Tender For Providing Of Certain Otm Accommodation At Kargil
Tender Value
2.70 Crore
Estimated cost
Bid Submission
26 Sep 2026
34 days left
EMD
3.45 Lakhs
Bank guarantee accepted
Document Fee
2000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
kargil → Jammu And Kashmir
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender For Providing Of Certain Otm Accommodation At Kargil
BOQ
| Sl. No. | Item Description |
| 1 | NOTE: Schedule ‘A’ Part - I to Part -IX are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only. |
| 2 | Total amount of Sch 'A' Part - I (BUILDING Works) |
| 3 | Total amount of Sch 'A' Part - II (SITE CLEARANCE,EXCAVATION & EARTH WORK) |
| 4 | Total amount of Sch ‘A’ Part - III (INTERNAL ELECTRIFICATION) |
| 5 | Total amount of Sch ‘A’ Part - IV (INTERNAL WATER SUPPLY) |
| 6 | Total amount of Sch ‘A’ Part - V(FENCING AND GATE ) |
| 7 | Total amount of Sch ‘A’ Part - VI(ROAD,PATH AND HARDSTANDING ) |
| 8 | Total amount of Sch ‘A’ Part - VII(SEWAGE DISPOSAL) |
| 9 | Total amount of Sch ‘A’ Part - VIII(HOT WATER SUPPLY) |
| 10 | Total amount of Sch 'A' Part - IX (EXTERNAL ELECTRIFICATION) |
| 11 | SCH 'A PART - X (Miscellaneous B/R and E/M works for Sch 'A' Part-II to Part-IX)Note: This schedule is not pre-priced by MES and the rate indicated as \\"Rs 0.00\\" under Col 5 signifies this fact only |
| 12 | M&L for construction of plateform of size 2500 x 2500 x 1200mm with brick construction in cement mortar 1:4 PCC (M-10 nominal mix) in foundation, 100mm thick RCC M-25 grade slab, with 8mm MS TMT bars 120mm c/c on bothway, brick masonary steps on one side XPM Jali fixed on angle iron 40x 40x6 mm post upto height of 8 feet above ground level and openable gate with locking arrangment including making provision for entry and exit of HT/LT cables and steps made to access to the top of plateform including plastering to bricks masonary complete including painting with 2 coats of whitewash on plastered surface and painting steel surface with 2 coats of red oxide primer complete all as specified and directed. |
| 13 | M&L for Demolition of PCC / Black top road of any specification for laying of cable/pipe and filling of PCC 1:4:8 type D2 upto 400mm depth and 300 mm width and PCC 1:1.5:3 Type B1 upto 200 mm depth and 300 mm width and including removal of excavated material from site complete all as specified and directed. |
| 14 | Supply & fixing LT feeder pillar (Outdoor type) with 400 Amps rated aluminium bus bar suitable for 4 pole double door type cubical type made out of CRCA sheet 3.15 mm thick dust and vermin proof fixed on angle iron size of 40 x 40 x 5 mm having 250 Amp MCCB,4 pole,415 V 36 KA as incomer and grouted in PCC 1:2:4 B1(20mm graded stone). Legs of panel should not be less than 450 mm in length.Panel should be covered from all side with front lockable door and hinges complete and powder coated complete all as specified and directed. |
| 15 | Supply,installation, commisioning and testing in factory made (CPRI approved) LT panel board of suitable size out door type (double dore) 415 volts,dust proof, vermin proof, made out of CRCA sheet 3.15 mm thick duly compartmentalised inside panel with 2 mm thick CRCA sheet, to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type , both side openable , air fins for ventilation , panel shall be mounted on angle of size (50x50x6 mm) & duly spray painted with seven tank process internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer supported on 04 legs of suitable long each duly grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20mm graded stone aggregate) or as manufacturer instruction and including notice board & danger plate complete with all connection incoming/outgoing complete all as specified and as directed by Engr-in-Charge. |
| 16 | Comprising of following accessories :- IN COMING (a) MCCB 4 pole 63 amps , 415 volt of breaking capacity not less than 25 KA(lcs=100% of lcu) with fixed TM range - 01 No for incoming. (b) Aluminium bus bar 150 Amps current rating duly sleeve insulated for set of 3 phase, 4 wire system 01 Set. OUTGOING (c) MCB TPN 40 Amps, 415 Volts 10 KA C- Series -02 Nos. (d) Digital type voltmeter range 0-500V, with inbuilt selector switch-01 Nos. (e) Digital type Ammeter range 0-100 Amps, with inbuilt selector switch and CT of suitable size - 01 SET. (f) LED indicator Lamps R,Y,B - 01 Set. (Near Transormer) |
| 17 | Supply,installation, commisioning and testing in factory made (CPRI approved) LT panel board of suitable size out door type (double dore) 415 volts,dust proof, vermin proof, made out of CRCA sheet 3.15 mm thick duly compartmentalised inside panel with 2 mm thick CRCA sheet, to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type , both side openable , air fins for ventilation , panel shall be mounted on angle of size (50x50x6 mm) & duly spray painted with seven tank process internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer supported on 04 legs of suitable long each duly grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20mm graded stone aggregate) or as manufacturer instruction and including notice board & danger plate complete with all connection incoming/outgoing complete all as specified and as directed by Engr-in-Charge. |
| 18 | Comprising of following accessories :- IN COMING (a) MCB TPN 63 amps, 415 volt of breaking capacity not less than 10 KA(lcs=100% of lcu) series - 01 No for incoming. (b) Aluminium bus bar 100 Amps current rating duly sleeve insulated for set of 3 phase, 4 wire system 01 Set. OUTGOING (c) MCB TPN 25 Amps, 415 Volts 10 KA C- Series -04 Nos. (d) Digital type voltmeter range 0-500V, with inbuilt selector switch-01 Nos. (e) Digital type Ammeter range 0-100 Amps, with inbuilt selector switch and CT of suitable size - 01 SET. (f) LED indicator Lamps R,Y,B - 01 Set. (Near Offr Living) |
| 19 | Supply,installation, commisioning and testing in factory made (CPRI approved) LT panel board of suitable size out door type (double dore) 415 volts,dust proof, vermin proof, made out of CRCA sheet 3.15 mm thick duly compartmentalised inside panel with 2 mm thick CRCA sheet, to accommodate the incoming and outgoing each switch gear shall have be independent opening, and having provision for front and rear side opening with rubber beading and brass cable glands for each cable to make it weather and vermin proof. double door hinged type , both side openable , air fins for ventilation , panel shall be mounted on angle of size (50x50x6 mm) & duly spray painted with seven tank process internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer supported on 04 legs of suitable long each duly grouted in plain cement concrete blocks in 1:2:4 type B1 (using 20mm graded stone aggregate) or as manufacturer instruction and including notice board & danger plate complete with all connection incoming/outgoing complete all as specified and as directed by Engr-in-Charge. |
| 20 | Comprising of following accessories :- IN COMING (a) MCB TPN 63 amps, 415 volt of breaking capacity not less than 10 KA(lcs=100% of lcu) series - 01 No for incoming. (b) Aluminium bus bar 100 Amps current rating duly sleeve insulated for set of 3 phase, 4 wire system 01 Set. OUTGOING (c) MCB DP 40 Amps, 415 Volts 10 KA C- Series -03 Nos. (d) Digital type voltmeter range 0-500V, with inbuilt selector switch-01 Nos. (e) Digital type Ammeter range 0-100 Amps, with inbuilt selector switch and CT of suitable size - 01 SET. (f) LED indicator Lamps R,Y,B - 01 Set (Near Sorting out Shed) |
| 21 | M&L for 150mm bore (DOUBLE WALL CORRUGATED) Pipes (150mm SN8),including fitting laid and jointed complete with collors all as directed and specified by Engr-in-Charge. |
| 22 | M&L for on site 10 Users LLDPE septic tank designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, Vent shaft, connection etc., complete for for hard/dense soil Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 21, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 26, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 34 daysSep 28, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 36 daysTender Documents
Download All (ZIP) ↓
Disclaimer