Tender For Repairs/Maint To Lt Panel Boards / Distribution Feeder Pillar Boxes And Control Panels At A, B & D Area Under Ge Chennai
Tender Value
25 Lakhs
Estimated cost
Bid Submission
12 Sep 2026
19 days left
EMD
50000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Chennai → Tamil Nadu
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repairs/Maint To Lt Panel Boards / Distribution Feeder Pillar Boxes And Control Panels At A, B & D Area Under Ge Chennai
BOQ
| Sl. No. | Item Description |
| 1 | Excavation in trenches not exc 1.5m in width and 1.5 m in depth and getting out excavated soft/loose soil complete all as specified and as directed. |
| 2 | Returning filling in including spreading, levelling, watering and well ramming in layers not exc 25cm complete all as specified and as directed. |
| 3 | Removing excavated material / soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 4 | Cushioning of cable laid in trenches using excavated soil, fine sieved and spreading levelling for cable trenches complete all as specified and directed. (Note: Punned thickness only shall be measured and paid.) |
| 5 | DWC (Double wall corrugated) pipe 100mm dia conforming to IS: 14930 / IS 16205 for protection of electric cables including necessary snap-fit coupler required for fixing complete all as specified and directed. |
| 6 | Supply and laying well burnt bricks sub class 'B' in trenches for cable protection of U/G cable complete all as specified and directed. |
| 7 | Taking out the existing PVC/XLPE, 1100 volts grade, LT UG electric cable of size 95 sqmm x 3.5 core from trenches/ walls (or) passing through pipes/in floor, removing the unserviceable fault cable and carefully stacking the serviceable cable for reusing complete all as specified and directed.Note:- Excavation and Earth work shall be measured and paid separately under appropriate item. |
| 8 | All as per item No.7 above but 150sqmm 3.5 core |
| 9 | All as per item No.7 above but 185 sqmm 3.5 core |
| 10 | All as per item No.7 above but 240 sqmm 3.5 core |
| 11 | Laying only the under ground cable any type obtained from Items No -07 above in trench/wall/floor etc are connecting with suitable cable lugs/sleeves etc, size 95 sqmm 3.5 core complete all as specified and directed . |
| 12 | Laying only the under ground cable any type obtained from Items No -07 above in trench/wall/floor etc are connecting with suitable cable lugs/sleeves etc, size 150 sqmm 3.5 core complete all as specified and directed . |
| 13 | Laying only the under ground cable any type obtained from Items No -08 above in trench/wall/floor etc are connecting with suitable cable lugs/sleeves etc, size 185 sqmm 3.5 core complete all as specified and directed . |
| 14 | Laying only the under ground cable any type obtained from Items No -09 above in trench/wall/floor etc are connecting with suitable cable lugs/sleeves etc, size 240 sqmm 3.5 core complete all as specified and directed . |
| 15 | Supply & Lay in trenches, fixed on wall (or) passing through pipes/in floors, connecting up, testing and commissioning of XLPE insulated armoured LT UG electric cable with aluminium conductor 1100V grade of size 95 sqmm 3.5 core complete all as specified and as directed. |
| 16 | All as per item No. 15.00 above but 150sqmm 3.5 core |
| 17 | All as per item No. 15.00 above but 185sqmm 3.5 core |
| 18 | All as per item No. 15.00 above but 240sqmm 3.5 core |
| 19 | Supply and jointing straight through heat shrink joint kit for PVC/XLPE LT UG cable of size 95 sqmm 3.5 core complete all as specified and as directed. |
| 20 | Supply and jointing straight through heat shrink joint kit for PVC/XLPE LT UG cable of size 150 to 185 sqmm 3.5 core complete all as specified and as directed. |
| 21 | Supply and jointing straight through heat shrink joint kit for PVC/XLPE LT UG cable of size 240 to 300 sqmm 3.5 core complete all as specified and as directed. |
| 22 | S & L for GI pipe light grade of size 100mm in trenches /fixed on walls by suitable clamps and jointing including taking down existing old GI pipes complete all as specified and as directed. |
| 23 | M & L for PCC type C1 1:3:6 (20mm graded aggregate) as in foundations, filling and mass concrete complete all as specified and directed. |
| 24 | Fabrication and installation of cable route indicator made out of 10 mm thick CI plate , oval shape of suitable size and embossed with Mark of \\"MES LT Cable \\" including 30 cm length angle iron support and embedded in and including PCC,including taking down existing old one complete all as specified and as directed. |
| 25 | S& F for GI earthing strip 25x4 mm with nut and bolts complete including taking down old one all as specified and directed. |
| 26 | S&F of GI Strip ISI marked of size 32x6 mm complete with nuts, bolts and washers, buried in ground including excavation complete and all as specified and directed. |
| 27 | S & F Manual change over switch of capacity 250Amps 4 Pole with stainless steel enclosure of suitable size complete all as specified and directed |
| 28 | Supply , install, testing and commissioning of cubical housing cabinet type LT feeder pillar of indoor type, platform mounted factory made, totally enclosed dust and vermin proof made out of 3 mm thick CRCA (Cold Rolled Cold Annealed) MS Sheet, Powder coated, CPRI approved having front and rear hinged doors, lifting lugs (2 Nos) , earthing strips at rear side , bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts , spring and washers, necessary foundation work as per manufacturer instruction including foundation and including taking down the old panel required at site and comprising following:-Note :- (i) The rate deemed to be inclusive of disconnecting the LT cable and reconnecting the same with suitable size of cable glands and connecting complete.(ii) LT danger notice with conventional skull and bones indication written with English and local language. Incoming (a) S&F for Electrolytic grade high conductivity solid 4 Nos Alu bus bars, rated 800 amps supported at required intervals sleeved with heat shrinkable PVC sleeves. The bars shall be colour coded at required intervals for identification - 04 Nos(b ) S&F for LED Indicating lamps for Main Supply indicating R', Y' B' - 01 Set of 3(C ) S&F Ammeter and voltmeter multimeter Nos -01 (d ) S&F for MCCB 400 Amp 36 KA 4 pole Thermal magnetic setting complete - N0s -01 Outgoing (a ) S&F MCCB of 4 pole of capacity 100 amps, with breaking capacity of 25 KA with fixed thermal & fixed magnetic setting - 03 Nos (b ) S&F MCCB of 4 pole of capacity 125 amps, with breaking capacity of 25 KA with fixed thermal & fixed magnetic setting - 03 Nos |
| 29 | Supply , install, testing and commissioning of cubical housing cabinet type LT feeder pillar of outdoor type, platform mounted factory made, totally enclosed dust and vermin proof openable from both front and rear side made out of 3 mm thick CRCA (Cold Rolled Cold Annealed) MS Sheet, Powder coated, CPRI approved having front and rear hinged doors, lifting lugs (2 Nos) , earthing strips at rear side , bottom detachable gland plate complete with suitable size zinc plated and passivated nut, bolts , spring and washers, necessary foundation work as per manufacturer instruction including foundation and including taking down the old panel required at site and comprising following:-Note :- (i) The rate deemed to be inclusive of disconnecting the LT cable and reconnecting the same with suitable size of cable glands and connecting complete.(ii) LT danger notice with conventional skull and bones indication written with English and local language.Incoming : (a) S&F for Electrolytic grade high conductivity solid 4 Nos Alu bus bars, rated 800 amps supported at required intervals sleeved with heat shrinkable PVC sleeves. The bars shall be colour coded at required intervals for identification - 04 Nos(b ) S&F for LED Indicating lamps for Main Supply indicating R', Y' B' - 01 Set of 3(C ) S&F Ammeter and voltmeter Multimeter Nos -01 (d ) S&F for MCCB 350 Amp 36 KA 4 pole Thermal magnetic setting complete - N0s -01 Outgoing :- (a ) S&F MCCB of 4 pole of capacity 63 amps, with breaking capacity of 16 KA with fixed thermal & fixed magnetic setting - 02 Nos (b ) S&F MCCB of 4 pole of capacity 160 amps, with breaking capacity of 36 KA with fixed thermal & fixed magnetic setting - 03 Nos (c ) S&F MCCB of 4 pole of capacity 200 amps, with breaking capacity of 36 KA with fixed thermal & fixed magnetic setting - 03 Nos |
| 30 | M&L for Repair to LT Panel board any type and size and scraping, removal of rust and complete removal of existing painting, cleaning and applying spray painting with two coats of synthetic enamel paint after attending welding work over a corroded portion and coat of red oxide primer and black for foundation / base frame including writing of feeder name complete all as specified and directed. |
| 31 | Earthing complete with galvanised steel earth plate electrode of size 60cm x 60cm x 6 mm thick buried directly in ground( earth pit not less than 2.25 m deep below the normal ground level) with top edge of the plate not less than 1.5m below normal GL connected to GI earth strip of size 32x6 mm by means of bolts, nuts, check nuts washers of GI or steel all as shown in electrical plate No-5 of SSR Part I connected to machinery/equipments installed power house/sub station all as specified including testing on completion complete all as specified and as directed. Note: The unit rate shall also include for excavation earth work in any type of soil PCC (1:3:6) type C1 pit RCC 1:2:4 type B-1 cover reinforced with 8 mm dia CTD bars @ 150mm C/C both ways funnel with 15mm bore GI watering pipe 20mm dia bore GI protection pipe wire mesh and copper lugs complete in addition to item No 1(a) to (e) of preamble ( Notes) Under sub heading earthing specified on SI page NO-451 of SSR Part-II 2020. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 21, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 12, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 19 daysSep 14, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 21 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender