Tender for Provn Of Installation Of Effluent Treatment Plant (Etp) In Mdc Khadki (East) Under Ge (Central) Khadki.
BOQ
| Sl. No. | Item Description |
| 1 | Supply erection and Commissioning 5 KLD Effluent Treatment Plant floor mounted with antifrictin shielded ball bearing on end. The alternator confirms to IS 4722,BS EN 60034-1 Suitable for tropical conditions. PCC foundation for ETP set all as per manufacturer recommendation or required at site or directed by Engineer-in-charge. |
| 2 | Supply and fixing PP-R (Polypropylene random copolymer) concealed pipes 25 mm bore SDR 7.4 (PN 16) UV stabilized and antimicrobial fusion welded having thermal stabilized for hot & cold water supply including all PP-R plain & brass threaded polyproplene random fittings fixed complete to wall, ceiling or in trenches all as specified and as directed. |
| 3 | Supply and fix in repair gun metal gate valve with iron wheel head, screwed both ends for iron pipes 25mm bore complete all as specified and as directed. |
| 4 | Excavation in trenches n.exc 1.5m wide and n.exc 1.5m in depth for laying of cables,pole foundation,stays etc and getting out in soft loose soil, complete all as specified and as directed. |
| 5 | Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete all as specified and as directed. |
| 6 | Removing of excavated material n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and as directed. |
| 7 | Supply and fix in repairs rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position of capacity 500 Ltrs complete all as specified and as directed. |
| 8 | Supply and fix vertical distribution board iron clad, double door with IP-43 1K-09 protection suitable for MCCB as incommer and MCB SPN as outgoing 415 Volts 3 phase 50 C/S 4 way, complete with appropriate size copper bus bar and neutral link confirming to cat pt No 607790 of Legrand or equivalent of make Hager / Merlin Gerin multi-9 complete including cutting chases to wall for fixing DB and making good the disturbed wall surface all as required at site or directed by Engr-in-Charge. |
| 9 | Supply and fix MCCB 3 pole 415 Volts, 125 Amps rating with rupturing cap 16 KA complete all as specified and directed. |
| 10 | Material and labour for fixing or passing through pipe, laid in trenches or fixed to pole/wall or fixed to LT panel board, XLPE insulated, armoured, heavy duty electric cable with aluminium stranded conductor, 1100 volts grade, heavy duty cable served with inner sheathing of PVC tape, armoured with galvanised steel wire or tape and overall PVC sheathed of size 10 Sqmm 4 Core complete all as specified and as directed. |
| 11 | Supply and fix in repair double wall corrugated (DWC) high density polythene pipes having corrugation on the outer wall and plain surface on the inner wall confirming to IS 16205 & IS14930 ( Part I and II) for protection of underground cable of size 40 mm outer dia with all fittings such as clamps. coupler etc laid in trenches / road/ nallah or fixed along wall. poles or laid under floor (including cutting floor/Road and making good to match with existing adjoining surface etc for cable protection all as specified (excavation and earth work shall be measured and paid separately) |
| 12 | Earthing complete with and including galvanised steel earth plate electrode 600 mm x 600 mm x 6 mm surrounded by a mixture of charcoal and salt in alternate layers burried directly in ground vertically in a pit of depth not less than 2.25 m deep below ground level with top edge of earth plate at a depth of not less than 1.5 m below ground level, connected with and including galvanised iron or steel earth wire, 4mm dia (No. 8 SWG) by means bolts, nuts, check nuts and washers made out of galvanised iron, 15 mm bore (light grade) GI pipe for protection of earthing lead, 20 mm bore (light grade) GI pipe for watering with funnel, wire mesh and including necessary excavation and earth work, PCC 1:2:4 type B-1 pit and 50 mm thick RCC M-25(Design mix) reinforced with XPM (weight not less than 3 kg/sq m) pit cover, C.I frame, charcoal and comman salt filling in alternate layers, complete all as shown and specified in electrical plate No. 3 of SSR Part-I (2009) complete all as specified and directed by Engineer-in-Charge.NOTE :- The unit rate includes for protecton pipe 15mm and GI earth strip 4mm from top of earth plate upto 7.50 metre above ground level. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 24, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 15, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 19 daysSep 17, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 21 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender