Tender For Supplying, Installation, Testing And Commissioning Of 11Kv Substation With Standby Transformer Near Chemical Department Pilot Plant Along With Supplying And Laying Of L.T Cables From 11Kv Substation (Pilot Plant Chemical Department To Main
Tender Overview
Project Description
Tender for Supplying, Installation, Testing And Commissioning Of 11Kv Substation With Standby Transformer Near Chemical Department Pilot Plant Along With Supplying And Laying Of L.T Cables From 11Kv Substation (Pilot Plant Chemical Department To Main Library) Along With Allied Equipments In P.U C Us, Sector - 14, Chandigarh.
BOQ
| Sl. No. | Item Description |
| 1 | Supplying and installaton following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required. |
| 2 | 300 mm width X 50 mm depth X 1.6 mm thickness (DSR ref. 4.1.4) |
| 3 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required (DSR ref. 5.4) |
| 4 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required (DSR ref. 5.15) |
| 5 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required |
| 6 | 120 mm dia (OD-120 mm & ID-103 mm nominal) (DSR ref. 15.16.3) |
| 7 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required |
| 8 | 70/ 95 sq.mm (DSR ref. 23.4.1) |
| 9 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required |
| 10 | 70/ 95 sqmm (DSR ref. 23.5.1) |
| 11 | Supply, Installation, Testing and Commissioning of 11/0.433, 3 Phase, 50Hz, 1000KVA, OLTC (On-Load Tap Changer) with Remote Tap Changer Control (RTCC) and Automatic Voltage Regulating Relay (AVR), Copper Wound, Oil type Outdoor Transformer complete with Breather, Conservator Tank etc. The transformer should be level-2 type tested certified.The job includes testing and commissioning, loading/ un-loading at site including frieght upto site from works complete in all respect to the entire satisfaction of the Engineer-in-charge. The specifications of transformer is as follows:- (NS) (Complete specification reference as per DNIT Item no. 7) |
| 12 | Supply, installation, testing & commissioning of INCOMMER totally enclosed, single busbar, floor mounting metal clad indoor extensible type flush fronted Horizontal draw out, Horizontal Isolation type Vacuum Circuit Breaker suitable for installation in 11kv 3 phase, 3 wire, 50Hz effectively earthed supply system having a fault level of 500MVA at 11kv compact size, floor mounted trolly M-2 CLASS MECHANISM INDURANCE SUITABLE FOR 10000 OPERATIONS. The VCB Panel should be confirming to IEC-62271-100 & Panel as per IEC- 62271-200, & IEC-60694 as amended up to date. The job also includes making connection of HT cable, testing, commissioning etc including loading, unloading etc. as required to complete the job to the entire satisfaction of the E.I.C. of the work. The VCB panel should comprises of following (NS) (Complete specification reference as per DNIT Item no. 8) |
| 13 | Supply, installation, testing & commissioning of OUTGOING totally enclosed, single busbar, floor mounting metal clad indoor extensible type flush fronted Horizontal draw out, Horizontal Isolation type Vacuum Circuit Breaker suitable for installation in 11kv 3 phase, 3 wire, 50Hz effectively earthed supply system having a fault level of 500MVA at 11kv compact size, floor mounted trolly M-2 CLASS MECHANISM INDURANCE SUITABLE FOR 10000 OPERATIONS. The VCB Panel should be confirming to IEC-62271-100 & Panel as per IEC- 62271-200, & IEC-60694 as amended up to date. The job also includes making connection of HT cable, testing, commissioning etc including loading, unloading etc. as required to complete the job to the entire satisfaction of the E.I.C. of the work. The VCB panel should comprises of following (NS) (Complete specification reference as per DNIT Item no. 9) |
| 14 | Supply and laying of XLPE insulated PVC inner sheathed aluminum conductor Armoured, non-magnetic armouring aluminium (Single core) cable of size 630 sqmm, 1100V grade in the existing trench complete in all respect to the entire satisfaction of the Engineer-in-Charge (NS) |
| 15 | Supply and erection of 11KV (Earthed) HT XLPE armoured power cable Stranded Compactedt Circular Aluminium Conductor, Conductor Screen with Extruded Semi Conducting Compound, XLPE Insulated, Insulation Screening with Extruded Semi Conducting Compound in Combination with Copper Tape, Cores Laid Up, Innersheath of PVC, Galvanised Steel Flat Strip Armoured, & Overall PVC Sheathed Cable Conforming to IS 7098 (Part-2) 2011 with upto Date Amendments and laying in exsting DWC HDPE Pipe (NS) |
| 16 | Size 95 sqmm 3 core HT XLPE Cable |
| 17 | Size 70 sqmm 3 core HT XLPE Cable |
| 18 | Supply and laying of XLPE insulated PVC inner sheathed aluminum conductor Armoured (3.5 core) cable of size 400 sqmm, 1100V grade in the existing DWC HDPE Pipe complete in all respect to the entire satisfaction of the Engineer-in-Charge (NS) |
| 19 | Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of Factory fabricated cubical type, Indoor type floor mounted, free standing single front, dust proof & compartmentalized L.T Panel made out of C.R.C.A sheet (2.0mm thick for load bearing structure & 1.6mm thick for the doors & covers), Base frame/I.S.M.C as appropriate. The panel shall be totally Modular Type having bolted structure (Partially Type Tested Assembly - PTTA) with IP42 degree of protection. The panel should be pre-treated with sand blasting treatment and duly painted with siemens grey powder coated paint complete in all respect to the entire satisfaction of the E.I.C. Make of C.R.C.A Sheet- TATA/ SAIL/ ESSAAR/ JINDAL (NS) (Complete specification reference as per DNIT Item no. 13) |
| 20 | Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of Factory fabricated cubical type, Indoor type floor mounted, free standing single front, dust proof & compartmentalized L.T Panel made out of C.R.C.A sheet (2.0mm thick for load bearing structure & 1.6mm thick for the doors & covers), Base frame/I.S.M.C as appropriate. The panel shall be totally Modular Type having bolted structure (Partially Type Tested Assembly - PTTA) with IP42 degree of protection. The panel should be pre-treated with sand blasting treatment and duly painted with siemens grey powder coated paint complete in all respect to the entire satisfaction of the E.I.C. Make of C.R.C.A Sheet- TATA/ SAIL/ ESSAAR/ JINDAL (NS) (Complete specification reference as per DNIT Item no. 14) |
| 21 | Supply and erection of 4 nos. sand buckets of 10 Ltr. Capacity each made out of 24 Gauge G I sheet The buckets with sand shall be hanged on Suitable size of angle iron stand fabricated out of 1 ¼ x 11/4 x 1/8” angle iron having hooks for hanging the buckets in two rows. The job includes the cost of painting with two coats of red paint of superior quality after one coat of primer on buckets and stands to complete the job up to the entire satisfaction of the Engineer-in-charge (NS) |
| 22 | Supply of first aid kit for primary care during injury/ accident/ sprain containing a box with medicated first aid dressing, thermometer, antiseptic solution, crepe & gauze, bandage, cotton roll, sissors, pain relief gel, cream for wound and burn injury, analgesic tablet. Make - Medicon/ Tata 1mg/ or other reputed make (NS) |
| 23 | Supply and Erection of shock treatment chart written in Hindi and English and local language duly framed in wood frame with glass complete as required as per India Electricity Act 2003. (Safety guidelines as per CEA). (NS) |
| 24 | Supply and Erection of Fire Extinguishers ISI marked duly erected/ hung on wall with hooks including the cost of hooks with all material & labour required to complete the job in all respect upto the entire satisfaction of the Engineer-in-charge of work |
| 25 | CO2 type of 9 Kg capacity, 250 kgf/sqcm fire extinguishers mounted on trolley Conforming to IS 16018 of make Ceasfire/ Kanex/ Safex (NS) |
| 26 | Supply and Erection of M.S. sheet danger notice plate at least 2 mm thick. Complete in all respect to the entire satisfaction of the Engineer-in-charge. (NS) |
| 27 | Supply and erection of rubber mat of size 6’x3' 12mm thick (ISI marked) Wide of superior quality and of approved make as approved by the Engineer-in-Charger /EC to be laid on floor in HT room in Front of panels and transformers. (NS) |
| 28 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan)including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge. |
| 29 | All kinds of soil (DSR ref. 2.6.1) |
| 30 | Supplying and filting in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. (DSR ref. 2.27 civil) |
| 31 | Providing and laying in position cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, D.G. set etc. including form work etc. as required. (DSR ref. 4.1.6) civil |
| 32 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. |
| 33 | Thermo-Mechantcally Treated bars of grade Fe-500D or more. (DSR ref. 5.22.6) civil |
| 34 | Providing and laying in position reinforced cement concrele 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required (excluding reinforcement). (DSR ref. 5.1.3) civil |
| 35 | Providing 12 mm thick cement plaster of mix |
| 36 | 1 :4 (1 cement : 4 fine sand) (DSR ref. 13.1) civil) |
| 37 | Centering and shuttering including strutting, propping etc. and removal of form for all heights: |
| 38 | Foundation, footings, base of columns etc for mass concrete (DSR ref. 5.9.1) civil |
| 39 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in |
| 40 | Cement mortar 1:6 (1 cement : 6 coarse sand) (DSR ref. 6.1.2) civil |
| 41 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required |
| 42 | In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works (DSR ref. 10.25.2) |
| 43 | Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-Charge) of total coated thickness 0.50 mm (base metal of minimum 0.45 mm thickness with total coating thickness of 0.05mm) with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required (DSR ref. 12.50) |
| 44 | Providing & fixing BRC fabric grill manufactured from M.S. 40x40x5mm angle iron frame & 40x40x5mm M.S. Tee in centre as support where ever required and 1\\"x1\\" B.R.C fabric of 12 gauge fix with M.S. flat beading of size20x3mm, with openable shutter, locking arrangment, concrete band (1:2:4) for vertical members and necessary hardware. The steel work is to be finished with one coat of steel primer and 2 coats of synthetic enamel paint approved colour and make Complete in all respects to the entire satisfaction of the engineer-in-charge. (NS) |
| 45 | Supplying and laying of G.I Pipe 40mm dia \\"B' class including excavation and refilling the trench complete in all respect to the entire satisfaction of the Engineer-in-charge (NS) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
CompletedBid Opening Date
Technical bids will be opened and evaluated.
TodayTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender