Water Resources and Irrigation Government Departments Closing in 0 days TDR #57170273

Tender For Construction of 10 Nos (7 Nos ) Tube Well Well In Bharoli & Jawalamukhi Area In Tehsil Jawalamukhi Distt Kangra (H.P)(C/O 2 No Pump House Near Tubewell At Bohal Khals A , Gured , Rising Main , Pumping Machinery & Distribution System Of Tub

Issued by Government Departments · Kangra, Himachal Pradesh
Tender Value
55.76 Lakhs
Estimated cost
Bid Submission
02 Sep 2026
0 days left
EMD
1.08 Lakhs
Bank guarantee accepted
Document Fee
2000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Kangra → Himachal Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Construction of 10 Nos (7 Nos ) Tube Well Well In Bharoli & Jawalamukhi Area In Tehsil Jawalamukhi Distt Kangra (H.P)(C/O 2 No Pump House Near Tubewell At Bohal Khals A , Gured , Rising Main , Pumping Machinery & Distribution System Of Tube Well At Bohal Khalsa , Gured)

BOQ

Name of Work:- C/o 10 Nos (7 Nos ) Tube well Well in Bharoli & Jawalamukhi area in Tehsil Jawalamukhi Distt Kangra (H.P)(C/o 2 No pump house near Tubewell at Bohal Khals a , Gured , Rising main , pumping machinery & Distribution system of tube well at Bohal Khalsa , Gured)
Sl. No. Item Description
1Excavation in foundations,trenches etc.in earth work in all kind & upto all height stacking in excavate soil not more than 3mt clear from the edge of the excavation & then returning the stacked soil in 15cm layers,when required into plinths sides of foundation etc. consolidating each deposited layer by ramming and watering and then disposing of all surplus excavated earth with in all lead and lifts complete in all respect as per direction of Engineer in charge.
2Providing and laying cement concrete 1:6:12(One cement :Six sand : Twelve graded stone aggregate 40mm nominal size and curing complete excluding the cost of form work in foundation and plinth with in all lead and lifts complete in all respect as per direction of Engineer in charge.
3Squarred rubble masonary coursed with hard stone of approved quiality in foundation and plinth including racking out joints in cement mortar 1:6 (1cement:6sand) with in all lead and lifts complete in all respect as per direction of Engineer in charge.
4Providing and laying damp proof course 38mm thick with cement concrete 1:2:4 (One cement:two sand: four graded stone aggregate 12.50mm nominal size and curing complete with in all lead and lifts complete in all respect as per direction of Engineer in charge.
5Applying a coat of hot bitumen (mexphalt 80/100 equivalent) using 1.70 Kg. per Sqm. on damp proof course after cleaning the surface with a piece of cloth lightly socked in kerosene oil with in all lead and lifts complete in all respect as per direction of Engineer in charge.
6Brick work using common burnt clay building bricks (IInd class) in super structure above plinth level upto floor two level in cement mortar 1:6 (One cement: Six sand) with in all lead and lifts complete in all respect as per direction of Engineer in charge.
7Providing wood work in frames of doors, windows, clearstory, windows and other frames wrought, framed and fixed in position in 2nd class deodar wood with in all lead and lifts complete in all respect as per direction of Engineer in charge.
8Providing and fixing glazed and panelled glazed or panelled and glazed shutters for doors windows & clear story windows including black enamelled iron butt hinges with necessary screws 40mm thick 2nd class deodar wood with in all lead and lifts complete in all respect as per direction of Engineer in charge.
9Providing and fixing wire gauge shutters using glavanised MS wire gauge of IS gauge destination 85 G with wire of dia 0.56mm for doors, windows including bright finished black enamelled iron hinges with necessary screws 40mm thick 2nd class deodar wood (40mm thick) With in all lead and lifts complete in all respect as per direction of Engineer in charge.
10Providing form work with steel plates 3.15mm thick welded with angle iron in frame 30x30x5mm, so as to give a fair finish including centring, shuttering, strutting and propping etc. with wooden battons and ballies, height of propping and centring below supporting floor to ceiling not exceeding 4.00mtrs. and removal of the same for in-situ-reinforced and plain concrete work in:-
11Flat surfaces such as soffits of suspended floors, roofs, landing and the like floor etc. upto 200mm in thickness with in all lead and lifts complete in all respect as per direction of Engineer in charge.
12Beams, cantilevers, girders and lintels:-Sides and soffits of beam haunching cantilever, girder, bressumers and lintels not exceeding 1.00 meter in depth with in all lead and lifts complete in all respect as per direction of Engineer in charge.
13Vertical surfaces such as walls ( Any Thickness ) partitions and the like including attached Plasters buttress Plinth and string courses and the like .With in all lead and lifts complete in all respect as per direction of Engineer in charge.
14Providing and laying cement concrete work 1:2:4 (One cement : Two sand : Four graded stone aggregate 20mm nominal size and curing complete excluding cost of form work and reinforcement for reinforced concrete work in:-
15Suspended floor, roofs landing and shelves and their supports balconies beams girders bressumers and cantilevers upto floor two level with in all lead and lifts complete in all respect as per direction of Engineer in charge.
1640mm thick cement concrete flooring 1:2:4( One cement:two sand: four graded stone aggregate 20mm nominal size laid in one layer and finished with a floating coat of neat cement With in all lead and lifts complete in all respect as per direction of Engineer in charge.
1720 mm thick cement plaster in single coat on rough side of bricks /stone masonary for interior plastering up to floor two level including arrises, internal rounded angles chamfers and/or rounded angles not exceeding 80mm in girth and finished even and smooth in cement mortar 1:6 (One cement: Six sand) With in all lead and lifts complete in all respect as per direction of Engineer in charge.
186 mm thick cement plaster to ceiling in cement mortar 1:3(One cement :three sand)With in all lead and lifts complete in all respect as per direction of Engineer in charge.
19Providing plinth protection 50 mm thick in cement concrete 1:3:6(One cement : Three sand : Six graded stone aggregate 20mm nominal size) including finishing of the top surface of concrete smooth within all leads and lifts.
20Providing tor steel reinforcement for RCC work including bending, binding and placing in position complete upto floor two level with in all lead and lifts complete in all respect as per direction of Engineer in charge.
21Applying two coat of wood preservative on new wood based surface after and including preparing the surface by thoroughly cleaning dirt ,dust and other foreign matter ,sand papering and knoting With in all lead and lifts complete in all respect as per direction of Engineer in charge.
22Applying a priming coat over new wood and wood based surface after and including preparing the surface by thoroughly cleaning oil dirt grease and other foreign matter sand papering and knotting ready mixed paint brushing wood primer pink with in all lead and lifts complete in all respect as per direction of Engineer in charge.
23Painting two coats (excluding priming coat) on new wood and wood based surfaces with ready mixed paint brushing to give an even shade including cleaning of all dirt, dust and other foreign matter and sand papering and stopping with ready mixed paint other than white With in all lead and lifts complete in all respect as per direction of Engineer in charge.
24White washing with lime on un-decorated walls surfaces( two coats) to give an even shade, including thoroughly brooming the surface to remove all dirt, dust mortar, dust and other foreign matter With in all lead and lifts complete in all respect as per direction of Engineer in charge.
25Finsihing wall with water proofing cement paint of approved brand and manufacture and required shade on un-decorated wall surfaces (two coats) to give an even shade after thoroughly brushing the surface to remove all dirt and remains of loose powdered materials With in all lead and lifts complete in all respect as per direction of Engineer in charge.
26Providing and fixing MS fan clamp type-I of 16 mm dia Ms bar bend to shape with hooked ends in RCC slab during laying including painting the exposed portion of loop as per standard design with in all lead and lifts complete in all respect as per direction of Engineer in charge.
27Providing 40x3 mm flat iron hold fast 40 cm long including fixing to frame with 10mm diameter bolts nuts and wooden plugs and embeding in cement concrete block 30x10x15cm 1:3:6 (One cement: three sand: six graded stone aggregate 20mm nominal size) with in all lead and lifts complete in all respect as per direction of Engineer in charge.
28Providing and fixing of following anodized alluminium fittings of anodized transparent and shade with necessary screws etc. With in all lead and lifts complete in all respect as per direction of Engineer in charge.
29Sliding door bolts 250x16mm.
30Tower bolts ( Barrel type) 200x10mm.
31Tower bolts ( Barrel type) 150x10mm
32Handles 125mm.
33Providing and fixing of M.S. round or square bars with M.S. flats at required spacings in wooden frames of windows and clerestory windows with in all lead and lifts complete in all respect as per direction of Engineer in charge.
34Stone/Boulder filling under floors/behind retaining walls with in all lead and lifts complete in all respect as per direction of Engineer in charge.
35Providing and Installation of electrical wiring fitting in pump house & Providing 2 Nos ciling fan with in all lead and lifts complete in all respect as per direction of Engineer in charge.
36Providing and laying cement concrete 1:1.5:3 (1 cement: 1.5 sand : 3 graded stone aggregate 20mm nominal size) and curing complete excluding the cost of form work and reinforcment for RCC work in :-In foundation and plinth With in all lead and lifts complete in all respect as per direction of Engineer in charge.
37In Foundation, fotting bases of columns and the like and mass concrete With in all lead and lifts complete in all respect as per direction of Engineer in charge.
38Wall ( any thickness but not less than 0.10 mtrs thickness ) attached pillaster, buttresss plinth & string courses etc. from top of foundation level upto floor two level with in all lead and lifts complete in all respect as per direction of Engineer in charge.
39Providing and fixing of MS cover on chamber with MS sheet of 2.0 MM thick fixed with angle iron frame25x25x3mm of having locking arrangement complete with the size of 0.80 m x .80m with in all lead and lifts complete in all respect as per direction of Engineer in charge.
40Rising Main (Three Layer):- Laying , jointing & testing of bevelled ended G.I.pipe (Medium class) Circumferential with butt welded joints where ever required by electrical arc welding ( welding thickness shall be equal to pipe wall thickness)and testing of G.I.pipe make of following dia meters confirming to IS-1239-1990 (part-II), having wall thickness as specified below capable of withstanding required test pressure, including manufacturing and fabrication of reducers/tapers, all short pieces, bends etc. as per site requirement made from parent tubes. The laying of pipe shall also include welding of flanged joints of every XVIIth pipe duly welded in three layers (two inner one outer) and all operations such as cutting, welding, jointing, fabrication of bends, tees, making bevelled pipe ends suitable for butt welding, lowering & laying in excavated trenches to ensure required level complete in all respects to the best satisfaction of the Engineer-in-charge (earth work in trenches to be measured and paid for separately). The fabricated bends shall have three or four cuts having its radius not less than five times the dia of pipe.The welding electrodes shall be as per IS-814 of Advani Orelikon/L&T of ISI marked make. The damagted portion of the pipes (if damaged during laying & jointing operation of pipe) and all other specials made from the parent tube shall be provided with anticorrosive treatment by applying two coats of anticorrosive bituminous paint over a priming coat as per AWWA specifications C-203-1978. The rates also includes entire carriage of material, flusing, cleaning & hydraulic testing of pipes, D.P. test of butt welded joints complete in all respect and to the entire satisfaction & direction of Engineer-in-charge within all leads and lifts. Booster Stage:- Tube-Well to Main Delivery tank.
41Tube-Well Bohal Khalsa GMS pipe (medium classs) 125mm dia Table-5 (4.80mm thick ) RD 0/0 to 460 =460 Rmt
42Tube-Well Gured GMS pipe (medium classs) 125mm dia Table-5 (4.80mm thick ) RD 0/0 to 500 =500 Rmt
43Providing and fixing MS flanges ( In pairs) for the joints of GI pipes mentioned as below and same shall conform to BIS 6392-1971 ( Latest with upto date amendments) incluidng the cost of nuts and bolts of required sizes, 3mm thick compressed asbestos fiber/synthetic rubber gaskets conforming to relevant BIS standards and it shall also include carriage of materials within all leads and lifts complete in all respect to the best satisfaction and direction of Engineer-in-Charge. G.I. pipe Medium Class 125 mm Dia with table -5
44PUMPING MACHINERY:Supply of submersible pumping set of KSB / Kalatoka/ Kalsi / Jyoti / Johnston / Crompton / Kirloskar make conforming to BIS-8034-1989 or latest suitable for lifting Underground Water (latest with up-to-date amendments) fitted with bronze impellers / suitable alloys. The pump should be fitted with free-flow impellers of bronze/suitable alloys directly coupled to squirrel cage electric induction motor of same make as (manufacturer standard) conforming to BIS-9283-1979 (latest with up-to-date amendments) and totally waterproof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearing & provided with stainless steel thrust bearing plate to withstand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard suction clamps, manufacturer cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:-
45Total head in mtr: 87.32 mtr. Discharge required: 12.46 LPS each set. No. of Pump required: 1.00 No.(0 act as stand-by).Location of the site of installation of machinery: (Bohal Khalsa) Distance of: Km from by road & Km by Head Load (for the installation of both machinery).The Altitude of place: The Altitude of place is 500 mtr above MSL Type of Current: AC three phase supply withRated Voltage: 415 +/- 10%Type of water and its Characteristics of water: a) Ambient: deg C b) Turbidity NTU: NTU c) Hardness: 260 Mg/Ltr d) PH Value: 7.5 e) Total Solid Mg/Ltr/ PH Value: f) Other:Total head in mtr: 73.9 mtr.Length of Rising main: 460 mtr.Dia of Rising main: 125 mm dia.No. of working hours: 20 Hours.Limit of Pump: (-) 15% (+) 10%ofR.P.M. of Pumping: 2900 RPM(or to be specified by the tenderer).Test run: 20 Hourscontinuously for 7 days.
46Providing and fixing of double flanged cast iron Sluice valve heavy size one dia higher than pump size to delivery Pump class PN 1.6 of Kirloskar/Leader make conforming to BIS latest with up-to-date amendments having seat pressure 16.32 \{ Kg/cm}^2 complete in all respect. With in all lead and lifts complete in all respect as per direction of Engineer in charge.
47Supply of Kirloskar/Leader make cast iron class double flanged (swing check type) reflux valve having by-pass arrangement class PN 1.6 conforming to relevant BIS 1868-API-600 latest edition (to be provided on delivery side) of size one step higher than the delivery size of pump and should be suitable for withstanding nominal seat pressure 16.32 \{ Kg/cm}^2.With in all lead and lifts complete in all respect as per direction of Engineer in charge.
48Providing and laying PVC insulated jointless flat water proof copper cable of Siemens / Finolex/Grandlay/Gloster make conforming to BIS-1554 (Part-I)-1988 or(latest with upto date amendments) of suitable size for the pump sets offered (One cable carrying all three phases) including all other electrical equipment/ accessories such as thimbles, flexible pipe, solder, nut & bolts, cable glands etc. laid in pipes or trenches under floor. The type, size & make will be subject to approval of HPSEB authorities. In case of non acceptance by HPSEB authority, it shall have to be replaced by the tenderer free of cost.With in all lead and lifts complete in all respect as per direction of Engineer in charge.On supply side of 3 ½ core copper cable \text{mm}^2 (From HPSEB meter to Switch & starter).
49On motor side 3 core flat joint less copper cable of size \text{mm}^2 (From switch & Starter to motor) pump installed in the T/Well.
50Providing and laying column assembly of GI/MSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set. The pipe shall conform to relevant BIS code & capable of withstanding the failed test pressure equal to 1.5 times the operating pressure including all type of fitting such as bends, tapers/ reducers, flanges at every 3 mtrs length with flange confirming to BIS: 6392-1971/BIS 1239(Table-5) rubber, gaskets 3mm thick nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer in charge. The pipe material shall conform to relevant BIS code and capable of withstanding FTP equal to 1.50 times the operating pressure the complete arrangement shall be compromise of: Columns Assembly:
51Erection of all equipment of pumping machinery including cost of tees, bends, tapers and any other fittings required as per site conditions and as per direction of Engineer-in-charge.
52Supply, Installation, Testing & commissioning of Premium Automated starter panel for submersible pump made out of 16 gauge sheet, powder coated dust & vermin proof wall/ base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pumps (Both working) each of rating for required HP through star delta starter mechanism. Starter should be capable enough to handle the following fault like short circuit over current, under current over voltage dry run protection and phase loss with LED ON/OFF & Trip indicator. Make: Aarnation Electric / L & T / Schneider
53Switchgear of required ratings as per type-2 co-ordination for required HP Starter.
54Voltage Protection device to protect panel from over voltage and under voltage.
55Single phasing and phase reversal protection device to safeguard system from single phasing and phase reversal of the supply voltage.
56Multi-function meter indicating different parameters like Current, Voltage, KWH, PF & THD etc. with RS 485 communication. Make: Aarnation / L&T / Schneider /Siemens
57Main incomer MCB/MCCB suitable capacity of L&T/ Schneider/ ABB make on the feeder for pumping set conforming to BIS 2516-1985 (Latest edition).
58Individual Starter incomer MCCB/MCB of suitable capacity of L&T/ Schneider/ ABB make on the feeder for pumping set conforming to BIS 2516-1985 (Latest edition).
59Three phase indicating lamps complete with toggled switches for individual motors conforming to BIS 3452 (Part-I & II) latest with upto date amendments.
60LED On/Off & Trip indicator and push buttons, Control and power wiring, Power capacitor, Cooling fan 230 VAC, Control terminal, Bus bar, i.e. Bolt, insulator, etc.
61Surge suppressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
62Control Transformer to provide a stable control voltage to safeguard the control circuit of all the components from the voltage surges and spikes.
63Supply installation testing and commissioning of timer based automation for submersible pump Make: Aarnation Electric / L & T / Schneider
64Installation of global system for mobile communication-based module to give On & OFF command to enable switch on switch off starter. Make: Aarnation Electric / L & T /Schneider
65Installation of Mobile application (Android/iOS) to give On & OFF command to enable switch on switch off command to starter through a mobile app and also it should give message about the ON and OFF status of starter.Make: Aarnation Electric / L & T / Schneider
66Supply of submersible pumping set of KSB / Kalatoka/ Kalsi / Jyoti / Johnston / Crompton / Kirloskar make conforming to BIS-8034-1989 or latest suitable for lifting Underground Water (latest with up-to-date amendments) fitted with bronze impellers / suitable alloys. The pump should be fitted with free-flow impellers of bronze/suitable alloys directly coupled to squirrel cage electric induction motor of same make as (manufacturer standard) conforming to BIS-9283-1979 (latest with up-to-date amendments) and totally waterproof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearing & provided with stainless steel thrust bearing plate to withstand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard suction clamps, manufacturer cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:-
67SITE CONDITIONS:-Total Head 84.59mtrDischarge required: 9.67 LPSeach set.No. of Pump required: 1.00 No.(0 act as stand-by).Location of the site of installation of machinery: (Gured) Distance of: Km from by road & Km by Head Load (for the installation of both machinery).The Altitude of place: The Altitude of place is 500 mtr above MSL.Type of Current: AC three phase supply withRated Voltage: 415 +/- 10%Type of water and its Characteristics of water: a) Ambient: deg C b) Turbidity NTU: NTU c) Hardness: 260 Mg/Ltr d) PH Value: 7.5 e) Total Solid Mg/Ltr/ PH Value: f) Other:Static head in mtr: 73.85 mtr.Length of Rising main: 500 mtr.Dia of Rising main: 125 mm dia.No. of working hours: 20 Hours.Limit of Pump: (-) 15% (+) 10%of R.P.M. of Pumping: 2900 RPM(or to be specified by the tenderer).Test run: 20 Hours continuously for 7 days.
68Providing and fixing of double flanged cast iron Sluice valve heavy size one dia higher than pump size to delivery Pump class PN 1.6 of Kirloskar/Kilburn/Leader make conforming to BIS latest with up-to-date amendments having seat pressure 16.32 \{ Kg/cm}^2 With in all lead and lifts complete in all respect as per direction of Engineer in charge.
69Supply of Kirloskar/Kilburn/Leader make cast iron class double flanged (swing check type) reflux valve having by-pass arrangement class PN 1.6 conforming to relevant BIS 1868-API-600 latest edition (to be provided on delivery side) of size one step higher than the delivery size of pump and should be suitable for withstanding nominal seat pressure 16.32 \{ Kg/cm}^2.With in all lead and lifts complete in all respect as per direction of Engineer in charge.
70Providing and laying PVC insulated jointless flat water proof copper cable of Siemens / Finolex/Grandlay/Gloster make conforming to BIS-1554 (Part-I)-1988 or(latest with upto date amendments) of suitable size for the pump sets offered (One cable carrying all three phases) including all other electrical equipment/ accessories such as thimbles, flexible pipe, solder, nut & bolts, cable glands etc. laid in pipes or trenches under floor. The type, size & make will be subject to approval of HPSEB authorities. In case of non acceptance by HPSEB authority, it shall have to be replaced by the tenderer free of cost.
71On supply side of 3 ½ core copper cable \text{mm}^2 (From HPSEB meter to Switch & starter).
72On motor side 3 core flat joint less copper cable of size \text{mm}^2 (From switch & Starter to motor) pump installed in the T/Well.
73Providing and laying column assembly of GI pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set. The pipe shall conform to relevant BIS code & capable of withstanding the failed test pressure equal to1.5 times the operating pressure including all type of fitting such as bends, tapers/ reducers, flanges, at every 3mtrs length confirming to BIS:: 6392-1971/ BIS: 1239( Table-5)rubber, gaskets 3mm thick nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer in charge. The pipe material shall conform to relevant BIS code and capable of withstanding FTP equal to 1.50 times the operating pressure the complete arrangement shall be compromise of: Column assembly
74Erection of all equipment of pumping machinery including cost of tees, bends, tapers and any other fittings required as per site conditions and as per direction of Engineer-in-charge.
75Supply, Installation, Testing & commissioning of Premium Automated starter panel for submersible pump made out of 16 gauge sheet, powder coated dust & vermin proof wall/ base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pumps (Both working) each of rating for required HP through star delta starter mechanism. Starter should be capable enough to handle the following fault like short circuit over current, under current over voltage dry run protection and phase loss with LED ON/OFF & Trip indicator. Make: Aarnation Electric / L & T / Schneider
76Switchgear of required ratings as per type-2 co-ordination for required HP Starter.
77Voltage Protection device to protect panel from over voltage and under voltage.
78Single phasing and phase reversal protection device to safeguard system from single phasing and phase reversal of the supply voltage.
79Multi-function meter indicating different parameters like Current, Voltage, KWH, PF & THD etc. with RS 485 communication. Make: Aarnation / L&T / Schneider /Siemens
80Main incomer MCB/MCCB suitable capacity of L&T/ Schneider/ ABB make on the feeder for pumping set conforming to BIS 2516-1985 (Latest edition).
81Individual Starter incomer MCCB/MCB of suitable capacity of L&T/ Schneider/ ABB make on the feeder for pumping set conforming to BIS 2516-1985 (Latest edition).
82Three phase indicating lamps complete with toggled switches for individual motors conforming to BIS 3452 (Part-I & II) latest with upto date amendments.
83LED On/Off & Trip indicator and push buttons, Control and power wiring, Power capacitor, Cooling fan 230 VAC, Control terminal, Bus bar, i.e. Bolt, insulator, etc.
84Surge suppressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
85Control Transformer to provide a stable control voltage to safeguard the control circuit of all the components from the voltage surges and spikes.
86Supply installation testing and commissioning of timer based automation for submersible pump Make: Aarnation Electric / L & T / Schneider
87Installation of global system for mobile communication-based module to give On & OFF command to enable switch on switch off starter. Make: Aarnation Electric / L & T /Schneider
88Installation of Mobile application (Android/iOS) to give On & OFF command to enable switch on switch off command to starter through a mobile app and also it should give message about the ON and OFF status of starter.Make: Aarnation Electric / L & T / Schneider
89Distribution System Laying, Jointing and testing & carriage HDPE pipe of grade PE 80 following dia and pressure complete in all respect including fittings and accessories With in all lead and lifts complete in all respect as per direction of Engineer in charge.
9090mm dia (OD) 6.00 Kg/Sq.cm
91110mm dia (OD) 6.00 Kg/Sq.cm
92125mm dia (OD) 6.00 Kg/Sq.cm
93140mm dia (OD) 6.00 Kg/Sq.cm
94160mm dia (OD) 6.00 Kg/Sq.cm
95180mm dia (OD) 6.00 Kg/Sq.cm
96Providing and supplying 50MM hydrant including GI riser pipe, 50mm gun metal control Valve, 50mm pump connecting Nipple, plain concrete grouting for GI tee, connecting riser pipe with sub main including complete set of fitting etc.With in all lead and lifts complete in all respect as per direction of Engineer in charge.
97Providing and supplying off cast iron Sluice valve double flanged of reputed make as per IS 780-1984, class PN 1.00 of Following dia With in all lead and lifts complete in all respect as per direction of Engineer in charge.
9880mm dia
99100mm dia
100125mm dia
101150mm dia
102200mm dia
103Providing and fixing of air release Valve 50mm dia with MS saddle and GI riser With in all lead and lifts complete in all respect as per direction of Engineer in charge.
104Providing and supplying of duly coupled 63 mm HDPE based portable sprinkler pipes ( IS 14151-I Marked) to withstand pressure of 3.20 kg/ cm^2With in all lead and lifts complete in all respect as per direction of Engineer in charge.
1056 mtr long
1063 mtr long
107Providing 63 mm duly coupled bend
108Providing tee of 63 mm x 63 mm x 63mm
109Providing end cap 63 mm Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57170273
AUTHORITY Government Departments
TENDER VALUE 55.76 Lakhs
LAST DATE 02-09-2026
Authority
Authority Name Irrigation And Public Health Department
Work Description Tender for Construction of 10 Nos (7 Nos ) Tube Well Well In Bharoli & Jawalamukhi Area In Tehsil Jawalamukhi Distt Kangra (H.P)(C/O 2 No Pump House Near Tubewell At Bohal Khals A , Gured , Rising Main , Pumping Machinery & Distribution System Of Tube Well At Bohal Khalsa , Gured)
Basic Detail
Tender No 2747-81 Dated 22.08.2026
Bidding Type Tender
Location
City Kangra
State Himachal Pradesh
Key Dates
Publish Date 24 Aug 2026
Submission Date 02 Sep 2026
Open Date 02 Sep 2026
Finance
Tender Value 55.76 Lakhs
Tender Fee 2000
EMD 1.08 Lakhs
Exemption Not Available
Document List
0097f206-9559-4192-b251-e4f71f59e2b6.html
BOQ_210671.xls
Form6.pdf
Form8.pdf
Tendernotice_1 (11).pdf
TermsAndConditions.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 24, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 02, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Today
Sep 02, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Today

Tender Documents

Download All (ZIP) ↓
html

0097f206-9559-4192-b251-e4f71f59e2b6.html

xls

BOQ_210671.xls

pdf

Form6.pdf

pdf

Form8.pdf

pdf

Tendernotice_1 (11).pdf

pdf

TermsAndConditions.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender