Bids Are invited for Custom Bid For Services - Supply, Installation, Testing Commissioning Of Fire Hydrant Pump System And Upgradation Of Fire Pump Room - Fire Main Pump: Supplying, Erecting, Testing, Perfect Aligning, Proper Levelling And Commission
Tender Overview
Project Description
Bids Are invited for Custom Bid For Services - Supply, Installation, Testing Commissioning Of Fire Hydrant Pump System And Upgradation Of Fire Pump Room - Fire Main Pump: Supplying, Erecting, Testing, Perfect Aligning, Proper Levelling And Commissioning Of Fire Service Main Pump Of 4550 Lpm (Litres/Min) At 88 M Head End Suction Centrifugal Pump Type Single Stage/Multistage Pump, Of Suitable Hp To Satisfy 150% Performance Criteria Including With Automatic Air-Relief Valve, Anti Vibration Pad, Foundation Bolt, Hardware Etc As Required As Per Specification And As Per Latest Indian Standard , Fire Diesel Engine/ De Pump: Supplying, Erecting, Testing, Perfect Aligning, Proper Levelling And Commissioningof Horizontal Centrifugal Back Pull Out Pump Rated 4550 Lpm (Litres/Min) At 88 M Head Coupled To A Diesel Engine With Diesel Storage Tank, Battery Backup, Exhaust Chimney Including With Anti-Vibration Pad, Foundation Bolt, Hardware Etc Automatic Air-Relief Valve, Suction & Discharge Pressure Gauges, Engine Driven Fire Pump Controller & Accessories As Per Specification And As Per Latest Indian Standard. Also Dismantling Of The Old Pump. , Fire Jockey Pump: Supplying, Erecting, Testing, Perfect Aligning, Proper Levelling And Commissioning Of Jockey Pump Vertical S S Type Of 240 Lpm At 90 M Head End Suction Centrifugal Pump Type ,3 Phase 440 Ac, Of Suitable Hp With Suitable Stage As Per Specification. With Automatic Air-Relief Valve, Anti Vibration Pad, Foundation Bolt, Hardware Etc As Required As Per Specification, As Per Indian Standard , Fire Pump Control Panel: Supplying, Erecting, Testing, Perfect Aligning, Proper Levelling And Commissioning Of Common Auto Control Panel Suitable For Auto Operation Of Above 5 Pumps. Jockey Pump To Be Auto Start - Auto Stop And Hydrant And Standby Diesel Pump Auto Start - Manual Stop, As Per Specification. (3 Nos New Pumps + 2 Existing Pump Sets) Control Panel Should Consist Of Siren With Range Of 1 Km. It Should On When Any Of The Pump Turns On. The Siren Should Be With Auto On/Off And Manual On/Off Switches , Supplying, Erecting & Terminating Xlpe Armoured Cable 3 Core 95 Sq. Mm. Frls Aluminium Conductor With Continuous 5.48 Sq. Mm. (12 Swg) G.I. Earth Wire Complete Erected With Glands & Lugs, On Wall/Trusses/Pole Or Laid In Provided Trench/ Pipe As Per Specification. Supply Of Brass Cable Gland And Crimped Copper Lugs Shall Also Be Included In This Item. , Supplying, Erecting & Terminating Xlpe Armoured Cable 3 Core 6 Sq. Mm. Frls Copper Conductor Continuous 5.48 Sq. Mm. (12 Swg) G.I. Earth Wire Complete Erected With Glands & Lugs, On Wall/Trusses/ Pole Or Laid In Provided Trench/ Pipe As Per Specification. Supply Of Brass Cable Gland And Crimped Copper Lugs Shall Also Be Included In This Item. , Supplying, Erecting & Terminating Xlpe Armoured Cable 6 Core 1.5 Sq. Mm. Frls Copper Conductor Complete Erected With Glands & Lugs, On Wall/Trusses/ Pole Or Laid In Provided Trench/ Pipe As Per Specification. Supply Of Brass Cable Gland And Crimped Copper Lugs Shall Also Be Included In This Item. , Supplying And Installing Pressure Gauge (Glycerine Pressure Gauge) Type Of 100 Mm Dia., 0-300 Psi Or 0-14 Kg Per Cm Square Fitted With 12/15 Mm Dia. Pad Cock Valve, And G.I. Pipe, Elbow Etc. Complete As Per Specification. , Supplying And Installing Pressure Switch With 12/15 Mm Dia Isolation Valve, G.I. Nipple, Elbow, Etc Complete As Per Specification -Ul Listed / Fm Approved , Refixing & Testing Of Existing Air Vessel As Per The Spec With Air Release Valve On Top, Drain Arrangement With 25 Mm Dia Gun Metal Wheel Valve, With Required Accessories, Pressure Gauge And Painting With Expoxy Primer 2 Coats And Two Caots Synthetic Enamel Paint Of Approved Shade/ Fire Red Paint Shade As Per Is Code. , Sitc Of Double Flanged Sluice Valve Of 16 Kg / Cm2 Pressure Rating, Bronze/ Gun Metal Seat,Isi Marked Complete With Nuts, Bolts, Washers, Gaskets, Of Following Sizes. , Sitc Of Swing Check Type Non – Return Valve Of Pn 16 Of Following Sizes Complete With Rubber Gasket, Gi Bolts, Nuts Washers Etc As Required. , Sitc Of Cast Iron Body Bucket Type Strainer With Ss-304 Jali And Matching Flanges Etc As Required , Sitc Of Dual Plat Nrv Of Following Sizes Confirming Complete With Rubber Gasket, Gi Bolts, Nuts Washers Etc As Required. Gear Operated , Sitc Of Butterfly Valve Of Following Sizes Confirming To Is 13095 Pn 16, Lockable Type Construction, Complete With Rubber Gasket, Gi Bolts, Nuts Washers Etc As Required. Lever Operated , Sitc Of Class ‘C Heavy Duty M.S Pipe Conforming To Is 3589 / 1239 Including Fittings Like Elbows, Tees, Flanges, Tapers, Nuts Bolts, Gaskets Cl , Anchor Fasteners Etc. Fixing The Pipe On The Wall / Ceiling With Suitable Cl S And Painting With Two Coats Of Primer And Two Ormore Coats Of Synthetic Enamel Paint Of Required Shade Including Tapping With Existing System Complete, As Required , Supply, Fabrication, Erection, Alignment And Fixing Of Structural Steel Work For Structural Support Grating Etc. Made Out Of Rolled Steel Angles, Plates, Steel Tubes Etc., Including Splicing, Cutting, Bending, Drilling, Welding, Riveting, Bolting Etc., With All Tools And Tackles, Plant Andmachinery Including Preparation Of Detailed Shop Drawings As Per Design Drawings And Specifications, Wire Brushing To Remove Mill Scales Etc With Two (2) Coats Of Synthetic Enamel Paint Over Two(2)Coats Of Red Oxide Zinc Chromate Primer. , Sitc Of 40 Mm Dia Pressure Silent Ficher Pressure Relife Valve With With Piping For Delivery Header , Sitc Of Following Sizes Expansion Rubber Bellows For Pump Suction & Delivery Side With Matching Flanges Nut,Bolt Etc As Required. , Dismantling, Reinstallation, Testing & Commissioning Of Existing 100 Hp Capacity Sprinkler Main Pump Sets With Allied Piping Work & Control Valve As Directed By Engineering In Charge. , Dismantling, Reinstallation, Testing & Commissioning Of Existing 15 Hp Capacity Sprinkler Jockey Pump Sets With Allied Piping Work & Control Valve As Directed By As Directed By Engineering In Charge. , Providing & Construction Of Rcc/Pcc Pump Foundation With Pocket And Grouting Of Bolts Of Pump Base Frames As Per The Oem Assignment Drawing Including Chemical Fastner,Tmt Steel Bar, Entering Etc As Required.(3Nos New Pump & 2Nos Existing Pump Sets). , Dismantling & Shifting Of Existing Main Fire Pump, De Pump & Jockey Pump, Control Panelwith Piping & Accessories , Fire Extinguishers
BOQ
| Sl. No. | Item Title | Item Description |
| 1 | Fire Main Pump: Supplying, erecting, testing, perfect aligning, proper levelling and commissioning of Fire Service Main pump of 4550 LPM (Litres/min) at 88 m head end suction centrifugal pump type single stage/Multistage pump, of suitable HP to satisfy 150% performance criteria including with Automatic Air-Relief Valve, anti vibration pad, foundation bolt, hardware etc as required as per specification and as per latest Indian standard | Fire Main Pump: Supplying, erecting, testing, perfect aligning, proper levelling and commissioning of Fire Service Main pump of 4550 LPM (Litres/min) at 88 m head end suction centrifugal pump type single stage/Multistage pump, of suitable HP to satisfy 150% performance criteria including with Automatic Air-Relief Valve, anti vibration pad, foundation bolt, hardware etc as required as per specification and as per latest Indian standard |
| 2 | Fire Diesel engine/ DE Pump: Supplying, erecting, testing, perfect aligning, proper levelling and commissioningof horizontal centrifugal back pull out pump rated 4550 LPM (Litres/min) at 88 m head coupled to a diesel Engine with diesel storage tank, battery backup, exhaust chimney including with anti-vibration pad, foundation bolt, hardware etc Automatic Air-Relief Valve, Suction & Discharge Pressure Gauges, Engine Driven Fire Pump Controller & accessories as per specification and as per latest Indian standard. Also dismantling of the old pump. | Fire Diesel engine/ DE Pump: Supplying, erecting, testing, perfect aligning, proper levelling and commissioningof horizontal centrifugal back pull out pump rated 4550 LPM (Litres/min) at 88 m head coupled to a diesel Engine with diesel storage tank, battery backup, exhaust chimney including with anti-vibration pad, foundation bolt, hardware etc Automatic Air-Relief Valve, Suction & Discharge Pressure Gauges, Engine Driven Fire Pump Controller & accessories as per specification and as per latest Indian standard. Also dismantling of the old pump. |
| 3 | Fire Jockey Pump: Supplying, erecting, testing, perfect aligning, proper levelling and commissioning of Jockey pump vertical S S type of 240 LPM at 90 m head end suction centrifugal pump type ,3 phase 440 AC, of suitable HP with suitable stage as per specification. With Automatic Air-Relief Valve, anti vibration pad, foundation bolt, hardware etc as required as per specification, as per Indian standard | Fire Jockey Pump: Supplying, erecting, testing, perfect aligning, proper levelling and commissioning of Jockey pump vertical S S type of 240 LPM at 90 m head end suction centrifugal pump type ,3 phase 440 AC, of suitable HP with suitable stage as per specification. With Automatic Air-Relief Valve, anti vibration pad, foundation bolt, hardware etc as required as per specification, as per Indian standard |
| 4 | Fire Pump Control Panel: Supplying, erecting, testing, perfect aligning, proper levelling and commissioning of Common Auto Control Panel suitable for Auto operation of above 5 pumps. Jockey pump to be auto start - auto stop and Hydrant and standby diesel pump auto start - manual stop, as per specification. (3 nos new pumps + 2 existing pump sets) Control Panel Should Consist of Siren with range of 1 km. It should ON when any of the pump turns ON. The Siren Should be with Auto ON/OFF and Manual ON/OFF Switches | Fire Pump Control Panel: Supplying, erecting, testing, perfect aligning, proper levelling and commissioning of Common Auto Control Panel suitable for Auto operation of above 5 pumps. Jockey pump to be auto start - auto stop and Hydrant and standby diesel pump auto start - manual stop, as per specification. (3 nos new pumps + 2 existing pump sets) Control Panel Should Consist of Siren with range of 1 km. It should ON when any of the pump turns ON. The Siren Should be with Auto ON/OFF and Manual ON/OFF Switches |
| 5 | Supplying, erecting & terminating XLPE armoured cable 3 core 95 sq. mm. FRLS aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/trusses/pole or laid in provided trench/ pipe as per specification. Supply of Brass cable gland and crimped copper lugs shall also be included in this item. | Supplying, erecting & terminating XLPE armoured cable 3 core 95 sq. mm. FRLS aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/trusses/pole or laid in provided trench/ pipe as per specification. Supply of Brass cable gland and crimped copper lugs shall also be included in this item. |
| 6 | Supplying, erecting & terminating XLPE armoured cable 3 core 6 sq. mm. FRLS copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/trusses/ pole or laid in provided trench/ pipe as per specification. Supply of Brass cable gland and crimped copper lugs shall also be included in this item. | Supplying, erecting & terminating XLPE armoured cable 3 core 6 sq. mm. FRLS copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/trusses/ pole or laid in provided trench/ pipe as per specification. Supply of Brass cable gland and crimped copper lugs shall also be included in this item. |
| 7 | Supplying, erecting & terminating XLPE armoured cable 6 core 1.5 sq. mm. FRLS copper conductor complete erected with glands & lugs, on wall/trusses/ pole or laid in provided trench/ pipe as per specification. Supply of Brass cable gland and crimped copper lugs shall also be included in this item. | Supplying, erecting & terminating XLPE armoured cable 6 core 1.5 sq. mm. FRLS copper conductor complete erected with glands & lugs, on wall/trusses/ pole or laid in provided trench/ pipe as per specification. Supply of Brass cable gland and crimped copper lugs shall also be included in this item. |
| 8 | Supplying and installing pressure gauge (glycerine pressure gauge) type of 100 mm dia., 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, and G.I. pipe, elbow etc. complete as per specification. | Supplying and installing pressure gauge (glycerine pressure gauge) type of 100 mm dia., 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, and G.I. pipe, elbow etc. complete as per specification. |
| 9 | Supplying and installing pressure switch with 12/15 mm dia isolation valve, G.I. nipple, elbow, etc complete as per specification -UL Listed / FM approved | Supplying and installing pressure switch with 12/15 mm dia isolation valve, G.I. nipple, elbow, etc complete as per specification -UL Listed / FM approved |
| 10 | Refixing & Testing of existing Air vessel as per the spec with air release valve on top, drain arrangement with 25 mm dia gun metal wheel valve, with required accessories, pressure gauge and painting with expoxy primer 2 coats and two caots synthetic enamel paint of approved shade/ Fire red paint shade as per IS code. | Refixing & Testing of existing Air vessel as per the spec with air release valve on top, drain arrangement with 25 mm dia gun metal wheel valve, with required accessories, pressure gauge and painting with expoxy primer 2 coats and two caots synthetic enamel paint of approved shade/ Fire red paint shade as per IS code. |
| 11 | SITC of double flanged Sluice valve of 16 kg / cm2 pressure rating, bronze/ gun metal seat,ISI marked complete with nuts, bolts, washers, gaskets, of following sizes. | SITC of double flanged Sluice valve of 16 kg / cm2 pressure rating, bronze/ gun metal seat,ISI marked complete with nuts, bolts, washers, gaskets, of following sizes. |
| 12 | SITC of Swing check type non – return valve of PN 16 of following sizes complete with rubber gasket, GI bolts, nuts washers etc as required. | SITC of Swing check type non – return valve of PN 16 of following sizes complete with rubber gasket, GI bolts, nuts washers etc as required. |
| 13 | SITC of cast iron body Bucket Type strainer with SS-304 jali and matching flanges etc as required | SITC of cast iron body Bucket Type strainer with SS-304 jali and matching flanges etc as required |
| 14 | SITC of Dual Plat NRV of following sizes confirming complete with rubber gasket, GI bolts, nuts washers etc as required. Gear Operated | SITC of Dual Plat NRV of following sizes confirming complete with rubber gasket, GI bolts, nuts washers etc as required. Gear Operated |
| 15 | SITC of butterfly valve of following sizes confirming to IS 13095 PN 16, lockable type construction, complete with rubber gasket, GI bolts, nuts washers etc as required. Lever Operated | SITC of butterfly valve of following sizes confirming to IS 13095 PN 16, lockable type construction, complete with rubber gasket, GI bolts, nuts washers etc as required. Lever Operated |
| 16 | SITC of class ‘C’ heavy duty M.S pipe conforming to IS 3589 / 1239 including fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets’ clamp, anchor fasteners etc. fixing the pipe on the wall / ceiling with suitable clamps and painting with two coats of primer and two ormore coats of synthetic enamel paint of required shade including tapping with existing system complete, as required | SITC of class ‘C’ heavy duty M.S pipe conforming to IS 3589 / 1239 including fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets’ clamp, anchor fasteners etc. fixing the pipe on the wall / ceiling with suitable clamps and painting with two coats of primer and two ormore coats of synthetic enamel paint of required shade including tapping with existing system complete, as required |
| 17 | Supply, fabrication, erection, alignment and fixing of structural steel work for structural support grating etc. made out of rolled steel angles, plates, steel tubes etc., including splicing, cutting, bending, drilling, welding, riveting, bolting etc., with all tools and tackles, plant andmachinery including preparation of detailed shop drawings as per design drawings and specifications, wire brushing to remove mill scales etc with two (2) coats of synthetic enamel paint over two(2)coats of red oxide zinc chromate primer. | Supply, fabrication, erection, alignment and fixing of structural steel work for structural support grating etc. made out of rolled steel angles, plates, steel tubes etc., including splicing, cutting, bending, drilling, welding, riveting, bolting etc., with all tools and tackles, plant andmachinery including preparation of detailed shop drawings as per design drawings and specifications, wire brushing to remove mill scales etc with two (2) coats of synthetic enamel paint over two(2)coats of red oxide zinc chromate primer. |
| 18 | SITC of 40 mm dia Pressure silent ficher pressure relife Valve with with piping for delivery header | SITC of 40 mm dia Pressure silent ficher pressure relife Valve with with piping for delivery header |
| 19 | SITC of following sizes Expansion Rubber bellows for Pump suction & delivery side with matching flanges nut,bolt etc as required. | SITC of following sizes Expansion Rubber bellows for Pump suction & delivery side with matching flanges nut,bolt etc as required. |
| 20 | Dismantling, Reinstallation, Testing & commissioning of existing 100 HP capacity Sprinkler main pump sets with allied piping work & Control valve as directed by Engineering In charge. | Dismantling, Reinstallation, Testing & commissioning of existing 100 HP capacity Sprinkler main pump sets with allied piping work & Control valve as directed by Engineering In charge. |
| 21 | Dismantling, Reinstallation, Testing & commissioning of existing 15 HP capacity Sprinkler Jockey pump sets with allied piping work & Control valve as directed by as directed by Engineering In charge. | Dismantling, Reinstallation, Testing & commissioning of existing 15 HP capacity Sprinkler Jockey pump sets with allied piping work & Control valve as directed by as directed by Engineering In charge. |
| 22 | Providing & construction of RCC/PCC Pump foundation with pocket and grouting of bolts of pump base frames as per the OEM assignment drawing including chemical fastner,TMT steel bar, entering etc as required.(3nos new pump & 2nos existing pump sets). | Providing & construction of RCC/PCC Pump foundation with pocket and grouting of bolts of pump base frames as per the OEM assignment drawing including chemical fastner,TMT steel bar, entering etc as required.(3nos new pump & 2nos existing pump sets). |
| 23 | Dismantling & Shifting of existing Main fire pump, DE pump & Jockey pump, Control panelwith piping & Accessories | Dismantling & Shifting of existing Main fire pump, DE pump & Jockey pump, Control panelwith piping & Accessories |
| 24 | Fire extinguishers | Fire extinguishers |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 18 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 18 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender