Tender For Repairs/ Renewal Of Apfc Panels, Lt Feeder Pillers, Lt Switch Gears And Allied Works At Div Unit Areas, Assay Lines, Map Jco/Or Accn, Medows Line, Thimmaiah Line, Robert Road & Robert Line, Asha Colony, Bso North And Adjoining Area Under A
Tender Overview
Project Description
Tender for Repairs/ Renewal Of Apfc Panels, Lt Feeder Pillers, Lt Switch Gears And Allied Works At Div Unit Areas, Assay Lines, Map Jco/Or Accn, Medows Line, Thimmaiah Line, Robert Road & Robert Line, Asha Colony, Bso North And Adjoining Area Under Age Em Ii Of Ge (Utility) Secunderabad
BOQ
| Sl. No. | Item Description |
| 1 | Repair/maintenance, excluding major spares but including regular maintenance of the Automatic Power factor correction panel capacity up to 200 KVARs and up to 12 stages installed at various locations at Garden cell area including carrying out complete maintenance/repairs as required of all the sub systems viz. based control panels, feeder pillar, APFC relay, Power capacitor bank, Power contactors, Control wiring, Monitoring CT, MCBs/MCCBs for isolation (with all the accessories) any breakdown maintenance and replacement of unserviceable parts, refixing of old serviceable parts/new parts if any project completion and troubleshooting responsibility also lies with contractor including following provisions complete all as specified and directed. Notes:-(i) Rate quoted by tenderer is deemed to be inclusive of checking of system fortnightly, replacement of defective control wiring, small part such as Push button, lugs any auxiliary contatct, auto selector switch etc and necessary servicing repair by expert technician and register will be maintained for the same. (ii) The scope of work includes the labour charges required for removing, repairing, refixing, carrying out electrical termination, capacitors bank, APFC relay, power contactor, control CT, MCBs/MCCB and fixing/installing/testing and commissioning the complete system. (iii) capacitors bank, APFC relay, power contactor, control CT, MCBs/MCCB shall be measured and paid separately |
| 2 | Supply and fix power contactor suitable size having capacity of rated Amps 4 pole 2NO+2NC complete all as specified and directed. |
| 3 | Supply and fix in replacement of power factor correction capacitor, 5 KVAR, heavy duty 440 volts 50 Hz complete including taking down old unserviceable capacitor complete all as specified and directed. |
| 4 | All as per item No 3.00 here-in-before but 10 KVAR Capacitor Bank |
| 5 | All as per item No 3.00 here-in-before but 15 KVAR Capacitor Bank |
| 6 | All as per item No 3.00 here-in-before but 20 KVAR Capacitor Bank |
| 7 | All as per item No 3.00 here-in-before but 25 KVAR Capacitor Bank |
| 8 | Supply and fixing in replacement of capacitor duty contactor suitable for rating 5 kvar, 50Hz, 440v, 3-ph, 3-pole in existing panel including necessary wiring & misc. accessories for satisfactory completion of job taking down old unserviceable one complete all as directed by Engineer-in-Charge. |
| 9 | All as per item No 8.00 above but 10 KVAR capacitor duty contactor |
| 10 | All as per item No 8.00 here-in-before but 15 KVAR capacitor duty contactor |
| 11 | All as per item No 8.00 here-in-before but 20 KVAR capacitor duty contactor |
| 12 | All as per item No 8.00 here-in-before but 25 KVAR capacitor duty contactor |
| 13 | Supply & Fixing in replacement of Auto/Manual selector switch and indicating lampsin existing panel including necessary wiring & misc. accessories for satisfactory completion of job taking down old unserviceable one complete all as directed by Engineer-in-Charge. |
| 14 | Supply, installation, testing and commissioning of single-line LED digital panel meter in replacement of existing defective meter, suitable for existing apfc panel with required accuracy, capable of displaying required electrical parameters (Voltage / Current / Frequency as applicable), complete with necessary wiring modifications, termination, fixing accessories, mounting hardware, and calibration all as specified and directed |
| 15 | Supply, installation, testing and commissioning of Power Factor Controller (APFC relay) with CT sensing in replacement of existing defective unit, suitable for 415V, 50Hz, 3-phase system, having required number of stages (6/8/10 as per existing panel), with auto configuration, programmable switching sequence, alarm indications, and LED/LCD display. |
| 16 | Supply & Replace in replacement MCCB along with both side spreader link and nut bolts of appropriate size in existing LT Panel box / Feeder Pillar boxes (KIOSK), in MCCB DBs of capacity 160 Amps, 3 Pole, 36 KA, 415 Volt including disconnecting/taking out existing old unsv/burned MCCB complete all as specified and directed. |
| 17 | All as per item No 16.00 but for 63 Amps 25 KA |
| 18 | S&F in replacement MCB, TP 25-63 Amps, 'C' Curve with breaking capacity 10KA, including disconnecting/taking out existing old unsv/burned Isolator complete all as specified and directed. |
| 19 | S&F in replacement MCB, SPN 32 Amps, 'C' Curve with breaking capacity 10KA, including disconnecting/taking out existing old unsv/burned Isolator complete all as specified and directed. |
| 20 | M& L in repairs Advance Maintenance Free G.I. SAFE EARTHING Electrode with PIPE of not less than 50 mm outer dia) and two meter length, The electrode should be of galvanised (80 -100 micron) along with earth lead as Galvanised steel strip of size 32 X6 mm and length of 7.5 m . The GI Electrode shall be pre-filled with Crystalline Conductive Material (CCM) . The GI electrode shall be surrounded with 25 kg Backfill compound to provide maximum contact between the electrode and Back Fill Compound. Connected to earthing test point including excavation, earth work, PCC pit, RCC cover 50 mm thick, lifting rod and testing on completion, complete all as specified and directed.Make: ASHLOK/GRAVIN/TRUE POWER/JVM |
| 21 | S&F in replacement of Galvanised Iron Strip 32x6mm with Saddles and fixing Screws for Roof/Earth Conductors and Down Conductors above Ground including taking down unserviceable Strip, complete all as specified and as directed.NOTE : All Joints should be joined by Brazing or by using of nuts and bolts& washers. |
| 22 | M&L in repairs Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size Complete all as specified and as directed |
| 23 | Supply, fixing, connecting and commissioning and testing of outdoor type (automatic and manual operation) power factor improvement panel of capacity 120 Kvar including interconnection with LT panel with appropriate size of electric cable for transformer (Outdoor/Indoor) type panel factory made, weather proof, dust and vermin proof suitable for 1100 V/440 V grade 3 phase 50 HZ AC supply floor mounted, fabricated with suitable thickness CRCA sheet and having four Nos angle iron legs made out of 50 x 50 x 6mm 90 cm long angle iron below frame with front door and Side/Back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 sq mm / extension strips and connected with suitable size thimbles, lugs duly painted with siemens grey epoxy powder coating after suitable chemical treatment, legs duly embedded in ground up to 45 Cms in PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting, with required sheet metal enclosures, thimbles with on line monitoring of Power Factor on web based application as specified and directed by Engr-in-Charge. |
| 24 | Incoming feeder:- A. Incomer MCCB 160- Amp, Three Pole, Thermal based release with adjustable O/L, Adj S/C Setting Front Face, 36 KA rupturing capacity, Ics=100%Icu, Isolation with Positive Break Indication with Double Break Contacts, Standard Extended Rotary Handle, Spreaders, Phase Barrier.- 1 No B.Metering Section- Digital Ammeter (0-150)Amps, digital Volt Meter (0-500)Volts, RYB Indicating Lamps, 1 Set Control fuses, CTs. 3 C. Insulated Busbar of Aluminium of 200A Capacity for 3 phase, fixed on Insulators, Busbar Should be PVC Sleeved with red. Yellow. Blue Colour, Busbar Support should be of smc/dmc - 1 set. D. Multi 10 Step 440V, 5A (144 x 144) microprocessor based power factor controller provided in the command module for target power factor setting, automatic adjustment of dead bank ratio, digital power factor display. |
| 25 | Outgoing feeder :- E. Accessories for 5 KVAR heavy duty box type Capacitor Bank - 4 Nos :- Capacitor Duty Contactor 10 kvar with Damping Resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 20 A having breaking capacity 10 KA with std. duty capacitor on indicators and selector switch. F.Accessories for 10 KVAR heavy duty box type Capacitor Bank - 3 Nos :- Capacitor Duty Contactor 10 kvar with Damping Resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 20 A having breaking capacity 10 KA with std. duty capacitor on indicators and selector switch. F. G.Accessories for 20 KVAR heavy duty box type Capacitor Bank - 1Nos :- Capacitor Duty Contactor 20 kvar with Damping Resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 63 A having breaking capacity 10 KA with std. duty capacitor on indicators and selector switch. H. Accessories for 25 KVAR heavy duty box type Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 20 kvar with Damping Resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 63 A having breaking capacity 10 KA with std. duty capacitor on indicators and selector switch. I. Ventilating fans of required size to dissipate the heat liberated by capacitor unites complete with automatic switching on/off of fans depending upon the temperature of the pane; 230vac 1500rpm, 160cu.m/h flying leads J. 7 Stpes Automatic Power Factor controller steps Relay Micro processor based for switchting ON and OFF of capacitors to Display of voltage, current, Active power, apparent Power display of COS Ø, THD voltage, THD current, alarm indication for defective step, low power factor and access temperature. The relay having volt free c/o contact, automatic detection and uses of optimum capacitor capable of 4 Quadrant operation and any phase offset requirement. Switching program :LIFO combi Filter, manual mode built in under and over voltage release with auto reset large voltage input band of 90V to 440 volt, 45 to 65 HZ, current measuring 10MA-5A suitable for CT x/1A and/5A Commissiong without additional setting and programming. Three decimal power reading .Phasing out of fault capacitor bank Automatically . K. All accessories prewired with suitable size copper Wire with stand high temperature, housed in cubical panel made out of 3.15mm thick CRCA Sheet factory made duly powder coated front and rear door open able with locking arrangement complete with foundation as required or recommended by manufacturer. Note: APFC Panel shall be manufactured by original manufacturer only. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. |
| 26 | Supply, fixing, connecting and commissioning and testing of outdoor type (automatic and manual operation) power factor improvement panel of capacity 80 Kvar including interconnection with LT panel with appropriate size of electric cable for transformer (Outdoor/Indoor) type panel factory made, weather proof, dust and vermin proof suitable for 1100 V/440 V grade 3 phase 50 HZ AC supply floor mounted, fabricated out of 3.15mm thick CRCA sheet and having four Nos angle iron legs made out of 50 x 50 x 6mm 90 cm long angle iron below frame with front door and Side/Back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 sq mm / extension strips and connected with suitable size thimbles, lugs duly painted with siemens grey epoxy powder coating after suitable chemical treatment, legs duly embedded in ground up to 45 Cms in PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting, with required sheet metal enclosures, thimbles with on line monitoring of Power Factor on web based application as specified and directed by Engr-in-Charge. |
| 27 | Incoming feeder:- |
| 28 | A. Incomer MCCB 160- Amp, Three Pole, Thermal based release with adjustable O/L, Adj S/C Setting Front Face, 36 KA rupturing capacity, Ics=100%Icu, Isolation with Positive Break Indication with Double Break Contacts, Standard Extended Rotary Handle, Spreaders, Phase Barrier.- 1 No |
| 29 | B.Metering Section- Digital Ammeter (0-150)Amps, digital Volt Meter (0-500)Volts, RYB Indicating Lamps, 1 Set Control fuses, CTs. 3 |
| 30 | C. Insulated Busbar of Aluminium of 150A Capacity for 3 phase,, fixed on Insulators, Busbar Should be PVC Sleeved with red. Yellow. Blue Colour, Busbar Support should be of smc/dmc - 1 set. |
| 31 | D. Multi 10 Step 440V, 5A (144 x 144) microprocessor based power factor controller provided in the command module for target power factor setting, automatic adjustment of dead bank ratio, digital power factor display. |
| 32 | Outgoing feeder :- |
| 33 | E. Accessories for 1 KVAR heavy duty box type Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 1 kvar with Damping Resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 10 A having breaking capacity 10 KA with std. duty capacitor, on indicators and selector switch. |
| 34 | F. Accessories for 2 KVAR heavy duty box type Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 2 kvar with Damping Resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 10 A having breaking capacity 10 KA with std. duty capacitor on indicators and selector switch. |
| 35 | G. Accessories for 5 KVAR heavy duty box type Capacitor Bank - 3 Nos :- Capacitor Duty Contactor 5 kvar with Damping Resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 10 A having breaking capacity 10 KA with std. duty capacitor on indicators and selector switch. |
| 36 | H. Accessories for 10 KVAR heavy duty box type Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 10 kvar with Damping Resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 20 A having breaking capacity 10 KA with std. duty capacitor on indicators and selector switch. |
| 37 | J. Accessories for 20 KVAR heavy duty box type Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 20 kvar with Damping Resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 63 A having breaking capacity 10 KA with std. duty capacitor on indicators and selector switch. |
| 38 | K. Ventilating fans of required size to dissipate the heat liberated by capacitor unites complete with automatic switching on/off of fans depending upon the temperature of the pane; 230vac 1500rpm, 160cu.m/h flying leads |
| 39 | L. 10 Stpes Automatic Power Factor controller steps Relay Micro processor based for switchting ON and OFF of capacitors to Display of voltage, current, Active power, apparent Power display of COS Ø, THD voltage, THD current, alarm indication for defective step, low power factor and access temperature. The relay having volt free c/o contact, automatic detection and uses of optimum capacitor capable of 4 Quadrant operation and any phase offset requirement. Switching program :LIFO combi Filter, manual mode built in under and over voltage release with auto reset large voltage input band of 90V to 440 volt, 45 to 65 HZ, current measuring 10MA-5A suitable for CT x/1A and/5A Commissiong without additional setting and programming. Three decimal power reading .Phasing out of fault capacitor bank Automatically . |
| 40 | M. All accessories prewired with suitable size copper Wire with stand high temperature, housed in cubical panel made out of 3.15mm thick CRCA Sheet factory made duly powder coated front and rear door open able with locking arrangement complete with foundation as required or recommended by manufacturer. Note: APFC Panel shall be manufactured by original manufacturer only. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. |
| 41 | Supply, fixing, connecting and commissioning and testing of outdoor type (automatic and manual operation) power factor improvement panel of capacity 70 Kvar including interconnection with LT panel with appropriate size of electric cable for transformer (Outdoor/Indoor) type panel factory made, weather proof, dust and vermin proof suitable for 1100 V/440 V grade 3 phase 50 HZ AC supply floor mounted, fabricated out of 3.15mm thick CRCA sheet and having four Nos angle iron legs made out of 50 x 50 x 6mm 90 cm long angle iron below frame with front door and Side/Back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 sq mm / extension strips and connected with suitable size thimbles, lugs duly painted with siemens grey epoxy powder coating after suitable chemical treatment, legs duly embedded in ground up to 45 Cms in PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting, with required sheet metal enclosures, thimbles with on line monitoring of Power Factor on web based application as specified and directed by Engr-in-Charge. |
| 42 | Incoming feeder:- |
| 43 | A. Incomer MCCB 160- Amp, Three Pole, Thermal based release with adjustable O/L, Adj S/C Setting Front Face, 36 KA rupturing capacity, Ics=100%Icu, Isolation with Positive Break Indication with Double Break Contacts, Standard Extended Rotary Handle, Spreaders, Phase Barrier.- 1 No |
| 44 | B.Metering Section- Digital Ammeter (0-150)Amps, digital Volt Meter (0-500)Volts, RYB Indicating Lamps, 1 Set Control fuses, CTs. 3 |
| 45 | C. Insulated Busbar of Aluminium of 150A Capacity for 3 phase,, fixed on Insulators, Busbar Should be PVC Sleeved with red. Yellow. Blue Colour, Busbar Support should be of smc/dmc - 1 set. |
| 46 | D. Multi 10 Step 440V, 5A (144 x 144) microprocessor based power factor controller provided in the command module for target power factor setting, automatic adjustment of dead bank ratio, digital power factor display. |
| 47 | Outgoing feeder :- |
| 48 | E. Accessories for 1 KVAR heavy duty box type Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 1 kvar with Damping Resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 10 A having breaking capacity 10 KA with std. duty capacitor, on indicators and selector switch. |
| 49 | F. Accessories for 2 KVAR heavy duty box type Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 2 kvar with Damping Resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 10 A having breaking capacity 10 KA with std. duty capacitor on indicators and selector switch. |
| 50 | G. Accessories for 5 KVAR heavy duty box type Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 5 kvar with Damping Resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 10 A having breaking capacity 10 KA with std. duty capacitor on indicators and selector switch. |
| 51 | H. Accessories for 10 KVAR heavy duty box type Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 10 kvar with Damping Resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 20 A having breaking capacity 10 KA with std. duty capacitor on indicators and selector switch. |
| 52 | J. Accessories for 20 KVAR heavy duty box type Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 20 kvar with Damping Resistors which limits inrush current 440 volt, 3phase, 50 hz, coil-220vac, MCB TP 63 A having breaking capacity 10 KA with std. duty capacitor on indicators and selector switch. |
| 53 | K. Ventilating fans of required size to dissipate the heat liberated by capacitor unites complete with automatic switching on/off of fans depending upon the temperature of the pane; 230vac 1500rpm, 160cu.m/h flying leads |
| 54 | L. 8 Stpes Automatic Power Factor controller steps Relay Micro processor based for switchting ON and OFF of capacitors to Display of voltage, current, Active power, apparent Power display of COS Ø, THD voltage, THD current, alarm indication for defective step, low power factor and access temperature. The relay having volt free c/o contact, automatic detection and uses of optimum capacitor capable of 4 Quadrant operation and any phase offset requirement. Switching program :LIFO combi Filter, manual mode built in under and over voltage release with auto reset large voltage input band of 90V to 440 volt, 45 to 65 HZ, current measuring 10MA-5A suitable for CT x/1A and/5A Commissiong without additional setting and programming. Three decimal power reading .Phasing out of fault capacitor bank Automatically . |
| 55 | M. All accessories prewired with suitable size copper Wire with stand high temperature, housed in cubical panel made out of 3.15 mm thick CRCA Sheet factory made duly powder coated front and rear door open able with locking arrangement complete with foundation as required or recommended by manufacturer. Note: APFC Panel shall be manufactured by original manufacturer only. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. |
| 56 | M&L in replacement for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area laid in trenches / duct or fixed to wall / passing through pipe on pole with suitable size cable glands, crimping type cable lugs for stranded aluminium conductor of following sizes complete all as specified and directed :- 4C X 25 Sqmm |
| 57 | All as per item No 26.00 above 3.5 Core X 35 Sqmm |
| 58 | All as per item No 26.00 above 3.5 Core X 50 Sqmm |
| 59 | All as per item No 26.00 above 3.5 Core X 70 Sqmm |
| 60 | All as per item No 26.00 above 3.5 Core X 95 Sqmm |
| 61 | All as per item No 26.00 above 3.5 Core X 120 Sqmm |
| 62 | All as per item No 26.00 above 3.5 Core 150 Sqmm |
| 63 | All as per item No 26.00 above 3.5 Core 185 Sqmm |
| 64 | All as per item No 26.00 above 3.5 Core 240 Sqmm |
| 65 | Excavation in trenches, n exc 1.5 m wide and n exc 1.5 m in depth, for foundation of PCC/Steel pole, laying of cable in trenches etc and getting out in hard / dense soil complete all as specified and directed. |
| 66 | Supplying and laying of following size DWC HDPE pipe for cable protection ISI marked along with all accessories conforming to IS 16205, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. Up to 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 67 | All as per item No 36.00 above. but 125mm dia (OD-120 mm & ID- 102 mm nominal) |
| 68 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm in soils complete all as specified and directed. |
| 69 | Removing excavated material (soils) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed. |
| 70 | Supply and fix aluminium lugs of following sizes:16 to 25 Sqmm Size |
| 71 | All as per item No 40.00 above 35 to 50 Sqmm Size |
| 72 | All as per item No 40.00 above 70 to 95 Sqmm Size |
| 73 | All as per item No 40.00 above120 to 150 Sqmm Size |
| 74 | All as per item No 40.00 above185 to 240 Sqmm Size. |
| 75 | Supply, installation, testing and commissioning of factory-made outdoor LT feeder panel, cubicle type, fabricated from CRCA sheet of suitable thickness and size, complete with vermin-proof provided with aluminium bus bars of adequate rating for 3-phase and half neutral, with neutral identified by colour-coded heat shrinkable PVC sleeves with necessary supports, angle iron framework with stand, proper locking arrangements, and painted with one coat of red oxide primer and two coats of powder coted paints. All internal wiring carried out using suitable size copper conductors with necessary accessories, mounted on proper insulators, and enclosed within a dedicated bus bar chamber and panel equipped with digital voltmeter and ammeter with selector switch, current transformers (CTs) of appropriate ratio, and pilot indication lamps complete along with provision for cable entry and exit for all incoming and outgoing cable glands incl PCC foundation etc complete testing and commissioning complete and consisting Incoming:(a) MCCB 4 pole, 400 Amp, 415 Volts 36KA - 01 No Outgoings: (b) MCCB 4 pole, 200 Amp, 415 Volts 36KA - 02 Nos (c) MCCB 4 pole, 100 Amp, 415 Volts 25KA - 03 Nos (d) MCCB 4 pole, 63 Amp, 415 Volts 16KA - 02 Nos(e) Indicating lamps (set 03 Nos) - 01 set (R, Y & B)(f) Digital Voltmeter, Ammeter three phases including suitable CTs of ratio with selector switch. Note: (a) All existing incoming and out going cables are to be connected to the above panel with proper lugs glands nuts, bolts etc the cost of work is deemed to be included in the above item.(b) The cost shall also be include the breaking of floors/walls etc including digging of trenches for removing of cables of loops and connecting to the new panel boards and making good the disturbed surfaces to match with the existing surfaces. |
| 76 | Supply, lay, commissioning and testing of cable jointing Kit Heat shrinkable type for 1100 V grade cable for straight through joint with jointing material and accessories suitable for LT UG cable of size 16 to 50 Sqmm, 3.5 Core complete all as specified and directed. |
| 77 | All as per item No 46.00 above but suitable for aluminium conductor cable of size from 70 sqmm, 3.5 Core to 95 Sqmm, 3.5 Core |
| 78 | All as per item No 46.00 above but suitable for aluminium conductor cable of size from 120 sqmm, 3.5 Core to 150 Sqmm, 3.5 Core |
| 79 | All as per item No 46.00 above but suitable for aluminium conductor cable of size from 185 sqmm, 3.5 Core to 240 Sqmm, 3.5 Core |
| 80 | Supply, lay, commissioning and testing of cable jointing Kit for 1100 V grade cable for outdoor End termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 16 to 50 Sqmm, complete all as specified and directed. |
| 81 | All as per item No 46.00 above but suitable for aluminium conductor cable of size from 70 sqmm, 3.5 Core to 95 Sqmm, 3.5 Core |
| 82 | All as per item No 46.00 above but suitable for aluminium conductor cable of size from 120 sqmm, 3.5 Core to 150 Sqmm, 3.5 Core |
| 83 | All as per item No 46.00 above but suitable for aluminium conductor cable of size from 185 sqmm, 3.5 Core to 250 Sqmm, 3.5 Core |
| 84 | Cutting the existing road/PCC surface straight by manual, depth and width not less than 1 mtr below ground level for passing of underground cable and filling back with excavated soil up to 75% road portion and 25% shall be made with cement concrete 1:2:4 (using 20 mm graded aggregate stone complete all as specified and directed. |
| 85 | Supply & lay Galvanised in repairs Iron tubing 40 mm bore, light grade in protection of cable at road crossing/hard standing/pole protection fixed with MS clamps of size 40 X 4 mm, nut bolts and washer as per site requirement including taking down old unserviceable pipes complete all as specified and directed. |
| 86 | Supply & lay Galvanised in repairs Iron tubing 50 mm bore, light grade in protection of cable at road crossing/hard standing/pole protection fixed with MS clamps of size 40 X 4 mm, nut bolts and washer as per site requirement including taking down old unserviceable pipes complete all as specified and directed. |
| 87 | Trimming/pruning and removing of tree branches or any other foreign objects from HT/LT over head conductor and clearing the OH Line of any type and size for one span of any length in 2 way /4 way/6 way conductor system. Notes:(i) Insulators of any type, connectors and ACSR conductor of any size required at site will be measured and paid separately under relevant item of this schedule. (ii) The contractor is responsible for provision of Necessary T & P including crane and safety equipments to complete the job. |
| 88 | Cutting unaxious green growth and grass by manual labour or by machine at all 11 KV Electric Installation premises/around 2/4 Pole structure/along the boundary fencing and removing rubbish from the site of work complete all as specified and directed. |
| 89 | Supply and fixing of LT heat shrinkable sleeves 25mm dia 2mm thick made of silicon colour Red on detriorate insulation of LT cables / OH conductors complete all as directed. |
| 90 | Supply and fixing of LT heat shrinkable sleeves 25mm dia 2mm thick made of silicon colour Yellow on detriorate insulation of LT cables / OH conductors complete all as directed. |
| 91 | Supply and fixing of LT heat shrinkable sleeves 25mm dia 2mm thick made of silicon colour Blue on detriorate insulation of LT cables / OH conductors complete all as directed. |
| 92 | Supply and fixing of LT heat shrinkable sleeves 25mm dia 2mm thick made of silicon colour Black on detriorate insulation of LT cables / OH conductors complete all as directed. |
| 93 | M&L for cleaning and painting APFC/LT panel boards of any size thoroughly with necessary cleaning agent including scrapping up of old corroded paint dirt / rust carefully and applying two coats of synthetic enamel paint OVER A COAR OF RED OXIDE PRIMER COMPLETE all as specified and directed. |
| 94 | Supply, fabrication, installation, and commissioning of a retro-reflective glow sign board for Complaint cell and electrical installations with respective rating and Area, complete in all respects and as specified and directed by the Engineer-in-Charge. The work comprises providing a double-sided sign board of size 2000 mm × 1500 mm made of 2 mm thick Aluminium Composite Panel with 2 mm aluminium skin, incorporating High-Intensity Prismatic Type IV retro-reflective sheeting conforming to IRC:67–2012, with a green background and white computerized cut vinyl reflective lettering as approved by the Engineer-in-Charge, designed to reflect light when illuminated by external sources such as vehicle headlights. The sign board shall be supported on two 40 mm diameter mild steel (MS) pipes of 3 mm thickness conforming to IS:1239, fixed at a height of 3.5 m above ground level, complete with base plates of size 150 mm × 150 mm × 6 mm and anchor bolts. The MS members shall be finished with two coats of anti-corrosive primer followed by two coats of synthetic enamel paint in green colour. The work includes providing PCC M15 (1:2:4) foundations for each pole measuring 0.40 m × 0.40 m × 0.60 m, including excavation, reinforcement with four numbers of 8 mm diameter MS bars conforming to IS:432, cantering, formwork, backfilling, and curing. The sign board shall be securely fixed using stainless steel bolts, nuts, and washers (M10) conforming to IS:1367. The job includes all labour, materials, tools, plants, transportation, alignment, levelling, erection, and finishing, complete in accordance with relevant IS standards, IRC specifications, MES practices, and as directed by the Engineer-in-Charge. |
| 95 | Supply & Replace MCCB along with both side spreader link and nut bolts of appropriate size (Conforms to IEC:60947-II/ IS:13947-II) in existing LT Panel box/ Feeder Pillar boxes (KIOSK), in MCCB DBs of capacity 630 Amps, 4 Pole, 50 KA, 415 Volt including disconnecting/ taking out existing old unsv/ burned MCCB complete all as specified and directed. |
| 96 | All as per item No 65.00 above but suitable for 250 Amps 36 KA |
| 97 | All as per item No 65.00 above but suitable for 200 Amps 36 KA |
| 98 | All as per item No 65.00 above but suitable for 160 Amps 25 KA |
| 99 | All as per item No 65.00 above but suitable for 100 Amps 25 KA |
| 100 | All as per item No 65.00 above but suitable for 63 Amps 16 KA Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
TodayBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 21 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 28 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender