Housing Urban and Rular Development Government Departments Closing in 2 days TDR #57099727

Tender For Electrification Work In Sdo Cum Tehsil Building At Bari Distt Dholpur.

Issued by Government Departments · Sawai Madhopur, Rajasthan
Tender Value
38.20 Lakhs
Estimated cost
Bid Submission
23 Aug 2026
2 days left
EMD
76400
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Sawai Madhopur → Rajasthan
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Electrification Work In Sdo Cum Tehsil Building At Bari Distt Dholpur.

BOQ

Name of Work:- Electrification work in SDO Cum Tehsil Building at Bari Distt Dholpur.
Sl. No. Item Description
1Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, Aluminum round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 6 A Modular switch, Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required.
2Short point (up to 3 mtr.)
3Medium point (up to 6 mtr.)
4Long point (up to 10 mtr.)
5Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 6 A modular switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required.
6On board
7S&F following sizes (dia.) of ISI marked MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including making jhiri in the wall,clamps at suitable spacing, covering conduit and making good the same as required.
820 mm
925 mm
1032 mm
1140 mm
12Supplying and laying FR PVC insulated & unsheathed flexible copper conductor of following nominal sizes with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required.
132 x 1.5 sq.mm
141 x 2.5 sq.mm
152 x 2.5 sq. mm. + 1x1.5sqmm
161 x 4.0 sq.mm
172 x 4.0 sq. mm. + 1 x 2.5 sq. mm.
184 x 6.0 sq.mm
191 x 10.0 sq.mm
204 x 10.0 sq.mm
21Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR
22Single pole MCB (With B/C curve tripping Characteristics)
236 A to 32 A rating
24Four pole MCB (With B/C curve tripping Characteristics)
2550/63 A rating
26Double pole MCB(With B/C curve tripping Characteristics)
2740 A rating
28Supplying and Laying PE Insulated & PVC Sheathed unarmoured telephone cable with 0.5 mm dia. Solid Annealed electrolytic grade bare Copper Conductor as per IS: 8130/84 & confirming to TEC specification GR / WIR/06-03 March 2002 in existing surface or recessed conduit/casing capping. including ferruling on each pair for Identification etc. as required.
292 pair
30P & F Krone module with base frame in the recess / surface made out of 1.2 mm thick sheet steel box, front openable, having locking arrangements duly powder coated ,including dressing, ferruling and punching of telephone cable with krone tool etc. as required.
3110 Pairs
32Providing & Fixing of 240/415 V Residual current circuit breaker (RCCB) conforming to (IS:12640-1)/ IEC 61008 -1 , rated 4 KV impulse withstand voltage truly current operated and shall operate on CBCT mechanisum, provision for pad lock, min. Electrical operation 10,000 upto 63 A rating and 5000 for 100 A rating and minimum phase termination capacity of 25 sq.mm. rigid wire , IP 20 contact protection with existing distribution board / sheet including making connections, testing etc. as required.
33Two pole 30 mA sensitivity
3432/40 A rating
3563A rating
36Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door (Metal / Glazed / Acrylic) Distribution board with Metal end box made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, complete with 100 amp. insulated copper bus bar/shorting link , brass neutral link with shrouds, brass earth link , door earthing arrangement, color coded interconnecting wire set of minimum 10.0 sqmm size and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required.
37Metal door (single phase) IK-09 and IP-43 with Metal end box
388 Way
39Metal door (Three phase) Per phase isolation, Horizontal IK-09 and IP-43 with Metal end box
406Way {8 Incomer + 6 Sub Incomer (2+2+2) + 18 out going }
41Providing & Fixing of single / multi tone electronic call bell / remote bell including making connection testing etc. as required.
42Providing & Fixing of modular type 100W Step Fan regulator duly ISI marked (IS 11037) with CM/L no. printed made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including making connections, testing etc as required.
435 step fan regulator 2 Module
44Providing & Fixing of following modular accessories, made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating, including making connections, testing etc as required.
45RJ-11 telephone jack single line
46Blanking plate
47Supplying and fixing of power plug point with Modular accessories on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost of ISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required.
48SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:-
49(a) Thickness of CRCA sheet shall not be less than 1.6 mm upto 450 mm length/ width of any compartment and be 2.0 mm above 450 mm, load bearing structure shall be 2.0 mm thick sheet supported by base M.S. channel if required, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided
50(b) complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side(Inner & Outer side) of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire.
51[c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra )
52(d) Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram.
53(e) All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.
54(f) Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra )
55(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out.
56(h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI type Test certificates for Temp. rise test, Short circuit test for 50 kA and IP test is to be submitted)
57Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator, with short circuit withstand capacity of 31 MVA for 1 Sec. , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves.
58Electrolytic grade Aluminium bus bar 6010 grade
59Providing & Fixing of 110/220 V, unibody LED Indicating lamp IEC 60947 with integral circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 27 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDC including connection etc. as required.
60Red/yellow/Green colour
61Blue / white Colour
62Providing & Fixing of IS: 13875 & IEC :61326/IEC:62053-22 confirming LED Digital type (up to 500) V range Volt meter / Direct- Ammeter / CT opertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required.
63Single Phase Ammeter
64Single Phase Voltmeter
65SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation from 50 to 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle ( to be paid extra) , including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate.
664 pole MCCB With Thermal Magnetic release
67125 Amp , 25 kA, adjustable O/L & Fixed S/C setting,
68250 Amp , 35 kA, adjustable O/L & adjustable S/C setting,
69Supply and fixing of following accessories for Moulded case circuit breaker (MCCB) compatible to main MCCB OEM as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 including making connection etc complete in all respect.
70Spreaders upto 125A, 3 Pole MCCB
71Spreaders for 250A, 4 Pole MCCB
72Providing & Fixing of on load change over switch, front handle operated, four pole 415 V confirming to IS/lEC 60947-3 : 1999 including connections , testing etc. as required .in the following rating.
73Open execution type
74160 A
75Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size.
7670.0 Sq. mm
773.5 core
786.0 Sq. mm
794 core
80Plate Earthing as per IS:3043 with Hot dipped G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required.
81Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping double the width of strip and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.
8225mm x 4 mm Alum. Strip
83Providing & Fixing of BEE Star rated copper wounded with class of Insulation 'F', double ball bearing capacitor start, aluminium body & aluminium blade ceiling fan conforming to all the performance requirements laid down in IS 374:2019 with down rod up to 30 cm with secondary support safety cable ( steel rope) , cotter pin, shackle kit with 3 x 1.5 sq.mm pvc insulated flexible copper conductor and making connection testing etc. as required.
841200 mm Sweep BEE 1 Star rated (service value >=4.0 to < 4.5 )
85P & F 1.2 mm thick M.S. Recessed fan box and top lid screwed on Box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 150 mm length extended on each side as required.
86Providing & Fixing of of Double ball bearing, copper wounded capacitor start single phase metallic blade fresh air fan, in existing opening including cost of hardware , flexible 3 core 1.5 Sq.mm copper conductor ,making connections, testing etc. as required.
87300 mm sweep Minimum air delivery 1600 Cum / hour
88Providing & Fixing of Heavy duty capacitor start, copper wound Double ball bearing 900/1400 RPM single phase Exhaust fan conforming to IS:2312 marked in existing opening including making connections testing etc. as required.
89300 mm sweep(900 RPM)
90SITC of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminium housing with in built driver , System lumen efficacy ≥ 110 lm/Watt output only at CW (5700K to 6500K) , internal surge protection of 4.0 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required.
911170mm(+/-10%) LED batten with min. lumen output 2200 lm
92SITC of IP-20 LED Recessed / Surface Mounted, Round / Square backlit & SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS compliance 4.0 KV surge protected Isolated driver, with Short & Open circuit protection input 320VAC-48 hr protection, input 350VAC-2 hr protection), having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt,at CW (5700K to 6500K) , THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) as required.
93Surface Mounting (with extruded alumn. Housing )
94Minimum lumen output 1300 lm
95Minimum lumen output 1950 lm
96SITC of IP20, 2'x2' LED Surface/ Recessed mounting backlit & SMD Mid power type LED Light fixture not less than 35 mm housing depth made from CRCA sheet steel housing, high purity / transmissivity UV stabilized Non -yellowish diffuser for uniform light distribution. operating voltage range 140-285 V, HV cutoff - LV cutoff should be 300-100V . High efficiency with 4 KV internal surge protection BIS certified isolated driver having efficiency > 85% , with Short & Open circuit protection ( input 320VAC-48 hoursprotection,input 350VAC-2 hours protection) (Integral with light fixture). System lumen efficacy of ≥ 120 lm/Watt ,THD < 10 % , p.f.≥0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required.
97Surface Mounting (Driver should be Inside the Luminaire)
98Minimum lumen output 4800 lm
99Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing and secondary lens on each LED/ integrated lens diffuser without cover & should be High power LED of 3 to 5 watt each . The System efficacy >=135 lm/ wt and integrated metal case potted driver & has a unique BIS R number ( as per IS 15885) with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC & Low Voltage cutoff @>=90 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . LED driving output current <750mA. The luminaire shall be BIS certified (Fitting & driver both have separte BIS R number) and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs as required.
100LED Street Light fixture with Minimum lumen output 12150 lm
101Providing & Fixing of Street light bracket made out from following size of ' B ' class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required.
10232 mm Dia.
103Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, U/UTP (Unscreened/Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected by LSZH Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies ranging from 250 to 500 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack & ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect.
104Supply and Installation of unshielded/360 degree shielded PCB based Information outlets made of high impact plastic body with ABS, Flammability rating UL 94 V-0 with provision for protection against dust in jack or Faceplate, suitable for Cat 6/6A application complying to latest amendments, According. to Cat. 6/6A channel, It should support channel as well as components requirements of Cat 6/6A standards at frequencies 250/ 500 MHz. Cat 6/6A unshielded/shielded Jack should be suitable to terminate 4 pair, 23/24 AWG solid/stranded wire diameters, using 100 Ohm unshielded/shielded balance twisted pair cable, the jack should have toolless/impact termination on reliable copper tin plated Insulation displacement contact, with easy lock mechanism, It supports IEC 60603-7-4 and complied with ANSI/TIA 568 C.2 & ISO/IEC 11801 or latest standard. jack should be RJ11,RJ12 & RJ45 compatible. Should support Ethernet 1.2 Gb/s ATM,Digital video and broadband/baseband analog video, Voice over internet protocol (VOIP) Specifications in existing modular/MS Boxes along with necessary connections as required. All as per pre approved by Engineer in charge.
105Cat 6, Un-sheilded Information Outlet
106Supply & fixing of square Faceplate for Flush / Surface Mount Information Outlets Single/Dual or Quad Aperture with dust cover, material should be High-impact, flame retardant, thermoplastic, UL listed material, Suitable for RJ45 unshielded/shielded connection modules. Should match with I. O. OEM. Dimensions should be 86mm X 86mm as required complete in all respect. All as per pre approved by Engineer in charge.
107Single Aperture
108Supply, Installation, Testing and Commissioning of Rack mounted 19\\" 1U, 24 Port loaded, CRS chasis, powder coated, sheet steel, High-impact, flame retardant, thermoplastic, UL Listed, Modular Patch Panels with Rear Cable management system and mounting hardware to mount the patch panel. Should have port identification numbers printed/engraved on front of the panel. Etc. as required. All as per pre approved by Engineer in charge.
109Modular Patch Panel Loaded with Cat -6 I/O
110Supply , Installation and Testing of 4 pair, 100 Ohm impedance, Cat 6/6A /Class E/Ea patch cords should be constructed of minimum 23/24 AWG, stranded bare Copper cable with LSZH Jacket, with an enhanced performance by factory moulded RJ45 connectors with strain relief boots as per ANSI/TIA/EIA 568-C.2 suitable for Cat 6/6A application complying to latest ammendments Category 6/6A Standards, According. to TIA568C.2, ISO/IEC 11801, EN 50173, IEC 60603-7-51, EN 60603-7, IEEE 802.3an minimum requirement for 1G BASE-T to 10G BASE-T performance. Patch cords shall be straight thru cable compatible with both T568-A and T568-B wiring schemes, should support IEEE 802.3af / IEEE 802.3at for POE applications, Minimum 750 to 1000 mating cycles in plug contacts for long durability, Should support Ethernet 10GBASE-T, 1.2 Gb/s ATM, Token ring 4/16, Digital video and broadband/baseband analog video, Voice over internet protocal (VOIP).
111Cat 6, U/UTP (Unscreened/Un-sheilded Twisted Pair) Patch Cord
1121 Mtr
113Supply & Installation of IP-20 & IK-08 , Wall mounted Double Section Communication enclosure (Rack) made from powder coated (60 to 80 Micron) CRCA sheet, front sturdy sheet steel frame folded from one piece and welded with minimum 5mm toughened glass door,Vertical Mounting Rail 1.6 MM with 'U'Marking , with All round protective channel on the door aperture, lock integrated on front door, top and bottom cover with cable entry provision with gland plates, integrated side walls, 2 pair of 19\\" angles with wall mounting provision on wall. Accessories like: 1 No of 19\\" 1U Horizontal Cable manager, 1 No of 90 cfm 230V AC Fan with 1 mts long cable, mounting hardware , 1 No of 19\\" 1U, mountable socket strips with 5 nos of 5A universal sockets with 2 mts long power chord for supplying power to switches, fans etc along with earth continuity kit, indicator, moulded power supply cable. fixing on wall with Suitable Anchor fastner etc as required.
11415 U Rack with Width 600 mm & Depth 400 mm + 100 mm
115Supply , Installation, Testing and Comissioning of Unmanaged Switch Plug-and-play - easy setup with no configuration or no software needed, following Port fast ethernet - 8 port 10/100/1000 MBPS auto-negotiation RJ45 ports, IEEE 802.3x flow control ,supports auto-MDI/MDIX, eliminating the need for crossover cables including making connection etc as required complete in all respect.
11624 Port
117Supply , Installation, Testing and Commissioning of Inverter type Air cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R- 407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity up to 42 Degree Celsius ambient temperature. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electro technical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 degree C (out door ambient temperature)
118Cooling capacity 5000-5300 Watt, ISEER not less then 3.8
119Cooling capacity 6200-6350 Watt, ISEER not less then 3.8
120Supply, Fixing and testing of following capacity IS:8448 marked wall mounted stabilizer having output voltage variation from 200 V to 250 V(+/-5%) with input voltage variation from 170 V to 260 V, time delay facility from 2 to 4 minute and high cutoff at 270 V with providing of 16 Amp /20 Amp Industrial plug top making connection etc complete in all respect.
1215 kVA
122Supply , Installation, Testing and Comissioning of IS:1475 marked self contained drinking water cooler with hermetically sealed compressor,non CFC refrigerent suitable for operation on 230V/1pH/50Hz AC supply,Full stainless steel (SS304)body (0.8 mm thick) and tank (0.5 mm thick) , stainless steel water tray,minimum two nos Brass Chrome plated faucets and suitable drainage system complete in all respect with required height MS fabricated and Painted Angle iron frame ( Cost of frame to be paid Extra )complete in all respect of the following capacity.
123cooling capacity 150 Ltr./Hr. and storage capacity 150 Ltrs
124Supply & Fixing of Dry Powder Agent (as per IS 4308:2019), ABC type Fire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 28 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted.
125Providing & Fixing of IK07 IP65 protected Top/Bottom mounted LED Post top Luminarie top & bottom made of single piece construction powder coated die cast alluminium housing with UV stabalized Clear / frosted Polycarbonate diffuser and Aluminium anodised with powder quoted reflector. The System level Luminous efficacy ≥ 80 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N) and efficiency > 85%, PF>0.9, THD<10% and input Voltage range of 140-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained . LED Driving output current <750mA as required.
126Minimum lumen output 3600 lm Post top Luminarie
127Providing & Fixing of following size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.
1281/2 Module
129P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of trench, CC Haunching, Back filling of Earth with compaction is to be Paid Extra).
13063 mm
13190 mm
132SITC of following capacity BIS certified 1Phase Input, 1Phase Output advance DSP controlled IGBT based rectifier Online UPS with 0.99 Input power factor &0.8 Output factor, having Input voltage & frequency range of 180-300V on full load/ 110-300V on 60% load & 50 Hz +/- 5% and output voltage & frequency of 230V+/-1% & 50 +/- 0.1 Hz.Overloading of 105 - 110% 10 mins, 111 - 130% 2 mins,131 - 150% 30 sec, THDv of < 3% for Linear & < 5% for Non linear load.UPS should have LCD display showing load level, Battery Voltage Level, Input & Output Voltage, Input & Output Frequency. UPS should have protection from Input High / Low;Over Load;Short Circuit; Over Temperature and give audible alarms on Battery Mode;Low Battery;Fault;Over Load & Bypass Mode.SMF Batteries of 12V VRLA for 30 min back up with MS Rack and necessary cable for UPS to Batteries Installation. UPS should have CE, ROHS, IEC62040-1,2&3 compliance and should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location Etc. as required.
1332KVA UPS with 1872 VAH Battery
134Supply and erection of Galvanized Iron pole with galvanizing done in single dipping (Average coating thickness Minimum 65 Microns) continuously tapered poles having Octagonal / Circular/ Conical cross-sections designed to withstand the maximum wind speed as per IS 875, The pole shaft shall be made from sheet steel (HT Steel Conforming to grade S355JO) and confirming to BSEN 10025 and shall be continuously tapered with single longitudinal welding. There shall not be any circumferential welding. The welding of pole shaft shall be done by Submerged Arc Welding (SAW) process. pole shafts shall be provided with the rigid flange plate of suitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, The base plate shall be fillet welded to the pole shaft at two locations i.e. from inside and outside.The octagonal Poles shall have hinged lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) inside the pole at door opening for cable connection of following length and dimension as per table P-01 for Octagonal & P-02 for Conical with base plate and foundation bolt on the Existing cement concrete foundation. To ensure quality of product it's entire manufacturing process starting from sheet cutting to galvanization sould be done under one premises.
135Poles with Octagonal/Conical Cross Section
1367 Mtr.
137Supply and Fixing of Pole OEM fabricated hot dipped galvanised M.S. Overhang (48.3 X 3.25 mm) with cap ( 250x 88.9 / 114.3 x 3.25 mm) over the existing poles.
138Single arm overhang
139Double arm overhang
140Providing and Laying RCC Foundation for Octagonal / Conical Street Light poles as per Drawing attach at Table P-05 with Following Procedure
141A) Excavation of Pit for Foundation Size upto required depth from Ground level
142B) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface complete.
143C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness
144D) Reinforcement for R.C.C. work with TMT bars including straightening, cutting, bending, placing in position and binding all complete.
145E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing and Pedestal
146F) Providing & Fixing of 2 no. Required Size PLB HDPE Pipe & Foundation Bolt with template as per OEM Recommendations.
147G) Providing and Laying Reinforce cement Concrete of M-20 grade in Footing and Pedestal including Curing the foundation for minimum 7 days.
148H) Providing and Fixing Nosing Angle 25 mm x 25 mm x 3mm with 2 no. of 100 mm long, 6 mm dia fastener
149Pole Foundation for Octagonal pole from 7 Mtr. To 9 Mtr.
150SITC of RO water system with Filteration stages = Particilate filter- Membrane life enhancer filter- sediment filter- pre carbon filter- RO membrane filter- post carbon filter. Input power rating -230V AC, 50Hz, percentage of rejection TDS-90% or better, having following features (a) Double purification by RO with ESS or latest technology with TDS indicator. (b) Spin welded RO membrane housing to prevent tempering. (c) Push fit component for leak proof performance. (d) Fully automatic operation with auto start and auto off. (e) SS/ABS construction for corrosion free lifespan. (f) Equally suitable for water from all borewells, overhead storage tanks, water tankers and even municipal taps. (g) RO membrane flushing - Auto flush@ every start, every stop and every one hour of working for one minute, complete in all respect with following capacity.
151Purification capacity - 25LPH, duty cycle 170-250 liters/day
152Providing & Fixing of following size cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.
1531/2 Module
154Add @ 18 % GST Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57099727
AUTHORITY Government Departments
TENDER VALUE 38.20 Lakhs
LAST DATE 23-08-2026
Authority
Authority Name Public Works Department
Work Description Tender for Electrification Work In Sdo Cum Tehsil Building At Bari Distt Dholpur.
Basic Detail
Tender No NIT-11-2026-27
Bidding Type Tender
Location
City Sawai Madhopur
State Rajasthan
Key Dates
Publish Date 20 Aug 2026
Submission Date 23 Aug 2026
Open Date 24 Aug 2026
Finance
Tender Value 38.20 Lakhs
Tender Fee 500
EMD 76400
Exemption Available
Document List
Annexure.pdf
BOQ_1049317.xls
c905ff64-3b18-433c-b1bf-003088817e8e.html
Conditions.pdf
Tendernotice_1 (54).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 20, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Aug 23, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 2 days
Aug 24, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 3 days

Tender Documents

Download All (ZIP) ↓
pdf

Annexure.pdf

xls

BOQ_1049317.xls

html

c905ff64-3b18-433c-b1bf-003088817e8e.html

pdf

Conditions.pdf

pdf

Tendernotice_1 (54).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders