Tender For Supply Installation Testing and Commissioning of Newly Bore Of Tubewell At Nand Vihar Village Under Ac-34.(Re-Invite)
Tender Value
Ref. Documents
Estimated cost
Bid Submission
25 Aug 2026
2 days left
EMD
11000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Delhi → Delhi
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Supply Installation Testing and Commissioning of Newly Bore Of Tubewell At Nand Vihar Village Under Ac-34.(Re-Invite)
BOQ
| Sl. No. | Item Description |
| 1 | Lowering of sub p/set, sub cable, GI Pipe etc. as required, jointing of cable with pipes and jointing of D/F pipes etc. with nuts bolts and rubber packing etc. The job includes hiring of all T&P, tripod stand, chain pulley block and other material handling equipment’s, Safety gadgets as required and consumable material ( rubber packing and Nut Bolts) will be arranged by the firm as per site requirement |
| 2 | S/O Submersible P/Set dynamically balanced S Steel impeller mounted on stainless steel shaft with protection sleeve duly fitted with flanged tail piece. The pump will be directly coupled with sq. cage sub. Induction motor of 2900 rpm suitable for operation on 3 phase, 415 volts, 50 c/s AC supply with efficiency 70% at duty point of following duties : 7.5 HP, Discharge 200-450-600 LPM, head 71-50-29 mtr. or equivalent as per site requirement. Make :- BS/SU/Skope/DJB approved makes. |
| 3 | S/O PVC insulated PVC sheathed flat submersible cable with plain copper conductor having three core 4 sq mm 415/1100V (each roll 100 mtr) Make :- Havells/Fort Gloster/ICL/CCI/ICC/Universal/Grandlay/Havells/DJB approved |
| 4 | Making/supply of 50mm, 3 mtr long approx double flanged (OD 130mm)GI Pipe,medium conforming to IS:1239(2004)SWS,B Class having 3 No L-Type brackets duly welded on each side of flange. The flanges having four holes and One cut for cable. Make- TATA/Jindal Hisar |
| 5 | MS clamp suitable for holding 50 mm dia GI pipe made from 600x100x12 mm thick MS plate with complete set |
| 6 | F/S of MS bore cover suitable for 300mm dia MS Pipe. The bore well be fabricated with MS flat size 50mm width 5mm thickness and MS sheet 18SWG in 2 half pieces i/c suitable clamping arrangement having internal hole as per requirement |
| 7 | GI/CI double flanged 90 degree 50 mm dia size bend |
| 8 | Supply of 50 mm dia. CI double flanged PN 1.0 NRV without bypass. Make :- IVC/Kirloskar |
| 9 | Orifice Assembly 2 feet length 50 mm dia double side flannged 2'' x 2.5 ''. Complete |
| 10 | G.I tail piece 50 mm dia 0.5 mtr. Long with one end threaded & other end flanged having 3 No L-Type brackets duly welded with flange having 4 Nos. hole & cut for cable. |
| 11 | Supply of chemical dosing pump complete with container, injection valve assembly, suction valve assembly PVC tubing & accessories for installation, Capacity:- 4 LPH, Pressure:- 5.5 KG/cm2 Make:- Clomax/Milton roy |
| 12 | Installation and commissioning of dosing pumps set with proper wall supporting arrangement to hold the pump set , the work includes providing all pipes and special to supply sodium hypo chloride solution properly to main delivery line by making holes with utmost care and make the systems leak proof and testing on full load during the running of pump |
| 13 | Fixing of ms socket of required size by drilling/threading/welding and making it leak proof fixing suitable nozzle for injecting chlorine solution at the time of operation of t/well . |
| 14 | Supply of sodium hypochlorite solution having 9% to 12% available chlorine packed in 35 litre disposable PVC jerry can make:- Chopra/PACL/BIS approved. |
| 15 | Supply of Electric feeder pillar made out of MS sheet , tentative size of panel 700x500x250 mm of suitable size angle iron & MS sheet with door and inter locking arrangement duly painted with powder coating process suitable for up to 10 to 15 HP Motor / Pumps with Star Delta starting system and having suitable provisions for mounting / fixing of below switchgears, control gears, instruments and complete with the material as below duly installed with their complete connections and inter connections with copper cables / bus bars size25x6 mmetc. as per requirement. Make of insertions / Material:- L&T / C&S / BCH / Minilac / AE / DJB Approved:-63 Amp FP MCB 415V AC and manual Phase changeover for incoming supply -1 No, Earth Leakage protection - 01 No., Power Contactor 3 Pole 40 Amp – 3 No, Star Delta Timer -01 no., Over Load Relay for up to 10 HP to 15 Hp ( 14 Amp. To 44 amp.) – 1 No.,Automatic Phase changeover system in case of phase reversal (with 40A Contactors) – 1 set, Current Transformer - 3 No.,Phase Indication Lights & ON/OFF/Trip Indication Light -6 Nos., 6 AMP SP MCB -3 Nos.Start / Stop Push Button -2 Nos., Digital Ampere Meter - 1 No.Digital Volt Meter - 1 No., Ampere Meter Selector Switch – 1 No.Volt Meter Selector Switch – 1 No., 24 hour timer digital – 01 Motor protection relay 200-, Auto Manual Switch-01 No., Capacitor of 5KVAR -01 No. , MCB TP 32 Amp , Under voltage and over voltage protection unit |
| 16 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 17 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 18 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 19 | Grouting of existing LT Panel with 1:2:4 C:C material. Work includes grouting of both legs with C:C material to provide proper strength. |
| 20 | Wiring for light point/ fan point/ exhaust fan point with 1.5 sq. mm and 2.5 Sq mm FRLS PVS insulated copper conductor single core cable with all material like 5/6 amps switch, 3 pin 5/6 A socket outlet, 15/16 A switch ,6 pin 15/16 A socket outlet, 40 watt LED light 70/72 Watt LED street light box, fan etc. . as per site required. |
| 21 | Supply of LT XLPE, PVC sheathed, armoured cable with Aluminium conductor having 4 core, size 16 mm Sq. operating voltage 1100V Make: Fort Gloster/ICL/CCI/ Universal/Grandley/Havells or DJB approved make. |
| 22 | Supply and fixing of Copper wire 10 Sq. mm 4 core (Make:- Havells/ Granley/ DJB Aprroved |
| 23 | Supply and fixing of 100 amp 4 pole MCCB with enclosure Make :- L&T or as per DJB approved |
| 24 | Supply of MS Angle of size 50x50x5mm. (for 01 Tube well MS Angle = 12 Kgs) |
| 25 | Supply and febrication/cutting of MS Chequered Sheet of thickness 06 mm. with the help of gas cutter, grinder(for 01 Tube well MS Sheet = 27 Kgs) |
| 26 | Fabrication of MS angle of size 50x50x5 mm frame with the help of gas cutter, welding machine, grinder and making the frame of roof opening of size 2.6 x 2.6 sq. ft. Welding the above MS chequered sheet on the MS angle frame with hinges and handle for opening. |
| 27 | Fixing the MS Roof cover on the tube well with C:C material in the ratio 1:2:4 and along with other hardware items required as per site requirement. |
| 28 | Painting the complete MS Roof covers first with Primer and then two coats of enamel paint. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 19, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 25, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 2 daysAug 25, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 2 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender