Tender For special Repair Low Tension Panel In Otm And Md Accn In Eastern Area Of Hisar Military Station Under Ge Hisar
Tender Value
38.82 Lakhs
Estimated cost
Bid Submission
08 Sep 2026
15 days left
EMD
77640
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Hisar → Haryana
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for special Repair Low Tension Panel In Otm And Md Accn In Eastern Area Of Hisar Military Station Under Ge Hisar
BOQ
| Sl. No. | Item Description |
| 1 | Supply, installation, commissioning and testing in replacement of LT Panel out door type, LT 415 Volts, 50 Hz , 3-phase, 4 wire supply, size of LT panel not less than 1.5 m high x 2.5 m width x 1.0 m depth CPRI approved/tested, factory assembled, out door type, weather and vermin proof (Protection Class IP-54) made out of 3.15 mm (for external) and 2.00 mm (for internal) thick MS Sheet CRCA sheet with both side (front and back) hinged, double door opening for external, rubber lining, locking arrangement, painted internally and externally with powder coating of grey shade (RAL-7032) mounted on chanel iron of size 75mm x 40mm x 5 mm mounting on blocks of PCC 1:2:4 type C1 of block size 60x60x60 cm including Bus bar chamber having 4 nos air insulated Aluminium strip bus bars of rating not less than the 1.5 times the rated capacity of the incomer ACB/MCCB, bus bar must be colour coded heat shrinkable as well as outgoings shall have aluminium four pole (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs comprising of the following :- (A) INCOMING :- (i) ACB 4 pole , LT 415 Volts, 50 Hz AC grade of 800 Amps rating 50 KA rupturing capacitiy with Adjustable Thermal and Fixed Magnetic setting - 01 No.Contd/-............................. |
| 2 | (ii) Voltmeter 0-500 V digital type with 3 way rotary selector switch - 01 No (iii) Ammeter 0-800 Amp digital type with 3 way rotary selector switch - 01 No(iv) Indicating lamp one set of three (v) CT of suitable size class-1 ISI marked - 01 Set of three (B) OUTGOINGS :- (i) MCCB 4 pole, 415 Volts, 50 Hz AC, 250 Amps 36 KA rupturing capacitiy with Adjustable Thermal and Fixed Magnetic setting -8 Nos. (ii) MCCB 4 pole, 415 Volts, 50 Hz AC, 63 Amps 25 KA rupturing capacitiy with Adjustable Thermal and Fixed Magnetic setting - 1 Nos Notes :- (i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimples.(ii) The various feeders shall be indicated by 50mm size letters in synthetic enamel white paint (iii) All MCCB should be connected to Bus bar directly through expended links. |
| 3 | All as per item No 1 here-in-before, size of LT panel not less than 1.5 m high x 2.0 m width x 0.80 m depth but incommer & outgoing as per the following:- (A) INCOMING :- (i) ACB 4 pole , LT 415 Volts, 50 Hz AC grade of 630 Amps rating 50 KA rupturing capacitiy with Adjustable Thermal and Fixed Magnetic setting - 01 No. (ii) Voltmeter 0-500 V digital type with 3 way rotary selector switch - 01 No (iii) Ammeter 0-800 Amp digital type with 3 way rotary selector switch - 01 No(iv) Indicating lamp one set of three (v) CT of suitable size class-1 ISI marked - 01 Set of three (B) OUTGOINGS :- (i) MCCB 4 pole, 415 Volts, 50 Hz AC, 250 Amps 36KA - 04 Nos. (ii) MCCB 4 pole 63 Amps 16 KA - 04 No. |
| 4 | All as per item No 1 here-in-before, size of LT panel not less than 1.0 m high x 1.5 m width x 0.5 m depth but incommer & outgoing as per the following:- (A) INCOMING :- (i) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 400 Amps rating 36 KA - 01 No. (ii) Voltmeter 0-500 V digital type with 3 way rotary selector switch - 01 No (iii) Ammeter 0-400 Amp digital type with 3 way rotary selector switch - 01 No(iv) Indicating lamp one set of three (v) CT of suitable size class-1 ISI marked - 01 Set of three (B) OUTGOINGS :- (i) MCCB 4 pole, 415 Volts, 50 Hz AC, 250 Amps 36 KA -1 Nos. (ii) MCCB 4 pole, 415 Volts, 50 Hz AC, 63 Amps 16 KA -8 Nos. |
| 5 | All as per item No 1 here-in-before, size of LT panel not less than 1.0 m high x 1.5 m width x 0.5 m depth but incommer & outgoing as per the following:- (A) INCOMING :- (i) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 250 Amps rating 36 KA - 01 No. (ii) Voltmeter 0-500 V digital type with 3 way rotary selector switch - 01 No (iii) Ammeter 0-400 Amp digital type with 3 way rotary selector switch - 01 No(iv) Indicating lamp one set of three (v) CT of suitable size class-1 ISI marked - 01 Set of three (B) OUTGOINGS :- (i) MCCB 4 pole, 415 Volts, 50 Hz AC, 100 Amps 25 KA -8 Nos. (ii) MCCB 4 pole, 415 Volts, 50 Hz AC, 63 Amps 16 KA -1 Nos. |
| 6 | All as per item No 1 here-in-before, size of LT panel not less than 1.0 m high x 1.5 m width x 0.5 m depth but incommer & outgoing as per the following:- (A) INCOMING :- (i) MCCB 4 pole , LT 415 Volts, 50 Hz AC grade of 250 Amps rating 36 KA rupturing capacitiy with Adjustable Thermal and Fixed Magnetic setting - 01 No. (ii) Voltmeter 0-500 V digital type with 3 way rotary selector switch - 01 No (iii) Ammeter 0-400 Amp digital type with 3 way rotary selector switch - 01 No(iv) Indicating lamp one set of three (v) CT of suitable size class-1 ISI marked - 01 Set of three(B) OUTGOINGS :- (i) MCCB 4 pole, 415 Volts, 50 Hz AC, 100 Amps, 25 KA - 05 Nos. (ii) MCCB 4 pole 63 Amps 16 KA - 03 No. |
| 7 | All as per item No 1 here-in-before, size of LT panel box (Kiosk) type not less than 1.0 m high x 1.0 m width x 0.5 m depth but incommer & outgoing as per the following:-(A) Incoming :- (i) MCCB 4 pole, LT 415 volts, 50 Hz, AC, 250 Amps rating with 36 KA rupturing capacity, thermal & magnetic release adjustable type (Ics=100%Icu) - 01 No(ii) Bus bar Aluminium TPN 400 Amps - 01 Set of 4Note:- (i) All incoming / outgoing cables shall be connected through suitable size gland plate/glands and these will be connected with Al lugs of suitable size (ii) The size of gland plates should be suitable capacity of cable(iii) The rate quoted shall deemed to be included necessary internal wiring with copper conductor of suitable size as per manufacture requirement |
| 8 | M&L for earthing complete with galvanized steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of plate not less than 1.5 m deep below normal ground level and connected to and including galvanized iron strip 25 x 4 mm by means of GI nuts, bolts, check nuts, washers thimbles, etc as shown in electrical plate No 3 of SSR Part-I and connection to main switch board/Test point/panel/equipment and testing on completion including excavation and earth work in any type of soil, returning filling in, and removal of surplus spoil to a distance not exc 50 metre, charcoal and salt in alternate layer 15 cm thick all around the earth plate electrode, MS funnel with wire mesh, GI pipe medium grade 20 mm bore for watering and 40 mm bore upto 7.50 metre long GI pipe light grade for earth wire protection fixed with poles/wall with two clamps, made from MS flat 25 mmx3mm, bolts, nuts and washers, PCC chamber (1:3:6) type C1, 40mm thick precast RCC cover 1:2:4 type B1 shall be provided on CI frame etc complete including taking down existing u/s earthing all as specified & as directed. Note :- PCC chamber shall be constructed at least 1.5m away from the earth electrode and pipe for watering shall be provided in slanting manners. |
| 9 | Taking out the old unserviceable LT underground cable 16 Sqmm 4 core 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors from trenches/wall/floor/road/ culverts or pole etc complete all as specified and directed. Note : Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing/cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately. |
| 10 | All as per item No 8 (here-in-before) but 25 Sqmm 3.5 core. |
| 11 | All as per item No 8 (here-in-before) but 35 Sqmm 3.5 core. |
| 12 | All as per item No 8 (here-in-before) but 70 Sqmm 3.5 core. |
| 13 | All as per item No 8 (here-in-before) but 120 Sqmm 3.5 core. |
| 14 | All as per item No 8 (here-in-before) but 185 Sqmm 3.5 core. |
| 15 | All as per item No 8 (here-in-before) but 240 Sqmm 3.5 core. |
| 16 | Supply , laying, jointing, testing and commissioning of size 16 Sqmm 4 core LT underground cable, 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased in GI pipe complete all as specified.Note : (i) All incoming and outgoing cable shall be connected by suitable size of thimples/legs. |
| 17 | All as per item No 15 (here-in-before) but 25 Sqmm 3.5 core. |
| 18 | All as per item No 15 (here-in-before) but 35 Sqmm 3.5 core. |
| 19 | All as per item No 15 (here-in-before) but 70 Sqmm 3.5 core. |
| 20 | All as per item No 15 (here-in-before) but 120 Sqmm 3.5 core. |
| 21 | All as per item No 15 (here-in-before) but 185 Sqmm 3.5 core. |
| 22 | All as per item No 15 (here-in-before) but 240 Sqmm 3.5 core. |
| 23 | Excavation in trenches not exceeding 1.5 m wide and not exc. 1.5 m depth for laying cables, foundation for pole etc and getting out in soft/loose soil etc complete all as specified and as directed.Note : 1. The rate inclusive of taking down and refixing of any type of cheqered tiles, interlocking tiles complete as per existing for good make. 2. The PCC work shall be measured & paid for separately uner respective item of Sch 'A' / BOQ |
| 24 | M&L for sand cushioning 230mm thickness with dry sand (one layer of 80mm thickness before laying of cable and other layer of 150mm thickness after laying of cable) and punned down to 180mm after laying of cable in trenches for protection of cable complete all as directed. Note :- For the purpose of payment only punned thickness shall be measured. |
| 25 | Old underviceable bricks laid as cable covers complete all as specified and directed. |
| 26 | M&L for brick covering to underground electric cable using sub class ‘B’ bricks, laid dry, flat, perpendicular to the direction of cable etc complete all as specified and directed. |
| 27 | Returning filling in incl spreading leveling watering and well ramming in layers n. exc 25cm thick etc complete all as specified and as directed. |
| 28 | Removing excavated material to distance n. exc 50m and depositing where directed at a level n. exc 1.5m above the starting point etc complete all as specified and as directed. . |
| 29 | M&L for boring of hole under road/pavement/hard standing or any other situation by mannual means and suitable for passing of GI pipe 100 mm bore and making good both ends all specified and directed. |
| 30 | Supply and fixing in replacement 40 mm bore steel tube of light grade galvanised with all fittings fixed to walls / floors / poles or under road etc of following sizes complete all as specified and directed. |
| 31 | Supply and fixing in replacement 80 mm bore steel tube of light grade galvanised with all fittings fixed to walls / floors / poles or under road etc of following sizes complete all as specified and directed. |
| 32 | Demolition of path /concrete in ground floors and pavings (below or above ground level) complete all as specified and as directed. Note : The rate inclusive of taking down and refixing of any type of cheqered tiles, interlocking tiles complete as per existing for good make as per direction of EIC. |
| 33 | M&L for cement concrete type B-2, 1:2:4 (40mm graded aggregate) complete all as specified and as directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 19, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 08, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 15 daysSep 10, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 17 daysTender Documents
Download All (ZIP) ↓