Tender For Ambala City Town, Supply, Installation, Testing And Commissioning Of Plc Scada, Flow Meters, Dataloggers, Cloud Dashboard, Industrial Displays, And Associated Works Including Calibration, Data Transmission To Cpcb/Hspcb At Stp Model Town A
Tender Overview
Project Description
Tender for Ambala City Town, Supply, Installation, Testing And Commissioning Of Plc Scada, Flow Meters, Dataloggers, Cloud Dashboard, Industrial Displays, And Associated Works Including Calibration, Data Transmission To Cpcb/Hspcb At Stp Model Town Ambala City In Jal Hi Amrut Initiative Of Amrut 2.0. (Package 1) :Rs.53.73 Lacs
BOQ
| Sl. No. | Item Description |
| 1 | Supply, Installation, testing and commissioning ofUltrasonic flow meter (Siemens/Emerson/E plusH/Inico/SBEM) with all accessories including D.I Specials. |
| 2 | 43` Industrial Display, IP65 protection, anti-glaretoughened glass,-) 500 nits brightness, HDM/VGA/DP input, wall/panel mountable. |
| 3 | SCADA/IOT Platform (Core Features): =500 tags: =35 widget types: customizable dashboards: alarms: HTTPS (TLS 1.2 plus ): CPCB/HSPCB API v2.0: local buffer =90days. Bidder must have own proprietary platform. No third party dashboards accepted. |
| 4 | Fail-Safe SCADA Operation: In case any sensor fails orcommunication is lost, the SCADA software shall continueautomation of the plant using analysis and reporting of old data (fail-safe operation). |
| 5 | Industrial IoT Datalogger/Controller Unit: Quad-coreprocessor, =4 GB RAM, =32 GB SSD/eMMC: Linux OS:=2 RS-485, Ethernet, Wi-Fi, HDMI: IP65 enclosure: UPS =2 hrs. |
| 6 | Analog Input Module: =8 channels, 16-bit resolution, 4-20mA/0-10 V |
| 7 | Digital I/O Module:=16 channels, optoisolated, 24 VDC logic |
| 8 | Remote RTU Panels: IP65 enclosure, RS485 interface, min. 8 I/Os. |
| 9 | pH Analyzer: Range 0–14, accuracy ±0.1, ATC, IP68 probe, NABL calibration. |
| 10 | DO Sensor: Optical, accuracy ±2% Rs-485 output |
| 11 | TSS Sensor: Optical,0–5000 mg/L, RS-485 output |
| 12 | Level Transmitters: Ultrasonic/pressure, 0–5 m, accuracy ± 0.25%, IP68 |
| 13 | Mobile and Browser Access Module: Secure multi-useraccess: responsive dashboards. |
| 14 | Industrial HMI Panel: 12–15” touch, IP65, Ethernet/RS-485 |
| 15 | Central Workstation: Industrial PC (i5/i7, 16 GB RAM, 512 GB SSD), dual 24” monitors, UPS 1 kVA. |
| 16 | Dual-SIM 4G/5G Modem with automatic failover... |
| 17 | Industrial Networking: Managed switches, cabling, surge protection. |
| 18 | SCADA Control Panel: IP65, housing controller, breakers, MCC interfacing. |
| 19 | UPS System: 10 kVA, =1 hr backup |
| 20 | Advanced Alarm and Notification Engine: SMS/email alerts escalation matrix. |
| 21 | Interactive Map Dashboard: GIS view:green/yellow/red status. |
| 22 | Custom Report Generator: Auto PDF/Excel reports:CPCB/HSPCB Format. |
| 23 | Role-based Multi-User Access: Operator/supervisor/admin roles: audit trail. |
| 24 | API Integration Module: JSON/HTTPS push to CPCB/HSPCB servers. |
| 25 | Customizable Widgets and Dashboards: =35 widget types: drop. |
| 26 | Installation, cabling, wiring, testing, commissioning |
| 27 | Training of staff, manuals, as-built drawings, accounts. |
| 28 | Cloud-Based Datalogging Backend: Minimum Tier-IIIVPS: Ubuntu Linux (latest LTS): =8 vCPU, =32 GB RAM, =400 GB SSD, Dedicated IPv4: secure HTTPS access, daily backup. |
| 29 | Edge Data Processing: Datalogger must perform local preprocessing (e.g averaging, filtering, anomaly detection)before sending to cloud/dashboard. This reducesbandwidth usage and ensures CPCB/HSPCB compliance even during weak or unstable networks. |
| 30 | Internet Hosting and SIM (Annual Service). |
| 31 | Fail-Safe Data Storage: Datalogger must provide localstorage (=32 GB SSD/eMMC) with automatic re-sync ofhistorical data to the cloud/dashboard once connectivityrestores. This ensures no data loss: many low-cost loggerswithout buffer/resync shall not be accepted. |
| 32 | Dual Communication Redundancy: Ethernet plus Wi-Fi plus Dual SIM failover. |
| 33 | OTA Updates: Remote firmware and dashboard updates |
| 34 | Custom Rule Engine: If/then logic for alarms and controls. |
| 35 | Multi-Tenant Architecture: Multiple sites under secure accounts. |
| 36 | Historical Data Explorer: Graphs with zoom/compare/overlay. |
| 37 | Role-based Custom Dashboards: Operator/Engineer/Admin-specific. |
| 38 | Event Log and Audit Trail: Full history of alarms, actions, logins. |
| 39 | Supply installation, testing and commissioning of electromagnetic flow meter with all accessories including D.I specials for 400 mm dia. |
| 40 | Calibration, support and data transmission to CPCB/HSPCB ( 6 Parameters i.e BOD, COD, TSS, PH, Total Flow and flow rate.*** Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
TodayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 1 dayTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender