Tender For Creation Of 63Kva Distribution Sub Station Alongwith Ht/Lt Line At New Potha Colony Ward No 5 Pyt Chak Bhagwana Block Bhalwal Akhnoor Under Cdf Of Shri Mohan Lal Bhagat Honble Mla Akhnoor Of J&K Ut For The Year 2026-27 In Respect Of Electr
Tender Overview
Project Description
Tender for Creation Of 63Kva Distribution Sub Station Alongwith Ht/Lt Line At New Potha Colony Ward No 5 Pyt Chak Bhagwana Block Bhalwal Akhnoor Under Cdf Of Shri Mohan Lal Bhagat Honble Mla Akhnoor Of J&K Ut For The Year 2026-27 In Respect Of Electric Division-Iii Jpdcl Jammu. Scheme Code Findc2627112308
BOQ
| Sl. No. | Item Description |
| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: Executive Engineer Electric Division-III , JPDCL Jammu Name of Work: Creation of 63KVA Distribution Sub station alongwith HT/LT line at new Potha colony ward no 5 pyt Chak Bhagwana Block Bhalwal Akhnoor under CDF of Shri Mohan Lal Bhagat Hon'ble MLA Akhnoor of J&K UT for the year 2026-27 in respect of Electric Division-III JPDCL Jammu. Scheme Code FINDC2627112308 Contract No: e-NIT No. 42 of 2026-27 dt. 21.08.2026 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # |
| 2 | Item Description |
| 3 | Supply, Installation & commissioning of 11/0.433 KV, 63 KVA Aluminium Wound Distribution Transformer. |
| 4 | Supply, Installation & commissioning of 11/0.433-63 KVA; 50 HZ, Aluminium woundDistribution transformer of latest energy efficiency level -2 ,(New), IS1180 Part-I; 2014 as per latest upto date amendment with externally fitted MCCB with cable box and 4x4Mtrs.suitable cable of ratings(Aluminium wound upto 200KVA, copper wound for 250KVA or higher KVA ratings). |
| 5 | Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type |
| 6 | Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type |
| 7 | Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A |
| 8 | Providing & Fixing of 70mm2 cable, 1.1 KV Grade, PVC Insulated Stranded Conductor FRLS Type. |
| 9 | Providing of 9Mtr Long Pole , ST-410 SP33 |
| 10 | Providing & Fixing of 11kV Polymeric composite Disc Insulator 12kV with Fitting ,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 11 | Providing of GI Channel/Angel/Flat of sizes including clamps |
| 12 | Providing of Galvanized Nuts and Bolts |
| 13 | Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 14 | Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 15 | Providing & Fixing of Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid Stay Rod & 7/3.15 mm dia stranded wire complete |
| 16 | Providing of Wedge Connectors/PG Clamps |
| 17 | Providing & Fixing of Danger Plates with Clamps |
| 18 | Providing of GI Barbed wire for Anti Climbing |
| 19 | Providing of Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole |
| 20 | Painting of Poles Red Oxide |
| 21 | Painting Of Poles Aluminium Paint |
| 22 | Sundry items like Aluminuim Lugs, Jumpers, Binding tape |
| 23 | Laying of 0.35Km LT Line (3-Phase, 4-Wire) on PCC Poles 8.0 Mtr long using 30mm2 ACSR Weasel ( Supplying including Transportation , Erection, Testing & Commissioning Comp. Job) |
| 24 | PCC Pole 8.0 Mtr long (WL 200 Kg) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. |
| 25 | GI U-Clamp (duly painted with twio coats of Red Oxide and Al. paint) for Shackle Insulator (Polymer/Porcelain) along with Nut & Bolt of sorts |
| 26 | 30mm2 ACSR Weasel |
| 27 | 16KN Polymer / Poreclain Shackle Insulators |
| 28 | Galvanised Nuts and bolts |
| 29 | Danger Plates with Clamps |
| 30 | Anti Climbing device with Clamps |
| 31 | Earthing Complete by GI Rod 20 mm, 2.5 Mtr Long through GI Strip |
| 32 | Stone Pad 300 mmx300mmx75mm |
| 33 | Aluminium Jointing sleeves |
| 34 | LT Line Spacers (3-Phase, 4-Wire) |
| 35 | Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid GS Stay Rod & 7/3.15 mm dia GI stranded wire complete |
| 36 | Conversion of LT Line (3-Phase, 4-Wire) on ST Poles 8.0 Mtr long from 1 Phase to 3phase4wire using ACSR Weasel ( Supplying including Transportation , Erection, Testing & Commissioning Comp. Job) |
| 37 | GI U-Clamp (duly painted with twio coats of Red Oxide and Al. paint) for Shackle Insulator (Polymer/Porcelain) along with Nut & Bolt of sorts |
| 38 | 30mm2 ACSR Weasel |
| 39 | 16KN Polymer / Poreclain Shackle Insulators |
| 40 | Galvanised Nuts and bolts |
| 41 | Danger Plates with Clamps |
| 42 | Anti Climbing device with Clamps |
| 43 | Earthing Complete by GI Rod 20 mm, 2.5 Mtr Long through GI Strip |
| 44 | Aluminium Jointing sleeves |
| 45 | LT Line Spacers (3-Phase, 4-Wire) |
| 46 | Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid GS Stay Rod & 7/3.15 mm dia GI stranded wire complete |
| 47 | Erection of 11kV tapping point ( Supplying including Transportation , Erection, Testing & Commissioning Comp. Job) |
| 48 | Providing of 9Mtr Long Pole , ST-410 SP33 |
| 49 | Providing of GI Channel/Angel/Flat of sizes including clamps |
| 50 | Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type |
| 51 | 30mm2 ACSR Weasel |
| 52 | PG clamps |
| 53 | Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 54 | Providing & Fixing of 11kV Polymeric composite Disc Insulator 12kV with Fitting ,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 55 | Providing of Galvanized Nuts and Bolts |
| 56 | Providing & Fixing of Danger Plates with Clamps |
| 57 | Anti Climbing device with Clamps |
| 58 | Earthing Complete by GI Rod 20 mm, 2.5 Mtr Long through GI Strip |
| 59 | Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid GS Stay Rod & 7/3.15 mm dia GI stranded wire complete Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 No Quoted Rate in Figures Item330 Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information Compatibility Report for BOQe-NIT68.xls Run on 05-03-2024 17:31 If the workbook is saved in an earlier file format or opened in an earlier version of Microsoft Excel, the listed features will not be available. Significant loss of functionality # of occurrences Version Any effects on this object will be removed. Any text that overflows the boundaries of this graphic will appear truncated. 3.0 Excel 97-2003 Some cells in this workbook contain data validation rules, which refer to values on other worksheets. These rules won't be saved. 4.0 Excel 97-2003 Minor loss of fidelity Some cells or styles in this workbook contain formatting that is not supported by the selected file format. These formats will be converted to the closest format available. 4.0 Excel 97-2003 PCC Pole 9.0 Mtr long (WL 300 Kg) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Item73 19.0 3.8 GI V Cross Arm with Top bracket including clamp Item75 289.0 57.8 GiI Channel X arm including clamps and braces. Item76 160.0 32.0 30mm 2 ACSR Weasel Item77 3.09 0.618 PG Clamps for 30 mm2 ACSR Weasel Item78 12.0 3.0 11kV Polymeric composite Pin Insulator 12kV,5kN, Lighting Impulse 75kV Positiveand 80kV Negative, creepage distance 320mm Item79 57.0 12.0 11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positiveand 80kV Negative, creepage distance 320mm Item80 12.0 2.4 Galvanised Nuts nad Bolts Item81 21.0 4.2 Danger Plates with Clamps Item82 21.0 4.2 Anti Climbing device with Clamps Item83 21.0 4.2 Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm, 2.5 Mtr Long through GI Strip Item84 21.0 4.2 Stone Pad 300 mmx300mmx75mm Item85 21.0 4.2 Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid GS Stay Rod & 7/3.15 mm dia stranded wire complete Item87 5.0 1.0 PCC Pole 8.0 Mtr long (WL 200 Kg) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Item137 19.0 3.8 GI U-Clamp (duly painted with twio coats of Red Oxide and Al. paint) for Shackle Insulator (Polymer/Porcelain) along with Nut & Bolt of sorts Item139 84.0 16.0 30mm2 ACSR weasel Item140 4.12 0.8 16KN Polymer/ Porcelain Shackle Insulators Item141 84.0 16.0 Galvanised Nuts and bolts Item142 21.0 4.2 Danger Plates with Clamps Item143 21.0 4.2 Anti Climbing device with Clamps Item144 21.0 4.2 Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm, 2.5 Mtr Long through GI Strip Item145 21.0 4.2 Stone Pad 300 mmx300mmx75mm Item146 21.0 4.2 Aluminium Jointing sleeves Item147 4.0 1.0 LT Line Spacers (3-Phase, 4-Wire) Item148 20.0 4.0 Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid GS Stay Rod & 7/3.15 mm dia GI stranded wire complete Item149 5.0 1.0 |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 20 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 22 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender