Tender for Provision Of New Administrative Building (G+ Five Storey) Inside Technical Area, Dmsrde, Kanpur
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 21-Aug-2026 | Corrigendum01 | Other | 24-Sep-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Note:- Schedule A Section-I (Item No. 1.01 to 1.10) and section-II to section-IV (Item No. 2.00 to 4.00) as under are not prepriced by MES and Estimated cost indicates 0.00 under Col-5 signifies this fact only. Bidders to quoted their Lump-Sum against each item. SCHEDULE 'A' SECTION-I (BUILDING WORKS) |
| 2 | Design and Build Administrative Building (G+5) based on DBR with RCC frame structure complete all as specified and as shown on Architectural drawings. |
| 3 | Design and Build Multilevel scooter/car parking (G+2) based on DBR with RCC frame structure complete all as specified and as shown on Architectural drawings. |
| 4 | Design and Build Storage Shed (Textile and liveries, Acid & POL Store) single storey with verandah based on DBR with RCC frame structure complete all as specified and as shown on Architectural drawings. |
| 5 | Design and Build Storage Shed (Chemical, Glassware and Hardware) single storey with verandah based on DBR with RCC frame structure complete all as specified and as shown on Architectural drawings. |
| 6 | Design and Build MT office (single storey) based on DBR with RCC frame structure complete all as specified and as shown on Architectural drawings. |
| 7 | Design and Build Pump House alongwith UG Sump (2.5 Ltr capacity) based on DBR with RCC frame structure complete all as specified and as shown on Architectural drawings. |
| 8 | Design and Build Sub station building based on DBR with RCC frame structure complete all as specified and as shown on Architectural drawings. |
| 9 | Design and Build MT Garage for 'B' vehicles and ambulance based on DBR with RCC frame structure complete all as specified and as shown on Architectural drawings. |
| 10 | Design and Build Toilet Block based on DBR with RCC frame structure complete all as specified and as shown on Architectural drawings. |
| 11 | Design and Build Loading & unloading Platform based on DBR complete all as specified and as shown on Architectural drawings. |
| 12 | Lump sum price worked out by the Contractor for “AIR CONDITIONING” as listed in Schedule ‘A’ Section-II. |
| 13 | Lump sum price worked out by the Contractor for “FIRE FIGHTING SYSTEM” as listed in Schedule ‘A’ Section-III. |
| 14 | Lump sum price worked out by the Contractor for “SOLAR PLANT” as listed in Schedule ‘A’ Section-IV. |
| 15 | Schedule 'A' Section-V to Section-XVIII under Serial No. 5.01 to 5.13 are prepriced by MES. |
| 16 | Lump sum price worked out by the Contractor for “SITE CLEARANCE, EXCAVATION AND EARTH WORK” as listed in Schedule ‘A’ Section-V. |
| 17 | Lump sum price worked out by the Contractor for “INTERNAL ELECTRIC SUPPLY” as listed in Schedule ‘A’ Section-VI. |
| 18 | Lump sum price worked out by the Contractor for “INTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Section-VII. |
| 19 | Lump sum price worked out by the Contractor for “ROAD/PATH/CULVERT” as listed in Schedule ‘A’ Section-VIII. |
| 20 | Lump sum price worked out by the Contractor for “SEWAGE DISPOSAL” as listed in Schedule ‘A’ Section-IX. |
| 21 | Lump sum price worked out by the Contractor for “AREA DRAINAGE” as listed in Schedule ‘A’ Section-X. |
| 22 | Lump sum price worked out by the Contractor for “EXTERNAL ELECTRIC SUPPLY” as listed in Schedule ‘A’ Section-XI. |
| 23 | Lump sum price worked out by the Contractor for “EXTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Section-XII. |
| 24 | Lump sum price worked out by the Contractor for “RAIN WATER HARVESTING” as listed in Schedule ‘A’ Section-XIII. |
| 25 | Lump sum price worked out by the Contractor for “LIFT” as listed in Schedule ‘A’ Section-XIV. |
| 26 | Lump sum price worked out by the Contractor for “AUDIO VIDEO SYSTEM” as listed in Schedule ‘A’ Section-XV. |
| 27 | Lump sum price worked out by the Contractor for “LIGHTENING PROTECTION” as listed in Schedule ‘A’ Section-XVI. |
| 28 | Lump sum price worked out by the Contractor for “ARBORICULTURE” as listed in Schedule ‘A’ Section-XVII. |
| 29 | Lump sum price worked out by the Contractor for “DEMOLITION” as listed in Schedule ‘A’ Section-XVIII. |
| 30 | SCHEDULE `A' SECTION - XIX (MISC. ITEMS) as here-in-after not prepriced by MES (To be quoted by the tenderer against each item) |
| 31 | INTERNAL ELECTRIC SUPPLY |
| 32 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required complete all as specified and directed. |
