Tender For Construction Of 132/33 Kv, 2X80 Mva Gis Substation At Shiv Enclave (Sanganer), Jaipur Alongwith Associated Transmission Lines Including Survey, Supply Of All Equipments/Materials, Erection (Including Civil Works), Testing And Commissioning
Tender Overview
Project Description
Tender for Construction Of 132/33 Kv, 2X80 Mva Gis Substation At Shiv Enclave (Sanganer), Jaipur Alongwith Associated Transmission Lines Including Survey, Supply Of All Equipments/Materials, Erection (Including Civil Works), Testing And Commissioning Against Specification No. Rvpn/Ehv/A&Sp/Tn-165
BOQ
| Sl. No. | Item Description |
| 1 | SUPPLY - 132 KV GIS SUBSTATION AT SHIV ENCLAVE (SANGANER) JAIPUR |
| 2 | SUBSTATION EQUIPMENTS |
| 3 | Power Transformer: |
| 4 | Power Transformer: 132/33 kV, 80 MVA Transformer with all accessories and 10% extra oil in non-returnable steel drums |
| 5 | RTCC Panel fitted with Transformer Monitoring cum Tap changer control System (TCS) alongwith associated acessories complete in all respect. |
| 6 | 132 kV Indoor GIS Switchgear Equipments |
| 7 | 145kV, 1250A, SF6 gas insulated Transformer bay module each comprising of SF6 gas insulated circuit breaker, current transformer, bus-bar disconnectors with common earthing switch, line disconnector with safety earthing switch, surge arrestors, SF6 gas monitoring system for complete bay, local control cubicle, SF6 Gas Insulated terminal connection for connecting Power Transformer (Air/ XLPE) with GIS through XLPE cable with cable termination enclosure and other accessories etc. to complete transformer bay module as indicated in the SLD/ Layout of substation and as per technical specifications. |
| 8 | 145kV, 1250A, SF6 gas insulated Feeder bay module each comprising of SF6 gas insulated circuit breaker, current transformer , bus-bar disconnectors with common grounding switch, line disconnector with safety grounding switch, high speed fault making grounding switch, surge arrestors, PT , SF6 gas monitoring system for complete bay, local control cubicle, gas insulated terminal connection for connecting XLPE cable with cable termination enclosure and other accessories with GIS etc. to complete feeder bay module as indicated in the SLD/ Layout of substation and as per technical specifications. |
| 9 | Double Bus Arrangement, 145kV, 3 Phase, SF6 gas insulated metal enclosed 2500A bus bars running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus bar set shall be complete with voltage transformer complete disconnector with safety earthing switch, local control cubicle (if required), SF6 gas monitoring system etc. for the complete bus as indicated in the SLD/ Layout of substation and as per technical specifications. |
| 10 | 145kV, 2500A, SF6 gas insulated Bus Coupler Bay Module comprising of SF6 gas insulated circuit breaker, current transformer, disconnectors with safety earthing switches, Local control cubicle, SF6 gas monitoring system for complete bay etc. as indicated in the SLD/ Layout of substation and as per technical specifications. |
| 11 | Suitable Capcity EOT Crane for GIS Hall/ Building |
| 12 | Ventilation system for GIS Hall/ Building (as per technical specification) |
| 13 | 36 kV Metal Clad GIS Indoor Switchboard |
| 14 | Metal clad Double Bus Indoor GIS Switchboard Including 2 No. Incomer Transformer Feeders, 10 No. Outgoing Feeders and 1 No. bus-Coupler (as per SLD) alongwith all associated accessories CTs. PTs, Control Cubicle and Complete with the Control & Protection schemes [ 36 kV, 3150A, 31.5 kA Class] alongwith 0.2 S class AC Static HT-TVM TOD type Energy Meter |
| 15 | Cable Termination/ Plug for terminating in Metal clad switchgear panels for 9 Nos. of Outgoing Feeder panels (for 2 Nos. 3-Phase Outgoing cable circuit in each) from each (Normally cable sizes is 300 Sq. mm or more and exact size shall be decided with the distribution company during detailed engineering) |
| 16 | 33 kV XLPE Cables & Accessories |
| 17 | 3 C, 95 Sq. mm. Al., 33 kV XLPE Cable with Suitable Outdoor & Indoor Terminations [3+3] for connecting the HV side of Substation Transformer to O/G of 36 kV Metal Clad GIS Switchgear |
| 18 | 1C, 1000 Sq. mm, Al., 33 kV XLPE Armoured Cable alongwith accosciated accessories and required material as per laying method adopted etc. (This include 12 lengths of cable with suitable Outdoor & Indoor [12+12] end Terminations) |
| 19 | C&R Panels & SAS system (Complete in all respect, refer Section-V A, B, Part-III, Volume-II) |
| 20 | 132 kV C&R Panel Type SAS-FCA |
| 21 | 132 kV C&R Panel Type SAS-FRA (with Numerical, Communicable Line Current Differential protection scheme as per scheme of main protection at point no. 9.3 of Technical Specification of C&R Panel) |
| 22 | 132 kV C&R Panel Type SAS-BCRA |
| 23 | 132 kV C&R Panel Type SAS-TCRA |
| 24 | 132 kV C&R Panel Type SAS-BBRA |
| 25 | Substation SAS Netorking Panel SAS-NW |
| 26 | Station HMI [Industrial grade Computer with Approx. 21\\"TFT monitor as per specification requirements] |
| 27 | Station HMI (Hot Standby) [Industrial grade Computer with Approx. 21\\"TFT monitor as per specification requirements] |
| 28 | HMI View Node[Industrial grad Computer with Approx. 21\\"TFT monitor as per specification requirements] |
| 29 | DR Work Station[Industrial grade Computer with Approx. 21\\"TFT monitor as per specification requirements] |
| 30 | A3 Size Color Laser Printer |
| 31 | Dot Matrix Printer |
| 32 | One Remote Workstation with HMI[Industrial grade Computer with 21\\"TFT monitor as per specification requirements] & Laser Printer (A4 Size) for RCC |
| 33 | Hardware Gateways (for data transmission to RCC & SLDC) |
| 34 | Modems (both sending and Receiving End) for communication to RCC & Sub SLDC[if required as Communication Equipments are proposed] |
| 35 | Software: Application as well as System Software as per specification requirements for various hardware elements for meeting of functional requirement of the specification. |
| 36 | Substation LAN Commnication Infrastructure |
| 37 | Ethernet Switches: |
| 38 | 132 kV Side C&R and Network Panels:16 Nos.{12 Port (8 Nos. 10/100 BaseTX + 4 No. 10/100/1000 Base FX)}, 2 Nos. {24 Port 10/100 Mbps TX + 4 port 10/100/1000 Base FX}] |
| 39 | 33 kV Side C&R Panels: 2 Nos.{16 Port (12 Nos. 10/100 BaseFX + 4 No. 10/100/1000 Base FX)} |
| 40 | Other Items: |
| 41 | Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the substation/ swithcyard LAN as per specification requirements. |
| 42 | Inverter (3 kVA Capacity) to be operatable on 230VAC and 220 VDCas per availability of supply (Normally on AC) |
| 43 | Inverter (1 kVA Capacity) to be operatable on 230VAC and 220 VDC as per availability of supply (Normally on AC) |
| 44 | 132 kV XLPE Cable & Termination |
| 45 | 500 Sq. mm 132 kV XLPE Cable |
| 46 | 132 kV Outdoor Cable Termination for XLPE to Air Termination on HV Side of Power Transformer |
| 47 | 132 kV GIS Termination for XLPE Cable |
| 48 | Solid bonding Link box with Link plates, bonding & grounding cable complete with other associated accessories for 1-phase |
| 49 | Surge Arresters |
| 50 | 132 kV Class of 120 kV rating LA's with grading ring discharge counter with mili ammeter |
| 51 | 33kV class of 30kV rating LAs |
| 52 | 33kV/415V, 250kVA station transformer complete with all accessories, fittings, terminal connectors etc as specified filled with transformer oil |
| 53 | Batteries & Battery Charger |
| 54 | Batteries (Sizing shall be as per requirement of technical specification) |
| 55 | 220 V [Min 400 AH] |
| 56 | 48 V [Min 300 AH] |
| 57 | Battery Charger System |
| 58 | 220 V Float and Boost |
| 59 | 48 V Float and Boost |
| 60 | Lighting System |
| 61 | Outdoor Lighting & other Works |
| 62 | Lighting Fixture Type -SF2 as per Specification |
| 63 | Lighting Fixture Type -EEC2 as per Specification |
| 64 | Lighting Fixture Type -SF1 as per Specification |
| 65 | Lighting Fixture Type -EEC1 as per Specification |
| 66 | Emergency Lighting Type-PF |
| 67 | Type-RO, 15A, 240V: Outdoor Receptacle 2 pole, 3-pin type |
| 68 | Type-RP, 63A, 415V : Interlocked switch socket outdoor Receptacle |
| 69 | Hot Dip Galvenized Octogonal Lighting Poles (12 m) |
| 70 | Street Lighting Type-EEA for mounting on above Poles |
| 71 | Sub-Lighting Boxes/Panels Type -SLP at Lighting Mast complete with all controgears and accessories, items etc. |
| 72 | Lighting Panel Type ACP-3 as per technical specification |
| 73 | Indoor Lighting & Other Works |
| 74 | Electrification |
| 75 | Electric Fitting (if not covered under Civil Works) with G.I. Conduit, Junction Boxes, pull out boxes, copper wiring, Modular Switchboards, Modular Switches, GI Wire (16SWG) etc. for control room, GIS Hall and administrative office building as per the requirements of the specifications |
| 76 | Illumiation |
| 77 | Lighting fixtures and Receptacles (including accessories/ materials etc. as per requirement alongwith complete accessories and mounting arrangements) |
| 78 | Indoor Lignting Panels |
| 79 | Lighting Panel (Indoor) Type ACP-1 as per technical specification |
| 80 | Lighting Panel (Indoor) Type DCP as per technical specification |
| 81 | Wall mounted fans Approx. 400 mm sweep |
| 82 | Ceiling Fan - Approx. 1400mm sweep with electronic Step regulator |
| 83 | Exhaust Fans |
| 84 | Fire Fighting System |
| 85 | Nitrogen Injection Fire Protection System for Power Transformer complete in all respects. |
| 86 | Fire Fighting equipment with necessary mounting stands. |
| 87 | DCP Type |
| 88 | i) 6 Kg. |
| 89 | ii) 9 Kg. |
| 90 | Carbon di oxide type – 4.5 Kg |
| 91 | Foam Type- Around 9 Liters |
| 92 | Sand type |
| 93 | i) GI Buckets Around 9 liters capacity |
| 94 | ii) Steel Stands for four buckets |
| 95 | Fire Detection and Alarm System |
| 96 | Siren along with all accessories as specified in technical specification |
| 97 | Microprocessor based Fire Detection & Alarm System alongwith the Desktop, System and application software for geographic monitoring and detection of fires, display of events and alarms etc. as specified in technical specification |
| 98 | Photo-electric Detectors, Smoke Detectors, Heat Detectors, Linear Heat Sensing Cables, Manual Call Points etc. Control Room, GIS Hall, Office Building, Store, Testing Laboratory etc. |
| 99 | Power & Control Cables for fire detection & alarm system |
| 100 | Air Conditioning System |
| 101 | High Wall Split AC units of 2 TR Capacity complete with Indoor, Outdoor Units and required accessories, Stablizers etc. |
| 102 | Substation Structures/Supports & Switchyard Erection |
| 103 | 145 kV GIS Switchgear Interconnections for Incomer Line (from incoming 132 kV XLPE Cable for which Cable Termination Kit with support to be supplied by Cable System Contractor) complete with all necessary enclosure support, clamps, connectors and other accessories for successful connection to GIS Switchgear as per Layout of the substation. |
| 104 | 145 kV GIS Interconnections for Transfomer Bay complete with all necessary enclosure support, clamps, connectors, other accessories for successful connection to GIS Switchgear as per Layout of the substation. |
| 105 | 33 kV Transformer Bay (from Power Transformer LV Terminals to SA, Isolator/ PI for Cable Termination) [Complete with Three Phase Al. (50 mm. Size) tubular conductor, Clamps (rigid/flexible/expansion type), Connectors, Straight/V/Y Taps, nut-bolts and other accessories] as per Layout of the substation. |
| 106 | Tubular/ Lattice Support for Equipments [Complete with all accessories] |
| 107 | 132 kV Side |
| 108 | 132 kV side Surge Arrestor |
| 109 | 132 kV Cable Termination (XLPE to Air termination for Power Transformer) |
| 110 | Isolators |
| 111 | 33 kV Side |
| 112 | Isolators (3 Phase) with Single Earth Switch |
| 113 | 33 kV XLPE Cable Termination support structure for Connecting to 33 kV Side of 132/33 kV Transformer including 33 kV Class of 30 kV rating LAs (3 Nos.), Supporting PI String (3 Nos.), nut bolts, fixing accessories etc. as per drawing appended in Section-IV of specification |
| 114 | Lightning Cum Lighting Masts |
| 115 | Post Insulators |
| 116 | 36 kV class Post Insulator Stack |
| 117 | Other Steel Structures/ members to be designed/ provided by the bidder for the project [Various items such as Galvenized/ Mild Steel Channels, Angles, Plates, round, joist, Hot dip galvenized Nut-Bolts, Electro Galvenized Spring Washers etc. considered for this component of price schedule] [ This shall also include the steel to be used in the civil works excluding reinforcement] |
| 118 | Marshalling KIOSK/box |
| 119 | AC Distribution Boxes (Outdoor Type) |
| 120 | Outdoor AC Distbibution Box (Double Front type) |
| 121 | Conduits, Cable Trays, Cable Tags, Cable Racks & Supports, Cable Glands, Cable Lugs, Gland Plates, Junction Boxes [Excluding the conduits, junction boxes etc. required for electrical & Lighting fittings/fixtures installation in control room building] |
| 122 | Isolators |
| 123 | Horizontal double break (HDB) motor operated 33kV isolator complete with all fittings including post insulators, accessories, terminal connectors and all other items (as specified in technical specification for 2000 A HDB isolator with single earth switch) |
| 124 | LT Switchgear |
| 125 | LT AC Main Panel |
| 126 | LT AC Distribution Board |
| 127 | Main Lighting Distribution Board |
| 128 | Emergency Lighting Distribution Board |
| 129 | 220V DCDB |
| 130 | 48V DCDB |
| 131 | Earthing System |
| 132 | 40 mm Dia MS Rod |
| 133 | 40 mm dia 3000 mm long MS rod (earth electrodes) with/without test links, RCC pits, C.I .cover hinged at C.I. frame alongwith all associated civil works |
| 134 | 40 mm dia, 3000 mm long GS pipe electrodes with test links and treated earth pits with C.I. cover hinged to C.I. frame alongwith all associated civil works |
| 135 | 3m, 20 mm Dia MS Rod Electrode |
| 136 | 3m, 40 mm Dia MS Rod Electrode |
| 137 | 3m, 42 mm Dia Safe Earthing Electrodes |
| 138 | 3m, 60 mm Dia Safe Earthing Electrodes |
| 139 | 50X12 mm GS Flat |
| 140 | 50X6 mm GS Flat |
| 141 | 50 X 6 mm MS Flat |
| 142 | 25 X 3 mm GS Flat |
| 143 | 50 X 6 mm Copper Flat (for GIS Switchgear Sceening, Sheilding and Earthing) |
| 144 | 3 m, 25 mm Copper Rod |
| 145 | Earth Enhancing Compound for treated pits as above and other requirement as per specification |
| 146 | 1.1kV Grade PVC insulated Al. conductor power cables and copper conductor armoured control cables [Excluding the wiring required for electrical & Lighting fittings/fixtures installation in control room building] |
| 147 | Power Cables(XLPE) |
| 148 | 3.5Cx300 sq.mm |
| 149 | 3.5C x 185 sq.mm |
| 150 | Power Cable(PVC) |
| 151 | 1Cx150 sq.mm |
| 152 | 3.5Cx70 sq.mm |
| 153 | 3.5Cx35 sq.mm |
| 154 | 4Cx16 sq.mm |
| 155 | 4Cx6 sq.mm |
| 156 | Control Cable (PVC) |
| 157 | 2Cx6 sq.mm |
| 158 | 4CX4 sq.mm. |
| 159 | 4CX6 sq.mm. |
| 160 | 2Cx2.5 sq.mm |
| 161 | 4Cx2.5 sq.mm |
| 162 | 5Cx2.5 sq.mm |
| 163 | 7Cx2.5 sq.mm |
| 164 | 10Cx2.5 sq.mm |
| 165 | 14Cx2.5 sq.mm |
| 166 | 19Cx2.5 sq.mm |
| 167 | For Establishment of fiber optic communication Link beween 132 kV GIS Siv Enclave (Sanganer) and Terminal Substations (220 kV GSS Sanganer and 220 kV GSS Mansarovar) |
| 168 | FOTE Terminal Equipments |
| 169 | OLTE equipment consisting of fully wired cabinet with base 19\\" equipment rack (incl. front cover, cable tray, common cards) with fan unit and control synchronization, Alarm, dual power supply input cables |
| 170 | Central Processing Card - CPU |
| 171 | Power supply unit -48VDC |
| 172 | OLTE - 4 Port STM-4 (633 Mbps Card) alongwith SFPs |
| 173 | OFC Patch Cords - (Set of 48 Nos.) |
| 174 | 8 Port 2w/4w E&M Interface Card |
| 175 | 4 Port Data Interface Card (Programmable) |
| 176 | Line Differential relay interface card (4 ports) |
| 177 | 12 Port Ethernet over SDH transport card (with four 10/100 DaseT, one 100Base-FX and one 1000Base-LX/SX Front interfaces) |
| 178 | Interface cables for Power, data, voice, teleprotection, time synchronisation etc. as per respective site requirement (1 lot for each site) |
| 179 | Engineering Order Wire Phone (VoIP Phone) |
| 180 | Optical Fibre Distibution Panel (for 96 Fibre) with splicing and patch ferrule |
| 181 | Craft Terminal Laptop with configuration Software for all Communication Equipments as offered (Core 7 processing family, 3.1GHz & above 15.0\\" LED,1TB HDD, 8GB RAM, DVD R/W) with configuration Software with latest preloaded licensed Microsoft Window OS as offered ) |
| 182 | TESTING & MEASURING INSTRUMENTS, TOOLS & TACKLES AND MISCELLANEOUS ITEMS |
| 183 | TESTING EQUIPMENT/ INSTRUMENTS [This shall consist of all the standard accessories, cables, software etc. required for satisfactory operation of equipment meeting functional requirements] |
| 184 | Insulation Tester |
| 185 | 5 KV , Digital |
| 186 | Dew Point Meter |
| 187 | SF6 Leakage Detector |
| 188 | SF6 Gas Filling, Evacuation, Filtering, Drying, Storage and Pumping Plant |
| 189 | Digital Multimeter |
| 190 | Earth Resistivity tester |
| 191 | Universal relay test kit |
| 192 | Analog Multimeter |
| 193 | Digital Tong Tester ( Low Range) |
| 194 | Maintenance Tools& Tackles |
| 195 | GIS Tools & Tackles |
| 196 | Inspection tools for dismantling nozzles of Circuit Breakers |
| 197 | Inspection tools for Dismantling arc contacts for Circuit Breakers |
| 198 | Box spanner, hexagonal spanner and snap ring cutting pillar for Circuit Breakers |
| 199 | Operating handle for manual operation for earthing switch |
| 200 | Operating handle for manual operation for disconnectors |
| 201 | Gas Mask |
| 202 | General Tools & Tackles |
| 203 | Oil Sampling Bottle (1 Liter Capacity) |
| 204 | Vaccum Cleaner |
| 205 | Telescopic ladder aluminium 6 meter height |
| 206 | Ring spanner set |
| 207 | Tube spanner set |
| 208 | Pipe wrench 24 inch |
| 209 | Pipe wrench 18 inch |
| 210 | Hydraulic crimping tools up to 1000 sq.mm |
| 211 | Threading die set for pipe threading |
| 212 | Welding machine (arc welding) 10kVA |
| 213 | Heavy duty drilling machine |
| 214 | Bench Vice |
| 215 | Insulated cuttingplier 12 inch |
| 216 | Insulated cuttingplier 8 inch |
| 217 | Screw driver 18 inch |
| 218 | Screw driver 12 inch |
| 219 | Hammer 8 lbs |
| 220 | Hammer 2 lbs |
| 221 | Chain pulley block 5 ton |
| 222 | Pipe derrick |
| 223 | Allen Keys |
| 224 | Box Spanners |
| 225 | Office and Miscellaneous Equipments/ Items |
| 226 | Insulation Rubber mat (5mX1mX 3 mm) |
| 227 | Isulation Rubber Gloves (15 kV Tested) |
| 228 | Furniture for Control Room Building: |
| 229 | Executive Desk bulit in wood and steel with lockable drawings on both side (6 feetX2 ½ feetx 2 ½ feet) |
| 230 | Junior executive table with three drawings on right side One Cup board left side with prelaminated decolam top 20mm thick over painted M.S. Frame ( 4 ½ feet x 2 ½ feetx 2 ½ feet). |
| 231 | Library Shelf with Glass Door (min 4 Shelf) |
| 232 | Steel tubular “S” type with continuous and one feet dia 14guage pipe, cane seat backing, teak wood with quality cane. |
| 233 | SCADA Room Furniture (Control Desk for specified consoles and Revolving Chair) matching with the overall interiors as per specification |
| 234 | Archival Storage 4 Drive Type |
| 235 | Lateral Filing Cabinets |
| 236 | 3 Drawer Unit |
| 237 | 4 Drawer Unit |
| 238 | Steel Almirah of size 6 ½ feetx 3 feet x 19 inch with four shelves making five compartments in 18 guage with three way locking system. |
| 239 | Steel Almirah (with Glass doors) of size 6 ½ feetx 3 feet x 19 inch with four shelves making five compartments in 18 guage with three way locking system. |
| 240 | Minor Almirah of size 4 ½ feet x30 inch x 17 inch with three shelves making four compartments in 18 guage with three waylocking system. |
| 241 | Steel rack of size 5 feet x 3 feet x 16 inches with six shelves making five compartments ( 22 guage). |
| 242 | Steel file trays of size 16 inches x11 inches x 3 inches of guage 14 SWG. |
| 243 | Steel stools of size 15 inch x15 inch x 18 inch square pipe 16 guage |
| 244 | Steel waste paper baskets of size 12 inch (H) and Approx. 10 inch Dia Round. |
| 245 | Key board (wooden) with Glass door |
| 246 | First Aid Box |
| 247 | Shock Treatment Chart [Laminated with Frame] |
| 248 | Safety Instruction Boards [ Laminated with Frame] |
| 249 | Drinking Water Arrangement |
| 250 | Water Cooler (Storage type, Storage Capacity 40 Ltr, Cooling Capcity 20 Ltr./hr) |
| 251 | RO/ Water Purifier |
| 252 | Refrigirator (380 Lt.) |
| 253 | Substation Name Board [1 No. Glow Type & 1 No. Painted Type] [Size and Color etc. be got approved from owner] |
| 254 | Danger Plate [Size and Color etc. be got approved from owner] |
| 255 | MANDATORY SPARES |
| 256 | POWER TRANSFORMER |
| 257 | HV bushing with metal parts and gaskets |
| 258 | LV bushing with metal parts and gaskets |
| 259 | Neutral bushing with metal parts and gaskets |
| 260 | Magnetic oil level gauge with low oil level alarm contacts |
| 261 | Winding temperature Hot indicator |
| 262 | Oil temperature indicator |
| 263 | Pressure relief device |
| 264 | Cooler fans |
| 265 | Buchlotz Relay |
| 266 | Complete set of Gasket |
| 267 | 132 kV Indoor GIS Switchgear Equipments |
| 268 | SF6 Gas pressure relief devices |
| 269 | Pressure gauges(of each type) alongwith Coupling device |
| 270 | Rubber Gaskets \\"0\\" Rings and Seal for SF6 Gas |
| 271 | Molecular filter for SF6 gas sets |
| 272 | Density Monitor for SF6 Gas |
| 273 | All type of Control Valve for SF6 Gas |
| 274 | Bottles of SF6 Gas (40 Kg each) |
| 275 | Closing coils for circuit breakers |
| 276 | Tripping coils for circuit breakers |
| 277 | Control switch and auxiliary relays of each type for local control cubicle |
| 278 | Miniature Circuit Breaker (as applicable) of each type |
| 279 | Operating Mechanism for Disconnectors |
| 280 | Operating Mechanism for Earth Switch |
| 281 | Motor for Disconnectors |
| 282 | Motor for Earth Switch |
| 283 | Motor for Circuit Breaker Operating Mechanism |
| 284 | One complete set of circuit breaker |
| 285 | Contact fingers and nozzles for circuit breakers |
| 286 | Valve block with drive cylinder for circuit breakers |
| 287 | One complete set of isolator and earthing switch (Single Phase Unit) |
| 288 | 36 kV Metal Clad GIS Switchgears |
| 289 | Drive Mechanism for Circuit Breaker |
| 290 | Drive Mechanism for Combined Disconnector |
| 291 | Spring Charge motor |
| 292 | Trip Coil |
| 293 | Close Coil |
| 294 | Rupture Disk/ Diapharm |
| 295 | LV Panel Equipments: Relay, MCB, Lamps, Push Buttons, terminal Blocks |
| 296 | Pressure Switches |
| 297 | Rubber Gaskets |
| 298 | CT (Each Rating) |
| 299 | Bay Control & Protection Unit |
| 300 | C&R Panels & SAS System |
| 301 | Bay Control Unit |
| 302 | Bay Protection Unit (Distance & Differential each type used) |
| 303 | Bay Unit/ Module for Busbar Protection System (each type used) |
| 304 | Breaker failure relay (numerical type) |
| 305 | Trip circuit supervision relay |
| 306 | Self reset trip relay (Each Type) |
| 307 | Hand reset trip relay (Each Type) |
| 308 | Timer relay (Each Type) |
| 309 | DC supervision relays |
| 310 | Flag relays (Each Type) |
| 311 | Auxiliary relays (Each Type) |
| 312 | Hard Disk Used in HMI Computer |
| 313 | Network Card With Driver Used in HMI Computer |
| 314 | Fan Assembly for HMI Computers |
| 315 | HMI Server/ Computer as supplied (CPU Part Only) |
| 316 | HMI View Node/ DR Computer as supplied (CPU Part only) |
| 317 | Mouse (Each Type) |
| 318 | Keboard (Each Type) |
| 319 | Fiber Optic Cable with Connectors (5 Nos. of each length used) |
| 320 | Ehternet LAN Cables with connectors (5 Nos. of each type used) |
| 321 | Transducers (2 Nos. of Each Type used in the autoamtion system) |
| 322 | Ethernet Switches (each type used) |
| 323 | Station Transformer |
| 324 | 10% of total Transformer Oil quantity in non-returnable drums |
| 325 | HV bushing |
| 326 | LV bushing |
| 327 | Pressure relief device |
| 328 | Tap charger contact |
| 329 | Set of valves |
| 330 | Set of gasket |
| 331 | Silica gel required for five replacements |
| 332 | Surge Arrester |
| 333 | 132 kV class 120 kV rating LA complete as specified. |
| 334 | 2 Nos. Terminal connector of each type as spare |
| 335 | 33kV class 30 kV rating LA complete as specified. |
| 336 | 2 Nos. Terminal connector of each type as spare |
| 337 | Battery & Battery Charger |
| 338 | 220 V & 48 V Type Battery |
| 339 | Spare battery cell without electrolyte |
| 340 | Terminal connectors with bolts & Nuts (each type) |
| 341 | Float level indicators (each type) |
| 342 | Vent Plugs (each type) |
| 343 | 220V/ 50V Battery Chargers |
| 344 | Set of Control Cards (each type) |
| 345 | Set of relays |
| 346 | Set of contactor |
| 347 | Micro-switches |
| 348 | Filter Capacitors |
| 349 | Thyristor/ Diode |
| 350 | Set of switches |
| 351 | Set of wound resistors |
| 352 | Potentiometers |
| 353 | Fuses of Thyristor with indicators |
| 354 | L.T. SWITCHGEAR : |
| 355 | Relays |
| 356 | CTs AND PTs |
| 357 | Switches/Push buttons and Meters |
| 358 | TPN Switches/MCB |
| 359 | L.T. Breaker spares |
| 360 | a) Spring charging motor |
| 361 | b) Aux. Contact sets |
| 362 | c) Busbar Seal off insulators |
| 363 | d) Arc-chutes |
| 364 | e) Moving contacts |
| 365 | f) Arcing contacts (Fixed/Moving) |
| 366 | g) Springs (Closing/Opening) |
| 367 | h) Closing coil |
| 368 | i) Tripping coil |
| 369 | j) Aux. finger contact |
| 370 | k) Limit switches |
| 371 | l) Jaw contacts |
| 372 | Busbar |
| 373 | a) Busbar insulators |
| 374 | b) Interphase barrier |
| 375 | c) Busbar strip 1mm (Aluminium) |
| 376 | LIGHTING SYSTEM |
| 377 | MCB (10 Nos. of each type and ratings which shall be supplied) |
| 378 | Triple pole MCB (2 Nos. of each type and rating which shall supplied) |
| 379 | Lighting Fixture (5% of each type of Lighting Fixture which shall be supplied) |
| 380 | Celing Fan of Supplied Type |
| 381 | Electronic Regulator for Celing Fans |
| 382 | Exhaust Fan |
| 383 | Clamps & Connectors (Each type) |
| 384 | Fire Protection System |
| 385 | NIFPES System |
| 386 | Fitted Nitrogen Cylinder [48 Lit Water Capacity] |
| 387 | Hose Pipe with Fittings |
| 388 | Heat Sensor Assembly |
| 389 | Fire Survival Cable [sufficient for 1 system] |
| 390 | Limit Switches for Fire Detector |
| 391 | Fire Detector (for NIFPES System) |
| 392 | Thermostat |
| 393 | Heating Element |
| 394 | Isolators |
| 395 | Solid core insulator stacks (Requirement of one Isolator) |
| 396 | Limit switches and auxiliary switches-- Each Set containing one no. of each type and rating as offered |
| 397 | Bearings (Requirement of one Isolator) |
| 398 | Current carrying assembly 2000A total (Requirement of one Isolator) |
| 399 | Relays, power contactors, MCB’s switch fuses, push buttons and resistors, timers, key inter lock for electrical control circuit as per approved schematic-- Each Set containing one no. of each type and rating as offered |
| 400 | Motor with gear assembly and bevel gear assembly. |
| 401 | Terminal connectors 1 set containing 1 No of each type. |
| 402 | Add: Any other item bidder may require to complete the GIS as well as EHV XLPE Cable System as per specification requirements |
| 403 | SUPPLY LINE WORK- Proposed 132 kV underground cable using 1 Core 630 sq. mm Copper XLPE cable, LILO (Loop In Loop Out) of one circuit of the existing 132 kV Sanganer – Mansarovar Double Circuit transmission line (Length Approx 4 KM) |
| 404 | Overhead Line |
| 405 | Monopole Type - 132kV D/C Tension Pole *PD(30-60d)_18mBxA\\" with 2 Nos. Aux Cross Arm for cable termination of LILO Ckt |
| 406 | Conductor |
| 407 | ACSR Panther conductor |
| 408 | Panther conductor hardware |
| 409 | a) Single Suspension Hardware |
| 410 | b) Single tension Hardware |
| 411 | c) M.S Joint |
| 412 | d) Al. Repair sleeve |
| 413 | e) Vibration damper |
| 414 | f) PA Rod |
| 415 | DISC INSULATORS (B&S type) |
| 416 | Disc Insulator 70 KN (B&S type) |
| 417 | Disc Insulator 120 KN (B&S type) |
| 418 | Earthing material |
| 419 | a) Pipe type |
| 420 | 24 Fibre (DWSM) OPGW Fibre cable |
| 421 | Installation Hardware set for above 24 fibre OPGW Fibre optic cabling includdind all cable fiting & accessories except joint box |
| 422 | Joint Box for (24 fibre) OPGW/OFC |
| 423 | Others |
| 424 | a) Number plate |
| 425 | b) Phase plate |
| 426 | c) Danger plate (132 KV) |
| 427 | UNDERGROUND CABLE & ACCESSORIES |
| 428 | 132 kV, Single Core 630 Sq. mm XLPE Copper Cable as per foregoing specification requirements |
| 429 | 145kV rated Voltage Pre-moulded Straight Through Joint suitable for above Cable |
| 430 | 145 KV rated voltage premolded Straight through Joint (with provision for sheath separation for cross bonding/ Mid point Earthing) suitable for above underground cable as per foregoing specifications |
| 431 | 145 kV rated voltage pre-moulded outdoor end termination kit complete with accessories suitable above Cable |
| 432 | 145 kV Plug in type pre-moulded outdoor end termination kit complete with accessories suitable above Cable and suitable for termination end GIS type switchgear end |
| 433 | Solid bonding Link box with Link plates, bonding & grounding cable complete with other associated accessories for 1-phase |
| 434 | Cross bonding Link box/ Mid Point Earthing, Co-axial/ Solid bonding cable, Sheath Voltage Limiters (SVL) (as per requirement) complete with other associated accessories for each 3-phase circuit |
| 435 | Galvanized steel supporting structures/ arrangement etc. for suitable and safe termination of XLPE cable to GIS switchgear |
| 436 | Earthing Material including cast iron pipes with suitable clamps, charcol, common salt etc. (for each circuit) |
| 437 | Terminal connector suitable for Panther Conductor on the Outdoor cable termination to connect cable end termination to ACSR Panther Line |
| 438 | Warning Tapes as per Specification |
| 439 | 24 Fibre OFC and hardware fittings/ accessories alongwith associated , Joint Box & accessories /items as per specification |
| 440 | OFAC/OFC and hardware fittings/ accessories alongwith associated Fibre optic Distribution Panel & accessories |
| 441 | 132kV class of 120kV rating LA with grading ring, discharge counter with milli meter |
| 442 | Line differential cum distance protection relay at both ends of GSS |
| 443 | Add: Any other item bidder may require to complete the Cable System as per specification requirements |
| 444 | Spare |
| 445 | 132 kV, Single Core 630 Sq. mm XLPE Copper Cable as per foregoing specification requirements |
| 446 | 145kV rated Voltage Pre-moulded Straight Through Joint suitable for above Cable |
| 447 | 145 KV rated voltage premolded Straight through Joint (with provision for sheath separation for cross bonding/ Mid point Earthing) suitable for above underground cable as per foregoing specifications |
| 448 | 145 kV Plug in type pre-moulded outdoor end termination kit complete with accessories suitable above Cable and suitable for termination end GIS type switchgear end |
| 449 | SERVICE - 132 KV GIS SUBSTATION AT SHIV ENCLAVE (SANGANER) JAIPUR |
| 450 | SUBSTATION EQUIPMENTS |
| 451 | Power Transformer: |
| 452 | Power Transformer: 132/33 kV, 80 MVA Transformer with all accessories and 10% extra oil in non-returnable steel drums |
| 453 | RTCC Panel fitted with Transformer Monitoring cum Tap changer control System (TCS) alongwith associated acessories complete in all respect. |
| 454 | 132 kV Indoor GIS Switchgear Equipments |
| 455 | 145kV, 1250A, SF6 gas insulated Transformer bay module each comprising of SF6 gas insulated circuit breaker, current transformer, bus-bar disconnectors with common earthing switch, line disconnector with safety earthing switch, surge arrestors, SF6 gas monitoring system for complete bay, local control cubicle, SF6 Gas Insulated terminal connection for connecting Power Transformer (Air/ XLPE) with GIS through XLPE cable with cable termination enclosure and other accessories etc. to complete transformer bay module as indicated in the SLD/ Layout of substation and as per technical specifications. |
| 456 | 145kV, 1250A, SF6 gas insulated Feeder bay module each comprising of SF6 gas insulated circuit breaker, current transformer , bus-bar disconnectors with common grounding switch, line disconnector with safety grounding switch, high speed fault making grounding switch, surge arrestors, PT , SF6 gas monitoring system for complete bay, local control cubicle, gas insulated terminal connection for connecting XLPE cable with cable termination enclosure and other accessories with GIS etc. to complete feeder bay module as indicated in the SLD/ Layout of substation and as per technical specifications. |
| 457 | Double Bus Arrangement, 145kV, 3 Phase, SF6 gas insulated metal enclosed 2500A bus bars running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus bar set shall be complete with voltage transformer complete disconnector with safety earthing switch, local control cubicle (if required), SF6 gas monitoring system etc. for the complete bus as indicated in the SLD/ Layout of substation and as per technical specifications. |
| 458 | 145kV, 2500A, SF6 gas insulated Bus Coupler Bay Module comprising of SF6 gas insulated circuit breaker, current transformer, disconnectors with safety earthing switches, Local control cubicle, SF6 gas monitoring system for complete bay etc. as indicated in the SLD/ Layout of substation and as per technical specifications. |
| 459 | Suitable Capcity EOT Crane for GIS Hall/ Building |
| 460 | Ventilation system for GIS Hall/ Building (as per technical specification) |
| 461 | 36 kV Metal Clad GIS Indoor Switchboard |
| 462 | Metal clad Double Bus Indoor GIS Switchboard Including 2 No. Incomer Transformer Feeders, 10 No. Outgoing Feeders and 1 No. bus-Coupler (as per SLD) alongwith all associated accessories CTs. PTs, Control Cubicle and Complete with the Control & Protection schemes [ 36 kV, 3150A, 31.5 kA Class] alongwith 0.2 S class AC Static HT-TVM TOD type Energy Meter |
| 463 | Cable Termination/ Plug for terminating in Metal clad switchgear panels for 9 Nos. of Outgoing Feeder panels (for 2 Nos. 3-Phase Outgoing cable circuit in each) from each (Normally cable sizes is 300 Sq. mm or more and exact size shall be decided with the distribution company during detailed engineering) |
| 464 | 33 kV XLPE Cables & Accessories |
| 465 | 3 C, 95 Sq. mm. Al., 33 kV XLPE Cable with Suitable Outdoor & Indoor Terminations [3+3] for connecting the HV side of Substation Transformer to O/G of 36 kV Metal Clad GIS Switchgear |
| 466 | 1C, 1000 Sq. mm, Al., 33 kV XLPE Armoured Cable alongwith accosciated accessories and required material as per laying method adopted etc. (This include 12 lengths of cable with suitable Outdoor & Indoor [12+12] end Terminations) |
| 467 | C&R Panels & SAS system (Complete in all respect, refer Section-V A, B, Part-III, Volume-II) |
| 468 | 132 kV C&R Panel Type SAS-FCA |
| 469 | 132 kV C&R Panel Type SAS-FRA (with Numerical, Communicable Line Current Differential protection scheme as per scheme of main protection at point no. 9.3 of Technical Specification of C&R Panel) |
| 470 | 132 kV C&R Panel Type SAS-BCRA |
| 471 | 132 kV C&R Panel Type SAS-TCRA |
| 472 | 132 kV C&R Panel Type SAS-BBRA |
| 473 | Substation SAS Netorking Panel SAS-NW |
| 474 | Station HMI [Industrial grade Computer with Approx. 21\\"TFT monitor as per specification requirements] |
| 475 | Station HMI (Hot Standby) [Industrial grade Computer with Approx. 21\\"TFT monitor as per specification requirements] |
| 476 | HMI View Node[Industrial grad Computer with Approx. 21\\"TFT monitor as per specification requirements] |
| 477 | DR Work Station[Industrial grade Computer with Approx. 21\\"TFT monitor as per specification requirements] |
| 478 | A3 Size Color Laser Printer |
| 479 | Dot Matrix Printer |
| 480 | One Remote Workstation with HMI[Industrial grade Computer with 21\\"TFT monitor as per specification requirements] & Laser Printer (A4 Size) for RCC |
| 481 | Hardware Gateways (for data transmission to RCC & SLDC) |
| 482 | Modems (both sending and Receiving End) for communication to RCC & Sub SLDC[if required as Communication Equipments are proposed] |
| 483 | Software: Application as well as System Software as per specification requirements for various hardware elements for meeting of functional requirement of the specification. |
| 484 | Substation LAN Commnication Infrastructure |
| 485 | Ethernet Switches: |
| 486 | 132 kV Side C&R and Network Panels:16 Nos.{12 Port (8 Nos. 10/100 BaseTX + 4 No. 10/100/1000 Base FX)}, 2 Nos. {24 Port 10/100 Mbps TX + 4 port 10/100/1000 Base FX}] |
| 487 | 33 kV Side C&R Panels: 2 Nos.{16 Port (12 Nos. 10/100 BaseFX + 4 No. 10/100/1000 Base FX)} |
| 488 | Other Items: |
| 489 | Fiber optic cables, connectors, ethernet cables, jack panels connectors, patch cords etc. for completing the substation/ swithcyard LAN as per specification requirements. |
| 490 | Inverter (3 kVA Capacity) to be operatable on 230VAC and 220 VDCas per availability of supply (Normally on AC) |
| 491 | Inverter (1 kVA Capacity) to be operatable on 230VAC and 220 VDC as per availability of supply (Normally on AC) |
| 492 | 132 kV XLPE Cable & Termination |
| 493 | 500 Sq. mm 132 kV XLPE Cable |
| 494 | 132 kV Outdoor Cable Termination for XLPE to Air Termination on HV Side of Power Transformer |
| 495 | 132 kV GIS Termination for XLPE Cable |
| 496 | Solid bonding Link box with Link plates, bonding & grounding cable complete with other associated accessories for 1-phase |
| 497 | Surge Arresters |
| 498 | 132 kV Class of 120 kV rating LA's with grading ring discharge counter with mili ammeter |
| 499 | 33kV class of 30kV rating LAs |
| 500 | 33kV/415V, 250kVA station transformer complete with all accessories, fittings, terminal connectors etc as specified filled with transformer oil |
| 501 | Batteries & Battery Charger |
| 502 | Batteries (Sizing shall be as per requirement of technical specification) |
| 503 | 220 V [Min 400 AH] |
| 504 | 48 V [Min 300 AH] |
| 505 | Battery Charger System |
| 506 | 220 V Float and Boost |
| 507 | 48 V Float and Boost |
| 508 | Lighting System |
| 509 | Outdoor Lighting & other Works |
| 510 | Lighting Fixture Type -SF2 as per Specification |
| 511 | Lighting Fixture Type -EEC2 as per Specification |
| 512 | Lighting Fixture Type -SF1 as per Specification |
| 513 | Lighting Fixture Type -EEC1 as per Specification |
| 514 | Emergency Lighting Type-PF |
| 515 | Type-RO, 15A, 240V: Outdoor Receptacle 2 pole, 3-pin type |
| 516 | Type-RP, 63A, 415V : Interlocked switch socket outdoor Receptacle |
| 517 | Hot Dip Galvenized Octogonal Lighting Poles (12 m) |
| 518 | Street Lighting Type-EEA for mounting on above Poles |
| 519 | Sub-Lighting Boxes/Panels Type -SLP at Lighting Mast complete with all controgears and accessories, items etc. |
| 520 | Lighting Panel Type ACP-3 as per technical specification |
| 521 | Indoor Lighting & Other Works |
| 522 | Electrification |
| 523 | Electric Fitting (if not covered under Civil Works) with G.I. Conduit, Junction Boxes, pull out boxes, copper wiring, Modular Switchboards, Modular Switches, GI Wire (16SWG) etc. for control room, GIS Hall and administrative office building as per the requirements of the specifications |
| 524 | Illumiation |
| 525 | Lighting fixtures and Receptacles (including accessories/ materials etc. as per requirement alongwith complete accessories and mounting arrangements) |
| 526 | Indoor Lignting Panels |
| 527 | Lighting Panel (Indoor) Type ACP-1 as per technical specification |
| 528 | Lighting Panel (Indoor) Type DCP as per technical specification |
| 529 | Wall mounted fans Approx. 400 mm sweep |
| 530 | Ceiling Fan - Approx. 1400mm sweep with electronic Step regulator |
| 531 | Exhaust Fans |
| 532 | Fire Fighting System |
| 533 | Nitrogen Injection Fire Protection System for Power Transformer complete in all respects. |
| 534 | Fire Fighting equipment with necessary mounting stands. |
| 535 | DCP Type |
| 536 | i) 6 Kg. |
| 537 | ii) 9 Kg. |
| 538 | Carbon di oxide type – 4.5 Kg |
| 539 | Foam Type- Around 9 Liters |
| 540 | Sand type |
| 541 | i) GI Buckets Around 9 liters capacity |
| 542 | ii) Steel Stands for four buckets |
| 543 | Fire Detection and Alarm System |
| 544 | Siren along with all accessories as specified in technical specification |
| 545 | Microprocessor based Fire Detection & Alarm System alongwith the Desktop, System and application software for geographic monitoring and detection of fires, display of events and alarms etc. as specified in technical specification |
| 546 | Photo-electric Detectors, Smoke Detectors, Heat Detectors, Linear Heat Sensing Cables, Manual Call Points etc. Control Room, GIS Hall, Office Building, Store, Testing Laboratory etc. |
| 547 | Power & Control Cables for fire detection & alarm system |
| 548 | Air Conditioning System |
| 549 | High Wall Split AC units of 2 TR Capacity complete with Indoor, Outdoor Units and required accessories, Stablizers etc. |
| 550 | Substation Structures/Supports & Switchyard Erection |
| 551 | 145 kV GIS Switchgear Interconnections for Incomer Line (from incoming 132 kV XLPE Cable for which Cable Termination Kit with support to be supplied by Cable System Contractor) complete with all necessary enclosure support, clamps, connectors and other accessories for successful connection to GIS Switchgear as per Layout of the substation. |
| 552 | 145 kV GIS Interconnections for Transfomer Bay complete with all necessary enclosure support, clamps, connectors, other accessories for successful connection to GIS Switchgear as per Layout of the substation. |
| 553 | 33 kV Transformer Bay (from Power Transformer LV Terminals to SA, Isolator/ PI for Cable Termination) [Complete with Three Phase Al. (50 mm. Size) tubular conductor, Clamps (rigid/flexible/expansion type), Connectors, Straight/V/Y Taps, nut-bolts and other accessories] as per Layout of the substation. |
| 554 | Tubular/ Lattice Support for Equipments [Complete with all accessories] |
| 555 | 132 kV Side |
| 556 | 132 kV side Surge Arrestor |
| 557 | 132 kV Cable Termination (XLPE to Air termination for Power Transformer) |
| 558 | Isolators |
| 559 | 33 kV Side |
| 560 | Isolators (3 Phase) with Single Earth Switch |
| 561 | 33 kV XLPE Cable Termination support structure for Connecting to 33 kV Side of 132/33 kV Transformer including 33 kV Class of 30 kV rating LAs (3 Nos.), Supporting PI String (3 Nos.), nut bolts, fixing accessories etc. as per drawing appended in Section-IV of specification |
| 562 | Lightning Cum Lighting Masts |
| 563 | Post Insulators |
| 564 | 36 kV class Post Insulator Stack |
| 565 | Other Steel Structures/ members to be designed/ provided by the bidder for the project [Various items such as Galvenized/ Mild Steel Channels, Angles, Plates, round, joist, Hot dip galvenized Nut-Bolts, Electro Galvenized Spring Washers etc. considered for this component of price schedule] [ This shall also include the steel to be used in the civil works excluding reinforcement] |
| 566 | Marshalling KIOSK/box |
| 567 | AC Distribution Boxes (Outdoor Type) |
| 568 | Outdoor AC Distbibution Box (Double Front type) |
| 569 | Conduits, Cable Trays, Cable Tags, Cable Racks & Supports, Cable Glands, Cable Lugs, Gland Plates, Junction Boxes [Excluding the conduits, junction boxes etc. required for electrical & Lighting fittings/fixtures installation in control room building] |
| 570 | Isolators |
| 571 | Horizontal double break (HDB) motor operated 33kV isolator complete with all fittings including post insulators, accessories, terminal connectors and all other items (as specified in technical specification for 2000 A HDB isolator with single earth switch) |
| 572 | LT Switchgear |
| 573 | LT AC Main Panel |
| 574 | LT AC Distribution Board |
| 575 | Main Lighting Distribution Board |
| 576 | Emergency Lighting Distribution Board |
| 577 | 220V DCDB |
| 578 | 48V DCDB |
| 579 | Earthing System |
| 580 | 40 mm Dia MS Rod |
| 581 | 40 mm dia 3000 mm long MS rod (earth electrodes) with/without test links, RCC pits, C.I .cover hinged at C.I. frame alongwith all associated civil works |
| 582 | 40 mm dia, 3000 mm long GS pipe electrodes with test links and treated earth pits with C.I. cover hinged to C.I. frame alongwith all associated civil works |
| 583 | 3m, 20 mm Dia MS Rod Electrode |
| 584 | 3m, 40 mm Dia MS Rod Electrode |
| 585 | 3m, 42 mm Dia Safe Earthing Electrodes |
| 586 | 3m, 60 mm Dia Safe Earthing Electrodes |
| 587 | 50X12 mm GS Flat |
| 588 | 50X6 mm GS Flat |
| 589 | 50 X 6 mm MS Flat |
| 590 | 25 X 3 mm GS Flat |
| 591 | 50 X 6 mm Copper Flat (for GIS Switchgear Sceening, Sheilding and Earthing) |
| 592 | 3 m, 25 mm Copper Rod |
| 593 | Earth Enhancing Compound for treated pits as above and other requirement as per specification |
| 594 | 1.1kV Grade PVC insulated Al. conductor power cables and copper conductor armoured control cables [Excluding the wiring required for electrical & Lighting fittings/fixtures installation in control room building] |
| 595 | Power Cables(XLPE) |
| 596 | 3.5Cx300 sq.mm |
| 597 | 3.5C x 185 sq.mm |
| 598 | Power Cable(PVC) |
| 599 | 1Cx150 sq.mm |
| 600 | 3.5Cx70 sq.mm |
| 601 | 3.5Cx35 sq.mm |
| 602 | 4Cx16 sq.mm |
| 603 | 4Cx6 sq.mm |
| 604 | Control Cable (PVC) |
| 605 | 2Cx6 sq.mm |
| 606 | 4CX4 sq.mm. |
| 607 | 4CX6 sq.mm. |
| 608 | 2Cx2.5 sq.mm |
| 609 | 4Cx2.5 sq.mm |
| 610 | 5Cx2.5 sq.mm |
| 611 | 7Cx2.5 sq.mm |
| 612 | 10Cx2.5 sq.mm |
| 613 | 14Cx2.5 sq.mm |
| 614 | 19Cx2.5 sq.mm |
| 615 | For Establishment of fiber optic communication Link beween 132 kV GIS Siv Enclave (Sanganer) and Terminal Substations (220 kV GSS Sanganer and 220 kV GSS Mansarovar) |
| 616 | FOTE Terminal Equipments |
| 617 | OLTE equipment consisting of fully wired cabinet with base 19\\" equipment rack (incl. front cover, cable tray, common cards) with fan unit and control synchronization, Alarm, dual power supply input cables |
| 618 | Central Processing Card - CPU |
| 619 | Power supply unit -48VDC |
| 620 | OLTE - 4 Port STM-4 (633 Mbps Card) alongwith SFPs |
| 621 | OFC Patch Cords - (Set of 48 Nos.) |
| 622 | 8 Port 2w/4w E&M Interface Card |
| 623 | 4 Port Data Interface Card (Programmable) |
| 624 | Line Differential relay interface card (4 ports) |
| 625 | 12 Port Ethernet over SDH transport card (with four 10/100 DaseT, one 100Base-FX and one 1000Base-LX/SX Front interfaces) |
| 626 | Interface cables for Power, data, voice, teleprotection, time synchronisation etc. as per respective site requirement (1 lot for each site) |
| 627 | Engineering Order Wire Phone (VoIP Phone) |
| 628 | Optical Fibre Distibution Panel (for 96 Fibre) with splicing and patch ferrule |
| 629 | Craft Terminal Laptop with configuration Software for all Communication Equipments as offered (Core 7 processing family, 3.1GHz & above 15.0\\" LED,1TB HDD, 8GB RAM, DVD R/W) with configuration Software with latest preloaded licensed Microsoft Window OS as offered ) |
| 630 | CIVIL WORKS |
| 631 | Site Levelling: Supplying all labour, machineries, Tools and plants and levelling the switchyard area to the required RL including cutting in hard soil in areas above FGL and filling up with excavated earth in layers not exceeding 250mm loose thickness in areas lower than FGL duly compacting and disposing the excess earth to any disposal point with all leads and lifts ,dismantaling of existing buildings/ structures/ foundations etc., complete as per specification, drawings and directions of the engineer incharge of the work |
| 632 | Foundations: Design, Engineering, supply of all labour, material and construction of RCC footings and pedestals of any section/size including the cost of excavation in all types of soil/rock, back filling with available approved earth or borrowed/new earth, disposal of surplus earth/rock to the places directed, concrete (RCC M20 Grade and Lean concrete 1:4:8), reinforcement steel,form work ,grouting , underpinning, foundation strengthening in expansive / B.C soil , curing, sundries and other items not mentioned herein but required for the completion of the work for the following station towers and equipments support structures as per technical specification, approved drawings and directions of the Engineer- in-charge of work |
| 633 | 132 kV Side |
| 634 | Equipment Support Structures |
| 635 | i) Indoor GIS Switchgear (complete for existing scope of work) |
| 636 | ii) XLPE to SF6 Interface [ Required civil work for making the interconnection onwards work of cable system bidder i.e. Cable with Cable Kit and support structure] for Incoming Lines (complete existing scope) |
| 637 | iii) XLPE to SF6 Interface [ Required civil work for making the interconnection to cable system bidder i.e. Cable with Cable Kit and support structure] for Transformer |
| 638 | 132 kV Cable Termination (XLPE to Air termination for Auto Transformer) |
| 639 | Surge Arrester |
| 640 | 33 kV Side |
| 641 | Isolators (3 Phase) with Single Earth Switch-Support Structure |
| 642 | 33 kV XLPE Cable Termination support structure for Connecting to 33 kV Side of 132/33 kV Transformer including 33 kV Class of 30 kV rating LAs (3 Nos.), Supporting PI String (3 Nos.),33 KV Isolators nut bolts, fixing accessories etc. as per drawing appended in Section-IV of specification |
| 643 | Common Switchyard items/ Other Items |
| 644 | Lightning Cum Lighting Masts |
| 645 | Lignting Poles |
| 646 | AC outdoor Box (double Front) |
| 647 | Marshalling KIOSK/ Box |
| 648 | Cable Trenches: |
| 649 | Design, Engineering,supply of all labour, material and construction of RCC (grade M-20) cable trenches and pipe trenches for required section /size including the cost of excavation in all types of soil/rock , Backfilling with available approved earth or borrowed/new earth, disposal of surplurs earth to the places directed, concrete (RCCM20 grade and lean concrete 1:4:8) precast RCC covers, form work, curing, water stops, brickworks, wherever required, reinforcement steel, steel angles, flats, plates, cable trays, sundries and other items not mentioned herein but required for completion of work as per technical specification, approved drawings and directions of the Engineer-in-charge of work. |
| 650 | Section in mm |
| 651 | i) A-Type 850x750 mm |
| 652 | ii) B-Type 550x600 mm |
| 653 | iii) C-Type 550x450 mm |
| 654 | iv) D-Type 400x300 mm |
| 655 | v) 33kV Outgoing Feeders 3500x2500 mm |
| 656 | Antiweed Treatment: |
| 657 | Providing & supply of all labour, material etc. required for soil sterlization/ antiweed treatment including removing of all vegitation, roots etc. and to achieve final formation level in required grade with rolling, compaction etc. ensuring safety of civil structures. After preparing base, providing and laying plain cement concrete (1:3:6) in required gradient 100 mm thick as per technical specification. |
| 658 | JELLY SPREADING: |
| 659 | a) Supplying all labour, materials, equipments and Providing and laying 100mm thick granite/trap/basalt jelly using 20mm size jelly including the cost of jelly, sundries and other items not mentioned herein but required for the competion of the work as per technical specifications drawings and direction of the engineer incharge of the work. The jelly used shall be free from dirt, organic material and flakes etc. including cost of cement concrete block masonary barricade as per specification wherever required/as per direction of engineer. |
| 660 | b)Concrete Block Masonry Barricades : supplying all labour, materials and Providing barricades to confine jelly spreading including the cost of the following works and other items not mentioned herein but required for the completion of the work as per specifications and directions of the engineer incharge of the workincluding earth work excavation in all types of soil /rock, backfilling and disposal of surplus stuff to the places directed, construction of solid concrete block masonry in cement mortar 1:6 with cement concrete solid blocks of proportion (1:5:3), crushing strength not less than 50Kg per Sq. Cm, 40 x 20 x 20 Cms size (l.b.h) conforming to ISS 2185-1967 including necessary curing etc., complete. The concrete blocks shall be 100mm above FGL, plastering to masonry 12mm thick in CM 1:6 and two coats of water proof cement painting to exposed faces over one coat of primer |
| 661 | Transformer foundation and associated rail track: Design, Engineering, supply of labour, material, equipments and construction of transformer and radiator foundations, rail tracks(Concrete grade M-20) including all associated works, jacking pads, Anchor blocks, MS gratings, gravel filling, pylon support system including the cost of excavation in all types of soil/rock, back filling with available approved earth or borrowed/new earth,disposal of surplus soil/rock to the places directed, concrete (RCC M20 grade and lean concrete 1:4:8), reinforcement steel, strucutural steel, form work, grouting , jelly , painting, curing, sundries and other items not mentioned herein but required for the completion of the work as per technical specification, drawing and directions of the Engineer in-charge of work |
| 662 | i)80MVA, 132/33 kV Transformer |
| 663 | iii)Baffle/Fire Wall (132/33kV Transfomer): Design, Engineering supply of all laobour materials and construction of baffle/fire wall as per technical specification, drawing and directions of engineer incharge of work. (RCC M20) |
| 664 | Stone Masonry Transformer Platform: |
| 665 | Construction of size stone masonry Transformer platform for 630kVA,33/0.433kV LT Transformer as per drawing enclosed, technical specifications and directions of the Engineer- in-charge of work, incuding the cost of excavation in all types of soil/rock , backfilling with available approved earth or borrowed/new earth, disposal of surplus soil/rock to the places directed, concrete (PCC 1:1.5:3 for coping and lean concrete 1:4:8) Strengthening of foundation in expansive /B.C soil Size stone masonry for foundation and basement in cement mortar 1:6 using hammer dressed/chistle dressed stones of not less 15 cm. high with bond stones in each course, plastering 20mm thick in CM 1:6, to the exposed faces, structural steel, reinforcemet steel, curing, water proof cement painting to the exposed faces and other items not mentioned herein but required for the completion of the work. |
| 666 | Road Works: |
| 667 | Design and construction of roads and walkways/shoulders within sub-station or outside the station as per specification, layout ,sectional detail drawing and directions of Engineer-in-charge of work etc. complete in all respect. [ Area of Concrete Surface shall be considered for measurement] |
| 668 | STORM WATER DRAIN, DECK SLAB CULVERT/PIPE CULVERT FOR DRAIN CROSSINGS:Design, Engineering and construction of Strom water drain, deck slab culvert and pipe culverts with the following items of work |
| 669 | i) Earth work excavation for foundation, pipe line and drainages and removing the excavated earth to a distance not exceeding 50m and with a lift upto 1.50m. In hard soil |
| 670 | ii) Providing and laying cement concrete using 40mm and down size stone aggregate for foundation laid in 15cms thick layers and well compacted including curing etc., complete cement concrete 1:4:8 |
| 671 | iii) Random Rubble stone masonry in courses not less than 20cms high with bond stones 2m apart in each course, edges of stones chistle dressed and all quoins 2 line dressed 5cms. Wide on each face including curing etc., complete as per specification in CM 1:6. |
| 672 | iv) Providing pointing to stone Masonary in CM 1:3 after raking the joints to a depth of 2.50 cms and nicely lining curing etc., complete. |
| 673 | v) Earth work filling by using available earth including compacting by filling 15cm layers and consolidation with water etc., complete. |
| 674 | vi) Disposing of the excess earth away from the premises including all loading and unloading, transportation , leads lifts etc., complete |
| 675 | vii) Providing and laying cement concrete using 20mm and down size stone aggragate including mixing, laying, tamping, curing and smooth finished for exposed faces and with necessary centering and form work etc.,complete for SILLS, COPING,BOND SLAB, Basement and for any other such works Cement Concrete 1:2:4. |
| 676 | viii) Providing Haulig and Laying 450mm dia. NP3 class RCC hume pipe in position carefully and jointing with CM:1:2 and curing etc., complete (including the cost pipes and collars) with all leads and lifts whereever required |
| 677 | ix) Providing and fabricating MILD/ HYSD steel reinforcement conforming to IS 1786 including supply of steel and labour for straightening, cutting, bending, hooking, lapping and/or welding wherever required placing in position, tieing with binding wire of approved quality and gauge including the cost of binding wire and anchoring to the adjoining members wherever necessary etc complete as per design specification and directions |
| 678 | x) Providing and laying insitu vibrated cement concrete Grade M20 using 20mm and down size graded coarse aggregate using clean sieved approved sand, including cost and conveyance of all materials, all leads and lifts, labour, hire charges of machinery, scaffolding, form work, centering vibrating, finishing curing etc., complete for solid Deck Slab. |
| 679 | Switchyard fencing: |
| 680 | Design Engineering and construction of new security wall cum chain link fencing and strengthening of existing security wall with chain link fencing,including Earth work excavation for foundation and removing the excavated earth to a distance not exceeding 50m and with a lift upto 1.50m. in hard soil , concrete using 40mm and down size aggregate for foundation laid in 15cms thick layers and well compacted , complete cement concrete 1:4:8, Providing and laying cement concrete using 20 mm down size stone aggregate including mixing, laying, tamping, and smooth fihished for exposed faces and with necessary centering and form work etc., for SILLS, COPING, BOND SLAB, Basement and for any other such works Cement Concrete 1:2:4 ,Stone masonry, stones hammer dressed in courses not less than 20cms high with bond stones 2m apart in each course including curing etc., complete as per specification in CM 1:6.for foundation structural steel using ISMC, ISA, M.S. flats etc., for providing structural works incuding cost of materials, consumables required for the completion of work including charges for fixing welding, cutting, straightening, bending, fastening, grinding, welding etc., complete including two coats of synthetic enamel paint ,etcbarbed G I wire fencing of 12 X 12 guage drawn into stone or iron pillars including drawing in holes wherever necessary excluding the cost of pillars but including the cost of barbed wire and binding wire etc |
| 681 | Providing and fixing M.S gate to RCC pillars, fabricated as per the drawing and directions of the Engineer incharge of the work. Rate includes cost of RCC supports, gate, fixing to RCC supports , painting etc., complete chain link fencing 50mm size of 8 guage properly stretched between rectangular poles and fixed with suitable bolts and nuts, the free ends shall be welded to the pole and block pipe at top and bottom as required including cost of all materials, labour and lifts, cutting, bending wherever necessary wastages and lapping etc., complete as per direction of Engineer- in- charge of work including two coats of approved quality synthetic enamel paint over one coat of shop preimer MS rectangular poles made out of 2 equal angles of 65x65x6mm welded together and fixed in CC 1:2:4 with two nos. of 16 mm dia. MS hold fast rods each of length 25 cms. Including cost of all materials cutting, bending, scaffolding wherever necessary nicely finishing the welded joints with all lead and lifts and as per the directions of engineer incharge of the work including providing 2 coats of approved quality synthetic enamel paints over one coat of shop painting. Disposing of the excess earth away from the premises with all lead and lifts including all loading and unloading transportation etc., complete |
| 682 | Control Room Building: Design, Engineering, supply of all labour, materials equipments, tools and plants etc., and construction of Control Room building (RCC M-20 grade) as per the drawing, directions of the engineer incharge of the work with the following items of work. water supply, sanitary ( internal and external ) electrification/illumination, construction of various cable ducts comming within the building are in the scope. The building shall be designed for 2nd floor office loads. The scope is for construction of ground, first and second floor with stair case cabin. |
| 683 | 132KV GIS Hall Building: Design, Engineering, supply of all labour, materials equipments, tools and plants etc., and construction of 132KV GIS Building (RCC Frame Structure) with RCC M-20 grade as per the drawing & directions of the engineer incharge inlucluding electrification/ illumination, construction of various cable ducts comming within the building & its supports are included in the scope. The GIS Building Consists of 132KV GIS Hall, LCC Panels and AHU Room as shown in Layout. Please refer Scope for actual requirement of Bays. |
| 684 | Rain Water Harvesting: Design Engineering , Supply of all labour, material, tools & plants etc. and construction of Rainwater Harvesting as per technical specification. |
| 685 | Interior Works for the SCADA Room including designer false celing (with rodent repellent sytem installed above it), furnishing, specialized illumination system etc. Complete in all respect as per specifications. |
| 686 | Design, Engineering & Construction of water supply system including Ground level Reservoir having capacity of 15000 ltrs & with pump room including making connection with all the buildings complete in al respect as per direction of Engineer in charge. |
| 687 | Training |
| 688 | Training on Overall Design, Operation and Maintenance of 132 kV Gas Insulated Switchgear: This training will be for the acquaintance of the GIS technology, brief design principles, Operation and maintenance practices and recommendations of manufacturer. |
| 689 | Training on Overall Design, Operation and Maintenance of 36 kV Metal enclosed Gas Insulated Switchgear: This training will be for the acquaintance of the GIS technology, brief design principles, Operation and maintenance practices and recommendations of manufacturer. |
| 690 | Training on Overall Design, Operation and Maintenance of IEC-61850 based SAS System: This training will be for the acquaintance of the IEC-61850, brief design principles, Operation and maintenance of deployed system. |
| 691 | Maintenance |
| 692 | Maintenance Charges for 3 Years |
| 693 | Add: Any other item bidder may require to complete the GIS as well as EHV XLPE Cable System as per specification requirements |
| 694 | SERVICE LINE WORK- Proposed 132 kV underground cable using 1 Core 630 sq. mm Copper XLPE cable, LILO (Loop In Loop Out) of one circuit of the existing 132 kV Sanganer – Mansarovar Double Circuit transmission line (Length Approx 4 KM) |
| 695 | SERVICE PART |
| 696 | OVERHEAD LINE |
| 697 | DETAIL SURVEY AS PER TENTATIVE ROUTE INCLUDES THE FOLLOWING MAJOR ACTIVITIES: |
| 698 | Pegging of line route , providing of survey pillar at an interval of 3-4 Km line route with required jungle clearance for survey, profile preparation of approved route on graph sheet and marking of offset on either side of line , marking of side clearance for hills, sand dunes etc., as per specification and tower scheduling. |
| 699 | CHECK SURVEY AS PER APPROVED ROUTE OF LINE WHICH INCLUDES: |
| 700 | Rechecking of the line route as per approved profile, tower centre marking, pit marking, bisection of angle tower as per required at site. |
| 701 | ERECTION OF MONOPOLE TOWERS:- |
| 702 | Monopole Type - 132kV D/C Tension Pole *PD(30-60d)_18mBxA\\" with 02 Nos Aux. Cross Arm for cable termination of LILO Ckt |
| 703 | Earthing of Transmission Tublar Monopoles alongwith all required as per the requirment of specification. |
| 704 | CONDUCTOR STRINGING: |
| 705 | (a) Stringing of ACSR Panther including hoisting of insulator string, laying, jointing & tensioning of conductor, clamping with Armour rods and fixing of vibration damper per route KM of the line. |
| 706 | (i) Single conductor |
| 707 | OPGW STRINGING (24 fibre) |
| 708 | (i) Stringing of 24 fibre (DWSM) OPGW fibre optic cable including laying, tensioning, clamping, clipping, fixing vibration damper, earth bond etc. up to placement of junction box. |
| 709 | (ii) Installation Hardware set for 24 fibre OPGW fibre optic cabling including all cable fittings & accessories except joint box. (1 set of installation of hardware shall contain all installation hardware fittings as may be required for 1 km of OPGW/approach fibre optic cable) |
| 710 | Installation of joint box (24 Fiber OPGW/OFC) |
| 711 | UNDERGROUND CABLE |
| 712 | SURVEY |
| 713 | Surveying of cable route excavation of trial holes as per field requirement, prepartion of cable route profile, drawings for cable laying , final route alignment, marking lines & grades/prepartion of final cable route darwings after approval & preparing bill of materials for complete route shown in drawings i.e. between terminal sub stations. |
| 714 | Evalutions of thermal resistivity of soil along cable route (as per tecnical specifications) |
| 715 | Cable Installation: |
| 716 | Handling,Transportation to site & laying of 132 kV, Single Core, 630 Sq. mm XLPE Copper cable as per foregoing specification requirements. |
| 717 | Establishing of 3-phase double circuit having (3 Phase each circuit) 132kV single core,630 sq. mm copper cable in trefoil/ approved formation along-with pilot fiber cable, providing of Warning tape ,tagging, fixing pipes for drain & gate crossing as per drawings and specifications in trench by pulling, drawing, etc. including cables, using standard cable installation equipments and as per directions of the engineer in charge and returning of unused items in Store. |
| 718 | Handling & making of straight through joints for 132 kV, Single Core 630 Sq. mm power cable (XLPE copper cable) as per specification. |
| 719 | Handling and making of Straight through Joint (with provision for sheath separation for cross bonding/ Mid point Earthing) suitable for above underground cable as per foregoing specifications |
| 720 | Handling and making of outdoor type cable end terminations for 132 kV single core power cable as per specification |
| 721 | Erection of 145 kV rated voltage plug in type pre-moulded end termination kit complete with accessories suitable for the above underground cable for termination in GIS type switchgear |
| 722 | Installation of solid bonding Link box with Link plates, bonding & grounding cable complete with other associated acessories for 1-phase. |
| 723 | Installation of Cross bonding Link box/ Mid Point Earthing, Co-axial/ Solid bonding cable, Sheath Voltage Limiters (SVL) (as per requirement) complete with other associated accessories for each 3-phase circuit |
| 724 | Installation of Galvanized steel supporting structures/ arrangement etc. for suitable and safe termination of XLPE cable to GIS switchgear |
| 725 | Installation of Earthing material including cast iron pipes with suitable clamps, charcol, common salts etc. complete set for each cable circuit (each having 3 core) |
| 726 | Terminal connector suitable for Panther Conductor on the Outdoor cable termination to connect cable end termination to ACSR Panther Line |
| 727 | Installation of Underground Optical Fiber Cable and associated accessories/items as per specification alongwith XLPE cable (24F X 2) |
| 728 | OFAC/OFC and hardware fittings/ accessories alongwith associated Fibre optic Distribution Panel & accessories |
| 729 | Installation of 132 kV class of 120 kV rating Surge Arrestor with grading ring, discharge counter with Milli meter |
| 730 | Line differential cum distance protection relay at both ends of GSS |
| 731 | Charges of conducting pre commissioning tests as per specification & successful commissioning of circuit |
| 732 | Add: Any other item bidder may require to complete the installation work as per specification requirements |
| 733 | Destringing/ Restringing of Conductor/ Earth wire / OPGW:- |
| 734 | Destringing of Conductor/ Earth wire / OPGW:- |
| 735 | (a) Destringing of ACSR Panther conductor Dismanting of vibration damper s and armour rods removal of conductor from clamp and fitting in roliers , detensioning dehoisting of insulator string as reqired and collecting the material & depositing the same in our store and stacking . |
| 736 | (i) Single conductor |
| 737 | (b) Destrining of of 24 fibre (DWSM) OPGW fibre optic cable including laying, tensioning, clamping, clipping, fixing vibration damper, earth bond etc. up to placement of junction box. |
| 738 | Restringing of Conductor/Earth Wire :- |
| 739 | (a) Restringing of ACSR Panther conductor:Dismantling of vibration dampers and armour rods, fitting in rollers,de-tensioning, holding & lowering of conductor, de-hoisting of insulator string as required, adding/ removing and jointing of conductor, hoisting of insulator string, lifting of conductinto rollers and re-tensioning, jointing, fitting of armour rods and vibration dampers and clamping per route KM of the line section to be restrung dismantled material not re-used to be deposited in our stores & stacked. |
| 740 | (i) Single conductor |
| 741 | (b) Restrining of of 24 fibre (DWSM) OPGW fibre optic cable including laying, tensioning, clamping, clipping, fixing vibration damper, earth bond etc. up to placement of junction box. |
| 742 | CIVIL WORKS |
| 743 | OVERHEAD LINE WORK: |
| 744 | EXCAVATION: |
| 745 | Soil investigation of Tubular Monopoles |
| 746 | Foundation of 132kV D/C Tension Pole *PD(30-60d)_18mBxA\\" with 02 Nos Aux. Cross Arm for cable termination of LILO Ckt |
| 747 | Transmission Tubular Monopoles footing protection work including required items as per specification |
| 748 | UNDERGROUND CABLE WORK: |
| 749 | Cutting Black Bitumen surface upto any depth including all layers of crust for laying Power Cables etc, staking of useful material and disposal of surplus debries including all leads including barricading, providing danger board/diversion board, lighting, reflectors etc. |
| 750 | Earth work in excavation for burried cable trenches/foundations including dressing of sides and ramming of bottoms, lift upto 2.5 mtr. including taking out the excavated soil & backfilling of jhiri with watering & ramming ,timbering & shoring ( wherever required ) disposal of surplus excavated soil as directed with all lead and lift including barricading, providing danger board/diversion board, lighting, reflectors etc. |
| 751 | Horizontal Direct Drilling (Trenchless Digging) method (with 250 mm HDPE pipe of minimum 6PN and strength complying to relevant ISS) wherever open cut method cannot be adopted (for double circuit with 3 cable core in each circuit.) (If required) |
| 752 | Poviding and laying of Cement concrete including curing, etc using stone aggregate 40 mm nominal size (crusher broken) in foundation plinth, excluding the cost of shuttering using 1 cement: 4 sand: 8 stone aggregate (For equipment foundation, junction box etc.) |
| 753 | P&L cement concrete in R.C.C. work in foundation,rafts,footings,strap beams, bases of columns etc.,'including curing ,compaction,finishing with rendering in cement sand mortar 1:3 (1cement :3 sand) and making good the joints, excl., the cost of centering and shuttering and reinforcement :M-20 grade mix 1:1.5:3 (1cement:1.5coarse sand : 3 graded stone aggregate 20 mm nominal size (For equipment foundation, junction box , culvert etc.) |
| 754 | Brick wall works, if required |
| 755 | Providing and fabricating steel reinforcement for R.C.C. work bending ,placing in position and binding complete including cost of binding wire in foundation ,raft footing ,strap beams base of column etc., up to plinth level hot rolled deformed (I.S.1139) cold twisted (I.S.1786)bars (For equipment foundation, junction box \ etc.) |
| 756 | Centering and shuttering with plywood or steel plates including strutting, propping bracing both ways with wooden members and removal of formwork for superstructure up to 4.5m height above plinth level for (For equipment foundation, junction box etc.) |
| 757 | Providing & Fixing of steel febrication made of angles, tees, square bars or other flats black pipe with hold fast and fittings complete as per design @ drawing including cutting welding & fabrication with priming coat of redoxide. |
| 758 | Providing,Laying & Jointing RCC class NP-2 Non Pressure pipes (IS:458 Mark) of approved make with collars, jointed with CM 1:2 or having Spigot & socket ends with flexible rubber rings joint including testing of joints etc. complete: 450 mm D. |
| 759 | Providing & Fixing of Reinforced Ferro Cement Cable Trench Covers designed for 'A' & 'AA' loading duly marked on cover with adequate reinforcement having thickness 75mm to 100 mm anti corrosive bitumen pained MS plate Rim & MS lifting hooks admixtures like plasticizer bond -improving compound, shrinkage resistance compound, abrasion resistant complete as per approved design ( For cable joint box) (For any span) |
| 760 | Providing & Laying HDPE pipe heavy duty of approved make jointed with solvent cement |
| 761 | (i) 250 mm dia. (for double circuit, 3 phase formation) |
| 762 | (ii) HDPE PLB Duct for Optical Fiber Cable |
| 763 | Supply and laying inter locking RCC cable covers as per approved drawing |
| 764 | Supply, spreading of clean river sand in the cable trench and cable joint pit as per specification. |
| 765 | Providing & Fixing Cable Route Marker along the route of cable at the spacing of 50 meter etc. as per drawing and site requirement. |
| 766 | RR Stone masonary in F/P CSM 1:4/ Brick Work |
| 767 | Plastering 20 mm thickness CSM 1:6 |
| 768 | Providing & laying plane cement concrete M20 Grade |
| 769 | Maintenance Service [these charges shall be applicable after the completion of guaranteed performance period of cable system for 4 years excluding of item/ material/ equipment already covered for performance guarantee of 5 years.The charges shall be payable on actuals |
| 770 | Maintenance services per visit towards any breakdown of cable system which includes services of expert engineers, technicians alongwith necssary tools/ tackles, testingnequipments, fault locating equipments to detect the faults and its subsequent ractification, re-testing and restoring the electric supply through cable system for both cable circuits Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 37 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 38 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender