Housing Urban and Rular Development Government Departments Closing in 17 days TDR #57198812

Tender For Design, Supply, Installation, Testing And Commissioning Of Fire Fighting Works At Chief Engineer North Kashmir Office At Delina Baramulla.

Issued by Government Departments · Baramulla, Jammu and Kashmir
Tender Value
45.08 Lakhs
Estimated cost
Bid Submission
15 Sep 2026
17 days left
EMD
90160
Bank guarantee accepted
Document Fee
1100
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Baramulla → Jammu and Kashmir
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Design, Supply, Installation, Testing And Commissioning Of Fire Fighting Works At Chief Engineer North Kashmir Office At Delina Baramulla.

BOQ

Name of Work:- Design, Supply, Installation, Testing and Commissioning of Fire Fighting works at Chief Engineer North Kashmir office at Delina Baramulla.
Sl. No. Item Description
1PIPES & ACCESSORIESProviding laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required.150 mm. Dia
2Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges,tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
325 mm dia
480 mm dia
5100 mm dia
6150 mm dia
7200 mm dia(min wall Thickness 6.3 mm)
8Supplying and fixing single headed internalhydrant valve with instantaneous Gunmetal/ Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal / Stainless Steel cap and chain as required :Single headed Gunmetal:
9Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel,ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required :Single headed Gunmetal:
10Supplying and fixing orifice plate made out of 6 mm thick Stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.
11Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :Gun Metal:
12Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red,conforming to IS 884 complete with the following as required.20 mm nominal internal dia water hose thermoplastic(Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle.Drum and brackets for fixing the equipmets on wall.Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.30m:
13Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :
144 way - 150 mm dia M.S. Pipe
152 way - 100 mm dia M.S. Pipe
16Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shadeas required.
17Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :Gun metal:
18Providing and fixing Weather proof hose cabinets for yard and Internal hydrant fabricated from 16 g MS sheet with full glass door and locking arrangement, suitable to accommodate one hydrant valve, 2 nos.15m long hose, 1 No branch pipe and one fireman's axe. The cabinet shall be painted with one coat of primer and finished stove enamelled \\"Fire Red\\", \\"Fire Hose\\" written on front including suitably mounted on a raised masonry platform as required. (Approx 0.75mx0.6 mx 0.25 m).
19Providing and fixing standard fireman's axe with heavy insulated rubber handle conforming to IS: 926 complete.
20Supplying, Installation, Testing and Commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :(a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.(b) Suitable HP Squirrel cage induction motor, TEFC,synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-12615: 2018(c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.(d) Suitable cement concrete foundation duly plasteredwith anti vibration pads.1620 lpm at 70 m Head
21Supplying, installation, testing and commissioning of Diesel engine driven main fire pump confirming to S 12469:2019 suitable for automatic operation and consisting of following,complete in all respects, as required : (Diesel Driven Pump) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft,mechanical seal as required.Suitable HP, 1500 RPM water cooled with radiator,diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer,instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. 1620 lpm at 70 m Head
22Supplying, Installation, Testing and Commissioning ofElectric Driven pressurisation pump conforming to IS 12469:2019 suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump)Horizontal type, multistage, centrifugal pump of castiron body and bronze impeller with stainless steel shaft,mechanical seal as required. Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 12615: 2018. M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads.180 lpm at 70 m Head
23Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors,dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears andaccessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specificationwith following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply withenclosure protection class IP 42 as required :Incomings: 400A, 50kA 4 Pole MCCB, Ics=100% Icu ratingDigital Voltmeter 0-500V with selector switchAmmeter (0-630 A) with selector swtich & CTs etc.LED type RYB phase indicating lamps, ON, OFF, tripindicating lampsSet of Copper Bus Bar 500AmpsOutgoings:Note all the outgoing feeders for pumps should have digital ammeter wiith selectors sitches and LED Type ON OFF trip indicaing Lamps)Main Fire Pump200 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 75 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFFoperation.Jockey Pump100 A, 50kA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring Required for automatic operation, selector switch for local/ remote, auto/manual/OFF operation.Diesel Engine ControlControl for diesel engine comprising -Automatic/Manual selctor switch & 3 attemptsstarting device, timers and relays as required,push buttons, start/stop in manual modeIndicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter, All standard relays and accessories for automatic operation of diesel engine.System ControllerDesigning, Supply, Installation, Testing and commisssioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification.
24Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
25100mm dia
26150mm dia
27200mm dia
28Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required :
29150 mm dia
30Supplying, fixing, testing and commissioning of Dismantling Joint of PN 1.6 rating of Ductile Iron ISI marked complete with nuts, bolts, washers, gaskets of following sizes as required :
31150 mm dia
32Supply, installation, testing and commissioning of Rubber Expansion Joint, Rubber Bellows (Flexible coupling) with required flanges,nuts,bolts & accessories
33150 mm dia
34Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :
3580 mm dia
36100 mm dia
37150 mm dia
38Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm diaholes with stainless steel flange.
39150 mm dia
40Providing and fixing pressure switch with required fittings and accessories complete.
41Supply, installation, testing & commissioning of Gun Metal Fire brigade suction hose coupling (Draw-out Connection) with nut for female coupling as per IS:902-1974 complete with 100 mm dia. GI suction pipe and 100 mm dia. 1 No. CI foot valve flanged (to be connected to static water tank).
42Providing and fixing MS cabinet (to enclose above Draw-out/Fire brigade inlet connections) fabricated from 16g sheet with full front glass door and locking arrangement duly painted with one coat of primer and two or more coats of synthetic enamel paint of approved make and shade and suitably mounted on a raised masonry platform as required (Approx.0.6 m x 0.6 m x 0.45 m).
43Providing, fixing, testing and commissiong of double flanged vertical air vessel fabricated from 10mm MS plate with dished ends from 10mm MS plate, outside with one coat of primer and two coats of synthetic enamel paint of approved shade, complete with approved quality of pressure switches, pressure gauge and all other required accessories to operate commonly main fire pump, sprinkler pump and Jockey pump at drop of pressure, automatically at required pressure setting :Recommended dia. : 450mmHeight of shell : 2000mmWorking pressure : 5.5 kg/cm2 Test Pressure : 10 kg/cm2
44Supply, installation, testing & commissioning of pressure gauges with isolation cocks and chrome plated copper pipes as hydrant station to read pressure from 0-25 kg/cm2 complete and of dial dia 100-150 mm
45Providing and fixing brass/bronze lever operated ball valve of full flow with stainless steel ball (AISI 304 and spindle AISI 410) with setting and gland of superior quality having minimum working pressure of 20 kg/cm2.25 mm dia
46Supply and installation of Following Sizes of Puddle Flanges made out of high quality G.I Pipe.The puddle flange to be tested up to 25 bar water pressure and should work excellently on any weather conditions. (For Details Refer the Drawing)
47150 mm dia
48Supply and fixing of illuminated Fire exit signages. This sign may be used to Indicate all exits which can be used in the event of an emergency. It shall be accompanied: by an arrow as per IS-12349(1988) standards
49Supplying, installing and commissioning of ABC Powder 6 Kg Fire Extinguisher containing Mono Ammonium Phosphate Powder 50, Stored Pressure Type, Pressure Gauge, fittted with discharge hose, wall mounting bracket etc., Discharge Time less than 15 Secs, Controllable discharge mechanism, Range minimum 4 Meters, applicable on Class A,B,C and electrically started Fire, A Rating- 8A, B Rating 34B, Can Construction : Deep drawn & Co2 Mig welded, Valve Construction : Forging & Machining, Internal Coating of Can : Epoxy Powder coating, External Coating of Can : Epoxy Polyster Powder coating, Sheet metal thickness : 1.60MM, ISI approved as per IS:15683:2006
50Terrace Pump A. Supply Installation Testing and Commissioning of Electric Driven terrace pump conforming to IS 12469: 2019 suitable dor automatic operation and consisting of following complete in all respects (Terrace Pump)B. Horizontal Type multistage cntrifugal split casing pump of cast iron body & bronze impeller with stainless steel shaft mechanical seal as required.C. Suitable HP Squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz, AC Supply with IP55 class of protection for enclosure, horizontal foot mounted type with class F insulation conforming to IS-12615:2018D. M.S Fabricated common base plate, coupling, Coupling Guard Foundation bolts etc as required.E. Suitable Cement concrete foundation duly plastered and with anti vibration pads450 lpm at 35 m head
51Supply and instalintion of CO2 fire extinguishers consisting of Aluminium eylindricaln body, (besring IS: 15683 marking) squeeze lever discharge valve fitted with internal discharge tube, high pressure discharge hose, discharge nozzle, suspension bracker, confirming to IS 934 fitished extemally with red enamel paint and lixed to wall with brackets with rawl plug/dash fasteners complete with internal charge. The Carbon-di-oxide filled in the cylinder must be as per IS 15222.Capacity 4.5 kg (I.S.I marked)
52Supply and Installationm of Wet Chemical 6 liter K Type Fire Extinguisher as per IS Standards
53Supplying and Fixing Heavy Duty Copper/Aluminium armored cable 1.1 KVA grade including necessary support clamps at ceiling level and connection legs complete in all respects
543.5 C X 95 Sq.mm A2XFY
553.5 C X 25 Sq.mm A2XFY
5612 C X 2.5 Sq.mm Copper Armoured
573 C X 2.5 Sq.mm Copper Armoured
584 C X 2.5 Sq.mm Copper Armoured
59Supply and Making end Termination with Brass Compression Gland and Aluminium/Copper Lugs for the Following Sizes of PVC insulated and PVC Sheathed/XLPE Aluminium Conductor Cable of 1.1 KV Grade as Required.
603½ X 95 sq. mm (45mm)
613.5 C X 25 Sq.mm A2XFY
6212 C X 2.5 Sq.mm Copper Armoured
633 C X 2.5 Sq.mm Copper Armoured
644 C X 2.5 Sq.mm Copper Armoured
65Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
66150mm (W) x 50 mm (H) x 2mm thick cable tray perforated type
67Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
68Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
69Providing and fixing of polyethlene Six layers (Minimum) water tank on terrace of Caopcity 2000 Leters IS:12701
70Supplying and Fixing of Rockwool insulation of 75 mm thickness minimum 30-50kg/m3 density with thermal conductivity of min K= 0.04 W/mK at minus 25 degree celcius.
71Providing of interconnections between 3 Nos of water tanks at the bottom so that all the tanks act as onereserviour by way of fixing tank nipple ball valve of rewquired dia and other accessories required to complete the Job
72Electric PanelFabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors,dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required :Incomings: 63A, 25KA 4 Pole MCCB, Ics=100% Icu rating Digital Voltmeter 0-500V with selector switch Digital Ammeter (0-100 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 100AmpsOutgoings:24-32 A, 50kA MPCB, with suitable HP fully automatic star/Delta Starter with overload protection current sensing type single phase preventer complete with all accessories and internal wiring required for automatic operation selector switch for l;ocal/remote auto/manual/OFF operation Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57198812
AUTHORITY Government Departments
TENDER VALUE 45.08 Lakhs
LAST DATE 15-09-2026
Authority
Authority Name Public Works Department
Work Description Tender for Design, Supply, Installation, Testing And Commissioning Of Fire Fighting Works At Chief Engineer North Kashmir Office At Delina Baramulla.
Basic Detail
Tender No RnB/MDNK/2026-27/NIT/13
Bidding Type Tender
Location
City Baramulla
State Jammu and Kashmir
Key Dates
Publish Date 25 Aug 2026
Submission Date 15 Sep 2026
Open Date 16 Sep 2026
Finance
Tender Value 45.08 Lakhs
Tender Fee 1100
EMD 90160
Exemption Available
Document List
9d7e9e15-deae-463f-9cbb-32e69e2523e3.html
BOQ_1080223.xls
Tendernotice_1 (12).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 25, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 15, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 17 days
Sep 16, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 18 days

Tender Documents

Download All (ZIP) ↓
html

9d7e9e15-deae-463f-9cbb-32e69e2523e3.html

xls

BOQ_1080223.xls

pdf

Tendernotice_1 (12).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail