Tender For Repair And Maintenance Of Street Light Fitting , Stand By Dg Sets, Timer Switch, Street Light Panels, Service Connections, Earthing And Other Connected Electrical Works At Pal Ur Mil Stn.
Tender Value
Ref. Documents
Estimated cost
Bid Submission
10 Sep 2026
17 days left
EMD
80000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Kangra → Himachal Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair And Maintenance Of Street Light Fitting , Stand By Dg Sets, Timer Switch, Street Light Panels, Service Connections, Earthing And Other Connected Electrical Works At Pal Ur Mil Stn.
BOQ
| Sl. No. | Item Description |
| 1 | Servicing of Diesel Engine Generating sets of different rating as is carried out as schedule given under :-B-Check :-(i) Change lubricating oil (ii) Clean lubricating oil filters (iii) Change fuel filters (iv) Change coolant (v) Check engine wiring for damage (vi) Drain fuel supply tank (vii) Change by pass lubricant filters (viii) Change air filters (ix) Check oil pressure (x) Change fuel water separatorC-Check :-(i) Adjust valves (ii) Steam clean engine (iii) Replace hoses as reqd (iv) Check turbo charger mounting nuts (v) Check engine heater (vi) Clean radiator (vii) Inspect following parts & replace as required (Alternator, starter etc) (viii) Clean fuel tank from inside (ix) Change engine oil(x) Servicing of DG set will be done by Authorised dealer of Kirloskar/Cummins only.Note : (i) Maintenance of Diesel Gen Set as per maintenance schedule chart.(ii) Schedule of service, Diesel Gen Set M/C No wise is attached in PS.(iii) B-Check and C-Check spare parts will be done by Authorised dealer of Kirloskar/Cummins only.(iv) B-Check of DG set items i.e item no. 1.1 to 1.09 |
| 2 | All as per Item No-1.00 above but DG Set 7.5 KVA |
| 3 | All as per Item No-1.00 above but DG Set 30 KVA |
| 4 | All as per Item No-1.00 above but DG Set 40 KVA |
| 5 | All as per Item No-1.00 above but DG Set 62.5 KVA |
| 6 | All as per Item No-1.00 above but DG Set 75 KVA |
| 7 | All as per Item No-1.00 above but DG Set 82.5 KVA |
| 8 | All as per Item No-1.00 above but DG Set 160 KVA |
| 9 | All as per Item No-1.00 above but DG Set 140 KVA |
| 10 | All as per Item No-1.00 above but DG set 250 KVA |
| 11 | Supply only new fuel oil filter elements with 'O' ring for 7.5 KVA DG Set complete all as specified and as directed. |
| 12 | All as per Item No-2.00 above but DG Set 30 KVA |
| 13 | All as per Item No-2.00 above but DG Set 40 KVA |
| 14 | All as per Item No-2.00 above but DG Set 62.5 KVA |
| 15 | All as per Item No-2.00 above but DG Set 75 KVA |
| 16 | All as per Item No-2.00 above but DG Set 82.5 KVA |
| 17 | All as per Item No-2.00 above but DG Set 160 KVA |
| 18 | All as per Item No-2.00 above but DG Set 140 KVA |
| 19 | All as per Item No-2.00 above but DG set 250 KVA |
| 20 | Supply only new Lubricant oil filter cartridge element with 'O' ring for 7.5KVA DG Set complete all as specified and as directed. |
| 21 | All as per Item No-3.00 above but DG Set 30 KVA |
| 22 | All as per Item No-3.00 above but DG Set 40 KVA |
| 23 | All as per Item No-3.00 above but DG Set 62.5 KVA |
| 24 | All as per Item No-3.00 above but DG Set 75 KVA |
| 25 | All as per Item No-3.00 above but DG Set 82.5 KVA |
| 26 | All as per Item No-3.00 above but DG set 160 KVA |
| 27 | All as per Item No-3.00 above but DG Set 140 KVA |
| 28 | All as per Item No-3.00 above but DG set 250 KVA |
| 29 | Supply only new By pass Lubricant Oil filter cartridge element with 'O' ring for 7.5 KVA DG Set complete all as specified and as directed. |
| 30 | All as per Item No-4.00 above but DG Set 30 KVA |
| 31 | All as per Item No-4.00 above but DG Set 40 KVA |
| 32 | All as per Item No-4.00 above but DG Set 62.5 KVA |
| 33 | All as per Item No-4.00 above but DG Set 75 KVA |
| 34 | All as per Item No-4.00 above but DG Set 82.5 KVA |
| 35 | All as per Item No-4.00 above but DG Set 160 KVA |
| 36 | All as per Item No-4.00 above but DG set 140 KVA |
| 37 | All as per Item No-4.00 above but DG set 250 KVA |
| 38 | Supply only new air filter (both outer & inner) element with 'O' ring for 7.5 KVA DG Set complete all as specified and as directed. |
| 39 | All as per Item No-5.00 above but DG Set 30 KVA |
| 40 | All as per Item No-5.00 above but DG Set 40 KVA |
| 41 | All as per Item No-5.00 above but DG Set 62.5 KVA |
| 42 | All as per Item No-5.00 above but DG Set 75 KVA |
| 43 | All as per Item No-5.00 above but DG Set 82.5 KVA |
| 44 | All as per Item No-5.00 above but DG Set 160 KVA |
| 45 | All as per Item No-5.00 above but DG Set 140 KVA |
| 46 | All as per Item No-5.00 above but DG set 250 KVA |
| 47 | Supply only of fuel water separator filter complete with banjo bolt and washer for 7.5 KVA capacity DG Sets complete all as specified and as directed. |
| 48 | All as per Item No-6.00 above but DG Set 30 KVA |
| 49 | All as per Item No-6.00 above but DG Set 40 KVA |
| 50 | All as per Item No-6.00 above but DG Set 62.5 KVA |
| 51 | All as per Item No-6.00 above but DG Set 75 KVA |
| 52 | All as per Item No-6.00 above but DG Set 82.5 KVA |
| 53 | All as per Item No-6.00 above but DG Set 160 KVA |
| 54 | All as per Item No-6.00 above but DG set 140 KVA |
| 55 | All as per Item No-6.00 above but DG set 250 KVA |
| 56 | Supply only of Coolent of DG Set 15W40 grade in DG Set complete all as specified and as directed. |
| 57 | Supply only of Engine oil 15W40 grade in DG Set complete all as specified and as directed. |
| 58 | Supply only V-Belt off sizes, complete all as per site requirement complete all as specified and directed. |
| 59 | Supply only of Oil pressure gauge ISI mark complete all as specified and as directed. |
| 60 | Supply only of Fuel temperature gauge ISI mark complete all as specified and as directed. |
| 61 | Supply only of Fuel gauge meter ISI mark operated on 24V DC complete all as specified and as directed. |
| 62 | Supply only of high temprature diesel Hose pipe of 1000 PSI of size 12.5mm dia for connecting from diesel tank outlet to Engine complete with banjo bolt & washer. |
| 63 | Supply only of high temperature diesel Hose pipe of 1250 PSI of size 10.3mm dia for connecting from engine to diesel tank complete all as specified and directed. |
| 64 | Supply only of distilled water for battery complete all as directed |
| 65 | Dismantling taking down complete radiator assy from DG set form different capacity and transport to workshop for cleaning of the same with suitable cleaning reagent to remove rust & scaling , plugging of any water leakage by brazing and refluxing including replacement of rubber hose pipe complete with jupiter clamps for any capacity of DG Sets, complete all as specified and as directed. |
| 66 | Dismantling of defective dynamo from engine, supplying and fixing new dynamo 24 Volt DC -Make- TVS Lucas,including replacement of worn out nuts bolts mounting clamp etc. complete all as specified and as directed. |
| 67 | Dismantling of self starter 24V DC by disconnecting battery connection, taking out to civil workshop for carrying out following repair work and refuxing including testing complete:- (i) Rewinding of armature & Field coil.(ii) Replacement of Carbon brush and solenoid switch (iii) Replacement of gear assembly. |
| 68 | Supplying and replacement of Digital meter square type 96x96mm suitable for measuring 3-ph combined voltage, ammpermere & frequency simultaneously in three independent windows with ultra LED display complete all as specified and directed. |
| 69 | Supply and fixing 440/volt DC 24 V relay suitable for 140KVA/250 KVA DG Set complete all as specified and directed. |
| 70 | Supply and fixing 220Volt AC 24 V relay suitable for 62.5 KVA/100 KVA DG Set complete all as specified and as directed. |
| 71 | Supplying and replacement self starter 12 Volts DC suitable for DG Set 40/63/82.5/100 KVA complete all as specified and as directed. |
| 72 | Supplying and replacement self starter 24 Volts DC suitable for DG Set 160/200/250 KVA complete all as specified and as directed. |
| 73 | M&L for spray painting to Panels, enclosure of DG sets, duct plates etc at DG installations with two coats of synthetic enamel paint of two coats of synthetic enamel paint of red oxide primer after making the surface free from oil/grease/rust and applying a coat of red oxide primer complete all as specified and as directed. |
| 74 | Supply and fixing Battery 12V, 180 AH with 25 Nos Electro plates including battery lead positive & negative battery terminal complete duly charged . |
| 75 | Supply and fixing Battery 12V, 150 AH with 25 Nos Electro plates including battery lead positive & negative battery terminal complete duly charged . |
| 76 | M & L for Door joint and handle locks arrangement for any size/capacity DG set complete all as specified and directed. |
| 77 | Opening the coupling of DG set of capacity 82.5KVA /250 KVA the outer cover and taking out the fly wheel ring and shifting to workshop for repair in and including replacement of fly wheel ring by pressing machine and reinstated the same after repair to make it fully functional complete all as specified and directed. |
| 78 | Opening the coupling of DG set of capacity 40KVA /82.5 KVA the outer cover and taking out the fly wheel ring and shifting to workshop for repair in and including replacement of fly wheel ring by pressing machine and reinstated the same after repair to make it fully functional complete all as specified and directed. |
| 79 | Supply and replacement of compact type panel mounted battery charger sutable for charging 02 Bty, 12 V 180 AH Each complete all as specified and directed with 2m copper leads -02 Nos & brass clamps. |
| 80 | Supply and replacement of compact type battery charger unit suitable for charging 01 Bty ,12 V 180 AH complete all as specified and as directed with 2m copper leads -02 Nos & brass clamps. |
| 81 | Taking out FIP from DG set , of any cap (40 to 250KVA) transportation to authorised service centre for repair /maintenance and refixing to DG set including replacement of necessary spare parts such as Plunzers, governor kit with pin , Nozzels , Head ball guide kit, Head sheet, Rock rod, Roller bearing, oil seal, piston & rings pain, jain kit and sleeves complete all as directed and specified. |
| 82 | M&L cleaning of diesel tank of DG set of any capacity including replacement of worn out pipe line and measuring scale and fixing in original position and make it leak proof with necessary clamps complete all as specified and directed. |
| 83 | M&L for earthing with steel earth plate electrode of size 60x60x6mm thick buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr deep below normal ground level connected to GI strip of size 32x6mm as earthing lead by means of nuts, bolts and washers of galvanized iron or steel after welding of GI strip to earth electrode to the full length of earth plate, 40mm dia GI tubing light grade protection pipe upto test point, 20mm dia GI watering pipe med grade GI funnel and wire mesh, PCC pit 1:3:6 with pit cover of size 30x30cm made of RCC 1:3:6 with suitable handle,angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, removal of surplus soil and returning fill in all as required at site including test point size not out of steel plate of size 75x75x6mm fixed to wall as specified in plate No 3 of SSR Part-I and directed by GE. |
| 84 | All as per item SrI No 34 above but by using GI wire 4mm dia as earth lead & 15mm bore medium grid pipe for protection of earth wire from plate to main switch board,complete all as specified and as directed. |
| 85 | M&L for provn of Earthing complete with Copper earth plate electrode 600 x 600 x 3 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal GL) with top edge of the plate not less than 1.50 m below normal GL, connected to copper earth strip 25 x 3.15 mm upto 7.5 mtr protection pipe by means of copper bolts, nuts, check nuts and washers incl excavation, PCC (1:3:6) type C-1 chamber with RCC cover (1:2:4) type B0, 40 mm thick reinforced with 6 mm dia bar, 3 Nos. both way, 40mm dia light grade GI protection pipe, funnel with wire mesh,watering pipe of size 20 mm dia med. grade, lugs, main Earthing lead upto 7.5 mtr incl. Charcoal dust, salt etc. all as shown in electrical plate No.3 of SSR Pt-I specification. Note :- (i) The excess requirement (if more than 7.5 Mtr) of copper strip, GI protection pipe 40 mm dia and their joints for connecting upto the test point will be measured and paid separately) (ii) The excavation exceeds,if any of the above will be deemed to be included in the item rate |
| 86 | Supply & Fixing in replacement Lubrication oil pump complete all as specified and directed. |
| 87 | Supply & Fixing in replacement Lubrication oil Pipe complete all as specified and directed. |
| 88 | Supply & Fixing in replacement lever for stopping of engoine as per site requirement for DG set complete all as specified and directed. |
| 89 | Supply and fixing in repairs automatic voltage regulator up to 82.5 KVA as per sample complete all as specified and directed. |
| 90 | Supply and fixing in repairs automatic voltage regulator for 100 KVA to 250 KVA as per sample complete all as specified and directed. |
| 91 | Supply and fixing in repairs automatic voltage regulator suitable for 250 KVA as per sample complete all as specified and directed. |
| 92 | Supply and fixing in replacement of MCCB 125 Amp rating, 4-pole 415V, 50 Hz breaking capacity 16 KA, Adjustable & fixed magnetic setting type. |
| 93 | Supply and fixing in replacement of MCCB 160 Amp rating, 4-pole 415V, 50 Hz breaking capacity 25 KA, Adjustable & fixed magnetic setting type. |
| 94 | Supply and fixing in replacement of MCCB 200 Amp rating, 4-pole 415V, 50 Hz breaking capacity 25 KA, Adjustable & fixed magnetic setting type. |
| 95 | Supply and fixing in replacement of MCCB 250 Amp rating, 4-pole 415V, 50 Hz breaking capacity 36 KA, Adjustable & fixed magnetic setting type. |
| 96 | Supply and fixing in replacement of MCCB 100Amp rating 415V, breaking capacity 16KA. |
| 97 | Supply and fixing in replacement of MCCB 63Amp rating,4-pole 415V, breaking capacity 16KA. |
| 98 | Supplying and fixing of Off-load type Changeover switch 125 Amp, 4-pole, 415 volt, with enclosure type complete all as specified and as directed. |
| 99 | Supplying and fixing of Off-load type Changeover switch 200 Amp, 4-pole, 415 volt, with enclosure complete all as specified and as directed. |
| 100 | Excavation in trenches in any type of soil not exceeding 1.5 mtr in depth and not exceeding 1.5 mtr wide for laying of cables, erection of poles,struts, stays etc and getting out complete all as specified and as directed. |
| 101 | Returning, filling in including spreading, levelling,watering and well ramming excavated soil in layers not exceeding 25 cm thick each, filling back in trenches after cables have been laid and tested, poles,stays,struts have been erected and tested complete all as specified and as directed. |
| 102 | Removal of excavated surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and as directed. |
| 103 | M&L for sand cushioning to under ground cables 8 cm thick before laying the cable and 15 cm, thick after laying, stretching and testing the cable complete all as specified and as directed. |
| 104 | M&L for laying in trenches burnt brick sub class 'B' for cable protection laid adjacent to each other length wise perpendicular to the central axis of cable complete all as specified and as directed. |
| 105 | Taking down old unserviceable underground cable any type and size complete all as specified and as directed. |
| 106 | Supply & laying of UG cable XLPE insulated armoured heavy duty elect cable with stranded aluminium conductor 1100 volts grade cross section area 70Sqmm 3.5 core laid in trenches/ fixing on panels/walls/poles or passing through pipe including connecting with suitable lugs, glands, nuts and bolts and testing complete all as specified and directed. |
| 107 | All as per item No.57 above but of cross sectional area 50 Sqmm, 3.5 core complete all as specified and directed. |
| 108 | All as per item No. 57 above but of cross sectional area 16 Sqmm, 4 core complete all as specified and directed. |
| 109 | M&L for demolition concrete of any description and any position not otherwise specifically provided for floor plinth protection or hard standing complete all as specified and as directed. |
| 110 | M&L Plain cement concrete 1:2:4, Type B-1 by using 20 mm graded granite stone aggregate in coping including necessary form work and finishing exposed surfaces fair & even complete all as specified and as directed. |
| 111 | Supply and fix power contactor 3-pole, 150Amp, 440V rating MCX41 type all as Cat Part No LC1D150M7 complete all as specified and as directed. |
| 112 | Supply and fix coil suitable for MCX41 power contactor all as specified and directed. |
| 113 | M & L for GI Pipe medium grade 100mm bore for cable protection in floor/road crossing/along pole complete all as specified and as directed. |
| 114 | M & L for GI Pipe medium grade 80mm bore for cable protection in floor/road crossing/along pole complete all as specified and as directed. |
| 115 | M&L for removal green vegetation and dressing around the plinth/PCC hardstanding up to 1.5 mtr of sub stations and 2/4 pole structure etc including disposal of vegitation /material up to 50 mtr distance from the site and levelling/surfacing the ground complete all as specified and as directed. |
| 116 | M&L for Trimming /chopping and cutting of branches in each tree of any girth which are coming across the over head line LT up to 3 m both sides from the centre of conductor as required and removing the same from site of work complete all as specified and as directed. |
| 117 | Supply and fix MS Chequred plate 6.0 mm thick sheet having with Hook, and painting it with one coat of black paint suitable for cable duct cover in pump house and sub stn complete all as specified and directed |
| 118 | S&F bus bar chamber TPN suitable for 100A TPN Copper bus bar with four outgoings ways complete all as specified and directed |
| 119 | S&F DG Set control panel display suitable for 40 to 63.5 KVA DG set complete all as specified and directed |
| 120 | Supply & Fixing Air termination, single pointed aluminium rod 12mm dia and 300mm long, complete all as specified and directed |
| 121 | Supply and fixing Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw, complete all as specified and as directed. |
| 122 | Supply and fixing for Aluminium strip of size 25 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground,, complete all as specified and as directed. |
| 123 | Supply and fixing of Galvanised iron strip of size 32 x 6mm buried in ground., complete all as specified and directed. |
| 124 | M&L for scraping, stretching, cleaning the old paint, preparation of the surface for repainting. Painting LT 09 Mtr long steel tubular pole with two coats of aluminum paint and writing pole Nos. including snowsem on PCC muff all as directed by Ge. |
| 125 | M&L Checking of Earth Resistance of GI/Copper /Chemical/Normal Earthing and maintaining the resistance as required Earth Pit 09 Mtr long steel tubular pole with two coats of aluminum paint and writing pole Nos. including snowsem on PCC muff all as directed by Engr-In-Charge. Resistance Tester will be provided by the Contractor/Worker and will be recorded in Register, same will be put up to the Engineer-in-Charge. Contractor will be responsible for pouring of water in the Earth Pits at his own arrangement with Water Tanker, etc. However, water will be provided by the Department. complete all as specified and as directed. |
| 126 | M&L Taking out loose/displaced Serviceable Aluminium Strip/ Copper Strip of any size and any description with Accessories and refixing the same with necessary Fixing Arrangement like Screws, Saddles, Nuts and Bolts, complete all as specified and as directed.NOTE : Cost of Screws, Saddles, Nuts and Bolts, etc. will deemed to be included in the Quoted Unit Rate. |
| 127 | Supply and fixing of Copper Strip 20x3.15mm with Saddles and fixing screws for Roof Earth Conductors and Down Conductors above Ground, complete all as specified and directed. Pure Resin based Chemical anchoring system. |
| 128 | Supply & Fixing porcelain insulator of required size not exceeding than 10 cm long with two nos hole each on both end for fixing properly with fastener, nuts & bolts on wall & roof of buildings for separated earthing stirp from building all as required at site & directed by Engineer In Charge. Note : (i) Water leak protection has to be ensured, Pure Resin based Chemical anchoring system. |
| 129 | Material and labour for overhauling of existing 16/20meters height high mast lighting system by degreasing and cleaning of double drum winch, gear box, wire rope, clamp, bobbin arrangement, power tool motor, mechanical torque limiter, lowering the high mast head assembly, degreasing and cleaning the pulley, docking arm etc and applying new grease / lubricating oil for all mechanical moving / rotating parts, checking all the electrical parts such as timer panel, cable connections in control panel, motor, junction box, flood light fittings and aviation obstruction light fitting including testing for proper functioning complete all as specified and directed by Engineer-in-Charge. Note: Defective spare parts shall be measured and paid seperately. The servicing/Maintenance of the system will be carried out |
| 130 | Supply and fix in replacement of unserviceable battery 12.5 volt, 30Ah lead acid battery type duly charged complete all as specified and as directed. |
| 131 | Supply and fixing LED flood light 100 watt, 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp |
| 132 | S&F surge protection device sitable for LED flood light fitting complete all as specified |
| 133 | M&l for repair to suspension system of high mast light service greasing and cleaning and testing for proper functioning of suspension system complete all as specified and directed. |
| 134 | M&L for dismantling motor from high mast light and bring to civil workshop for servicing and overhauling of motor and replacement defective parts including testing and refixing the same at site complete all as specified and directed by Engr in Charge |
| 135 | S&F LED Curb stone light with blue colour of length 500mm height 200mm and width 150mm with connector male and female including connection with adaptor complete wiring and testing complete all as specified and as directed |
| 136 | S&F connector for curb stone light with DC supply complete with wiring and connected items |
| 137 | Supply and fix in replacement of Integral LED aviation light 6watt, 500 mmwth IP 65 protection fitting comprising of aluminium housing with polycarbonate enclosure including taking down existing unserviceable aviation light of any description complete all as specified and as directed. |
| 138 | Taking down unsev security light fitting, Flood light, and decorative LED light fitting of any wattage from poles / roof at any position and dismentling the light fitting and replace the unsv driver, PCB card and reassemble at the existing bracket and refixing the same complete all as directed by Engr-in-Charge. (Note LED driver and PCB card will be measuredand paid seperately as supply only) |
| 139 | Supply only driver suitable for LED street light fittings of 45 watt complete all as specified and as directed. |
| 140 | Supply only driver suitable for LED street light fittings of 60 watt complete all as specified and as directed. |
| 141 | Supply only driver suitable for LED street light fittings of 90 watt complete all as specified and as directed. |
| 142 | Supply only driver suitable for LED street light fittings of 120 watt complete all as specified and as directed. |
| 143 | Supply only PCB Card suitable for Multi LED Light Fitting of capacity 45 Watt complete all as specified and as directed. |
| 144 | Supply only PCB Card suitable for Multi LED Light Fitting of capacity 60 Watt complete all as specified and as directed. |
| 145 | Supply only PCB Card suitable for Multi LED Light Fitting of capacity 90 Watt complete all as specified and as directed. |
| 146 | Supply only PCB Card suitable for Multi LED Light Fitting of capacity 120 Watt complete all as specified and as directed. |
| 147 | S&F LED Tricolor (Orange/White/Green) 3 in 1 Tiranga Single Strip Light with 18 Meter length, LED Decorative Pole Lighting Etc-Pack of 1, IP 65 rating withstand harsh weather poof complete all as specified and directed. |
| 148 | Supply, fixing & testing 45W LED street light fitting IP66 Powder coated pressure die cast aluminium High power LED street light with heat resistant toughened glass with lens embedded PC cover complete with all accessories duly prewired and suitable fixing arragement for mounting on existing MS frame bracket including connecting the fitting complete all as specified and directed including taking down |
| 149 | Supply, fixing & testing 60W LED street light fitting IP66 Powder coated pressure die cast aluminium High power LED street light with heat resistant toughened glass with lens, complete with all accessories duly prewired and suitable fixing arragement for mounting on existing MS frame bracket including connecting the fitting complete all as specified and directed including taking down |
| 150 | Supply, fixing & testing 90W LED street light fitting IP66 Powder coated pressure die cast aluminium High power LED street light with heat resistant toughened glass with lens, complete with all accessories duly prewired and suitable fixing arragement for mounting on existing MS frame bracket including connecting the fitting complete all as specified and directed including taking down |
| 151 | Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed 10 sq. mm 2 Core nominal cross section in service connections |
| 152 | Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed 16 sq. mm 4 Core nominal cross section in service connections |
| 153 | Supply & Fixing repairs cable junction box made of thermoplastic, halogen free, weather proof with metric Knock outs for cable entry including fourfive pole terminals and cable entry glands for incoming, out going and connection cable with protection grade IP-66/67 of size 205x255x112 mm and suitable for LT under ground cable any size/capacity including bracing clamp,bolts,nuts & washers. complete all as specified |
| 154 | Supply and fixing Double Wall Corrugated (DWC) pipe of size 63mm outer dia and 50mm inner dia confirming to IS:14930 Part-II including necessary pipe fittings such as couplers, end caps, bend etc. including fixed to wall/roof /pole/trench as required with suitable clamps for cable protection complete all as specified and directed. |
| 155 | Supply and fix in repairs time digital switch with built in PCB for street light complete all as specified |
| 156 | S&F LT cubical panel outdoor kiosk type with Aluminium bus bar 3 pin 4 wire metering and comprising of following :- (i) MCCB TPN63A - 01 No for I/C (ii) MCCB SPN 63 Amp -01 for O/G (iii) MCCB SPN 32 Amp -02 Nos complete all as specified |
| 157 | Supply , fixing, testing and commissioning of factory made LT panel board made out of CRCA sheet 3.15mm thick outdoor type totally enclosed with front opening hinged doors with canopy sloped top projected and floor mounted , weather and water proof as per IS-8623 with necessary locking arrangement all as specified and directed including painting with two coats of synthetic enamel paint over a coat of red oxide primer , internal electric connections as required suitable to accommodate the following :- (i) MCCB 100 Amp TPN -01 No( I/C), (ii) MCCB 63A -02 Nos (O/G) , Al bus bar, indication lamps -03 Nos |
| 158 | Supply and fix in repairs, flexible stranded copper conductor cable PVC insulated and PVC sheathed twin core of size 1.5 Sqmm |
| 159 | M&L for replacement of PCC Pit in Cement Concrete 1:3:6 (20mm graded stone aggregate) with Cast iron cover 10mm thick hinged, Cast Iron Frame, MS Rod 6mm, Funnel as shown in Electrical Plate No 3 of MES Schedule Part-I including excavation work required at site, complete all as specified and directed. |
| 160 | M&L for replacement of Pre-cast RCC Cover with Handle 2 Nos and hole of dia 40mm in Cement Concrete 1:2:4 (20mm graded stone aggregate) of size 540x540x60mm, reinforced with and including 10mm dia TMT Bars @ 250mm Centre to Centre in both ways, complete all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 20, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 10, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysSep 17, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 24 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender