Tender For Repair / Maintenance Of 33 Kv Main Receiving Station Yard And Other Allied Works At Kirby Under Age Em -I Of Ge (U) Electric Supply, Delhi Cantt-10.
Tender Value
95.03 Lakhs
Estimated cost
Bid Submission
15 Sep 2026
23 days left
EMD
1.68 Lakhs
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
New Delhi → Delhi
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair / Maintenance Of 33 Kv Main Receiving Station Yard And Other Allied Works At Kirby Under Age Em -I Of Ge (U) Electric Supply, Delhi Cantt-10.
BOQ
| Sl. No. | Item Description |
| 1 | M & L for carrying out following onsite tests for 33 / 11 KV Transformer of any capacity with required / suitable testing equipment by qualified and licensed personal, recording test results and submitted to GE to keep on record duly signed by all concerned complete all as specified and as directed: [a] IR Test [b] PI [c] Magnetic Balance Test [d] Ratio test [e] Di-electric Test of Oil [f] Short Circuit Test [g] Vector Group [h] Winding Resistance |
| 2 | M & L for carrying out following onsite tests for 11 / 0.433 KV Transformer of 100 KVA capacity with required / suitable testing equipment by qualified and licensed personal, recording test results and submitted to GE to keep on record duly signed by all concerned complete all as specified and as directed: [a] IR Test [b] PI [c] Magnetic Balance Test [d] Ratio test [e] Di-electric Test of Oil [f] Short Circuit Test [g] Vector Group [h] Winding Resistance |
| 3 | M & L for painting of transformer of 8/10 MVA(2 Nos) / 12.5/16 MVA(1 No) capacity complete with two coats of synthetic enamel paint externally and painting with a coat of oil resistant paint inside the Transformer shell complete all as specified and as directed. |
| 4 | M & L for overhauling OLTC of 33 KV / 11 KV Transformer of capacity 8/10 MVA (2 Nos) / 12.5/16 MVA( 1 No) by draining out of Transformer oil, dismantling of top cover, inspection of moving and fixed contacts of all three phases and checking the operation, cleaning and removal of contacts of all the three phases and checking the operation, cleaning and removal of all carbon particles, checking the thickness of leads in the OLTC board, moving / fixed contacts, inspection of transition resistance and replacement of gasket / contacts etc., if found damaged, reassembling complete, filling up of oil, testing complete all as specified and as directed. Note: Spares will be measured and paid separately |
| 5 | M & L for filtration of transformer oil of transformers installed at various locations to achieve di-electric strength not less than 60 KV at 2.5mm gap as per relevant IS with portable filtration plant, testing of the oil for the di-electric strength before filtration and after filtration complete all as specified and as directed. |
| 6 | Supply and topping up of transformer oil with di-electric strength not less than 60 KV in to the conservator tank / body tank of the transformer etc. complete all as specified and as directed. |
| 7 | Supply only HV Bushings (Primary side) made out porcelain alongwith brass/copper bushing rod 33 KV and suitable length/size all as per existing, complete 12.5/16 MVA distribution transformers of any make/size/type all as directed including dismantling old one. |
| 8 | -Ditto- all as per srl item No 7.00 here-in-before but 10 MVA |
| 9 | -Ditto- all as per srl item No 7.00 here-in-before but 8 MVA |
| 10 | Supply only HV Bushing (Secondary side) alongwith brass/copper bushing rod 11 KV with threading and suitable length/size all as per existing etc, complete 12.5/16 MVA capacity power transformers of any make/size/type all as directed including dismantling old one. |
| 11 | -Ditto- all as per srl item No 10.00 here-in-before but 10 MVA |
| 12 | -Ditto- all as per srl item No 10.00 here-in-before but 8 MVA |
| 13 | S & F butterfly valve for radiatior suitable size all as per existing etc, complete for power transformers of any make/size/type all as directed including dismantling old one. |
| 14 | S & F WTI (Winding Tempreture Indicator) for 8/10 MVA Power Transformer suitable size all as per existing etc, complete of any make/size/type all as directed including dismantling old one. |
| 15 | S & F OTI (Oil Tempreture Indicator) for 8/10 MVA Power Transformer suitable size all as per existing etc, complete of any make/size/type all as directed including dismantling old one. |
| 16 | S & F SRC gasket for 12.5/16 MVA Power Transformer suitable size all as per existing etc, complete of any make/size/type all as directed including dismantling old one. |
| 17 | Supply & filling of Silica Gel in existing Breather of Power Transformer |
| 18 | M & L for rewinding of cooling fan motor of size 24 inch including removal and refixing in its original position . |
| 19 | Supply, install, testing and commissioning of REF 615, feeder protection and control relay, protections 50, 51, 50N, 51N, 46, 49, 64R, 67, 67N, 27, 59, 59N, 25, 81U, 81O, df/dt, 95, measurement for 3I, I0, 3U, U0, Kw, KVA, PF, Hz, Kwh, 12 DI + 10 DO, one front RJ45 Port, one rear RS485 port for modbus protocol, draw out type with CT shorting feature, small LCD display feature including taking down old relay of any description complete all as specified and as directed. |
| 20 | Supply, Install, testing and commissioning of ABB make RET 620/615, Transformer protection and control relay, protections 87T, 64R [High and Low Impedance], 50, 51, 50N, 51N, 67, 67N, 46, 49, 37, 24, 27, 59, 59N, 81U, 81O, df/dt, 95, measurement for 3I, I0, 3U, U0, Kw, KVA, Kwh, PF, Hz, 8 DI + 13 DO, 2 RTD Inputs, 1 mA Input, One front RJ45 Port, One Rear RS485 Port for Modbus Protocol, Draw Out with CT Shorting feature including taking down old relay of any description complete all as specified and as directed. |
| 21 | S & F in repairs master trip relay operating volt 100/110 V DC complete all as specified and as directed. |
| 22 | S & F in repairs auxiliary relays 30Y type VAA for Transformer Protection complete all as specified and as directed. |
| 23 | S & F in repairs digital voltmeter, 96 X 96 Sq.mm with 4 Position Selector switch complete all as specified and as directed. |
| 24 | S & F in repairs digital ammeter, 96 X 96 Sq.mm with 4 Position Selector switch complete all as specified and as directed. |
| 25 | S & F in repairs C.B. ON/OFF/TRIP/Trip Circuit Healthy and Unhealthy/Spring Charged complete all as specified and as directed. |
| 26 | S & F in repairs 8 window annunciator complete all as specified and as directed. |
| 27 | S & F in repairs T‐N‐C switch [Breaker Control Switch] complete all as specified and as directed. |
| 28 | S & F in repairs trip circuit healthy push button complete all as specified and as directed. |
| 29 | S & F in repairs control wiring, colour coded complete all as specified and as directed. |
| 30 | S & F in repairs test terminal block complete all as specified and as directed. |
| 31 | S & F in repairs local remote switch complete all as specified and as directed. |
| 32 | Supplying, laying and testing XLPE insulated and PVC sheathed, FRLS, heavy duty cable, ISI marked with multistranded copper conductor 1100 Volt grade of size 14 Core, 2.5 Sq.mm cross section suitable for earthed system, laying in trenches / duct / fixed to poles / drawn through pipes / sleeving through pipe in duct, including suitable size double compression copper stainless steel cable gland, crimping type cable lugs, sockets etc. including taking down old cables of any description complete all as specified and as directed. Please Enable Macros to View BoQ information |
| 33 | Supplying, laying and testing XLPE insulated and PVC sheathed, FRLS, heavy duty cable, ISI marked with multistranded copper conductor 1100 Volt grade of size 14 Core, 2.5 Sq.mm cross section suitable for earthed system, laying in trenches / duct / fixed to poles / drawn through pipes / sleeving through pipe in duct, including suitable size double compression copper stainless steel cable gland, crimping type cable lugs, sockets etc. including taking down old cables of any description complete all as specified and as directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 20, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 15, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 23 daysSep 22, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 30 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender