Tender For Shifting/Re-Alignment Of Ht/Lt Network Along With Sub-Stations From Budiwudder To Kreshbal For Road Widening To Be Carried By Executive Engineer, Division Ganderbal Pmgsy (Jkrrda) Falling Under The Jurisdiction Of Esd Nawakadal, Ed-3Rd (Tu
Tender Overview
Project Description
Tender for Shifting/Re-Alignment Of Ht/Lt Network Along With Sub-Stations From Budiwudder To Kreshbal For Road Widening To Be Carried By Executive Engineer, Division Ganderbal Pmgsy (Jkrrda) Falling Under The Jurisdiction Of Esd Nawakadal, Ed-3Rd (Turnkey Basis).
BOQ
| Sl. No. | Item Description |
| 1 | Shifting/Re-alignment of HT/LT Network along with Sub-Stations from Budiwudder to Kreshbal for road widening to be carried by Executive Engineer, Division Ganderbal PMGSY (JKRRDA) falling under the jurisdiction of ESD Nawakadal, ED-3rd (Turnkey Basis). |
| 2 | Supply, Installation, Testing and commissiong of S.T. poles 9.0 Meter long swaged Type conforming to ST 410 SP-33, IS: 2713 amended up-to date well finished and coated with black bituminous paint upto plant depth and Red-Oxide coated above ground level with earthing arrangement through bolt welded on pole of 14mm diameter, provided at height of 300mm above the planting depth which should be 1.5ms (SP 33). Top plate 3mm thick fully welded & bottom plate 35cm*35cm, 5mm thick fully welded. |
| 3 | Supply, installation, testing and commissioning of 11 KV Gapless Surge Arrestor,9 kV, 10 kA, LA with polymer housing, Stn. Type conforming to IEC-99-4 Capable of withstanding Maximum continuous operating voltages (M.C.O.V) |
| 4 | Supply, installation, testing and commissioning of 11 KV Horn, Gap (fuse 3-phase 200A) as per Relevant IS. |
| 5 | Supply, installation, testing and commissioning of 11KV 200 Amperes, Triple pole switches Gang Operated (G.O. Set) conforming: IS-2544, IS: 5340 (Part-III) and SS: 9921 (Part-I -V) |
| 6 | Supply, installation, testing and commissioning of 400 mm2 XLPE LT Cable Single Core, Un-Armoured, XLPE lnsulated Stranded Conductor FRLS type including lugs/clamps/thimbles. |
| 7 | Supply, Fabrication and fixing of GI Channel/Angle/Flat of sizes including clamps /Collars 50x8mm |
| 8 | Supply, Installation, Testing and commissiong of 11kV Polymeric composite Pin Insulator with pins 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 9 | Supply, Installation, Testing and commissiong of 11KV Disc Insulators (Polymer Type) 12 KV, 45KN Complete with fittings (Lighting Impulse 75 KV positive and 80 KV negative , creepage distance 320 mm) |
| 10 | Proving and laying of Pole Earthing Complete by GI Pipe 40 mm 3mtr long through GI Strip 25x3 mm |
| 11 | Providing of material and laying of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set, along with baby insulators & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 12 | Design, Fabrication, Supply, installation, testing and commissioning of LT Fuse Set for Distribution Transformers (Customised) as per KPDCL Drawing no. CE/P&P/DRG/2023/LTFS/001 |
| 13 | Supply and Fixing of GI Wire 6 SWG & 8 SWG |
| 14 | Supply, Laying, installation, testing and commissioning of 50 mm² ACSR Conductor |
| 15 | Supply and Fixing of Danger Plates with Clamps |
| 16 | Supply & fixing of PG Clamps/ Wedge connectors |
| 17 | Supply and Fixing of Anti-Climbing Device with Clamps |
| 18 | Supply and Fixing of Galvanized Nuts and Bolts of sizes |
| 19 | Supply and Painting of poles with red Oxide |
| 20 | Supply and Painting of poles with Aluminium Paint |
| 21 | Supply and fixing of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 )mm, nutbolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
| 22 | Supply, Installation, Testing and commissiong of S.T. poles 8.0 Meter long swaged Type conforming to ST 410 SP-15, IS: 2713 amended up-to date well finished and coated with black bituminous paint upto plant depth and Red-Oxide coated above ground level with earthing arrangement through bolt welded on pole of 14mm diameter, provided at height of 300mm above the planting depth which should be 1.5ms (SP 15). Top plate 3mm thick fully welded & bottom plate 35cm*35cm, 5mm thick fully welded. |
| 23 | Supply, Laying, installation, testing and commissioning of 100 mm² ACSR Conductor |
| 24 | Supply and Fixing of 16 kN Polymer Shackle Insulators along with GI U-Clamps |
| 25 | Supply and Fixing of GI U-Clamps |
| 26 | Providing of material and laying of Cement bottoming 1:2:4 mix as per Standards 0.40 cum /pole |
| 27 | Providing of material and laying of Cement bottoming 1:2:4 mix as per Standards 0.48 cum /pole |
| 28 | Shifting (Dismantling & re-erection, Testing and Commissioning) of 250 KVA Distribution Transformer from current site to Proposed Site including carriage, transportation, loading, unloading. |
| 29 | Dismantling of old PCC Poles (to be broken at site) |
| 30 | Dismantling of old ST Poles and Transportation of same to Divisional Stores including carriage, transportation, loading, unloading. |
| 31 | Dismantling of old ACSR of different sizes and Transportation of same to Divisional Stores including carriage, transportation, loading, unloading. |
| 32 | Dismantling of Allied Material of old sub-station, old isolator set and Transportation of same to Divisional Stores including carriage, transportation, loading, unloading. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 10 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 2 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender