate of sub main wiring shall include cutting chases for conduit/flush boxes etc. (b) PVC Conduits/Casing-caping, two run cables and one run of earth wire will be measured as one length. (c) All incoming and outgoing cable shall be connected by using proper lugs & sockets.
16Description all as per item no 15 here -in-before but for but size of copper conductor 2 run of 4 sqmm and 1 run of 4 Sqmm for earth.
17Description all as per item no 15 here -in-before but for size of copper conductor 2 run of 10 sqmm and 1 run of 10 Sqmm for earth.
18M & L for module cover plate with frame as per site requirement for following module complete all as specified and as directed.
19Description all as per item no 18 here -in-before but for 1 module
20Description all as per item no 18 here -in-before but for 2 module
21Description all as per item no 18 here -in-before but for 3 module
22Description all as per item no 18 here -in-before but for 4 module
23Description all as per item no 18 here -in-before but for 6 module
24Description all as per item no 18 here -in-before but for 8 module
25M & L for Modular metal Flush box as per site requirement.
26Description all as per item no 25 here -in-before but for 1/2 module
27Description all as per item no 25 here -in-before but for 3 module
28Description all as per item no 25 here -in-before but for 4 module
29Description all as per item no 25 here -in-before but for 6 module
30Description all as per item no 25 here -in-before but for 8 module
31S & F for modular switch 1 way 5/6 Amp 1 Module, 240 volts complete all as specified and as directed.
32S & F modular bell push 1 way 6A, 1 module complete all as specified and as directed.
33S & F for Modular Switch 1 way 16/20 Amp 1 Module, 240 volts complete all as specified and as directed.
34S & F for Modular Socket 6A 2/3 Pin universal 2 module, complete all as specified and as directed.
35S & F for Modular Socket 16A/ 6A 2/3 Pin combined 2 module ,complete all as specified and as directed.
36S & F call bell / Buzzer, Ding Dong AC, 230 volts, single pole complete all as specified and directed.
37S & F Modular fan step regulator 120 watt 2 module, complete all as specified and as directed by Engineer-in-charge.
38S & F Ceiling rose ceiling rose, 2 to 3 terminal PVC/ polycarbonate, isolated body type suitable for AC 230 volts complete all as specified.
39S & F in repair Switch piano, flush type, 5 Amps, single pole, one way, 240 Volts including taking down old unserviceable one complete all as specified and directed.
40S & F in repair Ceiling rose, 3 Terminal, PVC/polycarbonate, isolated body including taking down old unserviceable one complete all as specified and directed.
41S & F in repair Bell push, flush type, 5 Amps 230 Volts, including taking down old unserviceable one complete all as specified and directed.
42S & F in repair Call Bell Ding-Dong type, AC, 230 volts, single pole including taking down old unserviceable one complete all as specified and directed.
43S & F in repair Socket outlet, 3/5 pin , 5 Amps, flush type including taking down old unserviceable one complete all as specified and directed.
44S & F in repair Switch socket combination 2 in 1, 5 pin, 5 Amps, flush type, 240 volts including taking down old unserviceable one complete all as specified and directed.
45S & F in repair Switch socket combination 2 in 1, 6 pin, 6/16 Amps, flush type, 240 volts including taking down old unserviceable one complete all as specified and directed.
46S & F in repair Stepped type (five steps), electronic fan regulator, 220 volts, flush type including taking down old unserviceable one complete all as specified and directed. (Make: Anchor, Model No. 14502 or equivalent make as per list of manufacturer)
47S & F in repair PVC rectangular block for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover of size 200 mm x 150 mm and 50 mm deep, including taking down old unserviceable one complete all as specified and directed
48Description all as per item no 47 here -in-before but size 250 mm x 200 mm x 50 mm deep.
49Description all as per item no 47 here -in-before but size 350 mm x 300 mm x 50 mm deep.
50Description all as per item no 47 here -in-before but size 175 mm x 100 mm x 50 mm deep.
51Description all as per item no 47 here -in-before but size 100 mm x 100 mm x 50 mm deep.
52Re-Fixing only serviceable LED Tube light fitting 1x 18/20 Watt, 4 feet, 220V AC obtained from item No. 1.00 above complete all as specified and directed by Engineer-in-charge.
53S & F in lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings complete all as specified and directed.
54S & F LED Lamp 9 Watt complete all as specified and directed by Engineer-in-charge.
55S & F energy efficient 18/20 watt (4.0 feet) LED tube light batten made of extruded aluminum housing with a PC glossy diffuser duly prewired connection having a nominal system lumen output of 2000 lumens at a minimum system efficacy of 115 lumen per watt and total power consumption 18/20 watt including driver. It has a rated system life time of 40000 burning hours at L70 and should have a colour temperature of 6500K, CRI>80, THD<10% and PF>0.95 complete all as specified and directed.
56S & F energy efficient 10/12 watt (2.0 feet) LED tube light batten made of extruded aluminum housing with a PC glossy diffuser duly prewired connection having a nominal system lumen output of 1000 lumens at a minimum system efficacy of 115 lumen per watt and total power consumption 10/12 watt including driver. It has a rated system life time of 40000 burning hours at L70 and should have a colour temperature of 6500K, CRI>80, THD<10% and PF>0.95 complete all as specified and directed.
57S & F 10W LED, bulk head luminaire Energy saving new generation with opal diffuser having lumen output of 1100 lumens at a minimum system efficiency of 110 lumen per watt and total power consumption not more than 10 watt including driver. It has a rated system life time of 40000 burning hours at L70 and should have a colour temperature of 6500K including lamp including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed.
58S & F 36 watt Recess mounted deep drawn 2X2 feet CRCA housing having a nominal system lumen output of 3600 lumens at a minimum system efficiency of 115 lumen per watt and total power consumption not more than 36 watt including driver. It has a rated system life time of 40000 burning hours at L70 and should have a colour temperature of 6500K with higher power LED Seamless front frame with flat white hight transmission acrylic cover with built in PIR occupancy sensor offering flexibility of auto switching off when the space is not occupied all as specified and directed by Engr in charge.
59S & F LED wall bracket light asthetically designed with B22d & E27 lamp holder made up of Polycarbonate suitable for 9/10 W including suitable LED Bulb complete with all accessories internally pre-wired and including connecting up with twin core twisted flexiblecopper conductor cable with suitable size complete all as specified and directed. Make : Philips/Havells/Jaquar
60S & F LED building security Light fitting 35 watt, for opearting voltage between 110V to 320V system efficiency not less than 120 lumen / watt, PF-0.95 minimum, IP66 protection, 5700CCT(K), CRI between 80-85, confirming to LM79 and LM 80 standards or as per IS-16104:2012 and IS-16106:2012, for estimated life span of minimum 50,000 hrs consisting of high / low voltage cut off, maintenance free isolated Electronic driver circuits, Low THD, PMMA grade high quality Transmittance lens, Epoxy powder coated Die Cast Aluminium housing with LED street optics LENS for uniform light distribution, weather proof gasket for lamp & driver compartment, Heat resistance toughened UV stabilized glass fitted in cast aluminium housing with SS screws with IP 65/66 protection, complete all as specified and as directed by Engr-in-charge.
61Supply, installation, testing of SPN distribution board 2 way,single door, IP 43, as per IS 8623 including 100 Amps fully insulated copper bus bar, insulated neutral bar, earth bar, door earthing, reversible doors, PAN assembly for easy installation and also incoming and outgoing connections with suitable size of lugs/thimbles/glands including taking down existing unserviceable MCB/DBs including MCBs and making good the disturbed surfaces of wall/floor or ceiling to match with existing surface complete all as specified and directed.Note : The MCB shall be of same make as per distribution board
62Supply, installation, testing of SPN distribution board 4 way, double door, IP 43, as per IS 8623 including 100 Amps fully insulated copper bus bar, insulated neutral bar, earth bar, door earthing, reversible doors, PAN assembly for easy installation and also incoming and outgoing connections with suitable size of lugs/thimbles/glands including taking down existing unserviceable MCB/DBs including MCBs and making good the disturbed surfaces of wall/floor or ceiling to match with existing surface complete all as specified and directed.Note : The MCB shall be of same make as per distribution board
63Supply and Fix distribution board (DB), double door (CRCA sheet) dust and vermin proof SPN 8 way including 200 Amps rated copper busbar, neutral bar,internal earth bar and cable ties for cable management, reversible door forIP 43 & IP 54, IK 09 impact resistance, single pole and neutral 250 Volts, flush to wall including chases cutting in wall for fixing DB and making good distributed wall surfaces to match with existing specification complete all as specified and directed.DB shall be designed with provision for MCB SPN as incomer & MCB SP as outgoing as per requirement. Cost of the DBs will be without MCBs, and making good the disturbed surfaces of wall/floor or ceiling to match with existing surface complete all as specified and directed. Note - Rates are inclusive for flush(Concealed ) mounting of DB SPN Note : The MCB shall be of same make as per distribution board
64Supply and Fix distribution board (DB), double door (CRCA sheet) dust and vermin proof SPN 12 way including 200 Amps rated copper busbar, neutral bar,internal earth bar and cable ties for cable management, reversible door forIP 43 & IP 54, IK 09 impact resistance, single pole and neutral 250 Volts, flush to wall including chases cutting in wall for fixing DB and making good distributed wall surfaces to match with existing specification complete all as specified and directed.DB shall be designed with provision for MCB SPN as incomer & MCB SP as outgoing as per requirement. Cost of the DBs will be without MCBs, and making good the disturbed surfaces of wall/floor or ceiling to match with existing surface complete all as specified and directed. Note - Rates are inclusive for flush(Concealed ) mounting of DB SPN Note : The MCB shall be of same make as per distribution board
65Supply and fixing of sheet metal enclosures vertical distribution board VTPN, (MCCB DB) 4 ways, double door, 415 volts with 200 amps rated bus bar IP 43 protection, with shrouded neutral bar and insulated bus bar and earth link, with and including MCCB 4 pole thermal release type, 100 Amps, 16 KA as incomer and MCBs as out going complete with making suitable size of MS cabinet as per IS dully grouted on the wall (flush) with opening arrangement including making connections with suitable size of lugs/thimbles/glands and making good the disturbed surface matching with existing surface including taking down existing unserviciable MCCB/DBs including MCBs complete all as specified and directed.Note : The MCB shall be of same make as per distribution board
66S & F in repair MCB, 'C' Series, SP, 240 Volts, 06 to 32 Amps, 10KA capacity with all incoming/outgoing connections with proper size lugs including taking down old unserviceable one complete all as specified and directed.
67S & F in repair MCB, 'C' Series, SPN, 240 Volts, 25 to 32 Amps, 10KA capacity with all incoming/outgoing connections with proper size lugs including taking down old unserviceable one complete all as specified and directed.
68S & F in repair MCB, 'C' Series, SPN, 240 Volts, 40- 63 Amps, 10KA capacity all incoming/outgoing connections with proper size lugs including taking down old unserviceable one complete all as specified and directed.
69S & F in repair 415V, 10 KA 'C' curve miniature circuit breaker (MCB) of Triple pole and neutral and current carrying capacity 40 to 100 amps, in the MCB DB including taking down old unserviceable one with connection testing and commissionin complete all as specified and directed.
70M & L for Earthing complete with GI earth electrode plate of size 600x600x6mm thick, buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.50m below normal ground level, connected to GI wire 4mm dia as earth lead up to test point with suitable GI nuts/bolts and brazed properly up to main board including earth pit in cement concrete 1:2:4 type B-1 using 20mm graded stone aggregates, 40mm thick precast RCC cover in 1:2:4 reinforced with expanded metal (weight not less than 4 kg/sqm), and frame of angle iron 25x25x6mm with lugs 02 nos with 6mm dia MS bar handle made to shape, excavation and earth work in any type of soil and including light grade GI watering pipe 20mm bore with funnel and wire mesh and light grade GI earth wire protection pipe 15mm bore up to main board complete as shown in electrical plate no 3 of MES schedule Part-I, connected to earthing testing point and testing on completion complete all as specified and directed by Engr-in-charge.
71S & F in repair GI wire 4mm dia and fixing with proper clamp,saddles,nuts bolts,washers etc. properly and connected to pole, including taking down old unserviceable GI wire of any description complete all as specified and directed.
72S & F in repair GI Pipe light grade 15mm bore for protection of GI earth lead, including taking down old unsrviceable GI pipe of any description complete with all fittings all as specified and as directed.
73S & F in repair lamp holder, insulated body with back plate suitable for batten fittings including taking down old unserviceable one complete all as specified and directed.
74S & F in repair LED lamp 9 Watt self ballasted type with PBT body shell and DC Diffuser including taking down old unserviceable one complete all as specified and directed.
75S & F in repair LED tube light Inverter type with minium 4 hrs backup, batten (1.2M) made of extruded aluminum housing with a PC glossy diffuser duly prewired connection having a nominal system lumen output of 2000 lumens at a minimum system efficiency of 115 lumen per watt and total power consumption not more than 18/20 watt including driver. It has a rated system life time of 40000 burning hours at L70 and should have a colour temperature of 6500K, CRI>80, THD<10% and PF>0.95, including taking down old unserviceable one, complete all as specified and directed.
76S & F in repair energy efficient 18/20 watt (4.0 feet) LED tube light batten made of extruded aluminum housing with a PC glossy diffuser duly prewired connection having a nominal system lumen output of 2000 lumens at a minimum system efficacy of 115 lumen per watt and total power consumption 18/20 watt including driver. It has a rated system life time of 40000 burning hours at L70 and should have a colour temperature of 6500K, CRI>80, THD<10% and PF>0.95, including taking down old unserviceable LED light of any description, complete all as specified and directed.
77S & F in repair energy efficient 18/20 watt (4.0 feet) LED tube light batten made of extruded aluminum housing with a PC glossy diffuser duly prewired connection having a nominal system lumen output of 2000 lumens at a minimum system efficacy of 80 - 100lumen per watt and total power consumption 18/20 watt including driver. It has a rated system life time of 40000 burning hours at L70 and should have a colour temperature of 3000K (Warm White) CRI>80, THD<10% and PF>0.95, including taking down old unserviceable LED light of any description, complete all as specified and directed.
78S & F in repair energy efficient 10/12 watt (2.0 feet) LED tube light batten made of extruded aluminum housing with a PC glossy diffuser duly prewired connection having a nominal system lumen output of 1000 lumens at a minimum system efficacy of 115 lumen per watt and total power consumption 10/12 watt including driver. It has a rated system life time of 40000 burning hours at L70 and should have a colour temperature of 6500K, CRI>80, THD<10% and PF>0.95, including taking down old unserviceable LED light of any description complete all as specified and directed.
79S & F in repair energy efficient 10/12 watt (2.0 feet) LED tube light batten made of extruded aluminum housing with a PC glossy diffuser duly prewired connection having a nominal system lumen output of 1000 lumens at a minimum system efficacy of 80-95 lumen per watt and total power consumption 10/12 watt including driver. It has a rated system life time of 40000 burning hours at L70 and should have a colour temperature of 3000K, (Warm White) CRI>80, THD<10% and PF>0.95, including taking down old unserviceable LED light of any description complete all as specified and directed.
80S & F in repair 18/20 W surface and wall mounted LED batten with microwave motion technology made of aluminium housing integrated electronic driver, It has a rated system life time of 40000 burning hours at L70 and should have a colour temperature of 6500K, CRI>80, THD<10% and PF>0.95, including taking down old unserviceable LED light of any description complete all as specified and directed.
81S & F in repair 10W LED, bulk head luminaire Energy saving new generation with opal diffuser having lumen output of 1100 lumens at a minimum system efficiency of 110 lumen per watt and total power consumption not more than 10 watt including driver. It has a rated system life time of 40000 burning hours at L70 and should have a colour temperature of 6500K including lamp including connecting up with twin core twisted flexible copper conductor cable with suitable size size including taking down old unserviceable LED Bulk head of any description complete all as specified and directed.
82S & F in repair 36 watt Recess mounted deep drawn 2X2 feet CRCA housing having a nominal system lumen output of 3600 lumens at a minimum system efficiency of 115 lumen per watt and total power consumption not more than 36 watt including driver. It has a rated system life time of 40000 burning hours at L70 and should have a colour temperature of 6500K with higher power LED Seamless front frame with flat white hight transmission acrylic cover with built in PIR occupancy sensor offering flexibility of auto switching off when the space is not occupied including taking down old unserviceable recess light of any description complete all as specified and directed by Engr in charge.
83S & F in repair 36 watt Recess mounted deep drawn 2X2 feet CRCA housing having a nominal system lumen output of 3600 lumens at a minimum system efficiency of 115 lumen per watt and total power consumption not more than 36 watt including driver. It has a rated system life time of 40000 burning hours at L70 and should have a colour temperature of 3000K (Warm White colour) with higher power LED Seamless front frame with flat white hight transmission acrylic cover with built in PIR occupancy sensor offering flexibility of auto switching off when the space is not occupied including taking down old unserviceable recess light of any description complete all as specified and directed by Engr in charge.
84S & F in repair LED building security Light fitting 35 watt, for opearting voltage between 110V to 320V system efficiency not less than 120 lumen / watt, PF-0.95 minimum, IP66 protection, 5700CCT(K), CRI between 80-85, confirming to LM79 and LM 80 standards or as per IS-16104:2012 and IS-16106:2012, for estimated life span of minimum 50,000 hrs consisting of high / low voltage cut off, maintenance free isolated Electronic driver circuits, Low THD, PMMA grade high quality Transmittance lens, Epoxy powder coated Die Cast Aluminium housing with LED street optics LENS for uniform light distribution, weather proof gasket for lamp & driver compartment, Heat resistance toughened UV stabilized glass fitted in cast aluminium housing with SS screws with IP 65/66 protection, including taking down old unserviceable security light fitting of any description and in any position complete all as specified and as directed by Engr-in-charge.
85M&L in replacement for bracket made out of GI pipe 25mm dia medium grade, 1.2 mtr long bent to shape with welded MS flat 25 x 4 mm for mounting of fitting & MS flat iron clamps made out of 25mmX 4mm thick FI nuts, bolts painting with two coats of synthetic enamel paint over a red oxide primer complete all as directed by Engr-in-charge incl taking down old unsv bracket of any size all as directed by Engineer-in-Charge.
86S & F in repair LED wall bracket light asthetically designed with B22d & E27 lamp holder made up of Polycarbonate suitable for 9/10 W including suitable LED Bulb complete with all accessories internally pre-wired and including connecting up with twin core twisted flexiblecopper conductor cable with suitable size including disconnecting and taking down old unserviceable decorative light of any description complete all as specified and directed.
87S & F in repair post top lantern LED type 20 Watt 230 volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant including high voltage and short circuit protection IP 65, with necessary suitable fixing accessories /arrangements including disconnecting and taking down old unserviceable one complete all as specified and as directed.
88S & F in repair rigid non metallic medium white / ivory PVC casing caping medium grade ISI marked of size not less than 20 mm dia inclusive all fitting such as tee, bends, reducer, elbow, bell mouth, tube ends and all fixing accessories such as couplers lock, nuts, saddlers, fixed properly including taking down old unserviceable one complete all as specified and directed by the Engr-in-Charge.
89Supply and fixing of Tricolour flexible LED strip light length 18 mtrs length, SMD 5050, wattage 10-15W/m for mounting on existing pole comprising of high quality wheather proof minimum IP65 protection flexible LED strip capable of displaying saffron, white and green colours strip shall be suitable for outdoor use and with suitable controller for colour sequencing and uniform illumination including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed.
90S & F PVC duct cable tray PVC FRLS type size (60mmx45mm) along with mild steel screw of suitable size and length complete all as specified and directed by Engineer-in-charge.
91S & F PVC duct cable tray PVC FRLS type size (45mmx25mm) along with mild steel screw of suitable size and length complete all as specified and directed by Engineer-in-charge.
92Taking down carefully ceiling fans of 1200/1400mm sweep of any type or capacity from the height up to 6.0 mtr by disconnecting and insulating electric supply wire and dismantling the ceiling fans carefully for recognizing defects at site or depositing the same to MES store yard complete all as directed by Engineer in Charge. Note:- (i) Record of MES Number of ceiling fans shall be entered in a register / MB for further verification. (ii) Any damage or loss of fan during taking down shall be reiumburshed by the contractor at own cost.
93M&L for opening of ceiling fans of 1200/1400mm sweep for checking/assesing nature and details for repair/overhauling/ providing new lubricating, greasing in bearings and reassembling and testing of fans and refixing the ceiling to the position by providing nuts , bolts, locking bolts, blade screws, split pin, PVC connector, washers connecting up including provision of three core PVC insulated and unsheathed copper conductor cable of size 1.0 Sqmm from ceiling rose to connector to fan including complete all as directed by Engineer in Charge. Note:- (i) All major repair such as replacement of Bush/bearing/condensor etc shall be measured and paid seperetely under respective items all as specified and directed.(ii) Cost flexible connection wire as required will be measured and paid separately under respective items of this Schedule. Please Enable Macros to View BoQ information
94M&L for opening of ceiling fans of 1200/1400mm sweep for checking/assesing nature and details for repair/overhauling/ providing new lubricating, greasing in bearings and reassembling and testing of fans and refixing the ceiling to the position by providing nuts , bolts, locking bolts, blade screws, split pin, PVC connector, washers connecting up including provision of three core PVC insulated and unsheathed copper conductor cable of size 1.0 Sqmm from ceiling rose to connector to fan including complete all as directed by Engineer in Charge. Note:- (i) All major repair such as replacement of Bush/bearing/condensor etc shall be measured and paid seperetely under respective items all as specified and directed.(ii) Cost flexible connection wire as required will be measured and paid separately under respective items of this Schedule. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57199898
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 37.40 Lakhs
LAST DATE 15-09-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair/Maintenance Of Point Wiring Fixtures With Fittings & Sub Main Wiring,Mcb,Dbs,Ceiling Fan,Exhaust Fan,Bldg Security Lights And Other Connected Works To Various Md Accn And Certain Units And Repair/Maintenance Of Hot Water Apparatus(Geyser) Including Solar Water Heater,Ceiling Fans,Wall Mounted Fans,Air Circulator And Exhaust Fan And Connected Works At Out Pockets Under Ge Dinjan No.2
Basic Detail
Tender No 8957/E8
Bidding Type Tender
Location
City Tinsukia
State Assam
Key Dates
Publish Date 08 Sep 2026
Submission Date 15 Sep 2026
Open Date 22 Sep 2026
Finance
Tender Value 37.40 Lakhs
Tender Fee 500
EMD 75000
Exemption Available
Document List
515e746a-064d-4a4d-9686-5104700ac7fc.html
BOQ_881100.xls
Tender.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Sep 08, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 15, 2026
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 4 days
Sep 15, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 4 days
Sep 22, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 11 days