| 33 | Wiring for twin control light point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2-way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required complete all as specified and directed. |
| 34 | Point wiring for 5 Amps sockets on same board to be fixed on lights circuit board including socket switch and GI box, modular base and cover plate for 3 module complete all as specified and directed. |
| 35 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. for independent point as required complete all as specified and directed. |
| 36 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. for independent point as required complete all as specified and directed. |
| 37 | S & F for exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 200mm complete all as specified and directed. |
| 38 | Supplying, installation, Testing & Commissioning of Panel light 2x2 ft. of 36 W with built in PIR occupancy sensor offering flexibility of auto switching off when the space is not occupied as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 deg C to 40 deg C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 6500°K complete all as specified and directed. |
| 39 | Supplying, installation, Testing & Commissioning of Building security light LED 30W fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 deg C to 50 deg C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%, THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66, IK-10, CRI >70, under voltage and over voltage protection, EM EMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin),SDCM (Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) complete all as specified and directed. |
| 40 | Supplying and fixing of 32 mm dia X 2.00 metres long G.I. pipe (medium class) bracket for mounting of fluorescent / HPMV / HPSV street light fitting on pole including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts, bolts and washer, painting the flat iron with primer and finish paint etc. as required complete all as specified and directed. |
| 41 | Supply and fix Flame Proof Exhaust fan, steel body AC single Phase. 230V of size 300m sweep, 900 CFM with blades, frame and louvers complete all as specified and directed. |
| 42 | Supply and fixing waterproof Up Down 4w oval shape LED wall lamp aluminium IP 65 body 2 Ray , warm white, Indoor / outdoor decorative wall sconce light complete all as specified and directed. |
| 43 | Supply and fixing waterproof Down LED wall lamp aluminium IP 65 body 1 Ray , warm white, Indoor / outdoor decorative wall sconce light complete all as specified and directed. |
| 44 | Supplying and fixing 6 way double door, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) complete all as specified and directed. |
| 45 | Supplying and fixing of VTPN DB 4 way (4 + 12), Double door ways surface/ recess mounting, vertical type, 415 V, TPN distribution board MCCB as incomer of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required complete all as specified and directed.(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 46 | Supplying and fixing of TPN DB 4 way (4 + 12), Double door ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required complete all as specified and directed.(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 47 | Wiring for circuit/ submain wiring along with earth of the size 2 X 10.0 sq. mm + 1 X 6.0 sq. mm earth wire of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required complete all as specified and directed. |
| 48 | Wiring for circuit/ submain wiring along with earth of the size 4 X 16.0 sq. mm + 2 X 6.0 sq. mm earth wire of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required complete all as specified and directed. |
| 49 | Wiring for circuit/ submain wiring along with earth of the size 2 X 16.0 sq. mm + 2 X 6.0 sq. mm earth wire of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required complete all as specified and directed. |
| 50 | Supply & fixed PVC insulted telephone cables unarmoured 0.4 mm ATC 4 pair cable connection complete all as specified and directed. |
| 51 | Supply & fixed Telephone socket including GI box with cover, plate connection complete all as specified and directed. |
| 52 | Supply & fixed LAN network cable electrolytic grade solid annealed bare copper copper conductor, 4 pair unshielded twisted pair (UTP) CAT 6-23 AWG LAN cables network for DRONA, Internet Line, interanet Line connection complete all as specified and directed. |
| 53 | Supply & fixed 3 way info outlet socket including GI box with cover, plate connection complete all as specified and directed. |
| 54 | S&F GI solid cable tray 150 MM x 100 MM with cover including ties, fastener and connected accessories complete all as specified and directed. |
| 55 | S&F LED Aviation Light high intensity CI body with 10 Watt LED (Red Colour) 230 volts single phase complete all as specified and directed. |
| 56 | ROAD PATH AND CULVERTS |
| 57 | Providing and applying 2.5mm thick road marking strips (retro-reflective) of specified shade/ colour using hot thermoplastic material by fully/ semi automatic thermoplastic paint applicator machine fitted with profile shoe, glass beads dispenser, propane tank heater and profile shoe heater, driven by experienced operator on road surface including cost of material, labour, T&P, cleaning the road surface of all dirt, seals, oil, grease and foreign material etc. complete all as per direction of Engineer-in-Charge and accordance with applicable specifications. |
| 58 | Providing and laying 60mm thick factory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with line sand etc. complete all as specified and directed. |
| 59 | AREA DRAIN |
| 60 | M&L for 12mm thick cement plaster in 1:3 (1 Cement : 3 Coarse Sand) finished with a floating coat of neat cement on brick wall complete all as specified and directed. |
| 61 | Providing and placing in position 100mm thick factory made machine batched & machine mixed Precast RCC Rectangular Covers on drains of footpath of various sizes, of M-25 grade cement concrete for RCC Work, including cost of centering, shuttering, reinforcement of 8mm dia TMT bars of Fe-500 Grade @ maximum 100mm c/c on both ways, neat cement punning on finished surface, properly encased on all edges with 1.6mm thick, 100mm wide MS sheet duly painted over priming coat, reinforcement to be welded at edges with MS sheet and providing 2 Nos. 12mm dia bar for hooks etc. including cost of cartage, all leads & lift, handling at site etc. complete all as specified and directed. |
| 62 | M&L for brick work with common burnt clay machine moulded perforated bricks of class designation 12.5 conforming to IS: 2222 in superstructure above plinth level up to floor five level in cement mortar 1:6 (1 cement : 6 coarse sand) with modular bricks complete all as specified and directed. |
| 63 | EXTERNAL ELECTRIC SUPPLY |
| 64 | 1) Supplying, installation, testing and commissioning of 500 KVA capacity (continuous loading) BEE 3 Star rated (Corresponding Level 3) , 11/0.433 KV step down, 3 Phase, 50 Hz, Dyn 11 vector group, ONAN (Oil Natural Air Natural) copper wound transformer (Electrolytic grade 99.9% pure copper, Core made of first grade Cold Rolled Grain Oriented (CRGO) Core grade MOH or better, suitable for Outdoor applications with Offload Tap Changer/ On Load Tap Changer (OLTC) ( below 500 KVA offload and above 500 KVA On Load Tap Changer) on HV side having AVR relay and Remote Tap Changer Control (RTCC) for automatic sensing of incoming voltage, automatic operation of OLTC and facility for remote and manual operation of OLTC HV side in range of +5% to -15% in steps of 2.5%, having cable end boxes on HV side suitable for 3x95 sq.mm XLPE cable of 11 KV grade, including bus trunking arrangement on LV side including supplying and laying of copper conductor multicore control cable from transformer to HT breaker/panel for safety tripping, complete with all accessories and safety provisions as per relevant IS Code including first filling of filtered dehydrated oil, i/c supplying and grouting of suitable M.S. Channel with all accessories and transformer shall be confirming to IS : 2026 (Part 1 to Part 5), IS : 1180 and as per MES specifications complete in all respects etc. as required at site. The maximum flux density in any part of the core and yoke at rated voltage and frequency shall be such that the flux density with + 12.5 percent combined voltage and frequency variation from rated voltage and frequency does not exceed 1.9 Tesla. The permissible temperature-rise shall not exceed 35 deg C for oil and 40 dg. C up to 200 KVA and 40 deg C for oil and 45 deg C for above 200 KVA for winding. Inside of tank shall be painted with varnish or liquid resistant paint. For external surfaces one coat of thermo setting powder paint or one coat of epoxy primer followed by two coats of polyurethane base paint shall be used. IS: 1180 (Part 3) shall be referred to for paint thickness for normal to medium corrosive atmosphere. For highly polluted atmosphere and special application external paint work shall be as per direction of Engineer-in-Charge. |
| 65 | Item No 10.02 Contd..Design ambient condition : a) air temperature 50 deg C, b) Relative Humidity 90 % Max, c) Seismic Zone as per location of site, d) Altitude as per location/site. Noise level Shall not exceed limits as per NEMA TR-1 with all accessories running measured as per IEC 551 / NEMA standard. The transformer should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc. Marking Each transformer shall be provided with rating plate made of anodized aluminium/ stainless steel material securely fixed on the outer body, easily accessible, as per IS: 1180 Part-3. The entries on the rating plate shall be indelibly marked. Fitting and Accessories : The following fittings shall be provided:- a) Two earthing terminals with the earthing symbol b) Oil level gauge indicating oil level at minimum, 30°C and maximum operating temperature; c) Air release device (for non-sealed type transformers) d) Rating and terminal marking plates; e) Silica gel breather f) Drain-cum-sampling valve (¾″ nominal size thread, IS 554) preferably steel with plug for three phase transformers; g) Thermometer pocket with cap; h) Oil filling holes having (1¼″ nominal size thread) with cover (for sealed type transformers without conservator); i) Lifting lugs for the complete transformer as well as for core and winding assembly; j) Pressure relief device or explosion vent above 200 kVA; k) One filter valve on the upper side of the tank (for transformers above 200 kVA); l) Unidirectional flat rollers (for transformers above 200 kVA); m) Inspection hole (for transformers above 200 kVA); n) HV side neutral grounding strip (where one of the HV bushing terminal is connected to earth); o) Buchholz relay for transformers above 800 kVA. p) Arcing horns or suitable rating lightning arrestors for HT side – 3 Nos. q) Bird guard; r) Oil temperature indicator and winding temperature indicators for transformers above 200 kVA with suitable tripping mechanism above permissible limit s) Jacking pads (for transformer above 1 600 kVA); t) Additional Neutral separately brought out on bushing for earthing. u) Magnetic oil level gauge (for transformer above 1600 kVA) with low oil level alarm contact; v) Non return valve (for conducting pressure test); w) Pressure relief device or explosion vent x).Monogram Plate y) Inspection cover z). Detachable type radiators with top and bottom shutoff valve. aa) Oil Conservator with Oil level indicator, minimum level marking and drain plug for all transformers of capacity 50 KVA and above. bb) Necessary hardware, clamps, lugs etc. for termination on HV/MV etc. for all transformers. |
| 66 | Supplying , installation, testing and commissioning of 12 KV, 630 Amps having short circuit capacity 21kA/3-sec, Outdoor (IP54), RMU (Ring main unit) 3-way comprising of 01 Nos Motorized and manually operated Load Break Switch and 02 Nos 630 Amp Fixed Type Motorized and manually operated spring charging VCB electrolytic grade copper busbars all inside, gas-filled, robotically welded stainless steel 304 (Non Ferrite Non Magnetic Grade) tank with min. thickness 3+0.5 mm, IP 67 Degree of Protection , internal-arc classified 21kA/1sec for cable box and tank both, on-site-repairable with site replaceable bushing/coupling/ mechanism, gas refilling etc. The enclosure shall have pad lockable double-door access with anti-theft hinges, fully covering the front facia and cable boxes to ensure fail-safe anti-theft protection. The unit shall include the following along with all necessary accessories and fittings as required at site. (A) 01 Nos. Incoming Load Break Switch module for 3 Way RMU & 02 Nos. motored VCB as outgoing module for 3 Way RMU each consisting of following accessories :-(i) Each switching unit is designed as a three position switch. This three function switch combines the functions of switch – disconnector and earthing switch.(ii) 12V, 630A Load Break Switch with interlocked line-earthing scheme both short circuit current - 21kA/3-sec, Making Capacity - 50 kA - 01 No(iii) Auxiliary contacts - 1NO + 1NC-01 No(iv) Spring assisted snap action motorized mechanism with un- inhibited operating shaft for emergency manual operation with integrated earthing switch -01 No(v) Cable terminals (site replaceable Cable bushings situated not beyond 300mm from cable cover to allow ease of access for installation/testing/replacement purposes) with double door arrangement for enhanced safety (IP54+IP3X) interlocked to prevent access up to 11 KV, 120 Sqmm, 3 Core, XLPE AL cable termination in live condition. Each Set of 03(vi) Right angle boots (push on type) - Each Set of 03(vii) Arc proof cable covers having cable entry from bottom , front with Interlocking mechanism including earth switch - 01 No |
| 67 | Item No 10.03 Contd...(viii) Capacitive voltage indication fixed type system as per IEC 61243 with LED - 01 Set(ix) Fault Passage Indicator - It is to be provided for each incomer load break unit, FPI with LED/digital display to be added for detection of cable fault - 01 No(x) ON, OFF, EARTH mechanical indication on the front mimic of the panel - 01 No(B) 02 Nos. Outgoing VCB module for 3 Way RMU each consisting of following accessories: -(i) Each function unit consists of a vacuum circuit breaker in combination with a three-position switch. The three-position switch fulfils the operation of the disconnector function and earthing function.(ii) 12kV, 630A Fixed Type VCB module with series disconnector cum earthing switch of short circuit breaking current/withstand - 21kA/3-sec, Making Capacity - 50 kA - 01 No(iii) Aux. contacts - 1NO+1NC-01 No(iv) Stored energy motorized high endurance spring charging mechanism (M1+), with inbuilt spring charging lever and mechanically latched ON/OFF push buttons to allow handle less and un inhibited operation - 01 No(v) Cable terminals (site replaceable Cable bushings situated not beyond 300mm from cable cover to allow ease of access for installation/testing/replacement purposes) with double door arrangement for enhanced safety (IP54+IP3X) interlocked to prevent access up to 11 KV, 120 Sqmm, 3 Core, XLPE AL cable termination in live-condition. Each Set of 3(vi) Right angle boots (push on type) - Each set of 3 (vii) 3O/C + 1E/F self-powered numerical protection relay with Low and High set for Over current and Earth Fault. Relay should have facility to display the maximum loaded phase current also. Relay shall record minimum 5 fault records with time stamping. Relay shall be communicable with RS 485 Port on MODBUS Protocol - 02 No(viii) Associated ring core cast resin insulated CTs 50/1 Amp, 2.5 VA, 5P10 for protection - Each Set of 3 (ix) Arc proof cable covers with self-Interlocking mechanism with earth switch - 01 No Please Enable Macros to View BoQ information |
| 68 | Item No 10.03 Contd...(viii) Capacitive voltage indication fixed type system as per IEC 61243 with LED - 01 Set(ix) Fault Passage Indicator - It is to be provided for each incomer load break unit, FPI with LED/digital display to be added for detection of cable fault - 01 No(x) ON, OFF, EARTH mechanical indication on the front mimic of the panel - 01 No(B) 02 Nos. Outgoing VCB module for 3 Way RMU each consisting of following accessories: -(i) Each function unit consists of a vacuum circuit breaker in combination with a three-position switch. The three-position switch fulfils the operation of the disconnector function and earthing function.(ii) 12kV, 630A Fixed Type VCB module with series disconnector cum earthing switch of short circuit breaking current/withstand - 21kA/3-sec, Making Capacity - 50 kA - 01 No(iii) Aux. contacts - 1NO+1NC-01 No(iv) Stored energy motorized high endurance spring charging mechanism (M1+), with inbuilt spring charging lever and mechanically latched ON/OFF push buttons to allow handle less and un inhibited operation - 01 No(v) Cable terminals (site replaceable Cable bushings situated not beyond 300mm from cable cover to allow ease of access for installation/testing/replacement purposes) with double door arrangement for enhanced safety (IP54+IP3X) interlocked to prevent access up to 11 KV, 120 Sqmm, 3 Core, XLPE AL cable termination in live-condition. Each Set of 3(vi) Right angle boots (push on type) - Each set of 3 (vii) 3O/C + 1E/F self-powered numerical protection relay with Low and High set for Over current and Earth Fault. Relay should have facility to display the maximum loaded phase current also. Relay shall record minimum 5 fault records with time stamping. Relay shall be communicable with RS 485 Port on MODBUS Protocol - 02 No(viii) Associated ring core cast resin insulated CTs 50/1 Amp, 2.5 VA, 5P10 for protection - Each Set of 3 (ix) Arc proof cable covers with self-Interlocking mechanism with earth switch - 01 No Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 21, 2026
11:30 IST
Tender Published
Tender notice published.
Completed
Sep 24, 2026
18:00 IST
Corrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 31 daysSep 24, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 31 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender