Tender For Automation Of 10 Mld Wtp At Paralakhemundi
Tender Value
2.25 Crore
Estimated cost
Bid Submission
02 Sep 2026
10 days left
EMD
2.25 Lakhs
Bank guarantee accepted
Document Fee
10000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Gajapati → Odisha
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Automation Of 10 Mld Wtp At Paralakhemundi
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 20-Aug-2026 | Extension of Dates | Other | 02-Sep-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | AUTOMATION OF INTAKE WELL PLC panel for Intake Design manufacture supply installation testing and commissioning of indoor type PLC panel of size approx. 1000 mm X 700 mm X 1500mm LBH fabricated out of min. 2 mm thick CRCA sheet powder coated to Siemens gray color.The Panel shall be provided with reputed make PLC with following accessories as well as input output configuration.The PLC shall be programmed with IEC 61131 standards for control monitoring and communication of equipments and instruments at Raw water Pumphouse.PLC shall have Ethernet port and protocal for Modbus TCP communication with following IO.DI 16 num DO 16 num AI 8 num AO 4 num. 10 inch color TFT HMI complete with programming shall be provided to interact with PLC. The panel shall include all the accessories not limited to following to achieve purpose of smooth and trouble free operation of pump house.MCB 10A DP 1 num MCB 4A DP 4 num 24 VDC Power Supply 10A 1 num Push Buttons 7 num Selector Switch 2 num Control Contactor 2 num Annunciator with 6 Windows NO to NC TypeElectronic Hooter 1 num Control Transformer 1 num Emergency PB 1 num Panel Cooling Fan 1 numPanel Light with Door Switch 1 num Control Indication Lamp 5 num Wiring TB etc 1 lot Hardware 1 lot and all Complete Works as per specification and directions of Site Engineer Engineer in Charge |
| 2 | Windows based PC with latest configuration and OS complete with necessory office and antivirus softwares.PC configuration shall not be less than Intel i5 10th Gen CPU 16 GB Ram 128 GB SDD 500 GB HDD DVD RW Rs232 and Rs485 port 2 RJ45 ports Keyboard Optical Mouse 32 inch color TFT Monitor Latest Windows Pro OS Microsoft Office and Antivirus and Internet Sequrity software for 3 years license and completed as per Ingineering In Charge. |
| 3 | Supply Installation and commissioning of single phase 1KVA online UPS with pure sine wave and float cum boost charging with battery rack and maintenance free battery system for 1hour backup including cables power plug switch etc. all Complete Works. |
| 4 | Supply Installation of Control Desk 1 no. Table 1 no. and Chairs 2 nos. at SCADA room and completed as per Ingineering In Charge. |
| 5 | Supply Installation and commissioning of AC 1.5 Ton 5 star and complete as per Engineer In Charge. |
| 6 | Supply Installation Testing Intgeration and Commissioning of 43 LCD monitor at Conf. Room for display of total water system Online complete as per specification and directions of Site Engineer Engineer in Charge. |
| 7 | Designing Supplying Installing commissioning and testing of Ultrasonic level transmitter CE marked with following technical parameters Interfacing with PLC panel including mounting arrangement.Output 4 20 mA HART.Power supply 24V DC ext.Display 4 LEDRange 0 10 mtr 20 mtr.Accuracy 0.25 percent of FullScale or betterEnclosure IP 68Mounting On PLC panel all complete work as per direction of Engineer in charge. |
| 8 | SupplyingInstallation and testing of 4G Dual Sim LTE Router with 1 X LAN 1 X WAN RS485 on board with one at a time usage WI FI 802.11 b g n 1 X Cellular Antenna 1 X WIFI Antenna Model SW245 RS485 and complete work as per direction of Engineer in charge |
| 9 | Providing installation testing and commissioning of Diaphragm Type Pressure Gauges Dial size 150 mm glycerin filled shatterproof glass Over range protection 125 percent of maximum pressure Material of sensor and other wetted parts SS type 316 Housing material Die cast aluminum with linear scale and alland complete work as per direction of Engineer in chargeAll header and common header |
| 10 | Pressure Transmitter for raw and pure water pumping station Designing Supplying Installing commissioning and testing of pressure transmitter CE markd with following technical parameters at Raw Water Pump House and Interfacing with PLC panel including mounting arrangement.Output 4 20 mA HARTPower supply 24V DC ext.Display 4 LEDAccuracy 0.1 percent of full scaleor betterEnclosure IP 68 and complete work as per direction of Engineer in chargecommon Header |
| 11 | Designing Supplying Installing commissioning and testing with Terminating and Interfacing of 2 C x 1.5 sq.mm as per IS 694 twisted shielded copper armoured conductor on wall in GI tray or in ground suitable for supplied DC Voltage and all Complete Works as per specification and directions of Site Engineer Engineer in Charge |
| 12 | Supplying and erecting armoured control cable with ISI mark stranded solid copper conductor 1.1 kV grade complete erected on wall panel or in provided trench in an approved manner. 4c X 2.5 sq mm Copper conductor PVC insulated armoured control cable and all Complete Works as per specification and directions of Site Engineer Engineer in Charge |
| 13 | Designing Supplying Installing commissioning and testing with Terminating and Interfacing of 2 pair x 1.0 sq.mm. as per IS 694 copper shieled twisted multistraned armoured cable on wall in GI tray or on ground and all Complete Works as per specification and directions of Site Engineer Engineer in Charge. |
| 14 | Supply Installation and commissioning of Control cables to be inserted in conduit pipe in trenches cables to be laid in racks cleated on walls cable lugs cables glands conduits cablejoints Screened cable unarmoured etc all Complete Works as per specification and directions of Site Engineer Engineer in Charge. CAT 6 Dlink cable |
| 15 | Supply and installation of full bore type electromagnetic water flow meter at various locations for monitoring volume of water flow with following technical specification Drinking Water Application Liner Hard rubber Process Connection PN10 St37 2 FE 410W B flange EN1092 Electrodes 1.4435 3161 Calibration 0.5 percent Approval Nonhazardous area Housing Field Alu Sensor IP68 NEMA6P Cable Remote Version 20 m coll and signal cable Power Supply 20 28VDC 11 40VDC Display 2 line push buttons all Complete Works as per specification and directions of Site Engineer Engineer in Charge 350mm diaNear Intake and Near WTP |
| 16 | Supply and delivery of Actuator control sluice valve of PN 1.6 with Body and Bonnet of Ductile Iron GGG 40 SG 400 15 or GGG 50 SG 500 7 or Equivalent as per IS1865 IS 3896 2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM Replaceable Spindle Nut without gland packing with 3 O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100 percent leak proof . Fitting and fixing of sluice valves with tail pieces nesaceery rubber packing SS 204 nut bolt including labour T and P transportation to site from store and fixing the surface boxes with electric actuator resistant to high pressure and robust design torque 7 2000 Nm motion range 0 360A degree voltage 220V AC applicable for actuating multi turn valves with Case Body Opening Mete Inlet Wire Lock Rubber Cover of Handle Shaft No Bracket Installation Gear Box Cover Electric Cover Wiring Cover Handle Shaft Cover Output Shaft and Adapter and all Complete Works as per specification and directions of Site Engineer Engineer in Charge 250mm diaAll header |
| 17 | Supplying all materials labour t and p and fixing of PLC Compatable ATV 930 VFD 315 KW HEAVY DUTY 16 AMPWITH BREAKING UNIT VFD floor mounted Control Panel made out of 2MM C.R Powder coated sheet and alluminium BusBar interconnected with copper wire and lugsh having 50KA 125A MCCB including spreader link and extended ROM 1No RYB indicator 1set digital ammeter 1 No digital volt meter 1No 4A control For 150HP 3.0nos PumpCapacity of VFD 132KW |
| 18 | Supply installation testing and commissioning of Chemical earthing System with Backfill compound covered with earthpit and cover including transportation to site unloading etc. all complete as per direction of Engineer in charge |
| 19 | INSTRUMENTATION OF EXISTING WTP Supply and Laying of 40MM dia HDPE pipe Make Supreme equvalent in cable trench or buried as per specification and directions of Site Engineer Engineer in Charge. |
| 20 | Supply Installation and commissioning of Control cables to be inserted in conduit pipe in trenches cables to be laid in racks cleated on walls cable lugs cables glands conduits cablejoints etc. as per specification. all Complete Works Screened cable unarmoured and completed as per specification and directions of Site Engineer Engineer in Charge. Supply Installation and commissioning of CAT 6 Dlink cable and completed as per specification and directions of Site Engineer Engineer in Charge. |
| 21 | Supply and installation of LOH Loss of Head indicator with display unit 4 sets at filter house for auto wash of filter bed with following technical specifications Housing Cast Aluminium Powder Coated. Mounting Wall Mounting Power Supply 230 V AC 50 Hz Power Consumption 4 VA approximately Adjustment Range Span Min 10 percentcof Electrode Length Alarm A relay C O rated 6 Amps 230 V non inductiveload adjustable throughout range Current output 4 20mA DC non isolated max. load resistance 600 Ohms corresponding to differential level Accuracy Plus or Minus 4 percent of Electrode Length Option 1. Local as well as Control Room Display. 2. Loss of Head LoH can be supplied with Rate of Flow RoF in a common CA Housing with IP 55Protection and completed as per specification and directions of Site Engineer Engineer in Charge. Make Reputed make like Siemens Sapcon. |
| 22 | PLC panel for Filter bed Design manufacture supply installation testing and commissioning of indoor type PLC panel of size approx. 1000 mm X 700 mm X 1500mm LBH fabricated out of min. 2 mm thick CRCA sheet powder coated to Siemens gray color.The Panel shall be provided with reputed make PLC with following accessories as well as input output configuration.The PLC shall be programmed with IEC 61131 standards for control monitoring and communication of equipments and instruments at Raw water Pumphouse.PLC shall have Ethernet port and protocal for Modbus TCP communication with following IO.DI 16 num DO 16 num AI 8 num AO 4 num.10 inch color TFT HMI complete with programming shall be provided to interact with PLC. The panel shall include all the accessories not limited to following to achieve purpose of smooth and trouble free operation of pump house.MCB 10A DP 1 num MCB 4A DP 4 num 24 VDC Power Supply 10A 1 num Push Buttons 7 num Selector Switch 2 num Control Contactor 2 num Annunciator with 6 Windows NO to NC TypeElectronic Hooter 1 num Control Transformer 1 num Emergency PB 1 num Panel Cooling Fan 1 numPanel Light with Door Switch 1 num Control Indication Lamp 5 num Wiring TB etc 1 lot Hardware 1 lot and all Complete Works as per specification and directions of Site Engineer Engineer in Charge |
| 23 | Windows based PC with latest configuration and OS complete with necessory office and antivirus softwares.PC configuration shall not be less than Intel i5 10th Gen CPU 16 GB Ram 128 GB SDD 500 GB HDD DVD RW Rs232 and Rs485 port 2 RJ45 ports Keyboard Optical Mouse 32 inch color TFT Monitor Latest Windows Pro OS Microsoft Office and Antivirus and Internet Sequrity software for 3 years license and completed as per Ingineering In Charge. |
| 24 | Supply Installation and commissioning of single phase 1KVA online UPS with pure sine wave and float cum boost charging with battery rack and maintenance free battery system including cables power plug switch having application in 24V lot DC Battery drytype charging to output continuous 3 hrs power backup all Complete Works. |
| 25 | Supply and installation of Pressure Transmitter Designing Supplying Installing commissioning and testing of pressure transmitter CE markd with following technical parameters at Raw Water Pump House and Interfacing with PLC panel including mounting arrangement along with snubber and needle valve 1.0 sq.mm 2 core copper braided screen cable Wire screw grip and clamp for DI MS pipe fitting.Output 4 20 mA HARTPower supply 24V DC ext.Display 4 LEDAccuracy 0.1 percent of full scaleor betterEnclosure IP 68 and completed as per specification and directions of Site Engineer Engineer in Charge.Air blowing Pump Clear water loading pump |
| 26 | Providing installation testing and commissioning of Diaphragm Type Pressure Gauges Dial size 150 mm glycerin filled shatterproof glass Over range protection 125 percent of maximum pressure Material of sensor and other wetted parts SS type 316 Housing material Die cast aluminum with linear scale and all Complete Works as per specification and directions of Site Engineer Engineer in Charge Air blowing Pump Clear water loading pump |
| 27 | Design Supply Installation Testing of pH analyser as per IUPAC International Union for Pure and Applied Chemistryat A.F. and Interfacing with PLC panel including mounting arrangement.Range 0 to 14 pH Accuracy Better than 0.1 percent of full scale Supply Voltage 24V dc Output 4 to 20 mA HART As per IEC 61000 6 2 and IEC 61000 6 3. Inlet and Out Let |
| 28 | Design Supply Installation commissioning testing of Turbidity Anayser as per ISO 7027 scattering light method at A.F. and Interfacing with PLC panel. Turbidity analyser shall comprises of 3 components i.e. sensorssignal distributor and transmitter with indicator. with 2 Outputs 1 to PLC and anather to Local Display with mounting arrangement. Inlet and Out Let.Overall Range 0 to 2000 NTU Accuracy minus 0.02 NTU Supply Voltage 230 V ac Output 4 to 20 mA HART. |
| 29 | Designing Supplying Installing commissioning and testing of Ultrasonic level transmitter CE marked with following technical parameters Interfacing with PLC panel including mounting arrangement.Output 4 20 mA HART.Power supply 24V DC ext.Display 4 LEDRange 0 10 mtr 20 mtr.Accuracy 0.25 percent of FullScale or betterEnclosure IP 68Mounting On PLC panel all Complete Works as per specification and directions of Site Engineer Engineer in Charge at Back Wash Tank |
| 30 | Supply Installation and commissioning of soft Starter with six wire bypas arrangement up to 300HP and completed as per specification and directions of Site Engineer Engineer in Charge.Back Wash Tank fill Pump 2.0nos 20HP and Air Blowing pump 2.0nos 30HP Flush Mixtuer 5HP 2.0nos |
| 31 | Supply and delivery of Actuator control sluice valve of PN 1.6 with Body and Bonnet of Ductile Iron GGG 40 SG 400 15 or GGG 50 SG 500 7 or Equivalent as per IS1865 IS 3896 2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM Replaceable Spindle Nut without gland packing with 3 O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100 percent leak proof . Fitting and fixing of sluice valves with tail pieces nesaceery rubber packing SS 204 nut bolt including labour T and P transportation to site from store and fixing the surface boxes with electric actuator resistant to high pressure and robust design torque 7 2000 Nm motion range 0 360A degree voltage 220V AC applicable for actuating multi turn valves with Case Body Opening Mete Inlet Wire Lock Rubber Cover of Handle Shaft No Bracket Installation Gear Box Cover Electric Cover Wiring Cover Handle Shaft Cover Output Shaft and Adapter and completed as per specification and directions of Site Engineer Engineer in Charge. 100 mm2.0nos Air Blowing Tank 4.0nos at Filter Bed for air blowing |
| 32 | 150 mmBack Wash tank filling pump 2nos |
| 33 | 250 mmClear water out let from filter bed 4.0nos clarifloculator drain water pipe 2.0nos |
| 34 | 300 mmBack wash water pipe 4.0nos Back wash out let pipe 2.0nos |
| 35 | providing Actuator oparated Gates varies location as per specification and directions of Site Engineer Engineer in Charge Inlet chanel at Clariflocuter400X400 |
| 36 | Inlet chanel at fileter Bed450X450 |
| 37 | Designing Supplying Installing commissioning and testing with Terminating and Interfacing of 2 C x 1.5 sq.mm as per IS 694 twisted shielded copper armoured conductor on wall in GI tray or in ground suitable for supplied DC Voltage and all Complete Works as per specification and directions of Site Engineer Engineer in Charge |
| 38 | Supplying and erecting armoured control cable with ISI mark stranded solid copper conductor 1.1 kV grade complete erected on wall panel or in provided trench in an approved manner. 4c X 2.5 sq mm Copper conductor PVC insulated armoured control cable and all Complete Works as per specification and directions of Site Engineer Engineer in Charge |
| 39 | Designing Supplying Installing commissioning and testing with Terminating and Interfacing of 2 pair x 1.0 sq.mm. as per IS 694 copper shieled twisted multistraned armoured cable on wall in GI tray or on ground and all Complete Works as per specification and directions of Site Engineer Engineer in Charge |
| 40 | Supply installation testing and commissioning of Chemical earthing System with Backfill compound covered with earthpit and cover including transportation to site unloading etc. all complete as per direction of Engineer in charge |
| 41 | MCC Room Supply all material labour T and P for installation and testing commissioning of PLC System of appropriate capacity and sufficient provision of digital and analog input and output to rum the plant and machineries within the campus limit with minimum 20 percent spare cards being operated locally at WTP campus with provision of PLC operation On and Off of feed pump with respective Chlorine analyzer with an architecture of maintaining water quality in distribution pipeline at identified location. Complete operation of the feed pump depends upon the water quality communicated via point to pointP2P signal from the remote analyzer unit to main PLC. Provision should be there for LIVE data communication by agency between the PLC panels through FO Cable for the operation on and off of clear water Well Pumps as per the water requirement at MBR. Local data storing facility should be there and for monitoring and analysis as per the user needs and report generation. The Cost is inclusive of cost of materials installation and successful commissioning etc The PLC and all necessaries shall be of high standard make. Schneider Siemens Rockwell. |
| 42 | Design manufacture supply installation testing and commissioning of SCADA System for WTP Plant Sand Filter beds and pump house.Windows based PC with latest configuration and OS complete with necessory office and antivirus softwares. PC configuration shall not be less than Intel i5 10th Gen CPU 16 GB Ram 128 GB SDD 500 GB HDD DVD RWRs232 and Rs485 port 2no RJ45 ports Keyboard Optical Mouse32 inch color TFT Monitor Latest Windows Pro OS Microsoft Office and Antivirus and Internet Sequrity software for 3 years license.SCADA Software of reputed company with developer and runtime license with minimum 512 number of Tags with following features and functions.1. Supervise real time data in the form of graphical presentation.2. Control WTP processes locally or through Remote locations.3. Dynamic process Graphic It should resemble the process mimic. SCADA should have good library of symbols so that develop the mimic as per required. When operator sees the screen he should know what’s going in plant.4. Alarm summery and Alarm history SCADA system must be able to detect display and log alarms and events. When there are problems the SCADA system must notify the operators to take corrective action.5. Acquire real time data as well as logs data with Real time trend and Historical time trend.6. Web Connectivity Real time displays can be accessed on remotely attached PCs and notebooks using internet.SCADA Programming shall be done so as operator can visualize and control complete WTP operation from operator desk. All important alarms and events shall be logged. All the data from field instruments and equipments shall be logged. There shall be provision to take reports in required formats of real time and historical data events and alarms. There shall be provision of broadcasting messages emails of reporting information. There shall be provision of access security.An Industrial grade Din rail mounting ethernet switch with 5 ports shall be provided. An Industrial grade modem with 4G 5G GSM connectivity shall be provided complete as per specification and directions of Site Engineer Engineer in Charge. |
| 43 | Supply Installation and commissioning of single phase 1KVA online UPS with pure sine wave and float cum boost charging with battery rack and maintenance free battery system including cables power plug switch having application in 24V lot DC Battery drytype charging to output continuous 3 hrs power backup all Complete Works. |
| 44 | Windows based PC with latest configuration and OS complete with necessory office and antivirus softwares.PC configuration shall not be less than Intel i5 10th Gen CPU 16 GB Ram 128 GB SDD 500 GB HDD DVD RW Rs232 and Rs485 port 2 RJ45 ports Keyboard Optical Mouse 32 inch color TFT Monitor Latest Windows Pro OS Microsoft Office and Antivirus and Internet Sequrity software for 3 years license. |
| 45 | Supply Installation and commissioning of LT surge arrester having 5KA capacity with Spike and all accessories including cost of all materials labour T and P etc all complete. |
| 46 | Supply Installation 1TB SSD Solid State Device for RAM as per specification and direction of Enginer in charge |
| 47 | Supply Installation of 43 LED TV for SCADA PC Extension for operator station as per specification and direction of Enginer in charge. |
| 48 | Supply Installation of OFC Splicing with pigtails |
| 49 | Supply Installation of Fibre Pigtail patch cord 1 mtr as per specification and direction of Enginer in charge |
| 50 | Supply Installation of CAT 6 Delink cable as per specification and direction of Enginer in charge |
| 51 | Laying of CAT 6 cable either in HDPE duct underground or GI wire support as per specification and direction of Enginer in charge |
| 52 | Desiging supplying installing commissioning and testing of CCTV IR water proof camera suitable for upto 100ft.with IR Dome camera control key board DVR Hard Disk cables UPT transreceivers etc. complete. Make Hikvision CP Plus Evision Honeywell with 8 nos camera as per specification and direction of Enginer in charge. |
| 53 | Supply installation testing and commissioning of Chemical earthing System with Backfill compound covered with earthpit and cover including transportation to site unloading etc. all complete as per direction of Engineer in charge |
| 54 | Supply Installation of Control Desk 1 no. Table 1 no. and Chairs 2 nos. at Control Room as per specification and direction of Enginer in charge |
| 55 | Supply Installation of AC 2 Ton 5 Star as per specification and direction of Enginer in charge |
| 56 | CABLE TRENCH Excavation in unpaved areas of earth in work sites for conventional cable trenches for a depth upto 1.2metres or below towards laying of 40mm dia HDPE pipe along water Pipeline including backfilling the trench job complete in all respects including all labour and materials complete as per specification and directions of Site Engineer Engineer in Charge. |
| 57 | Hot Dip Galvanised Tees for Cable Tray |
| 58 | Hot Dip Galvanized Bends for Cable Tray |
| 59 | Supply Installation and commissioning of cable tray 80mm width to wall celling with necessary bracket for laying of power and data cable etc. as per specification. all Complete Works. |
| 60 | SupplyingInstallation and testing of network gateway often including firewall VPN and traffic management features of Firewall throughput 7000Mbps Firewall IMIX 2900Mbps IPS throughput 1355Mbps Threat protection throughput 330Mbps Concurrent Connection 1600000 New connection sec 44400 Xstream SSL TLS Inspection 420Mbps Xstream SSL TLS Concurrent connections 81924G and comlpeted as per specification and Ingineering_In Chargeas. |
| 61 | CLEAR WATER PUMP AT WTP AND INLET OF OGR.Pressure Transmitter Designing Supplying Installing commissioning and testing of pressure transmitter CE markd with following technical parameters at Raw Water Pump House and Interfacing with PLC panel including mounting arrangement along with snubber and needle valve 1.0 sq.mm 2 core copper braided screen cable Wire screw grip and clamp for DI MS pipe fitting.Output 4 20 mA HARTPower supply 24V DC ext.Display 4 LEDAccuracy 0.1 percent of full scaleor betterEnclosure IP 68 |
| 62 | Provision of Glycerine filled Pressure Gauge with fittings and isolation ball valve with socket including cost of all materials Transportation to site etc all complete all labours T and P etc. all complete as per the direction of Engineer in charge. |
| 63 | Design manufacture supply installation testing and commissioning of indoor type PLC panel of size approx. 1000 mm X 700 mm X 1500mm LBH fabricated out of min. 2 mm thick CRCA sheet powder coated to Siemens gray color.The Panel shall be provided with reputed make PLC with following accessories as well as input output configuration.The PLC shall be programmed with IEC 61131 standards for control monitoring and communication of equipments and instruments at Raw water Pumphouse.PLC shall have Ethernet port and protocal for Modbus TCP communication with following IO.DI 16 num DO 16 num AI 8 num AO 4 num.10 inch color TFT HMI complete with programming shall be provided to interact with PLC. The panel shall include all the accessories not limited to following to achieve purpose of smooth and trouble free operation of pump house.MCB 10A DP 1 num MCB 4A DP 4 num 24 VDC Power Supply 10A 1 num Push Buttons 7 num Selector Switch 2 num Control Contactor 2 num Annunciator with 6 Windows NO to NC TypeElectronic Hooter 1 num Control Transformer 1 num Emergency PB 1 num Panel Cooling Fan 1 numPanel Light with Door Switch 1 num Control Indication Lamp 5 num Wiring TB etc 1 lot Hardware 1 lot and all Complete Works as per specification and directions of Site Engineer Engineer in Charge. |
| 64 | Windows based PC with latest configuration and OS complete with necessory office and antivirus softwares.PC configuration shall not be less than Intel i5 10th Gen CPU 16 GB Ram 128 GB SDD 500 GB HDD DVD RW Rs232 and Rs485 port 2 RJ45 ports Keyboard Optical Mouse 32 inch color TFT Monitor Latest Windows Pro OS Microsoft Office and Antivirus and Internet Sequrity software for 3 years license and completed as per Ingineering In Charge. |
| 65 | Supply Installation and commissioning of single phase 1KVA online UPS with pure sine wave and float cum boost charging with battery rack and maintenance free battery system including cables power plug switch having application in 24V lot DC Battery drytype charging to output continuous 3 hrs power backup all Complete Works. |
| 66 | Supply Installation and commissioning of Control cables to be inserted in conduit pipe in trenches cables to be laid in racks cleated on walls cable lugs cables glands conduits cablejoints etc. as per specification. all Complete Works Screened cable unarmoured. 1.5 sqmm 4 C CU AR Shielded Cable |
| 67 | 1.5 sqmm 2 CU AR Shielded Cable |
| 68 | Instrument Cable 2 Pair 1.5 mm2 cable |
| 69 | Supply Installation and commissioning of Control cables to be inserted in conduit pipe in trenches cables to be laid in racks cleated on walls cable lugs cables glands conduits cablejoints Screened cable unarmoured etc all Complete Works as per specification and directions of Site Engineer Engineer in Charge. CAT 6 Dlink cable |
| 70 | Supply and delivery of Actuator control sluice valve of PN 1.6 with Body and Bonnet of Ductile Iron GGG 40 SG 400 15 or GGG 50 SG 500 7 or Equivalent as per IS1865 IS 3896 2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM Replaceable Spindle Nut without gland packing with 3 O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100 percent leak proof . Fitting and fixing of sluice valves with tail pieces nesaceery rubber packing SS 204 nut bolt including labour T and P transportation to site from store and fixing the surface boxes with electric actuator resistant to high pressure and robust design torque 7 2000 Nm motion range 0 360° voltage 220V AC applicable for actuating multi turn valves with Case Body Opening Mete Inlet Wire Lock Rubber Cover of Handle Shaft No Bracket Installation Gear Box Cover Electric Cover Wiring Cover Handle Shaft Cover Output Shaft and Adapter. 250 mm |
| 71 | Supply of Level Transmitter to be installed at wash water tank and CWR Clear Water Reservoir with following specification Range 0 to 8 mtr Type Ultrasonic Radar Power Supply Loop Powered 24V DC Out Put 4 20mA Make Vega Techtrol Forbes Marshall ABB at UGR |
| 72 | Supplying all materials labour t and p and fixing of PLC Compatable ATV 930 VFD 315 KW HEAVY DUTY 16 AMPWITH BREAKING UNIT VFD floor mounted Control Panel made out of 2MM C.R Powder coated sheet and alluminium BusBar interconnected with copper wire and lugsh having 50KA 125A MCCB including spreader link and extended ROM 1No RYB indicator 1set digital ammeter 1 No digital volt meter 1No 4A control For 100HP 2.0nos PumpCapacity of VFD 90KW |
| 73 | O and M for 5 YearsOperation and maintenance of P.H. Installation for 5 yrs as per scope of work and technical specificaion as per direction of EIC.(Comprehensive O&M including Manpower, Software & application licence renewal and material components for O&M etc) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 20, 2026
11:30 IST
Tender Published
Tender notice published.
Completed
Sep 02, 2026
18:00 IST
Corrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 10 daysSep 02, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 10 daysTender Documents
Download All (ZIP) ↓
Disclaimer