Housing Urban and Rular Development Government Departments Closing in 8 days TDR #57166473

Tender for Tender for Work Regarding The Supply And Installation Of Fire Alarm And Fire-Fighting Systems In The Collectorate Buildings Of Mathura District.

Issued by Government Departments · Agra, Uttar Pradesh
Tender Value
Ref. Documents
Estimated cost
Bid Submission
02 Sep 2026
8 days left
EMD
7.39 Lakhs
Bank guarantee accepted
Document Fee
2354
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Agra → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Work Regarding The Supply And Installation Of Fire Alarm And Fire-Fighting Systems In The Collectorate Buildings Of Mathura District.

BOQ

Name of Work:- जनपद मथुरा के कलैक्ट्रेट भवनों में फायर अलार्म एवं फायर फाइटिंग सिस्टम की आपूर्ति एवं स्थापना का कार्य।
Sl. No. Item Description
1Supplying, installation, testing & commissioning of heat detector operating at 54ºC/57ºC with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete with all connection etc. as required.
2Supplying, installation, testing & commissioning of smoke detector with builtin LED and mounting base complete with all connections etc. as required.
3Supplying, installation, testing & commissioning of manual call boxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required.
4Supplying, installation, testing & commissioning response indicator on surface/recess MS box having two LEDs metallic cover complete with all connections etc. as required.
5Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required.
6Supplying, installation, testing & commissioning sector panel suitable for 6 Zone complete with visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities as per IS:2189 with mimic diagram for all area/zone covered, complete with all connections, interconnections as required.
7Supplying and drawing of speaker cable Single pair, 2-core, 1.5 sq. mm. Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required.
8Supplying and fixing of 25 mm sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
9Fire Hydrant System(A) Supplying, installation, testing and commissioning of Electric driven Main Fire Pump 1620 lpm at 56 m Head conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all (B)Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal as required. respects, as required (C) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-12615: 2018. (D)M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required (E) Suitable cement concrete foundation duly plastered with anti vibration pads.
10(a) Supplying, installation, testing andcommissioning of diesel engine driven main fire pump 1620 lpm at 56 m Head conforming to IS 12469: 2019 suitable forautomatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump) (b) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal as required. (c)Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50mm thick glass wool with 1.0mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. (d)M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. (e)Suitable cement concrete foundation duly plastered and with anti vibration pads.
11(a) Supplying, installation, testing and commissioning of electric driven pressurisation pump 180 lpm at 56 m Head conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump) (b) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainles steel shaft, mechanical seal as required. (c) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class- 'F' insulation, conforming to IS-12615: 2018. (d) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (e) Suitable cement concrete foundation duly plastered and with anti vibration pads.
12(A) Supplying, installation, testing and commissioning of electric driven terrace pump 450 lpm at 35 m Head conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) (B) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal as required. (C )Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class- 'F' insulation, conforming to IS-12615: 2018. (D) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. ( E) Suitable cement concrete foundation duly plastered and with anti vibration pads.
13Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors,dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required: INCOMING -250A, 50KA 4 Pole MCCB, Ics=100% Icu rating Digital Voltmeter 0-500V with selector switch Digital Ammeter (0-250 A) with selector swtich & CTs etc.LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 300A OUTGOING-Main Fire Pump-125 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 60 HP pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation OUTGOING-Jockey Pump 63 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. DIESEL ENGINE CONTROL-Control for diesel engine comprising - Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine System Controller Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification
14Providing laying, testing & commissioning of 200 mm. Dia 'C' class heavy duty MS Pipe conforming to IS 1239/Class -II of IS: 3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. complete as required.
15Providing laying, testing & commissioning of 150 mm. Dia 'C' class heavy duty MS Pipe conforming to IS 1239/Class -II of IS: 3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. complete as required.
16Providing, laying, testing & commissioning of 25 mm. dia. 'C' class heavy duty MS pipe conforming to IS 1239/Class -II of IS: 3589 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
17Providing, laying, testing & commissioning of 50 mm. dia. 'C' class heavy duty MS pipe conforming to IS 1239/Class -II of IS: 3589 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
18Providing, laying, testing & commissioning of 80 mm. dia. 'C' class heavy duty MS pipe conforming to IS 1239/Class -II of IS: 3589 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
19Providing, laying, testing & commissioning of 100 mm. dia. 'C' class heavy duty MS pipe conforming to IS 1239/Class -II of IS: 3589 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
20Supplying and fixing Single headed Stainless steel external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required :
21Supplying and fixing of C.I. Ball Valve 25 mm. dia.
22Supplying and fixing of C.I. Ball Valve 50 mm. dia.
23Supplying, fixing, testing and commissioning of 80 mm dia butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
24Supplying, fixing, testing and commissioning of 100 mm dia butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
25Supplying, fixing, testing and commissioning of 150 mm dia butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
26Supplying, fixing, testing and commissioning of 200 mm dia butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
27Providing, installation, testing and commissioning of 80 mm dia. non-return valve confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :
28Providing, installation, testing and commissioning of 100 mm dia. non-return valve confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :
29Providing, installation, testing and commissioning of 150 mm dia. non-return valve confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :
30Providing, installation, testing and commissioning of foot valve of 200 mm dia. confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :
31Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange.
32Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :
33Supplying and fixing first-aid Hose Reel 30 mtr. with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.(a) 20 mm nominal internal dia water hosethermoplastic (Textile reinforced) type -2 as per IS: 12585(b) 20 mm nominal internal dia gun metal globe valve & nozzle.(c) Drum and brackets for fixing the equipmets on wall.(d) Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.
34Supplying & fixing 63 mm dia gun metal Stainless Steel (Grade 304) short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required:
35Supplying and fixing of 4 way - 150 mm dia M.S. Pipe fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required:
36Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required.
37Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required.
38Providing & fixing of pressure Gauge in M.S. pipe line including connection etc. as required.
39Provinding & fixing of 1.6 mm thick M.S. Hose Box/ Frame Door capable of accommodating fire Landing Valve Hose Pipes fitting & accessories The door shall have a front glass with lock and key arrangement & shall be painted with post office red colour.
40Providing and placingon terrace (at all floor levels) Polyethylene water storage tank, IS 12701 Marked, with cover and suitable locking arrangements and making ncessary holes for inlet, outlet and overflow pipes. Make-Sintax
41Supply and fixing of fire extinguisher CO2 type 4.5 kg capacity (ISI marked IS: 2878 & TAC approved) complete with intial charge and wall braket along with supply of all material and labour for proper completion of work.
42Supply and fixing of fire extinguisher ABC type 4 kg capacity (ISI marked IS: 15683 & TAC approved) complete with intial charge and wall braket along with supply of all material and labour for proper completion of work.
43Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required.
44Supplying and laying 25 mm X 5 mm G.I strip at 0.50metre below ground as strip earth electrode, includingconnection/ terminating with G.I. nut, bolt, spring,washer etc. as required. (Jointing shall be done byoverlapping and with 2 sets of G.I. nut bolt & springwasher spaced at 50mm)
45Supply and laying of 16 Sq. mm. 4Core aluminium conductor PVC insulated armoured served sheathed cables 1100 Volt grade at a depth of 750 mm. Below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run sell be fixed on M.S. clamps etc. of suitable size or as directed by engineer incharge complete in all respect including excavation and refilling. The armouring of the cable sell be properly connected with the earth conductor by clamps etc.
46Supply and laying of 25 Sq. mm. 3-1/2 Core aluminium conductor PVC insulated armoured served sheathed cables 1100 Volt grade at a depth of 750 mm. Below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run sell be fixed on M.S. clamps etc. of suitable size or as directed by engineer incharge complete in all respect including excavation and refilling. The armouring of the cable sell be properly connected with the earth conductor by clamps etc.
47Supply and laying of 70 Sq. mm. 3-1/2 Core aluminium conductor PVC insulated armoured served sheathed cables 1100 Volt grade at a depth of 750 mm. Below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run sell be fixed on M.S. clamps etc. of suitable size or as directed by engineer incharge complete in all respect including excavation and refilling. The armouring of the cable sell be properly connected with the earth conductor by clamps etc.
48Supplying and making end termination with brass compression gland and aluminium lugs for 4 X 16 sq. mm (28mm) of PVC insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade as required.
49Supplying and making end termination with brass compression gland and aluminium lugs for 3½ X 25 sq. mm (28mm) of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade asrequired.
50Supplying and making end termination with brass compression gland and aluminium lugs for 3½ X 70 sq. mm (38mm) of PVC insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade asrequired.
51Wiring for light point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.
52Wiring for fan point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.
53Wiring for exhaust fan point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.
54Supplying and Fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 Pin 5/6 A modular socket outlet and 5/6 A Modular switch, connection etc. as required.
55Supplying and Fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 Pin 5/6 & 15/16 A modular socket outlet and 15/16 A Modular switch, connection etc. as required.
56Installation of exhaust fan up to 450 mm. sweep in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.
57Supply, Installation, Testing and Commissioning of 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.
58Wiring for circuit/ submain wiring along with earth wire with the 2 x 1.5 Sq. mm. + 1 x 1.5 Sq. mm earth wire earth wire of FRLS PVC insulated copper conductor, single core cable in surface/ reccessed medium class PVC conduit as required.
59Wiring for circuit/ submain wiring along with earth wire 2 X 4 sq. mm + 1 X 4 sq. mm earth wire of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
60Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ reccessed medium class PVC conduit as required for 4 x 10 Sq. mm + 2 x 6 Sq. mm earth wire
61Supply and Fixing of 5A To 32A rating Single Pole 240/415V, 10ka, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc, as required.
62Supply and Fixing of 63 Amp 4Pole MCB (10KA) C Curve in the existing MCB DB complete with connection, testing and commissioning etc, as required.
63Supplying and Fixing 4 Way (4+12), Double Door Horizontal Type Three Pole and Neutral, Sheet Steel, MCB Distribution Board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).
64LED Batten light (System lumen efficacy ≥120 <135 lm/Watt) Supplying, installation, Testing & Commissioning of LED 18- 22 Watt surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per equirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not riseabove 90°C). Powder coated die cast /Extruded aluminiumBody (Thickness > 1.20 mm)
65Supply of fresh air Fan 300 mm. Make-Crompton and equivalent.
66Supply and Fixing of 16 SWG M.S. drum duly painted including making hole in the wall for exhaust fan and finishing properly complete in all respect.
67Supply and laying of 1800mm x 900mm x 12mm thick chequered rubber matting of lested quality
68Tubewell with boring & 5H.P. Sumersible Pump complete with all respect.
69Construction of one Pump House of size (7 Mtr. x 5 Mtr. x 3 Mtr.) DSR factor -0.735 x ( 109/107)=0.7487
70RCC under ground sump RCC tank 50000 Ltr. capacity. DSR factor -0.735 x ( 109/107)=0.7487 Note - 1- Rates are inclusive of all taxes but excluding GST which shall be paid extra as applicable 2- Labour cess @ 1% will be deducted from contractor's bill at the time of payment Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57166473
AUTHORITY Government Departments
TENDER VALUE Ref. Documents
LAST DATE 02-09-2026
Authority
Authority Name Public Works Department
Work Description Tender for Work Regarding The Supply And Installation Of Fire Alarm And Fire-Fighting Systems In The Collectorate Buildings Of Mathura District.
Basic Detail
Tender No 3504/6WE(Agra)-E/M Circle agra Dt.09.03.2026
Bidding Type Tender
Location
City Agra
State Uttar Pradesh
Key Dates
Publish Date 22 Aug 2026
Submission Date 02 Sep 2026
Open Date 02 Sep 2026
Finance
Tender Value Ref. Documents
Tender Fee 2354
EMD 7.39 Lakhs
Exemption Not Available
Document List
6dcf834a-c4b7-4370-9abb-395ac4aef74c.html
BOQ_2216564.xls
corrffm.pdf
firefightinmathura.pdf
Tendernotice_1 (59).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 22, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 02, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 8 days
Sep 02, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 8 days

Tender Documents

Download All (ZIP) ↓
html

6dcf834a-c4b7-4370-9abb-395ac4aef74c.html

xls

BOQ_2216564.xls

pdf

corrffm.pdf

pdf

firefightinmathura.pdf

pdf

Tendernotice_1 (59).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail