Tender For Construction Of 12 Nos. New 33/11Kv Substation With Associated 33Kv Line Including Civil Works, annual maintenance contract And O&M For 5 Years
Tender Value
262 Crore
Estimated cost
Bid Submission
02 Sep 2026
9 days left
EMD
2.87 Crore
Bank guarantee accepted
Document Fee
29500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Dehradun → Uttarakhand
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Construction Of 12 Nos. New 33/11Kv Substation With Associated 33Kv Line Including Civil Works, annual maintenance contract And O&M For 5 Years
BOQ
| Sl. No. | Item Description |
| 1 | Construction of 2x12.5MVA, 33/11kV Substation Khermansingh, Maldevta, Dehradun and associated 33kV (7.2km) Line including civil works, AMC and O&M for 5 yearsTotal BoQ2 Supply price |
| 2 | Total BoQ3Erection price |
| 3 | Total BoQ4 AMC and O&M Price for 5 years |
| 4 | Total BoQ5 Civil Price |
| 5 | Construction of 2x5MVA, 33/11kV Substation Purkul, Dehradun and associated 33kV (0.7km) Line including civil works, AMC and O&M for 5 yearsTotal BoQ6 Supply price |
| 6 | Total BoQ7 Erection price |
| 7 | Total BoQ8 AMC and O&M Price for 5 years |
| 8 | Total BoQ9 Civil Price |
| 9 | Construction of 2x12.5MVA, 33/11kV Substation Nakronda, Dehradun and associated 33kV (2x0.8km) LILO Line including civil works, AMC and O&M for 5 yearsTotal BoQ10 Supply price |
| 10 | Total BoQ11 Erection price |
| 11 | Total BoQ12 AMC and O&M Price for 5 years |
| 12 | Total BoQ13 Civil Price |
| 13 | Construction of 2x12.5MVA, 33/11kV Substation Landhaura, Rookree and associated 33kV (2x3.5km) LILO Laksar Line including civil works, AMC and O&M for 5 yearsTotal BoQ14 Supply price |
| 14 | Total BoQ15 Erection price |
| 15 | Total BoQ16 AMC and O&M Price for 5 years |
| 16 | Total BoQ17 Civil Price |
| 17 | Construction of 2x5MVA, 33/11kV Substation Suwakholi, Dehradun and associated 33kV (14km) Line including civil works, AMC and O&M for 5 yearsTotal BoQ18 Supply price |
| 18 | Total BoQ19 Erection price |
| 19 | Total BoQ20 AMC and O&M Price for 5 years |
| 20 | Total BoQ21 Civil Price |
| 21 | Construction of 2x12.5MVA, 33/11kV Substation Danda Lakhond, Dehradun and associated 33kV (2x0.135km) LILO Line including civil works, AMC and O&M for 5 yearsTotal BoQ22 Supply price |
| 22 | Total BoQ23 Erection price |
| 23 | Total BoQ24 AMC and O&M Price for 5 years |
| 24 | Total BoQ25 Civil Price |
| 25 | Construction of 2x12.5MVA, 33/11kV Substation Guniyal Gaon, Dehradun and associated 33kV (2x1.7km) & (2x0.1km) LILO Line including civil works, AMC and O&M for 5 yearsTotal BoQ26 Supply price |
| 26 | Total BoQ27 Erection price |
| 27 | Total BoQ28 AMC and O&M Price for 5 years |
| 28 | Total BoQ29 Civil Price |
| 29 | Construction of 2x12.5MVA, 33/11kV Substation Changa Majri, Roorkee and associated 33kV (2x0.5km) LILO Line including civil works, AMC and O&M for 5 yearsTotal BoQ30 Supply price |
| 30 | Total BoQ31 Erection price |
| 31 | Total BoQ32 AMC and O&M Price for 5 years |
| 32 | Total BoQ33 Civil Price |
| 33 | Construction of 2x5MVA, 33/11kV Substation Bharoni, Sitarganj, Distt. US Nagar and associated 33kV line including civil works, AMC and O&M for 5 yearsTotal BoQ34 Supply price |
| 34 | Total BoQ35 Erection price |
| 35 | Total BoQ36 AMC and O&M Price for 5 years |
| 36 | Total BoQ37 Civil Price |
| 37 | Construction of 2x12.5MVA, 33/11kV Substation Jafarpur, US Nagar and associated 33kV Line including civil works, AMC and O&M for 5 yearsTotal BoQ38 Supply price |
| 38 | Total BoQ39 Erection price |
| 39 | Total BoQ40 AMC and O&M Price for 5 years |
| 40 | Total BoQ41 Civil Price |
| 41 | Construction of 2x5 MVA 33/11kV Substation at Munar Block-Kapkot, Distt. Bageshwar and associated 33kV line including civil works, AMC and O&M for 5 yearsTotal BoQ42 Supply price |
| 42 | Total BoQ43 Erection price |
| 43 | Total BoQ 44 AMC and O&M Price for 5 years |
| 44 | Total BoQ45 Civil Price |
| 45 | Construction of 2x5 MVA 33/11kV Substation at Kaniya, Ramnagar, Distt. Nainital and associated 33kV Line including civil works, AMC and O&M for 5 yearsTotal BoQ46 Supply price |
| 46 | Total BoQ47 Erection price |
| 47 | Total BoQ48 AMC and O&M Price for 5 years |
| 48 | Total BoQ49 Civil Price |
| 49 | Supply for 33/11kV SubstationT/F 33/11 kV 12.5MVA |
| 50 | 8 m. LONG STP 410 SP-10 (BPHD GAL.) |
| 51 | 11 MTR. LONGSTP 410 SP-55(BPHD GAL.) |
| 52 | MS ROUND 32 mm |
| 53 | 11 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 54 | 33 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 55 | DISC FIT. B&S TYPE FOR PANTHER 90 KN |
| 56 | DISC FIT. B&S TYPE WEASEL/RABBIT 45 KN |
| 57 | 9 KV 10 KA Polymeric Lightning Arrestor |
| 58 | EARTHING ROD MS 20X2500mm |
| 59 | GI WIRE 5mm/6 SWG |
| 60 | STAY SET GI 16X1800mm |
| 61 | STAY WIRE GI 7/3.15mm 7/10SWG |
| 62 | ACSR DOG |
| 63 | ACSR PANTHER |
| 64 | CABLE AL 3X300 SQ. mm XLPE 11 kV |
| 65 | CABLE AL 3X400 SQ. mm XLPE 11 kV |
| 66 | CABLE AL 1X630 SQ. mm XLPE 11 kV |
| 67 | CABLE AL 3X70 SQ. mm XLPE 33kV |
| 68 | J/KIT FOR 3X300mm* 11kV XLPE CABLE(O/D) |
| 69 | J/KIT FOR 3X400mm° 11kV XLPE CABLE (O/D) |
| 70 | CONTROL CABLE 10X2.5 SQ. mm. |
| 71 | CONTROL CABLE 2X2.5 SQ. mm. |
| 72 | CONTROL CABLE 4X2.5 SQ. mm. |
| 73 | CONTROL CABLE 6X2.5 SQ. mm. |
| 74 | LT PVC CABLE 2X6 SQ.mm (ARMORED) |
| 75 | LT XLPE CABLE 3.5.X 70 SQ. mm. |
| 76 | LT PVC CABLE 4X10 SQ.mm |
| 77 | 33 KV H.S. Cable J/K 3x70 sq. mm (O/D) |
| 78 | 110 V BATTERY SET(300 AH) |
| 79 | 110V BATTERY CHARGER(300 AH) |
| 80 | JUNCTION BOX FOR 33kV PT |
| 81 | 33kV PT of RATIO 33 kV/110V OUTDOOR |
| 82 | 33 kV LIGHTNING ARRESTER |
| 83 | PANTHER TO PANTHER CTYPE WEDGE CONNECTOR |
| 84 | 33 kV FUSE SET |
| 85 | 33/0.433 KV, 63 KVA Station Transformer |
| 86 | MS STRUCTURE (ANGLE ,CHANNEL ETC.) |
| 87 | GI ITEM (Rail,Joist,ChanneI,Angle) |
| 88 | Cable Holding clamp with N&B |
| 89 | Holding Clamp FPR GI Pipe 8/10\\"& MS Ch. |
| 90 | PG CLAMP ALU ALLOY PANTHER TO DOG |
| 91 | Stay Clamp for SP-55 With Nut & Bolt |
| 92 | 33KV ISOLATOR CONN.CLAMP FOR PANTHER,N&B |
| 93 | 33 KV ISOLATOR CLAMP FOR ACSR DOG |
| 94 | PERFORATED TRAY 400MM FOR CABLE TRENCH |
| 95 | PERFORATED TRAY 200MM FOR CABLE TRENCH |
| 96 | PERFORATED TRAY 100MM FOR CABLE TRENCH |
| 97 | FLEXIBLE COOPER CONNECTOR SOXSOMM |
| 98 | DANGER BOARD |
| 99 | GI Pipe 4\\"' Dia |
| 100 | 250 W hpsv/led lamp with contrl gear |
| 101 | Insulated Electrical Piller Taparia |
| 102 | 11 KV Fuse Set |
| 103 | KM-21 G.I. Pipe 6\\" dia 3 meter long |
| 104 | Conne.Suitable for Panther for LA |
| 105 | Connector of Power T/F HV Side |
| 106 | Connector of Power T/F LV Side |
| 107 | GI STRIP 65MMX6MM |
| 108 | “HT' WARNING TAPE |
| 109 | 11KV,630Amp off load Isolator |
| 110 | Thimble junction box for cable support |
| 111 | 33KV C&R PANEL I/C-D |
| 112 | 33KV C&R PANEL O/G-D |
| 113 | 33KV C&R PANEL BUS COUPLER-D |
| 114 | 11KV C&R PANEL I/C-D |
| 115 | 11KV C&R PANEL O/G-D |
| 116 | 11KV C&R PANEL BUS COUPLER-D |
| 117 | PP clamp with N&B (GI) |
| 118 | G.I.Strip 35x4mm |
| 119 | 11 KV HS cable END T/K 1x630 mm* O/D |
| 120 | Cable Jointing Kit 1x630 Outdoor |
| 121 | 33 KV XLPE Cable AL 1x630 sq. mm -D |
| 122 | Iron Clad 30 Amp Switch |
| 123 | Connector Suit for CT/PT for Panther/Dog |
| 124 | 33 KV Isolator Vertical Type |
| 125 | 11kv 3P(400A)3pin vert. mount GO AB TPMO |
| 126 | Indoor type auto power factor controller |
| 127 | 12.65kV, 4800kVAr, Capacitor bank |
| 128 | 12KV C&R Panel with SCADA(Capacitor) |
| 129 | 36KV 1250A Gang ope PMA VCB(I/C) |
| 130 | 36KV 1250A Gang ope PMA VCB(O/G) |
| 131 | 12KV 1250A Gang ope PMA VCB(I/C) |
| 132 | 12KV 1250A Gang ope PMA VCB(O/G) |
| 133 | 12KV 1250A Gang ope PMA VCB(Capacitor) |
| 134 | 12KV 1250A Gang ope PMA VCB(B/C) |
| 135 | 36KV 1250A Gang ope PMA VCB(B/C) |
| 136 | 33kv Bus isolator manual&motor,SCADA COM |
| 137 | 33kv line isolator manual&motor,SCADA co |
| 138 | 11kv isolator manual&motor,SCADA comp. |
| 139 | Wire Mesh Fencing |
| 140 | 110V DC DISTRIBUTION BOARD-D |
| 141 | Name Plate of Equip. TG,LI,BI,CT,CB ect. |
| 142 | GI STRIP 50X6 MM |
| 143 | SUNDRISE ITEM LUG GLADE ETC |
| 144 | Alluminium Lug |
| 145 | Stone Pad 300x300x75mm |
| 146 | Connector Suitable. Panther for VCB |
| 147 | Dustbin 20 Litre Capacity (Colour Green) |
| 148 | RUBBER MAT(INSULATED )1MX1MX3MM |
| 149 | Fire Extingushier |
| 150 | Torch 3 Cell |
| 151 | 33 KV Hand Gloves |
| 152 | Earth Chain |
| 153 | First aid box |
| 154 | SHOCK TREATMENT CHART |
| 155 | SHUT DOWN/ BREAK DOWN BOARD |
| 156 | WALL CLOCK |
| 157 | D-SPANNER SET |
| 158 | PIPE WRENCH 12\\" |
| 159 | 2.5 KV MEGGAR DIGITAL |
| 160 | EARTH MEGGAR DIGITAL |
| 161 | INSTRUCTION BOARD |
| 162 | MAXIMUM & MINIMUM DISPLAY BOARD |
| 163 | SUB STATION NAMED BOARD |
| 164 | Portable Foam Type Fire Extinguisher SLT |
| 165 | Single Line Diagram Board |
| 166 | Door Mat |
| 167 | Name plate of feeder |
| 168 | Name plate of station \iI |
| 169 | 11KV Danger Board with Clamp |
| 170 | 33 KV Danger Board with Clamp |
| 171 | Steel Almirah |
| 172 | Office Table size (4x2.5) |
| 173 | Fire Bucket Stand with Buckets |
| 174 | Steel Cabinet |
| 175 | Steel office Table |
| 176 | Steel office chair Godrej |
| 177 | Meggar 5 KV Digital |
| 178 | Fire Bucket stand of MS angle |
| 179 | Supply for 33kV Line8.5 MRT. LONG STP 410 SP-23(BPHDGAL.) |
| 180 | 11 MTR. LONGSTP 410 SP-55(BPHDGAL.) |
| 181 | STP 13.0 M-IS 410 SP-72 (BPHD GAL.) |
| 182 | MS ANGLE 65X65X6 mm |
| 183 | MS CHANNEL 100X50 mm |
| 184 | MS CHANNEL 125X65 mm |
| 185 | Holding Clamp for ST Pole SP-23 with N&B |
| 186 | 11 kV POLYMER DISC INSULATOR(B&S) TYPE |
| 187 | 33 kV POLYMER DISC INSULATOR(B&S) TYPE |
| 188 | 11 kV POLYMER PIN INSULATOR WITH PIN |
| 189 | 33kV 10KN POLYMER PIN INSULATORWITH PIN |
| 190 | DISC FIT. B&S TYPE DOG/RACOON 70KN |
| 191 | DISC FIT. B&S TYPE WEASEL/RABBIT45 KN |
| 192 | LT Shackle Insulator |
| 193 | X ARM ANGLE 65X65X6 mm V TYPE 11kV |
| 194 | X ARM CHANNEL 100X50 mm V TYPE 33kV |
| 195 | Earth wire GI 7/1.6 mm 16 SWG |
| 196 | EARTHING ROD MS 20X2500mm |
| 197 | GI WIRE 4mm/8mm SWG |
| 198 | GI WIRE 5mm/6 SWG |
| 199 | STAY SET GI 20X1800mm |
| 200 | STAY WIRE GI 7/4.0 mm 7/8 SWG |
| 201 | ACSR RABBIT |
| 202 | ACSR PANTHER |
| 203 | LT XLPE AB CABLE 3X120+1X95+1 X16 |
| 204 | Bolt & Nut 150x12 mm |
| 205 | Bolt & Nuts 50x16 mm |
| 206 | Eye Bolt 190x16 mm With Nut & Bolt |
| 207 | Bracing Clamp SP-72 |
| 208 | LT Shackle Insulator Clamp |
| 209 | Holding Clamp FPR GI Pipe 8/10'' & MS Channel |
| 210 | E- CLAMP |
| 211 | Universal I Hook |
| 212 | F Clamp |
| 213 | EARTH WIRE CLAMP FOR SP-55 WITHN/B |
| 214 | PP & CLAMP WITH N&B ST POLE SP-55 |
| 215 | STAY CLAMP FOR SP-23 WITH NUT &BOLT |
| 216 | EARTH WIRE CLAMP FOR SP-23 WITHN/B |
| 217 | PP & CLAMP WITH N&B ST POLE SP-72 |
| 218 | STAY CLAMP FOR SP-72 WITH N/B |
| 219 | PG Clamp For Dog Conductor |
| 220 | SUSPENSION CLAMP |
| 221 | PP & CLAMP WITH N&B ST POLE SP-23 |
| 222 | NUMBER PLATE WITH CLAMP |
| 223 | Danger Board With Clamp N&B |
| 224 | BRACING CLAMP BOTTOM FOR SP-23WITH N/B |
| 225 | Bolt & Nuts off Size |
| 226 | Cable Holding Clamp with N&B of Size |
| 227 | PG Clamp For panther |
| 228 | PG Clamp |
| 229 | KM-21 G.I. Pipe 6\\" dia 3 meter long |
| 230 | STAY CLAMP FOR SP-55 WITH NUT & BOLT |
| 231 | Earth Wire Clamp |
| 232 | 33 KV Mid Span Jointing Kit |
| 233 | 33KV Biometric crimping Lug |
| 234 | 33 KV IPC with Al. Ball for Earthing |
| 235 | 33 KV Tension clamp with Bail & IPC |
| 236 | 33 KV IPC for covered to covered conduct |
| 237 | 33 KV Cable Ties for Insulator |
| 238 | Concrete route marker for HT cable |
| 239 | PP & CLAMP WITH NUT & BOLT FORGUARDING |
| 240 | 33 KV straight Through 1x630 sqmm |
| 241 | Disc fitting for Panther 120 KN |
| 242 | PP CLAMP FOR SPECIAL TYPEBRACKET |
| 243 | 33KV AAAC COVERED COND. AL-59,241SQ.MM. |
| 244 | Cable Jointing Kit 1x630 Outdoor |
| 245 | 33 KV XLPE Cable AL 1x630 sqmm - D |
| 246 | ALUMINIUM BINDING WIRE |
| 247 | BARBED WIRE |
| 248 | Stone Pad 300x300x75mm |
| 249 | Dead End Clamp With Nut & Bolt |
| 250 | Erection Work for Substation:7.2.1 (DSR CODE 2014) |
| 251 | NSI_EARTH FILLING |
| 252 | CEMENT CONCRETING WORK IN RATIO 1:4:8 |
| 253 | CEMENT CONCRETING WORK IN RATIO 1:2:4 |
| 254 | BRICK WORK IN 1:4 RATIO |
| 255 | CEMENT PLASTER WORK |
| 256 | FENCING OF YARD |
| 257 | RCC 1:1.5:3 |
| 258 | MAKING CABLE TRENCH |
| 259 | BRICK WORK 1:6 SUB STRUCTURE |
| 260 | BRICK WORK 1:6 SUPER STRUCTURE |
| 261 | CC WORK 1:1.5:2 |
| 262 | SUPPLY&ERRECT GRAVEL PITCHING 1/2\\"- 3/4\\" |
| 263 | ELECTRICAL INSPECTION FEE |
| 264 | SPECIAL EARTHING |
| 265 | FABRICATION OF STEEL |
| 266 | FIXING OF GI PIPE |
| 267 | ERECTION OF SINGLE SP-10 POLE |
| 268 | ERECTION OF SP-55 DOUBLE POLE |
| 269 | PAINTING OF SP-10 POLE |
| 270 | PAINTING OF SP-55 POLE |
| 271 | LAYING OF LT PVC CABLES(» 150 SQMM) |
| 272 | LAYING OF U/G 11 KV CABLE IN TRENCH |
| 273 | LAYING OF U/G 33 KV CABLE IN TRENCH |
| 274 | FIXING OF LIGHTNING ARRESTOR |
| 275 | FIXING OF 11 KV XLPE JOINTING KIT |
| 276 | FIXING OF 33 KV XLPE JOINTING KIT |
| 277 | CARTAGE OF PETTY MATERIAL,0-20 KM |
| 278 | CARTAGE 11 KV PANELS, 0-20 KM |
| 279 | CARTAGE OF PANELS, 0-20 KM |
| 280 | CARTAGE 5/8 MVA POWER T/ F(0-20KM) |
| 281 | MANUAL SHIFTING OF CONTROL PANEL |
| 282 | ERECTION OF POWER T/F(12.5/10 MVA) |
| 283 | ESCAVATION OF EARTH FOR STRUCT. ERECTION |
| 284 | GROUTING OF STRUCTURE IN CC 1:3:6 |
| 285 | FIXING OF 33 KV ISOLATOR VERTICAL TYPE |
| 286 | LAYING OF CONTROL CABLE |
| 287 | LAYING OF EARTH MAT |
| 288 | EARTHING OF STRUCTURE USING GI STRIP |
| 289 | COMM.OF 33/11KV VCB PANEL |
| 290 | COMPLETE TESTING WIRING |
| 291 | ERECTION & LAYING OF LT XLPE CABLE 2X6 |
| 292 | INST. & FIXING OF CHEMICAL EARTHING |
| 293 | INSTALLATION OF LINE/ BUS ISOLATOR |
| 294 | INSTALLATION OF DCDB INCLUDING TESTING |
| 295 | INSTALLATION OF ACDB INCLUDING TESTING |
| 296 | ERECTION OF 33/0.433KV S/S TRANSFORMER |
| 297 | ERECTION OF FLEXIBLE CU. CONN.500X50 MM |
| 298 | ERECTION OF STAY POST |
| 299 | ERRECTION OF 33KV PT |
| 300 | ERREC. 12.65kV 4800kVAr, CAPACITOR BANK |
| 301 | ERREC. 11KV, 630 AMP, OFF LOAD ISOLATOR |
| 302 | ERECTION OF 110V BATTERY SET(300AH) |
| 303 | ERECTION OF 110V BATTERY CHARGER(300AH) |
| 304 | FIXING OF 11 KV FUSE SET |
| 305 | FIXING OF 33 KV FUSE SET |
| 306 | LAYING OF 4X10SQ MM LT PVC CABLE |
| 307 | ERECTION OF EARTHING ELECTRODE&STRIP50X6 |
| 308 | FIXING OF SODIUM/LED LIGHT AT YARD |
| 309 | INSTALLATION OF FIRE EXTINGUISHERS |
| 310 | ERECTION OF NAME PLATES |
| 311 | ERECTION OF T&P ITEMS |
| 312 | ERECTION OF MISC. GI STRUCTURES |
| 313 | SHIFTING OF T/F B WORK |
| 314 | Erection Work for 33kV Line:7.2.1 (DSR CODE 2014) |
| 315 | CEMENT CONCRETING WORK IN RATIO1:4:8 |
| 316 | RCC 1:1:5:3 |
| 317 | ELECTRICAL INSPECTION FEE |
| 318 | ERECTION OF EARTHING ROAD |
| 319 | FABRICATION OF STEEL |
| 320 | FIXING OF GI PIPE |
| 321 | FIXING OF RCC CABLE ROUTE MARKER |
| 322 | ERECTION OF 33 KV STAY SET |
| 323 | ERECTION OF SINGLE SP-55 POLE |
| 324 | ERECTION OF SINGLE SP-72 POLE |
| 325 | ERECTION OF SP-55 DOUBLE POLE |
| 326 | ERECTION OF SP-72 DOUBLE POLE |
| 327 | ERECTION OF SP-72(11KV/33 KV) FOUR POLE |
| 328 | ERECTION OF BRACKET IN 11 KV LINE |
| 329 | LAYING OF PANTHER CONDUCTOR IN HT LINE |
| 330 | GUARDING OF 33 KV LINE |
| 331 | FIXING OF 33 KV XLPE JOINTING KIT |
| 332 | CARTAGE SP-21/23 POLE, 0-20 KM |
| 333 | CARTAGE SP-55 POLE, 21-50 KM |
| 334 | CARTAGE SP-72 POLE, 21-50 KM |
| 335 | HEADLOAD CARTAGE SP-21/23POLE(0-1 KM) |
| 336 | HEADLOAD CARTAGE SP-55 POLE(0-1 KM) |
| 337 | HEADLOAD CARTAGE SP-72 POLE(0-1 KM) |
| 338 | HEADLOAD CARTAGE OFMATERIAL(0-1 KM) |
| 339 | ESCAVATION OF EARTH FOR STRUCT.ERECTION |
| 340 | LAYING OF LTXLPE ABC 3X120+1X95+1X16 SQ. |
| 341 | ROAD CUTTING AND REPAIRING |
| 342 | CARTAGE OF PETTY MATERIAL,21-50KM |
| 343 | Supply & LAYING OF HDPE PIPE |
| 344 | FIXING OF 33 KV TENSION CLAMP WITHIPC |
| 345 | FIXING OF 33 KV IPC FOR CC TO CCCOND. |
| 346 | FIXING OF 33 KV MID SPAN JOINTINGKIT |
| 347 | FIXING OF 33 KV BIMETALIC LUG |
| 348 | FIXING OF IPC WITH AL. BAIL FOREARTHING |
| 349 | LAYING OF 33KV CABLE FOR POLERISING O/H |
| 350 | FIXING OF 33KV CABLE TIES |
| 351 | ERECTION OF TRI POLE FOR ST POLESP-72 |
| 352 | LAYING SPREADING,STRINGING AAAC CONDUCT. |
| 353 | COMPLETE TESTING WIRING |
| 354 | MAKING LOOP OF 33 KV XLPE CABLE |
| 355 | MANUAL DIGGING OF CABLE TRENCHUPTO 1 MT |
| 356 | SUPPLY & LAYING OF HDPE PIPE INOPEN CUT |
| 357 | PAINTING OF SINGLE POLE (SP-55) |
| 358 | PAINTING OF SINGLE POLE (SP-72) |
| 359 | PAINTING OF DOUBLE POLE (SP-55) |
| 360 | PAINTING OF DOUBLE POLE (SP-72) |
| 361 | PAINTING OF TRI POLE (SP-72) |
| 362 | PAINTING OF FOUR POLE (SP-72) |
| 363 | Steel (Reinforcement) |
| 364 | FIXING OF G.I PIPE 3 MTR LONG |
| 365 | SHIFTING REALIGNMENT 11KV SP,DP/ LT LINE |
| 366 | DELTA EARTHING WITH MS ROUNDELECTROD/GI |
| 367 | LOOPING AND CHOPPING OF TREEBRANCHES |
| 368 | Annual Maintenance Charges (AMC) and O&M of Project for 5 years on per year basis. |
| 369 | Construction of Control RoomEarth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 370 | Filling available excavated earth (excluding rock) in trenches, plinth sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5m |
| 371 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also includingramming and watering of the earth in layers not exceeding 20cm in trenches, plinth, sides of foundation etc. complete |
| 372 | Supplying and filling in plinth with Jamuna sand under floors including, watering, ramming consolidating and dressing complete. |
| 373 | Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1:2 (1 cement : 2 Coarse sand) to match the existing floor : With Chlorpyriphos/Lindane E.C. 20% with 1% concentration. |
| 374 | Providing and laying in position cement concrete in ratio 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 375 | Providing and laying in position cement concrete in ratio 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 40 mm nominal size) of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 376 | Providing and laying in position specified grade of reinforced cement concrete in ratio 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level |
| 377 | Reinforced cement concrete work in 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level excluding cost of centering, shuttering, finishing and reinforcement. |
| 378 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size). |
| 379 | Centering and shuttering including strutting, propping etc. and removal of form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 380 | Centering and shuttering including strutting, propping etc. and removal of form for Suspended floors, roofs, landings, balconies and access platform. |
| 381 | Centering and shuttering including strutting, propping etc. and removal of form for Almirah Shelves Bottom and Edges |
| 382 | Centering and shuttering including strutting, propping etc. and removal of form for Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 383 | Centering and shuttering including strutting, propping etc. and removal of form for Columns, Pillars, Piers, Abutments, Posts and Struts. |
| 384 | Centering and shuttering including strutting, propping etc. and removal of form for : Edges of slabs and breaks in floors and walls. Under 20 cm wide |
| 385 | Centering and shuttering including strutting, propping etc. and removal of form for Weather shade, Chajjas, corbels etc., including edges. |
| 386 | Providing, hoisting and fixing up to floor five level precast reinforced cement concrete in small lintels not exceeding 1.5m clear span up to floor five level including the cost of required centering, shuttering and finishing smooth with 6 mm thick cement plaster 1:3 (1 cement : 3 fine sand) on exposed surfaces but excluding the cost of reinforcement with 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size). |
| 387 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.Thermo-Mechanically Treated bars. |
| 388 | Smooth finishing of the exposed surface of R.C.C. work with 6 mm thick cement mortar 1:3 (1 Cement : 3 fine sand). |
| 389 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 390 | Brick work with F.P.S. bricks of class designation 75 in foundation and plinth in Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 391 | Brick work with F.P.S. bricks of class designation 75 in superstructure above plinth level up to floor V level in all shapes and sizes in Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 392 | Half brick masonry with F.P.S. brick of class designation 75 in foundations and plinth in. cement mortar 1:4 (1 cement : 4 coarse sand) |
| 393 | Half brick masonry with F.P.S. bricks of class designation 75 in superstructure above plinth level up to floor V level. |
| 394 | Providing and fixing 18mm thick gang saw cut mirror polished premoulded and prepolished) machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edge to give high gloss finish etc. complete at all levels. Granite of any colour and shade. Area of slab upto 0.50 sqm |
| 395 | Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge.Granite work |
| 396 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS:15622(thickness to be specified by the manufacturer), of approved make,in all colours, shades except burgundy, bottle green, black of any size asapproved by Engineer-in-Charge, in skirting, risers of steps and dados,over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) andjointing with grey cement slurry @ 3.3kg per sqm, including pointingin white cement mixed with pigment of matching shade complete. |
| 397 | Providing and fixing fly proof galvanized M.S. wire gauge to windows and clerestory windows using wire gauge with average width of aperture 1.4mm in both directions with wire of dia 0.63 mm all complete.With 12 mm mild steel U beading. |
| 398 | Providing and fixing ISI marked aluminium butt hinges anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete: 100x63x4 mm |
| 399 | Providing and fixing aluminium sliding door bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc. complete : 250x16 mm |
| 400 | Providing and fixing aluminium tower bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade with necessary screws etc. complete : 150x10 mm |
| 401 | Providing and fixing aluminium handles ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete :100 mm |
| 402 | Providing and fixing aluminium hanging floor door stopper ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade with necessary screws etc. complete. Single rubber stopper |
| 403 | Providing and fixing aluminium casement stays ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade with necessary screws etc. complete. |
| 404 | Strutural steel work riveted bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete: |
| 405 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp of internal dia 140mm, 73mm height, top lid of 1.5mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3mm dia. round headed screws, one lock at the corners. Clamp shall be made of 12mm dia M.S. bar bent to shape as per standard drawing. |
| 406 | Steel work welded in built up sections/ framed work including cutting,hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. |
| 407 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement including cement slurry, but excluding the cost of nosing of steps etc. complete.40mm thick with 20mm nominal size stone aggregate. |
| 408 | Providing and fixing glass strips in joints of terrazo/ cement concrete floors.40 mm wide and 4 mm thick. |
| 409 | Providing and laying Ceramic glazed floor tiles 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick Cement Mortar 1:4 (1 Cement : 4 Coarse sand) including pointing the joints with white cement and matching pigment etc., complete. |
| 410 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600x600 mm |
| 411 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes.75 mm diameter |
| 412 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes.110 mm diameter |
| 413 | 12 mm cement plaster of mix 1:6 (1 cement: 6 coarse sand) |
| 414 | 15mm cement plaster on rough side of single or half brick wall of mix: 1:6 (1cement :6 coarse sand) |
| 415 | 12 mm Cement plaster 1:3 (1 cement: 3 coarse sand) finished with a floating coat of neat cement. |
| 416 | 6mm Cement plaster finished with a floating coat of neat cement 1:3. |
| 417 | Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete |
| 418 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade.New work (two or more coats) over and including priming coat with cement primer. |
| 419 | Finishing walls with textured exterior paint of required shade for new work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including base coat of water proofing cement paint applied @ 2.20kg/10 sqm. |
| 420 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work |
| 421 | Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete including cutting and making good the walls and floors wherever required :White Vitreous china Orissa pattern W.C. pan of size 580x440mm with integral type foot rests. |
| 422 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required :One urinal basin with 5 litre white P.V.C. automatic flushing cistern |
| 423 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps,32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require :White Vitreous China Flat back wash basin size 550x400 mm with single 15 mm C.P. brass pillar tap. |
| 424 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete.Flexible pipe-----32 mm dia |
| 425 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 426 | Providing and fixing PTMT towel ring trapezoidal shape 215 mm long, 200 mm wide with minimum distances of 37 mm from wall face with concealed fittings arrangement of approved quality and colour, weighing not less than 88 gms. |
| 427 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply and all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall..15 mm nominal dia Pipes |
| 428 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply and all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work -Exposed on wall 20 mm nominal dia Pipes |
| 429 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :25 mm nominal bore |
| 430 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete :15 mm nominal bore |
| 431 | Providing and fixing uplasticised PVC connection pipe with brass unions : 30 cm length.15 mm nominal bore |
| 432 | Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design :With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 |
| 433 | Providing and fixing G.I. Union in G.I. pipe including cutting and threading the pipe and making long screws etc. complete (New work) :15 mm nominal bore |
| 434 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 435 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931: 15 mm nominal bore |
| 436 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931: 15 mm nominal bore |
| 437 | Providing and fixing PTMT grating of approved quality and colour. Circular type. 100 mm nominal dia |
| 438 | Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighing not less than 106 gms. |
| 439 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC/neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing and paneling to be paid for separately) : For.... fixed portion Powder coated aluminium (minimum thickness of powdercoating 50 micron) |
| 440 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC/neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing and paneling to be paid for separately) : For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of PVC / neoprene gasket required (Fittings shall be paid for separately). Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 441 | Providing and fixing 12mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge. Pre-laminated particle board with decorative lamination on both sides. |
| 442 | Providing and fixing 100mm brass locks (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete. |
| 443 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with PVC/ neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-incharge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 4 mm thickness |
| 444 | Grading roof for water proofing treatment with Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 445 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with moduler type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single core cable etc as required. Group B |
| 446 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required :2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 447 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 A switch |
| 448 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 A socket outlet |
| 449 | Supplying and fixing suitable size GI box with modular plate and cover in front on ...... providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection, painting etc. as required. |
| 450 | Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. |
| 451 | Supply and fixing following rating, 63 amps double pole, 240 volts, isolator in the existing MCB DB complete with connection, testing and commissioning etc. as required. |
| 452 | Supply and fixing 5 amps to 32 amps rating, 240 volts, 'C' serise, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole and neutral |
| 453 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar,interconnections, powder painted including earthing etc. as required. (But withoutMCB/RCCB/Isolator) 8 way , Double door |
| 454 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan withBrush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2nos. canopies, shackle kit, safetyrope, copper winding, PowerFactor not less than 0.9, ServiceValue (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulationresistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 455 | Supplying of Exhaust Fan 250 mm Sweep of Orient or equivalent make as approved by E.I. |
| 456 | Supplying of 20 watt LED Tubelight Philps or equivalent make as approved by E.I. |
| 457 | Engaging/S of suitable beldar for different type of works |
| 458 | Engaging suitable electrician with kit for petty work. (Based on DSR Code 1001) |
| 459 | Land Development WorksEarth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 460 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 and for all lift. |
| 461 | Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 moutside the periphery of the area cleared. |
| 462 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level: 1 : 1.5:3 ( 1 Cement: 1.5 coarse sand (zone-Ill) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 463 | 1 :2:4 (1 cement : 2 coarse sand (zone-Ill) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 464 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) |
| 465 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :1 :1.5:3 (1 cement : 1.5 coarse sand (zone-Ill) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 466 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size) |
| 467 | Centering and shuttering including strutting, propping etc. and removal of form for Foundations, footings, bases of columns, etc. for mass concrete |
| 468 | Centering and shuttering including strutting, propping etc. and removal of form for Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 469 | Centering and shuttering including strutting, propping etc. and removal of form for Columns, Pillars, Piers, Abutments, Posts and Struts. |
| 470 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.Thermo-Mechanically Treated bars. |
| 471 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 472 | Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with : Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 473 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 474 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.. |
| 475 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes.110 mm diameter |
| 476 | 12 mm cement plaster of mix 1:6 (1 cement: 6 coarse sand) |
| 477 | 15mm cement plaster on rough side of single or half brick wall of mix: 1:6 (1cement :6 coarse sand) |
| 478 | Pointing on stone work with cement mortar 1:3 (1 cement : 3 fine sand) : Flush/ Ruled pointing |
| 479 | Finishing walls with textured exterior paint of required shade for new work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including base coat of water proofing cement paint applied @ 2.20kg/10 sqm. |
| 480 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade. Two or more coats on new work. |
| 481 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 482 | Fencing with angle iron post placed at required distance embedded in cement concrete blocks, every 15th post, last but one end post and cornerpost shall be strutted on both sides and end post on one side only and provided with horizontal lines and two diagonals interwoven with horizontalwires, of barbed wire weighing 9.38 kg per 100 m (minimum), between the two posts fitted and fixed with G.I. staples, turn buckles etc. complete. (Costof posts, struts, earth work and concrete work to be paid for separately). Payment to be made per metre cost of total length of barbed wire used. With G.I. barbed wire |
| 483 | Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including makinggood the undulations etc. and re-rolling the sub grade and disposal of surplus earthwith lead upto 50 metres. |
| 484 | Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge). |
| 485 | Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge.80 mm thick C.C. paver block of M-30 grade with approved color design and pattern. |
| 486 | Supply for 33/11kV Substation8 m. LONG STP 410 SP-10 (BPHD GAL.) |
| 487 | 11 MTR. LONGSTP 410 SP-55(BPHD GAL.) |
| 488 | MS ROUND 32 mm |
| 489 | 11 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 490 | 33 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 491 | DISC FIT. B&S TYPE FOR PANTHER 90 KN |
| 492 | DISC FIT. B&S TYPE WEASEL/RABBIT 45 KN |
| 493 | 9 KV 10 KA Polymeric Lightning Arrestor |
| 494 | EARTHING ROD MS 20X2500mm |
| 495 | GI WIRE 5mm/6 SWG |
| 496 | STAY SET GI 16X1800mm |
| 497 | STAY WIRE GI 7/3.15mm 7/10SWG |
| 498 | ACSR DOG |
| 499 | ACSR PANTHER |
| 500 | CABLE AL 3X300 SQ. mm XLPE 11 kV |
| 501 | CABLE AL 3X400 SQ. mm XLPE 11 kV |
| 502 | CABLE AL 1X630 SQ. mm XLPE 11 kV |
| 503 | CABLE AL 3X70 SQ. mm XLPE 33kV |
| 504 | J/KIT FOR 3X300mm* 11kV XLPE CABLE(O/D) |
| 505 | J/KIT FOR 3X400mm° 11kV XLPE CABLE (O/D) |
| 506 | CONTROL CABLE 10X2.5 SQ. mm. |
| 507 | CONTROL CABLE 2X2.5 SQ. mm. |
| 508 | CONTROL CABLE 4X2.5 SQ. mm. |
| 509 | CONTROL CABLE 6X2.5 SQ. mm. |
| 510 | LT PVC CABLE 2X6 SQ.mm (ARMORED) |
| 511 | LT XLPE CABLE 3.5.X 70 SQ. mm. |
| 512 | LT PVC CABLE 4X10 SQ.mm |
| 513 | 33 KV H.S. Cable J/K 3x70 sq. mm (O/D) |
| 514 | 110 V BATTERY SET(300 AH) |
| 515 | 110V BATTERY CHARGER(300 AH) |
| 516 | JUNCTION BOX FOR 33kV PT |
| 517 | 33kV PT of RATIO 33 kV/110V OUTDOOR |
| 518 | 33 kV LIGHTNING ARRESTER |
| 519 | PANTHER TO PANTHER CTYPE WEDGE CONNECTOR |
| 520 | 33 kV FUSE SET |
| 521 | 33/0.433 KV, 63 KVA Station Transformer |
| 522 | MS STRUCTURE (ANGLE ,CHANNEL ETC.) |
| 523 | GI ITEM (Rail,Joist,ChanneI,Angle) |
| 524 | Cable Holding clamp with N&B |
| 525 | Holding Clamp FPR GI Pipe 8/10\\"& MS Ch. |
| 526 | PG CLAMP ALU ALLOY PANTHER TO DOG |
| 527 | Stay Clamp for SP-55 With Nut & Bolt |
| 528 | 33KV ISOLATOR CONN.CLAMP FOR PANTHER,N&B |
| 529 | 33 KV ISOLATOR CLAMP FOR ACSR DOG |
| 530 | PERFORATED TRAY 400MM FOR CABLE TRENCH |
| 531 | PERFORATED TRAY 200MM FOR CABLE TRENCH |
| 532 | PERFORATED TRAY 100MM FOR CABLE TRENCH |
| 533 | FLEXIBLE COOPER CONNECTOR SOXSOMM |
| 534 | DANGER BOARD |
| 535 | GI Pipe 4\\"' Dia |
| 536 | 250 W hpsv/led lamp with contrl gear |
| 537 | Insulated Electrical Piller Taparia |
| 538 | 11 KV Fuse Set |
| 539 | KM-21 G.I. Pipe 6\\" dia 3 meter long |
| 540 | Conne.Suitable for Panther for LA |
| 541 | Connector of Power T/F HV Side |
| 542 | Connector of Power T/F LV Side |
| 543 | GI STRIP 65MMX6MM |
| 544 | “HT' WARNING TAPE |
| 545 | 11KV,630Amp off load Isolator |
| 546 | Thimble junction box for cable support |
| 547 | 33KV C&R PANEL I/C-D |
| 548 | 33KV C&R PANEL O/G-D |
| 549 | 33KV C&R PANEL BUS COUPLER-D |
| 550 | 11KV C&R PANEL I/C-D |
| 551 | 11KV C&R PANEL O/G-D |
| 552 | 11KV C&R PANEL BUS COUPLER-D |
| 553 | PP clamp with N&B (GI) |
| 554 | G.I.Strip 35x4mm |
| 555 | 11 KV HS cable END T/K 1x630 mm* O/D |
| 556 | Cable Jointing Kit 1x630 Outdoor |
| 557 | 33 KV XLPE Cable AL 1x630 sq. mm -D |
| 558 | Iron Clad 30 Amp Switch |
| 559 | Connector Suit for CT/PT for Panther/Dog |
| 560 | 33 KV Isolator Vertical Type |
| 561 | 11kv 3P(400A)3pin vert. mount GO AB TPMO |
| 562 | Indoor type auto power factor controller |
| 563 | 12.65kV, 3600kVAr, Capacitor bank |
| 564 | 12KV C&R Panel with SCADA(Capacitor) |
| 565 | 36KV 1250A Gang ope PMA VCB(I/C) |
| 566 | 36KV 1250A Gang ope PMA VCB(O/G) |
| 567 | 12KV 1250A Gang ope PMA VCB(I/C) |
| 568 | 12KV 1250A Gang ope PMA VCB(O/G) |
| 569 | 12KV 1250A Gang ope PMA VCB(Capacitor) |
| 570 | 12KV 1250A Gang ope PMA VCB(B/C) |
| 571 | 36KV 1250A Gang ope PMA VCB(B/C) |
| 572 | 33kv Bus isolator manual&motor,SCADA COM |
| 573 | 33kv line isolator manual&motor,SCADA co |
| 574 | 11kv isolator manual&motor,SCADA comp. |
| 575 | Wire Mesh Fencing |
| 576 | 110V DC DISTRIBUTION BOARD-D |
| 577 | Name Plate of Equip. TG,LI,BI,CT,CB ect. |
| 578 | GI STRIP 50X6 MM |
| 579 | SUNDRISE ITEM LUG GLADE ETC |
| 580 | Alluminium Lug |
| 581 | Stone Pad 300x300x75mm |
| 582 | Connector Suitable. Panther for VCB |
| 583 | Dustbin 20 Litre Capacity (Colour Green) |
| 584 | RUBBER MAT(INSULATED )1MX1MX3MM |
| 585 | Fire Extingushier |
| 586 | Torch 3 Cell |
| 587 | 33 KV Hand Gloves |
| 588 | Earth Chain |
| 589 | First aid box |
| 590 | SHOCK TREATMENT CHART |
| 591 | SHUT DOWN/ BREAK DOWN BOARD |
| 592 | WALL CLOCK |
| 593 | D-SPANNER SET |
| 594 | PIPE WRENCH 12\\" |
| 595 | 2.5 KV MEGGAR DIGITAL |
| 596 | EARTH MEGGAR DIGITAL |
| 597 | INSTRUCTION BOARD |
| 598 | MAXIMUM & MINIMUM DISPLAY BOARD |
| 599 | SUB STATION NAMED BOARD |
| 600 | Portable Foam Type Fire Extinguisher SLT |
| 601 | Single Line Diagram Board |
| 602 | Door Mat |
| 603 | Name plate of feeder |
| 604 | Name plate of station \iI |
| 605 | 11KV Danger Board with Clamp |
| 606 | 33 KV Danger Board with Clamp |
| 607 | Steel Almirah |
| 608 | Office Table size (4x2.5) |
| 609 | Fire Bucket Stand with Buckets |
| 610 | Steel Cabinet |
| 611 | Steel office Table |
| 612 | Steel office chair Godrej |
| 613 | Meggar 5 KV Digital |
| 614 | Fire Bucket stand of MS angle |
| 615 | Supply for 33kV Line8.5 MRT. LONG STP 410 SP-23(BPHDGAL.) |
| 616 | 11 MTR. LONGSTP 410 SP-55(BPHDGAL.) |
| 617 | STP 13.0 M-IS 410 SP-72 (BPHD GAL.) |
| 618 | MS ANGLE 65X65X6 mm |
| 619 | MS CHANNEL 100X50 mm |
| 620 | MS CHANNEL 125X65 mm |
| 621 | 11 kV POLYMER DISC INSULATOR(B&S) TYPE |
| 622 | 33 kV POLYMER DISC INSULATOR(B&S) TYPE |
| 623 | 11 kV POLYMER PIN INSULATOR WITH PIN |
| 624 | 33kV 10KN POLYMER PIN INSULATORWITH PIN |
| 625 | DISC FIT. B&S TYPE DOG/RACOON 70KN |
| 626 | DISC FIT. B&S TYPE WEASEL/RABBIT45 KN |
| 627 | LT Shackle Insulator |
| 628 | X ARM ANGLE 65X65X6 mm V TYPE 11kV |
| 629 | X ARM CHANNEL 100X50 mm V TYPE 33kV |
| 630 | Earth wire GI 7/1.6 mm 16 SWG |
| 631 | EARTHING ROD MS 20X2500mm |
| 632 | GI WIRE 4mm/8mm SWG |
| 633 | GI WIRE 5mm/6 SWG |
| 634 | STAY SET GI 20X1800mm |
| 635 | STAY WIRE GI 7/4.0 mm 7/8 SWG |
| 636 | ACSR RABBIT |
| 637 | ACSR PANTHER |
| 638 | Bolt & Nut 150x12 mm |
| 639 | Bolt & Nuts 50x16 mm |
| 640 | Eye Bolt 190x16 mm With Nut & Bolt |
| 641 | Bracing Clamp SP-72 |
| 642 | LT Shackle Insulator Clamp |
| 643 | Holding Clamp FPR GI Pipe 8/10'' & MS Channel |
| 644 | E- CLAMP |
| 645 | F Clamp |
| 646 | EARTH WIRE CLAMP FOR SP-55 WITHN/B |
| 647 | PP & CLAMP WITH N&B ST POLE SP-55 |
| 648 | EARTH WIRE CLAMP FOR SP-23 WITHN/B |
| 649 | PP & CLAMP WITH N&B ST POLE SP-72 |
| 650 | STAY CLAMP FOR SP-72 WITH N/B |
| 651 | PP & CLAMP WITH N&B ST POLE SP-23 |
| 652 | NUMBER PLATE WITH CLAMP |
| 653 | Danger Board With Clamp N&B |
| 654 | BRACING CLAMP BOTTOM FOR SP-23WITH N/B |
| 655 | Bolt & Nuts off Size |
| 656 | Cable Holding Clamp with N&B of Size |
| 657 | PG Clamp For panther |
| 658 | KM-21 G.I. Pipe 6\\" dia 3 meter long |
| 659 | STAY CLAMP FOR SP-55 WITH NUT & BOLT |
| 660 | Earth Wire Clamp |
| 661 | 33 KV Mid Span Jointing Kit |
| 662 | 33KV Biometric crimping Lug |
| 663 | 33 KV IPC with Al. Ball for Earthing |
| 664 | 33 KV Tension clamp with Bail & IPC |
| 665 | 33 KV IPC for covered to covered conduct |
| 666 | 33 KV Cable Ties for Insulator |
| 667 | Concrete route marker for HT cable |
| 668 | PP & CLAMP WITH NUT & BOLT FORGUARDING |
| 669 | 33 KV straight Through 1x630 sqmm |
| 670 | Disc fitting for Panther 120 KN |
| 671 | PP CLAMP FOR SPECIAL TYPEBRACKET |
| 672 | 33KV AAAC COVERED COND. AL-59,241SQ.MM. |
| 673 | Cable Jointing Kit 1x630 Outdoor |
| 674 | 33 KV XLPE Cable AL 1x630 sqmm - D |
| 675 | ALUMINIUM BINDING WIRE |
| 676 | BARBED WIRE |
| 677 | Stone Pad 300x300x75mm |
| 678 | Erection Work for Substation:7.2.1 (DSR CODE 2014) |
| 679 | NSI_EARTH FILLING |
| 680 | CEMENT CONCRETING WORK IN RATIO 1:4:8 |
| 681 | CEMENT CONCRETING WORK IN RATIO 1:2:4 |
| 682 | BRICK WORK IN 1:4 RATIO |
| 683 | CEMENT PLASTER WORK |
| 684 | FENCING OF YARD |
| 685 | RCC 1:1.5:3 |
| 686 | MAKING CABLE TRENCH |
| 687 | BRICK WORK 1:6 SUB STRUCTURE |
| 688 | BRICK WORK 1:6 SUPER STRUCTURE |
| 689 | CC WORK 1:1.5:2 |
| 690 | SUPPLY&ERRECT GRAVEL PITCHING 1/2\\"- 3/4\\" |
| 691 | ELECTRICAL INSPECTION FEE |
| 692 | SPECIAL EARTHING |
| 693 | FABRICATION OF STEEL |
| 694 | FIXING OF GI PIPE |
| 695 | ERECTION OF SINGLE SP-10 POLE |
| 696 | ERECTION OF SP-55 DOUBLE POLE |
| 697 | PAINTING OF SP-10 POLE |
| 698 | PAINTING OF SP-55 POLE |
| 699 | LAYING OF LT PVC CABLES(» 150 SQMM) |
| 700 | LAYING OF U/G 11 KV CABLE IN TRENCH |
| 701 | LAYING OF U/G 33 KV CABLE IN TRENCH |
| 702 | FIXING OF LIGHTNING ARRESTOR |
| 703 | FIXING OF 11 KV XLPE JOINTING KIT |
| 704 | FIXING OF 33 KV XLPE JOINTING KIT |
| 705 | CARTAGE OF PETTY MATERIAL,0-20 KM |
| 706 | CARTAGE 11 KV PANELS, 0-20 KM |
| 707 | CARTAGE OF PANELS, 0-20 KM |
| 708 | CARTAGE 5/8 MVA POWER T/ F(0-20KM) |
| 709 | MANUAL SHIFTING OF CONTROL PANEL |
| 710 | ERECTION OF POWER T/F(8/5 MVA) |
| 711 | ESCAVATION OF EARTH FOR STRUCT. ERECTION |
| 712 | GROUTING OF STRUCTURE IN CC 1:3:6 |
| 713 | FIXING OF 33 KV ISOLATOR VERTICAL TYPE |
| 714 | LAYING OF CONTROL CABLE |
| 715 | LAYING OF EARTH MAT |
| 716 | EARTHING OF STRUCTURE USING GI STRIP |
| 717 | COMM.OF 33/11KV VCB PANEL |
| 718 | COMPLETE TESTING WIRING |
| 719 | ERECTION & LAYING OF LT XLPE CABLE 2X6 |
| 720 | INST. & FIXING OF CHEMICAL EARTHING |
| 721 | INSTALLATION OF LINE/ BUS ISOLATOR |
| 722 | INSTALLATION OF DCDB INCLUDING TESTING |
| 723 | INSTALLATION OF ACDB INCLUDING TESTING |
| 724 | ERECTION OF 33/0.433KV S/S TRANSFORMER |
| 725 | ERECTION OF FLEXIBLE CU. CONN.500X50 MM |
| 726 | ERECTION OF STAY POST |
| 727 | ERRECTION OF 33KV PT |
| 728 | ERREC. 12.65kV 3600kVAr, CAPACITOR BANK |
| 729 | ERREC. 11KV, 630 AMP, OFF LOAD ISOLATOR |
| 730 | ERECTION OF 110V BATTERY SET(300AH) |
| 731 | ERECTION OF 110V BATTERY CHARGER(300AH) |
| 732 | FIXING OF 11 KV FUSE SET |
| 733 | FIXING OF 33 KV FUSE SET |
| 734 | LAYING OF 4X10SQ MM LT PVC CABLE |
| 735 | ERECTION OF EARTHING ELECTRODE&STRIP50X6 |
| 736 | FIXING OF SODIUM/LED LIGHT AT YARD |
| 737 | INSTALLATION OF FIRE EXTINGUISHERS |
| 738 | ERECTION OF NAME PLATES |
| 739 | ERECTION OF T&P ITEMS |
| 740 | ERECTION OF MISC. GI STRUCTURES |
| 741 | SHIFTING OF T/F B WORK |
| 742 | Erection Work for 33kV Line:7.2.1 (DSR CODE 2014) |
| 743 | CEMENT CONCRETING WORK IN RATIO1:4:8 |
| 744 | ELECTRICAL INSPECTION FEE |
| 745 | ERECTION OF EARTHING ROAD |
| 746 | FABRICATION OF STEEL |
| 747 | FIXING OF GI PIPE |
| 748 | FIXING OF RCC CABLE ROUTE MARKER |
| 749 | ERECTION OF 33 KV STAY SET |
| 750 | ERECTION OF SINGLE SP-55 POLE |
| 751 | ERECTION OF SINGLE SP-72 POLE |
| 752 | ERECTION OF SP-55 DOUBLE POLE |
| 753 | ERECTION OF SP-72 DOUBLE POLE |
| 754 | ERECTION OF SP-72(11KV/33 KV) FOUR POLE |
| 755 | ERECTION OF BRACKET IN 11 KV LINE |
| 756 | LAYING OF PANTHER CONDUCTOR IN HT LINE |
| 757 | GUARDING OF 33 KV LINE |
| 758 | FIXING OF 33 KV XLPE JOINTING KIT |
| 759 | CARTAGE SP-21/23 POLE, 0-20 KM |
| 760 | CARTAGE SP-55 POLE, 0-20 KM |
| 761 | CARTAGE SP-72 POLE, 0-20 KM |
| 762 | CARTAGE OF PATTY MATERIAL, 0-20 KM |
| 763 | HEADLOAD CARTAGE SP-21/23POLE(0-1 KM) |
| 764 | HEADLOAD CARTAGE SP-55 POLE(0-1 KM) |
| 765 | HEADLOAD CARTAGE SP-72 POLE(0-1 KM) |
| 766 | HEADLOAD CARTAGE OFMATERIAL(0-1 KM) |
| 767 | ESCAVATION OF EARTH FOR STRUCT.ERECTION |
| 768 | ROAD CUTTING AND REPAIRING |
| 769 | FIXING OF 33 KV TENSION CLAMP WITHIPC |
| 770 | FIXING OF 33 KV IPC FOR CC TO CCCOND. |
| 771 | FIXING OF 33 KV MID SPAN JOINTINGKIT |
| 772 | FIXING OF 33 KV BIMETALIC LUG |
| 773 | FIXING OF IPC WITH AL. BAIL FOREARTHING |
| 774 | LAYING OF 33KV CABLE FOR POLERISING O/H |
| 775 | FIXING OF 33KV CABLE TIES |
| 776 | LAYING SPREADING,STRINGING AAAC CONDUCT. |
| 777 | COMPLETE TESTING WIRING |
| 778 | MAKING LOOP OF 33 KV XLPE CABLE |
| 779 | MANUAL DIGGING OF CABLE TRENCHUPTO 1 MT |
| 780 | SUPPLY & LAYING OF HDPE PIPE INOPEN CUT |
| 781 | PAINTING OF SINGLE POLE (SP-55) |
| 782 | PAINTING OF SINGLE POLE (SP-72) |
| 783 | PAINTING OF DOUBLE POLE (SP-55) |
| 784 | PAINTING OF DOUBLE POLE (SP-72) |
| 785 | PAINTING OF FOUR POLE (SP-72) |
| 786 | FIXING OF G.I PIPE 3 MTR LONG |
| 787 | SHIFTING REALIGNMENT 11KV SP,DP/ LT LINE |
| 788 | DELTA EARTHING WITH MS ROUNDELECTROD/GI |
| 789 | Annual Maintenance Charges (AMC) and O&M of Project for 5 years on per year basis. |
| 790 | Construction of Control RoomEarth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 791 | Filling available excavated earth (excluding rock) in trenches, plinth sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5m |
| 792 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also includingramming and watering of the earth in layers not exceeding 20cm in trenches, plinth, sides of foundation etc. complete |
| 793 | Supplying and filling in plinth with Jamuna sand under floors including, watering, ramming consolidating and dressing complete. |
| 794 | Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1:2 (1 cement : 2 Coarse sand) to match the existing floor : With Chlorpyriphos/Lindane E.C. 20% with 1% concentration. |
| 795 | Providing and laying in position cement concrete in ratio 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 796 | Providing and laying in position cement concrete in ratio 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 40 mm nominal size) of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 797 | Providing and laying in position specified grade of reinforced cement concrete in ratio 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level |
| 798 | Reinforced cement concrete work in 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level excluding cost of centering, shuttering, finishing and reinforcement. |
| 799 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size). |
| 800 | Centering and shuttering including strutting, propping etc. and removal of form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 801 | Centering and shuttering including strutting, propping etc. and removal of form for Suspended floors, roofs, landings, balconies and access platform. |
| 802 | Centering and shuttering including strutting, propping etc. and removal of form for Almirah Shelves Bottom and Edges |
| 803 | Centering and shuttering including strutting, propping etc. and removal of form for Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 804 | Centering and shuttering including strutting, propping etc. and removal of form for Columns, Pillars, Piers, Abutments, Posts and Struts. |
| 805 | Centering and shuttering including strutting, propping etc. and removal of form for : Edges of slabs and breaks in floors and walls. Under 20 cm wide |
| 806 | Centering and shuttering including strutting, propping etc. and removal of form for Weather shade, Chajjas, corbels etc., including edges. |
| 807 | Providing, hoisting and fixing up to floor five level precast reinforced cement concrete in small lintels not exceeding 1.5m clear span up to floor five level including the cost of required centering, shuttering and finishing smooth with 6 mm thick cement plaster 1:3 (1 cement : 3 fine sand) on exposed surfaces but excluding the cost of reinforcement with 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size). |
| 808 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.Thermo-Mechanically Treated bars. |
| 809 | Smooth finishing of the exposed surface of R.C.C. work with 6 mm thick cement mortar 1:3 (1 Cement : 3 fine sand). |
| 810 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 811 | Brick work with F.P.S. bricks of class designation 75 in foundation and plinth in Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 812 | Brick work with F.P.S. bricks of class designation 75 in superstructure above plinth level up to floor V level in all shapes and sizes in Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 813 | Half brick masonry with F.P.S. brick of class designation 75 in foundations and plinth in. cement mortar 1:4 (1 cement : 4 coarse sand) |
| 814 | Half brick masonry with F.P.S. bricks of class designation 75 in superstructure above plinth level up to floor V level. |
| 815 | Providing and fixing 18mm thick gang saw cut mirror polished premoulded and prepolished) machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edge to give high gloss finish etc. complete at all levels. Granite of any colour and shade. Area of slab upto 0.50 sqm |
| 816 | Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge.Granite work |
| 817 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS:15622(thickness to be specified by the manufacturer), of approved make,in all colours, shades except burgundy, bottle green, black of any size asapproved by Engineer-in-Charge, in skirting, risers of steps and dados,over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) andjointing with grey cement slurry @ 3.3kg per sqm, including pointingin white cement mixed with pigment of matching shade complete. |
| 818 | Providing and fixing fly proof galvanized M.S. wire gauge to windows and clerestory windows using wire gauge with average width of aperture 1.4mm in both directions with wire of dia 0.63 mm all complete.With 12 mm mild steel U beading. |
| 819 | Providing and fixing ISI marked aluminium butt hinges anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete: 100x63x4 mm |
| 820 | Providing and fixing aluminium sliding door bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc. complete : 250x16 mm |
| 821 | Providing and fixing aluminium tower bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade with necessary screws etc. complete : 150x10 mm |
| 822 | Providing and fixing aluminium handles ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete :100 mm |
| 823 | Providing and fixing aluminium hanging floor door stopper ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade with necessary screws etc. complete. Single rubber stopper |
| 824 | Providing and fixing aluminium casement stays ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade with necessary screws etc. complete. |
| 825 | Strutural steel work riveted bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete: |
| 826 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp of internal dia 140mm, 73mm height, top lid of 1.5mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3mm dia. round headed screws, one lock at the corners. Clamp shall be made of 12mm dia M.S. bar bent to shape as per standard drawing. |
| 827 | Steel work welded in built up sections/ framed work including cutting,hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. |
| 828 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement including cement slurry, but excluding the cost of nosing of steps etc. complete.40mm thick with 20mm nominal size stone aggregate. |
| 829 | Providing and fixing glass strips in joints of terrazo/ cement concrete floors.40 mm wide and 4 mm thick. |
| 830 | Providing and laying Ceramic glazed floor tiles 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick Cement Mortar 1:4 (1 Cement : 4 Coarse sand) including pointing the joints with white cement and matching pigment etc., complete. |
| 831 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600x600 mm |
| 832 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes.75 mm diameter |
| 833 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes.110 mm diameter |
| 834 | 12 mm cement plaster of mix 1:6 (1 cement: 6 coarse sand) |
| 835 | 15mm cement plaster on rough side of single or half brick wall of mix: 1:6 (1cement :6 coarse sand) |
| 836 | 12 mm Cement plaster 1:3 (1 cement: 3 coarse sand) finished with a floating coat of neat cement. |
| 837 | 6mm Cement plaster finished with a floating coat of neat cement 1:3. |
| 838 | Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete |
| 839 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade.New work (two or more coats) over and including priming coat with cement primer. |
| 840 | Finishing walls with textured exterior paint of required shade for new work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including base coat of water proofing cement paint applied @ 2.20kg/10 sqm. |
| 841 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work |
| 842 | Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete including cutting and making good the walls and floors wherever required :White Vitreous china Orissa pattern W.C. pan of size 580x440mm with integral type foot rests. |
| 843 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required :One urinal basin with 5 litre white P.V.C. automatic flushing cistern |
| 844 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps,32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require :White Vitreous China Flat back wash basin size 550x400 mm with single 15 mm C.P. brass pillar tap. |
| 845 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete.Flexible pipe-----32 mm dia |
| 846 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 847 | Providing and fixing PTMT towel ring trapezoidal shape 215 mm long, 200 mm wide with minimum distances of 37 mm from wall face with concealed fittings arrangement of approved quality and colour, weighing not less than 88 gms. |
| 848 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply and all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall..15 mm nominal dia Pipes |
| 849 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply and all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work -Exposed on wall 20 mm nominal dia Pipes |
| 850 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :25 mm nominal bore |
| 851 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete :15 mm nominal bore |
| 852 | Providing and fixing uplasticised PVC connection pipe with brass unions : 30 cm length.15 mm nominal bore |
| 853 | Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design :With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 |
| 854 | Providing and fixing G.I. Union in G.I. pipe including cutting and threading the pipe and making long screws etc. complete (New work) :15 mm nominal bore |
| 855 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 856 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931: 15 mm nominal bore |
| 857 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931: 15 mm nominal bore |
| 858 | Providing and fixing PTMT grating of approved quality and colour. Circular type. 100 mm nominal dia |
| 859 | Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighing not less than 106 gms. |
| 860 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC/neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing and paneling to be paid for separately) : For.... fixed portion Powder coated aluminium (minimum thickness of powdercoating 50 micron) |
| 861 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC/neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing and paneling to be paid for separately) : For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of PVC / neoprene gasket required (Fittings shall be paid for separately). Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 862 | Providing and fixing 12mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge. Pre-laminated particle board with decorative lamination on both sides. |
| 863 | Providing and fixing 100mm brass locks (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete. |
| 864 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with PVC/ neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-incharge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 4 mm thickness |
| 865 | Grading roof for water proofing treatment with Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 866 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with moduler type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single core cable etc as required. Group B |
| 867 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required :2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 868 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 A switch |
| 869 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 A socket outlet |
| 870 | Supplying and fixing suitable size GI box with modular plate and cover in front on ...... providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection, painting etc. as required. |
| 871 | Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. |
| 872 | Supply and fixing following rating, 63 amps double pole, 240 volts, isolator in the existing MCB DB complete with connection, testing and commissioning etc. as required. |
| 873 | Supply and fixing 5 amps to 32 amps rating, 240 volts, 'C' serise, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole and neutral |
| 874 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar,interconnections, powder painted including earthing etc. as required. (But withoutMCB/RCCB/Isolator) 8 way , Double door |
| 875 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan withBrush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2nos. canopies, shackle kit, safetyrope, copper winding, PowerFactor not less than 0.9, ServiceValue (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulationresistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 876 | Supplying of Exhaust Fan 250 mm Sweep of Orient or equivalent make as approved by E.I. |
| 877 | Supplying of 20 watt LED Tubelight Philps or equivalent make as approved by E.I. |
| 878 | Engaging/S of suitable beldar for different type of works |
| 879 | Engaging suitable electrician with kit for petty work. (Based on DSR Code 1001) |
| 880 | Land Development WorksEarth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 881 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 and for all lift. |
| 882 | Providing and laying in position cement concrete in ratio 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 883 | Providing and laying in position specified grade of reinforced cement concrete in ratio 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level |
| 884 | Reinforced cement concrete work in 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level excluding cost of centering, shuttering, finishing and reinforcement. |
| 885 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size). |
| 886 | Centering and shuttering including strutting, propping etc. and removal of form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 887 | Centering and shuttering including strutting, propping etc. and removal of form for Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 888 | Centering and shuttering including strutting, propping etc. and removal of form for Columns, Pillars, Piers, Abutments, Posts and Struts. |
| 889 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.Thermo-Mechanically Treated bars. |
| 890 | Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement: 6 coarse sand: 12 graded stone aggregate 20 mm nominal size) upto plinth level with: Cement mortar 1 :6 (1 cement : 6 coarse sand) |
| 891 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes.110 mm diameter |
| 892 | Supplying and stacking at site. 90 mm to 45 mm size stone aggregate |
| 893 | Supplying and stacking at site…..63 mm to 45 mm size stone aggregate |
| 894 | Supply for 33/11kV SubstationT/F 33/11 kV 12.5MVA |
| 895 | 8 m. LONG STP 410 SP-10 (BPHD GAL.) |
| 896 | 11 MTR. LONGSTP 410 SP-55(BPHD GAL.) |
| 897 | MS ROUND 32 mm |
| 898 | 11 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 899 | 33 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 900 | DISC FIT. B&S TYPE FOR PANTHER 90 KN |
| 901 | DISC FIT. B&S TYPE WEASEL/RABBIT 45 KN |
| 902 | 9 KV 10 KA Polymeric Lightning Arrestor |
| 903 | EARTHING ROD MS 20X2500mm |
| 904 | GI WIRE 5mm/6 SWG |
| 905 | STAY SET GI 16X1800mm |
| 906 | STAY WIRE GI 7/3.15mm 7/10SWG |
| 907 | ACSR DOG |
| 908 | ACSR PANTHER |
| 909 | CABLE AL 3X300 SQ. mm XLPE 11 kV |
| 910 | CABLE AL 3X400 SQ. mm XLPE 11 kV |
| 911 | CABLE AL 1X630 SQ. mm XLPE 11 kV |
| 912 | CABLE AL 3X70 SQ. mm XLPE 33kV |
| 913 | J/KIT FOR 3X300mm* 11kV XLPE CABLE(O/D) |
| 914 | J/KIT FOR 3X400mm° 11kV XLPE CABLE (O/D) |
| 915 | CONTROL CABLE 10X2.5 SQ. mm. |
| 916 | CONTROL CABLE 2X2.5 SQ. mm. |
| 917 | CONTROL CABLE 4X2.5 SQ. mm. |
| 918 | CONTROL CABLE 6X2.5 SQ. mm. |
| 919 | LT PVC CABLE 2X6 SQ.mm (ARMORED) |
| 920 | LT XLPE CABLE 3.5.X 70 SQ. mm. |
| 921 | LT PVC CABLE 4X10 SQ.mm |
| 922 | 33 KV H.S. Cable J/K 3x70 sq. mm (O/D) |
| 923 | 110 V BATTERY SET(300 AH) |
| 924 | 110V BATTERY CHARGER(300 AH) |
| 925 | JUNCTION BOX FOR 33kV PT |
| 926 | 33kV PT of RATIO 33 kV/110V OUTDOOR |
| 927 | 33 kV LIGHTNING ARRESTER |
| 928 | PANTHER TO PANTHER CTYPE WEDGE CONNECTOR |
| 929 | 33 kV FUSE SET |
| 930 | 33/0.433 KV, 63 KVA Station Transformer |
| 931 | MS STRUCTURE (ANGLE ,CHANNEL ETC.) |
| 932 | GI ITEM (Rail,Joist,ChanneI,Angle) |
| 933 | Cable Holding clamp with N&B |
| 934 | Holding Clamp FPR GI Pipe 8/10\\"& MS Ch. |
| 935 | PG CLAMP ALU ALLOY PANTHER TO DOG |
| 936 | Stay Clamp for SP-55 With Nut & Bolt |
| 937 | 33KV ISOLATOR CONN.CLAMP FOR PANTHER,N&B |
| 938 | 33 KV ISOLATOR CLAMP FOR ACSR DOG |
| 939 | PERFORATED TRAY 400MM FOR CABLE TRENCH |
| 940 | PERFORATED TRAY 200MM FOR CABLE TRENCH |
| 941 | PERFORATED TRAY 100MM FOR CABLE TRENCH |
| 942 | FLEXIBLE COOPER CONNECTOR SOXSOMM |
| 943 | DANGER BOARD |
| 944 | GI Pipe 4\\"' Dia |
| 945 | 250 W hpsv/led lamp with contrl gear |
| 946 | Insulated Electrical Piller Taparia |
| 947 | 11 KV Fuse Set |
| 948 | KM-21 G.I. Pipe 6\\" dia 3 meter long |
| 949 | Conne.Suitable for Panther for LA |
| 950 | Connector of Power T/F HV Side |
| 951 | Connector of Power T/F LV Side |
| 952 | GI STRIP 65MMX6MM |
| 953 | “HT' WARNING TAPE |
| 954 | 11KV,630Amp off load Isolator |
| 955 | Thimble junction box for cable support |
| 956 | 33KV C&R PANEL I/C-D |
| 957 | 33KV C&R PANEL O/G-D |
| 958 | 33KV C&R PANEL BUS COUPLER-D |
| 959 | 11KV C&R PANEL I/C-D |
| 960 | 11KV C&R PANEL O/G-D |
| 961 | 11KV C&R PANEL BUS COUPLER-D |
| 962 | PP clamp with N&B (GI) |
| 963 | G.I.Strip 35x4mm |
| 964 | 11 KV HS cable END T/K 1x630 mm* O/D |
| 965 | Cable Jointing Kit 1x630 Outdoor |
| 966 | 33 KV XLPE Cable AL 1x630 sq. mm -D |
| 967 | Iron Clad 30 Amp Switch |
| 968 | Connector Suit for CT/PT for Panther/Dog |
| 969 | 33 KV Isolator Vertical Type |
| 970 | 11kv 3P(400A)3pin vert. mount GO AB TPMO |
| 971 | Indoor type auto power factor controller |
| 972 | 12.65kV, 4800kVAr, Capacitor bank |
| 973 | 12KV C&R Panel with SCADA(Capacitor) |
| 974 | 36KV 1250A Gang ope PMA VCB(I/C) |
| 975 | 36KV 1250A Gang ope PMA VCB(O/G) |
| 976 | 12KV 1250A Gang ope PMA VCB(I/C) |
| 977 | 12KV 1250A Gang ope PMA VCB(O/G) |
| 978 | 12KV 1250A Gang ope PMA VCB(Capacitor) |
| 979 | 12KV 1250A Gang ope PMA VCB(B/C) |
| 980 | 36KV 1250A Gang ope PMA VCB(B/C) |
| 981 | 33kv Bus isolator manual&motor,SCADA COM |
| 982 | 33kv line isolator manual&motor,SCADA co |
| 983 | 11kv isolator manual&motor,SCADA comp. |
| 984 | Wire Mesh Fencing |
| 985 | 110V DC DISTRIBUTION BOARD-D |
| 986 | Name Plate of Equip. TG,LI,BI,CT,CB ect. |
| 987 | GI STRIP 50X6 MM |
| 988 | SUNDRISE ITEM LUG GLADE ETC |
| 989 | Alluminium Lug |
| 990 | Stone Pad 300x300x75mm |
| 991 | Connector Suitable. Panther for VCB |
| 992 | Dustbin 20 Litre Capacity (Colour Green) |
| 993 | RUBBER MAT(INSULATED )1MX1MX3MM |
| 994 | Fire Extingushier |
| 995 | Torch 3 Cell |
| 996 | 33 KV Hand Gloves |
| 997 | Earth Chain |
| 998 | First aid box |
| 999 | SHOCK TREATMENT CHART |
| 1000 | SHUT DOWN/ BREAK DOWN BOARD |
| 1001 | WALL CLOCK |
| 1002 | D-SPANNER SET |
| 1003 | PIPE WRENCH 12\\" |
| 1004 | 2.5 KV MEGGAR DIGITAL |
| 1005 | EARTH MEGGAR DIGITAL |
| 1006 | INSTRUCTION BOARD |
| 1007 | MAXIMUM & MINIMUM DISPLAY BOARD |
| 1008 | SUB STATION NAMED BOARD |
| 1009 | Portable Foam Type Fire Extinguisher SLT |
| 1010 | Single Line Diagram Board |
| 1011 | Door Mat |
| 1012 | Name plate of feeder |
| 1013 | Name plate of station \iI |
| 1014 | 11KV Danger Board with Clamp |
| 1015 | 33 KV Danger Board with Clamp |
| 1016 | Steel Almirah |
| 1017 | Office Table size (4x2.5) |
| 1018 | Fire Bucket Stand with Buckets |
| 1019 | Steel Cabinet |
| 1020 | Steel office Table |
| 1021 | Steel office chair Godrej |
| 1022 | Meggar 5 KV Digital |
| 1023 | Fire Bucket stand of MS angle |
| 1024 | Supply for 33kV LINE8.5 MRT. LONG STP 410 SP-23(BPHDGAL.) |
| 1025 | 9 MRT. LONG STP 410 SP-33(BPHD GAL.) |
| 1026 | 11 MTR. LONGSTP 410 SP-55(BPHDGAL.) |
| 1027 | STP 13.0 M-IS 410 SP-72 (BPHD GAL.) |
| 1028 | MS ANGLE 65X65X6 mm |
| 1029 | MS CHANNEL 100X50 mm |
| 1030 | MS CHANNEL 125X65 mm |
| 1031 | 11 kV POLYMER DISC INSULATOR(B&S) TYPE |
| 1032 | 33 kV POLYMER DISC INSULATOR(B&S) TYPE |
| 1033 | 11 kV POLYMER PIN INSULATOR WITH PIN |
| 1034 | 33kV 10KN POLYMER PIN INSULATORWITH PIN |
| 1035 | DISC FIT. B&S TYPE WEASEL/RABBIT45 KN |
| 1036 | LT Shackle Insulator |
| 1037 | X ARM ANGLE 65X65X6 mm V TYPE 11kV |
| 1038 | X ARM CHANNEL 100X50 mm V TYPE 33kV |
| 1039 | Earth wire GI 7/1.6 mm 16 SWG |
| 1040 | EARTHING ROD MS 20X2500mm |
| 1041 | GI WIRE 4mm/8mm SWG |
| 1042 | GI WIRE 5mm/6 SWG |
| 1043 | STAY SET GI 20X1800mm |
| 1044 | STAY WIRE GI 7/4.0 mm 7/8 SWG |
| 1045 | ACSR RABBIT |
| 1046 | Bolt & Nut 150x12 mm |
| 1047 | Bolt & Nuts 50x16 mm |
| 1048 | Eye Bolt 190x16 mm With Nut & Bolt |
| 1049 | Eart wire Clamp with Nut & Bolt |
| 1050 | Bracing Clamp SP-72 |
| 1051 | LT Shackle Insulator Clamp |
| 1052 | Holding Clamp FPR GI Pipe 8/10'' & MS Channel |
| 1053 | E- CLAMP |
| 1054 | F Clamp |
| 1055 | EARTH WIRE CLAMP FOR SP-55 WITHN/B |
| 1056 | PP & CLAMP WITH N&B ST POLE SP-55 |
| 1057 | PP & CLAMP WITH N&B ST POLE SP-72 |
| 1058 | STAY CLAMP FOR SP-72 WITH N/B |
| 1059 | PP & CLAMP WITH N&B ST POLE SP-23 |
| 1060 | NUMBER PLATE WITH CLAMP |
| 1061 | Danger Board With Clamp N&B |
| 1062 | Bracing Clamp top for SP-23 with Nut & Bolt |
| 1063 | Bolt & Nuts off Size |
| 1064 | Cable Holding Clamp with N&B of Size |
| 1065 | PG Clamp For panther |
| 1066 | KM-21 G.I. Pipe 6\\" dia 3 meter long |
| 1067 | STAY CLAMP FOR SP-55 WITH NUT & BOLT |
| 1068 | Earth Wire Clamp |
| 1069 | 33 KV Mid Span Jointing Kit |
| 1070 | 33KV Biometric crimping Lug |
| 1071 | 33 KV IPC with Al. Ball for Earthing |
| 1072 | 33 KV Tension clamp with Bail & IPC |
| 1073 | 33 KV IPC for covered to covered conduct |
| 1074 | 33 KV Cable Ties for Insulator |
| 1075 | Concrete route marker for HT cable |
| 1076 | PP & CLAMP WITH NUT & BOLT FORGUARDING |
| 1077 | 33 KV straight Through 1x630 sqmm |
| 1078 | Disc fitting for Panther 120 KN |
| 1079 | PP CLAMP FOR SPECIAL TYPEBRACKET |
| 1080 | 33KV AAAC COVERED COND. AL-59,241SQ.MM. |
| 1081 | Cable Jointing Kit 1x630 Outdoor |
| 1082 | 33 KV XLPE Cable AL 1x630 sqmm - D |
| 1083 | ALUMINIUM BINDING WIRE |
| 1084 | BARBED WIRE |
| 1085 | Stone Pad 300x300x75mm |
| 1086 | Erection Work for Substation:7.2.1 (DSR CODE 2014) |
| 1087 | NSI_EARTH FILLING |
| 1088 | CEMENT CONCRETING WORK IN RATIO 1:4:8 |
| 1089 | CEMENT CONCRETING WORK IN RATIO 1:2:4 |
| 1090 | BRICK WORK IN 1:4 RATIO |
| 1091 | CEMENT PLASTER WORK |
| 1092 | FENCING OF YARD |
| 1093 | RCC 1:1.5:3 |
| 1094 | MAKING CABLE TRENCH |
| 1095 | BRICK WORK 1:6 SUB STRUCTURE |
| 1096 | BRICK WORK 1:6 SUPER STRUCTURE |
| 1097 | CC WORK 1:1.5:2 |
| 1098 | SUPPLY&ERRECT GRAVEL PITCHING 1/2\\"- 3/4\\" |
| 1099 | ELECTRICAL INSPECTION FEE |
| 1100 | SPECIAL EARTHING |
| 1101 | FABRICATION OF STEEL |
| 1102 | FIXING OF GI PIPE |
| 1103 | ERECTION OF SINGLE SP-10 POLE |
| 1104 | ERECTION OF SP-55 DOUBLE POLE |
| 1105 | PAINTING OF SP-10 POLE |
| 1106 | PAINTING OF SP-55 POLE |
| 1107 | LAYING OF LT PVC CABLES(» 150 SQMM) |
| 1108 | LAYING OF U/G 11 KV CABLE IN TRENCH |
| 1109 | LAYING OF U/G 33 KV CABLE IN TRENCH |
| 1110 | FIXING OF LIGHTNING ARRESTOR |
| 1111 | FIXING OF 11 KV XLPE JOINTING KIT |
| 1112 | FIXING OF 33 KV XLPE JOINTING KIT |
| 1113 | CARTAGE OF PETTY MATERIAL,0-20 KM |
| 1114 | CARTAGE 11 KV PANELS, 0-20 KM |
| 1115 | CARTAGE OF PANELS, 0-20 KM |
| 1116 | CARTAGE 10/12.5 MVA POWER T/ F(0-20KM) |
| 1117 | MANUAL SHIFTING OF CONTROL PANEL |
| 1118 | ERECTION OF POWER T/F(12.5/10 MVA) |
| 1119 | ESCAVATION OF EARTH FOR STRUCT. ERECTION |
| 1120 | GROUTING OF STRUCTURE IN CC 1:3:6 |
| 1121 | FIXING OF 33 KV ISOLATOR VERTICAL TYPE |
| 1122 | LAYING OF CONTROL CABLE |
| 1123 | LAYING OF EARTH MAT |
| 1124 | EARTHING OF STRUCTURE USING GI STRIP |
| 1125 | COMM.OF 33/11KV VCB PANEL |
| 1126 | COMPLETE TESTING WIRING |
| 1127 | ERECTION & LAYING OF LT XLPE CABLE 2X6 |
| 1128 | INST. & FIXING OF CHEMICAL EARTHING |
| 1129 | INSTALLATION OF LINE/ BUS ISOLATOR |
| 1130 | INSTALLATION OF DCDB INCLUDING TESTING |
| 1131 | INSTALLATION OF ACDB INCLUDING TESTING |
| 1132 | ERECTION OF 33/0.433KV S/S TRANSFORMER |
| 1133 | ERECTION OF FLEXIBLE CU. CONN.500X50 MM |
| 1134 | ERECTION OF STAY POST |
| 1135 | ERRECTION OF 33KV PT |
| 1136 | ERREC. 12.65kV 4800kVAr, CAPACITOR BANK |
| 1137 | ERREC. 11KV, 630 AMP, OFF LOAD ISOLATOR |
| 1138 | ERECTION OF 110V BATTERY SET(300AH) |
| 1139 | ERECTION OF 110V BATTERY CHARGER(300AH) |
| 1140 | FIXING OF 11 KV FUSE SET |
| 1141 | FIXING OF 33 KV FUSE SET |
| 1142 | LAYING OF 4X10SQ MM LT PVC CABLE |
| 1143 | ERECTION OF EARTHING ELECTRODE&STRIP50X6 |
| 1144 | FIXING OF SODIUM/LED LIGHT AT YARD |
| 1145 | INSTALLATION OF FIRE EXTINGUISHERS |
| 1146 | ERECTION OF NAME PLATES |
| 1147 | ERECTION OF T&P ITEMS |
| 1148 | ERECTION OF MISC. GI STRUCTURES |
| 1149 | SHIFTING OF T/F B WORK |
| 1150 | Erection for 33kV LINECEMENT CONCRETING WORK IN RATIO 1:4:8 |
| 1151 | ELECTRICAL INSPECTION FEE |
| 1152 | ERECTION OF EARTHING ROAD |
| 1153 | FABRICATION OF STEEL |
| 1154 | FIXING OF GI PIPE |
| 1155 | FIXING OF RCC CABLE ROUTE MARKER |
| 1156 | ERECTION OF 33 KV STAY SET |
| 1157 | ERECTION OF SINGLE SP-55 POLE |
| 1158 | ERECTION OF SINGLE SP-72 POLE |
| 1159 | ERECTION OF SP-55 DOUBLE POLE |
| 1160 | ERECTION OF SP-72 DOUBLE POLE |
| 1161 | ERECTION OF SP-72(11KV/33 KV) FOUR POLE |
| 1162 | ERECTION OF BRACKET IN 11 KV LINE |
| 1163 | GUARDING OF 33 KV LINE |
| 1164 | FIXING OF 33 KV XLPE JOINTING KIT |
| 1165 | CARTAGE SP-21/23 POLE, 0-20 KM |
| 1166 | CARTAGE SP-33 POLE, 0-20 KM |
| 1167 | CARTAGE SP-55 POLE, 0-20 KM |
| 1168 | CARTAGE SP-72 POLE, 0-20 KM |
| 1169 | CARTAGE OF PATTY MATERIAL, 0-20 KM |
| 1170 | HEADLOAD CARTAGE SP-21/23POLE(0-1 KM) |
| 1171 | HEADLOAD CARTAGE SP-33 POLE(0-1 KM) |
| 1172 | HEADLOAD CARTAGE SP-55 POLE(0-1 KM) |
| 1173 | HEADLOAD CARTAGE SP-72 POLE(0-1 KM) |
| 1174 | HEADLOAD CARTAGE OFMATERIAL(0-1 KM) |
| 1175 | ROAD CUTTING AND REPAIRING |
| 1176 | Supply & LAYING OF HDPE PIPE |
| 1177 | FIXING OF 33 KV TENSION CLAMP WITHIPC |
| 1178 | FIXING OF 33 KV IPC FOR CC TO CCCOND. |
| 1179 | FIXING OF 33 KV MID SPAN JOINTINGKIT |
| 1180 | FIXING OF 33 KV BIMETALIC LUG |
| 1181 | FIXING OF IPC WITH AL. BAIL FOREARTHING |
| 1182 | LAYING OF 33KV CABLE FOR POLERISING O/H |
| 1183 | FIXING OF 33KV CABLE TIES |
| 1184 | LAYING SPREADING,STRINGING AAAC CONDUCT. |
| 1185 | COMPLETE TESTING WIRING |
| 1186 | MAKING LOOP OF 33 KV XLPE CABLE |
| 1187 | MANUAL DIGGING OF CABLE TRENCHUPTO 1 MT |
| 1188 | SUPPLY & LAYING OF HDPE PIPE INOPEN CUT |
| 1189 | PAINTING OF SINGLE POLE (SP-72) |
| 1190 | PAINTING OF DOUBLE POLE (SP-55) |
| 1191 | PAINTING OF DOUBLE POLE (SP-72) |
| 1192 | PAINTING OF FOUR POLE (SP-72) |
| 1193 | FIXING OF G.I PIPE 3 MTR LONG |
| 1194 | SHIFTING REALIGNMENT 11KV SP,DP/ LT LINE |
| 1195 | DELTA EARTHING WITH MS ROUNDELECTROD/GI |
| 1196 | Annual Maintenance Charges (AMC) and O&M of Project for 5 years on per year basis. |
| 1197 | Construction of Control RoomEarth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 1198 | Filling available excavated earth (excluding rock) in trenches, plinth sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5m |
| 1199 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also includingramming and watering of the earth in layers not exceeding 20cm in trenches, plinth, sides of foundation etc. complete |
| 1200 | Supplying and filling in plinth with Jamuna sand under floors including, watering, ramming consolidating and dressing complete. |
| 1201 | Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1:2 (1 cement : 2 Coarse sand) to match the existing floor : With Chlorpyriphos/Lindane E.C. 20% with 1% concentration. |
| 1202 | Providing and laying in position cement concrete in ratio 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 1203 | Providing and laying in position cement concrete in ratio 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 40 mm nominal size) of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 1204 | Providing and laying in position specified grade of reinforced cement concrete in ratio 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level |
| 1205 | Reinforced cement concrete work in 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level excluding cost of centering, shuttering, finishing and reinforcement. |
| 1206 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size). |
| 1207 | Centering and shuttering including strutting, propping etc. and removal of form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 1208 | Centering and shuttering including strutting, propping etc. and removal of form for Suspended floors, roofs, landings, balconies and access platform. |
| 1209 | Centering and shuttering including strutting, propping etc. and removal of form for Almirah Shelves Bottom and Edges |
| 1210 | Centering and shuttering including strutting, propping etc. and removal of form for Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 1211 | Centering and shuttering including strutting, propping etc. and removal of form for Columns, Pillars, Piers, Abutments, Posts and Struts. |
| 1212 | Centering and shuttering including strutting, propping etc. and removal of form for : Edges of slabs and breaks in floors and walls. Under 20 cm wide |
| 1213 | Centering and shuttering including strutting, propping etc. and removal of form for Weather shade, Chajjas, corbels etc., including edges. |
| 1214 | Providing, hoisting and fixing up to floor five level precast reinforced cement concrete in small lintels not exceeding 1.5m clear span up to floor five level including the cost of required centering, shuttering and finishing smooth with 6 mm thick cement plaster 1:3 (1 cement : 3 fine sand) on exposed surfaces but excluding the cost of reinforcement with 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size). |
| 1215 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.Thermo-Mechanically Treated bars. |
| 1216 | Smooth finishing of the exposed surface of R.C.C. work with 6 mm thick cement mortar 1:3 (1 Cement : 3 fine sand). |
| 1217 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 1218 | Brick work with F.P.S. bricks of class designation 75 in foundation and plinth in Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 1219 | Brick work with F.P.S. bricks of class designation 75 in superstructure above plinth level up to floor V level in all shapes and sizes in Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 1220 | Half brick masonry with F.P.S. brick of class designation 75 in foundations and plinth in. cement mortar 1:4 (1 cement : 4 coarse sand) |
| 1221 | Half brick masonry with F.P.S. bricks of class designation 75 in superstructure above plinth level up to floor V level. |
| 1222 | Providing and fixing 18mm thick gang saw cut mirror polished premoulded and prepolished) machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edge to give high gloss finish etc. complete at all levels. Granite of any colour and shade. Area of slab upto 0.50 sqm |
| 1223 | Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge.Granite work |
| 1224 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS:15622(thickness to be specified by the manufacturer), of approved make,in all colours, shades except burgundy, bottle green, black of any size asapproved by Engineer-in-Charge, in skirting, risers of steps and dados,over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) andjointing with grey cement slurry @ 3.3kg per sqm, including pointingin white cement mixed with pigment of matching shade complete. |
| 1225 | Providing and fixing fly proof galvanized M.S. wire gauge to windows and clerestory windows using wire gauge with average width of aperture 1.4mm in both directions with wire of dia 0.63 mm all complete.With 12 mm mild steel U beading. |
| 1226 | Providing and fixing ISI marked aluminium butt hinges anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete: 100x63x4 mm |
| 1227 | Providing and fixing aluminium sliding door bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc. complete : 250x16 mm |
| 1228 | Providing and fixing aluminium tower bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade with necessary screws etc. complete : 150x10 mm |
| 1229 | Providing and fixing aluminium handles ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete :100 mm |
| 1230 | Providing and fixing aluminium hanging floor door stopper ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade with necessary screws etc. complete. Single rubber stopper |
| 1231 | Providing and fixing aluminium casement stays ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade with necessary screws etc. complete. |
| 1232 | Strutural steel work riveted bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete: |
| 1233 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp of internal dia 140mm, 73mm height, top lid of 1.5mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3mm dia. round headed screws, one lock at the corners. Clamp shall be made of 12mm dia M.S. bar bent to shape as per standard drawing. |
| 1234 | Steel work welded in built up sections/ framed work including cutting,hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. |
| 1235 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement including cement slurry, but excluding the cost of nosing of steps etc. complete.40mm thick with 20mm nominal size stone aggregate. |
| 1236 | Providing and fixing glass strips in joints of terrazo/ cement concrete floors.40 mm wide and 4 mm thick. |
| 1237 | Providing and laying Ceramic glazed floor tiles 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick Cement Mortar 1:4 (1 Cement : 4 Coarse sand) including pointing the joints with white cement and matching pigment etc., complete. |
| 1238 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600x600 mm |
| 1239 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes.75 mm diameter |
| 1240 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes.110 mm diameter |
| 1241 | 12 mm cement plaster of mix 1:6 (1 cement: 6 coarse sand) |
| 1242 | 15mm cement plaster on rough side of single or half brick wall of mix: 1:6 (1cement :6 coarse sand) |
| 1243 | 12 mm Cement plaster 1:3 (1 cement: 3 coarse sand) finished with a floating coat of neat cement. |
| 1244 | 6mm Cement plaster finished with a floating coat of neat cement 1:3. |
| 1245 | Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete |
| 1246 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade.New work (two or more coats) over and including priming coat with cement primer. |
| 1247 | Finishing walls with textured exterior paint of required shade for new work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including base coat of water proofing cement paint applied @ 2.20kg/10 sqm. |
| 1248 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work |
| 1249 | Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete including cutting and making good the walls and floors wherever required :White Vitreous china Orissa pattern W.C. pan of size 580x440mm with integral type foot rests. |
| 1250 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required :One urinal basin with 5 litre white P.V.C. automatic flushing cistern |
| 1251 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps,32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require :White Vitreous China Flat back wash basin size 550x400 mm with single 15 mm C.P. brass pillar tap. |
| 1252 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete.Flexible pipe-----32 mm dia |
| 1253 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 1254 | Providing and fixing PTMT towel ring trapezoidal shape 215 mm long, 200 mm wide with minimum distances of 37 mm from wall face with concealed fittings arrangement of approved quality and colour, weighing not less than 88 gms. |
| 1255 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply and all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall..15 mm nominal dia Pipes |
| 1256 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply and all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work -Exposed on wall 20 mm nominal dia Pipes |
| 1257 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :25 mm nominal bore |
| 1258 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete :15 mm nominal bore |
| 1259 | Providing and fixing uplasticised PVC connection pipe with brass unions : 30 cm length.15 mm nominal bore |
| 1260 | Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design :With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 |
| 1261 | Providing and fixing G.I. Union in G.I. pipe including cutting and threading the pipe and making long screws etc. complete (New work) :15 mm nominal bore |
| 1262 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 1263 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931: 15 mm nominal bore |
| 1264 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931: 15 mm nominal bore |
| 1265 | Providing and fixing PTMT grating of approved quality and colour. Circular type. 100 mm nominal dia |
| 1266 | Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighing not less than 106 gms. |
| 1267 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC/neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing and paneling to be paid for separately) : For.... fixed portion Powder coated aluminium (minimum thickness of powdercoating 50 micron) |
| 1268 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC/neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing and paneling to be paid for separately) : For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of PVC / neoprene gasket required (Fittings shall be paid for separately). Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 1269 | Providing and fixing 12mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge. Pre-laminated particle board with decorative lamination on both sides. |
| 1270 | Providing and fixing 100mm brass locks (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete. |
| 1271 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with PVC/ neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-incharge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 4 mm thickness |
| 1272 | Grading roof for water proofing treatment with Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 1273 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with moduler type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single core cable etc as required. Group B |
| 1274 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required :2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 1275 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 A switch |
| 1276 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 A socket outlet |
| 1277 | Supplying and fixing suitable size GI box with modular plate and cover in front on ...... providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection, painting etc. as required. |
| 1278 | Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. |
| 1279 | Supply and fixing following rating, 63 amps double pole, 240 volts, isolator in the existing MCB DB complete with connection, testing and commissioning etc. as required. |
| 1280 | Supply and fixing 5 amps to 32 amps rating, 240 volts, 'C' serise, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole and neutral |
| 1281 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar,interconnections, powder painted including earthing etc. as required. (But withoutMCB/RCCB/Isolator) 8 way , Double door |
| 1282 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan withBrush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2nos. canopies, shackle kit, safetyrope, copper winding, PowerFactor not less than 0.9, ServiceValue (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulationresistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 1283 | Supplying of Exhaust Fan 250 mm Sweep of Orient or equivalent make as approved by E.I. |
| 1284 | Supplying of 20 watt LED Tubelight Philps or equivalent make as approved by E.I. |
| 1285 | Engaging/S of suitable beldar for different type of works |
| 1286 | Engaging suitable electrician with kit for petty work. (Based on DSR Code 1001) |
| 1287 | Land Development WorksEarth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 1288 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 and for all lift. |
| 1289 | Excavating, supplying, stacking and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in foundation trenches, plinth, sides offoundation etc. complete for all lift. |
| 1290 | Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 moutside the periphery of the area cleared. |
| 1291 | 1 :2:4 (1 cement : 2 coarse sand (zone-Ill) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 1292 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) |
| 1293 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :1 :1.5:3 (1 cement : 1.5 coarse sand (zone-Ill) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 1294 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size) |
| 1295 | Centering and shuttering including strutting, propping etc. and removal of form for Foundations, footings, bases of columns, etc. for mass concrete |
| 1296 | Centering and shuttering including strutting, propping etc. and removal of form for Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 1297 | Centering and shuttering including strutting, propping etc. and removal of form for Columns, Pillars, Piers, Abutments, Posts and Struts. |
| 1298 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.Thermo-Mechanically Treated bars. |
| 1299 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 1300 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 1301 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 1302 | Steel work welded in built up sections/ framed work including cutting,hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. |
| 1303 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes.110 mm diameter |
| 1304 | 12 mm cement plaster of mix 1:6 (1 cement: 6 coarse sand) |
| 1305 | 15mm cement plaster on rough side of single or half brick wall of mix: 1:6 (1cement :6 coarse sand) |
| 1306 | 6 mm cement plaster of mix :1:3 (1 cement : 3 fine sand) |
| 1307 | Finishing walls with textured exterior paint of required shade for new work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including base coat of water proofing cement paint applied @ 2.20kg/10 sqm. |
| 1308 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade. Two or more coats on new work. |
| 1309 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 1310 | Fencing with angle iron post placed at required distance embedded in cement concrete blocks, every 15th post, last but one end post and cornerpost shall be strutted on both sides and end post on one side only and provided with horizontal lines and two diagonals interwoven with horizontalwires, of barbed wire weighing 9.38 kg per 100 m (minimum), between the two posts fitted and fixed with G.I. staples, turn buckles etc. complete. (Costof posts, struts, earth work and concrete work to be paid for separately). Payment to be made per metre cost of total length of barbed wire used. With G.I. barbed wire |
| 1311 | Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earthwith lead upto 50 metres. |
| 1312 | Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge). |
| 1313 | Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge.80 mm thick C.C. paver block of M-30 grade with approved color design and pattern. |
| 1314 | Supply of 33/11kV SubstationT/F 33/11 kV 12.5MVA |
| 1315 | 8 m. LONG STP 410 SP-10 (BPHD GAL.) |
| 1316 | 11 MTR. LONGSTP 410 SP-55(BPHD GAL.) |
| 1317 | MS ROUND 32 mm |
| 1318 | 11 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 1319 | 33 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 1320 | DISC FIT. B&S TYPE FOR PANTHER 90 KN |
| 1321 | DISC FIT. B&S TYPE WEASEL/RABBIT 45 KN |
| 1322 | 9 KV 10 KA Polymeric Lightning Arrestor |
| 1323 | EARTHING ROD MS 20X2500mm |
| 1324 | GI WIRE 5mm/6 SWG |
| 1325 | STAY SET GI 16X1800mm |
| 1326 | STAY WIRE GI 7/3.15mm 7/10SWG |
| 1327 | ACSR DOG |
| 1328 | ACSR PANTHER |
| 1329 | CABLE AL 3X300 SQ. mm XLPE 11 kV |
| 1330 | CABLE AL 3X400 SQ. mm XLPE 11 kV |
| 1331 | CABLE AL 1X630 SQ. mm XLPE 11 kV |
| 1332 | CABLE AL 3X70 SQ. mm XLPE 33kV |
| 1333 | J/KIT FOR 3X300mm* 11kV XLPE CABLE(O/D) |
| 1334 | J/KIT FOR 3X400mm° 11kV XLPE CABLE (O/D) |
| 1335 | CONTROL CABLE 10X2.5 SQ. mm. |
| 1336 | CONTROL CABLE 2X2.5 SQ. mm. |
| 1337 | CONTROL CABLE 4X2.5 SQ. mm. |
| 1338 | CONTROL CABLE 6X2.5 SQ. mm. |
| 1339 | LT PVC CABLE 2X6 SQ.mm (ARMORED) |
| 1340 | LT XLPE CABLE 3.5.X 70 SQ. mm. |
| 1341 | LT PVC CABLE 4X10 SQ.mm |
| 1342 | 33 KV H.S. Cable J/K 3x70 sq. mm (O/D) |
| 1343 | 110 V BATTERY SET(300 AH) |
| 1344 | 110V BATTERY CHARGER(300 AH) |
| 1345 | JUNCTION BOX FOR 33kV PT |
| 1346 | 33kV PT of RATIO 33 kV/110V OUTDOOR |
| 1347 | 33 kV LIGHTNING ARRESTER |
| 1348 | PANTHER TO PANTHER CTYPE WEDGE CONNECTOR |
| 1349 | 33 kV FUSE SET |
| 1350 | 33/0.433 KV, 63 KVA Station Transformer |
| 1351 | MS STRUCTURE (ANGLE ,CHANNEL ETC.) |
| 1352 | GI ITEM (Rail,Joist,ChanneI,Angle) |
| 1353 | Cable Holding clamp with N&B |
| 1354 | Holding Clamp FPR GI Pipe 8/10\\"& MS Ch. |
| 1355 | PG CLAMP ALU ALLOY PANTHER TO DOG |
| 1356 | Stay Clamp for SP-55 With Nut & Bolt |
| 1357 | 33KV ISOLATOR CONN.CLAMP FOR PANTHER,N&B |
| 1358 | 33 KV ISOLATOR CLAMP FOR ACSR DOG |
| 1359 | PERFORATED TRAY 400MM FOR CABLE TRENCH |
| 1360 | PERFORATED TRAY 200MM FOR CABLE TRENCH |
| 1361 | PERFORATED TRAY 100MM FOR CABLE TRENCH |
| 1362 | FLEXIBLE COOPER CONNECTOR SOXSOMM |
| 1363 | DANGER BOARD |
| 1364 | GI Pipe 4\\"' Dia |
| 1365 | 250 W hpsv/led lamp with contrl gear |
| 1366 | Insulated Electrical Piller Taparia |
| 1367 | 11 KV Fuse Set |
| 1368 | KM-21 G.I. Pipe 6\\" dia 3 meter long |
| 1369 | Conne.Suitable for Panther for LA |
| 1370 | Connector of Power T/F HV Side |
| 1371 | Connector of Power T/F LV Side |
| 1372 | GI STRIP 65MMX6MM |
| 1373 | “HT' WARNING TAPE |
| 1374 | 11KV,630Amp off load Isolator |
| 1375 | Thimble junction box for cable support |
| 1376 | 33KV C&R PANEL I/C-D |
| 1377 | 33KV C&R PANEL O/G-D |
| 1378 | 33KV C&R PANEL BUS COUPLER-D |
| 1379 | 11KV C&R PANEL I/C-D |
| 1380 | 11KV C&R PANEL O/G-D |
| 1381 | 11KV C&R PANEL BUS COUPLER-D |
| 1382 | PP clamp with N&B (GI) |
| 1383 | G.I.Strip 35x4mm |
| 1384 | 11 KV HS cable END T/K 1x630 mm* O/D |
| 1385 | Cable Jointing Kit 1x630 Outdoor |
| 1386 | 33 KV XLPE Cable AL 1x630 sq. mm -D |
| 1387 | Iron Clad 30 Amp Switch |
| 1388 | Connector Suit for CT/PT for Panther/Dog |
| 1389 | 33 KV Isolator Vertical Type |
| 1390 | 11kv 3P(400A)3pin vert. mount GO AB TPMO |
| 1391 | Indoor type auto power factor controller |
| 1392 | 12.65kV, 4800kVAr, Capacitor bank |
| 1393 | 12KV C&R Panel with SCADA(Capacitor) |
| 1394 | 36KV 1250A Gang ope PMA VCB(I/C) |
| 1395 | 36KV 1250A Gang ope PMA VCB(O/G) |
| 1396 | 12KV 1250A Gang ope PMA VCB(I/C) |
| 1397 | 12KV 1250A Gang ope PMA VCB(O/G) |
| 1398 | 12KV 1250A Gang ope PMA VCB(Capacitor) |
| 1399 | 12KV 1250A Gang ope PMA VCB(B/C) |
| 1400 | 36KV 1250A Gang ope PMA VCB(B/C) |
| 1401 | 33kv Bus isolator manual&motor,SCADA COM |
| 1402 | 33kv line isolator manual&motor,SCADA co |
| 1403 | 11kv isolator manual&motor,SCADA comp. |
| 1404 | Wire Mesh Fencing |
| 1405 | 110V DC DISTRIBUTION BOARD-D |
| 1406 | Name Plate of Equip. TG,LI,BI,CT,CB ect. |
| 1407 | GI STRIP 50X6 MM |
| 1408 | SUNDRISE ITEM LUG GLADE ETC |
| 1409 | Alluminium Lug |
| 1410 | Stone Pad 300x300x75mm |
| 1411 | Connector Suitable. Panther for VCB |
| 1412 | Dustbin 20 Litre Capacity (Colour Green) |
| 1413 | RUBBER MAT(INSULATED )1MX1MX3MM |
| 1414 | Fire Extingushier |
| 1415 | Torch 3 Cell |
| 1416 | 33 KV Hand Gloves |
| 1417 | Earth Chain |
| 1418 | First aid box |
| 1419 | SHOCK TREATMENT CHART |
| 1420 | SHUT DOWN/ BREAK DOWN BOARD |
| 1421 | WALL CLOCK |
| 1422 | D-SPANNER SET |
| 1423 | PIPE WRENCH 12\\" |
| 1424 | 2.5 KV MEGGAR DIGITAL |
| 1425 | EARTH MEGGAR DIGITAL |
| 1426 | INSTRUCTION BOARD |
| 1427 | MAXIMUM & MINIMUM DISPLAY BOARD |
| 1428 | SUB STATION NAMED BOARD |
| 1429 | Portable Foam Type Fire Extinguisher SLT |
| 1430 | Single Line Diagram Board |
| 1431 | Door Mat |
| 1432 | Name plate of feeder |
| 1433 | Name plate of station \iI |
| 1434 | 11KV Danger Board with Clamp |
| 1435 | 33 KV Danger Board with Clamp |
| 1436 | Steel Almirah |
| 1437 | Office Table size (4x2.5) |
| 1438 | Fire Bucket Stand with Buckets |
| 1439 | Steel Cabinet |
| 1440 | Steel office Table |
| 1441 | Steel office chair Godrej |
| 1442 | Meggar 5 KV Digital |
| 1443 | Fire Bucket stand of MS angle |
| 1444 | Supply of 33kV LINE8.5 MRT. LONG STP 410 SP-23(BPHD GAL.) |
| 1445 | 11 MTR. LONGSTP 410 SP-55(BPHDGAL.) |
| 1446 | STP 13.0 M-IS 410 SP-72 (BPHD GAL.) |
| 1447 | MS ANGLE 65X65X6 mm |
| 1448 | MS CHANNEL 100X50 mm |
| 1449 | MS CHANNEL 125X65 mm |
| 1450 | 11 kV POLYMER DISC INSULATOR(B&S) TYPE |
| 1451 | 33 kV POLYMER DISC INSULATOR(B&S) TYPE |
| 1452 | 11 kV POLYMER PIN INSULATOR WITH PIN |
| 1453 | 33kV 10KN POLYMER PIN INSULATORWITH PIN |
| 1454 | DISC FIT. B&S TYPE DOG/RACOON 70KN |
| 1455 | DISC FIT. B&S TYPE FOR PANTHER 90KN |
| 1456 | DISC FIT. B&S TYPE WEASEL/RABBIT45 KN |
| 1457 | LT Shackle Insulator |
| 1458 | X ARM ANGLE 65X65X6 mm V TYPE 11kV |
| 1459 | X ARM CHANNEL 100X50 mm V TYPE 33kV |
| 1460 | Earth wire GI 7/1.6 mm 16 SWG |
| 1461 | EARTHING ROD MS 20X2500mm |
| 1462 | GI WIRE 4mm/8mm SWG |
| 1463 | GI WIRE 5mm/6 SWG |
| 1464 | STAY SET GI 20X1800mm |
| 1465 | STAY WIRE GI 7/4.0 mm 7/8 SWG |
| 1466 | ACSR RABBIT |
| 1467 | ACSR PANTHER |
| 1468 | MS NUT & BOLT OFF SIZE |
| 1469 | Bolt & Nut 150x12 mm |
| 1470 | Bolt & Nuts 50x16 mm |
| 1471 | Eye Bolt 190x16 mm With Nut & Bolt |
| 1472 | Bracing Clamp SP-72 |
| 1473 | LT Shackle Insulator Clamp |
| 1474 | Holding Clamp FPR GI Pipe 8/10'' & MS Channel |
| 1475 | E- CLAMP |
| 1476 | F Clamp |
| 1477 | EARTH WIRE CLAMP FOR SP-55 WITHN/B |
| 1478 | PP & CLAMP WITH N&B ST POLE SP-55 |
| 1479 | EARTH WIRE CLAMP FOR SP-23 WITHN/B |
| 1480 | PP & CLAMP WITH N&B ST POLE SP-72 |
| 1481 | STAY CLAMP FOR SP-72 WITH N/B |
| 1482 | PP & CLAMP WITH N&B ST POLE SP-23 |
| 1483 | NUMBER PLATE WITH CLAMP |
| 1484 | Danger Board With Clamp N&B |
| 1485 | BRACING CLAMP BOTTOM FOR SP-23WITH N/B |
| 1486 | Cable Holding Clamp with N&B of Size |
| 1487 | PG Clamp For panther |
| 1488 | KM-21 G.I. Pipe 6\\" dia 3 meter long |
| 1489 | STAY CLAMP FOR SP-55 WITH NUT & BOLT |
| 1490 | Earth Wire Clamp |
| 1491 | 33 KV IPC for CC to Bare Conn. In every sec |
| 1492 | 33 KV IPC for CC to Bare Conn. Both end |
| 1493 | 33 KV Mid Span Jointing Kit |
| 1494 | 33KV Biometric crimping Lug |
| 1495 | 33 KV IPC with Al. Ball for Earthing |
| 1496 | 33 KV Tension clamp with Bail & IPC |
| 1497 | 33 KV Cable Ties for Insulator |
| 1498 | Concrete route marker for HT cable |
| 1499 | PP & CLAMP WITH NUT & BOLT FORGUARDING |
| 1500 | 33 KV straight Through 1x630 sqmm |
| 1501 | Disc fitting for Panther 120 KN |
| 1502 | PP CLAMP FOR SPECIAL TYPEBRACKET |
| 1503 | 33KV AAAC COVERED COND. AL-59,241SQ.MM. |
| 1504 | Cable Jointing Kit 1x630 Indoor |
| 1505 | Cable Jointing Kit 1x630 Outdoor |
| 1506 | 33 KV XLPE Cable AL 1x630 sqmm - D |
| 1507 | 33 KV 630 Amp 3 Way RMU |
| 1508 | ALUMINIUM BINDING WIRE |
| 1509 | BARBED WIRE |
| 1510 | Stone Pad 300x300x75mm |
| 1511 | Erection of 33/11kV SUBSTATION7.2.1 (DSR CODE 2014) |
| 1512 | NSI_EARTH FILLING |
| 1513 | CEMENT CONCRETING WORK IN RATIO 1:4:8 |
| 1514 | CEMENT CONCRETING WORK IN RATIO 1:2:4 |
| 1515 | BRICK WORK IN 1:4 RATIO |
| 1516 | CEMENT PLASTER WORK |
| 1517 | FENCING OF YARD |
| 1518 | RCC 1:1.5:3 |
| 1519 | MAKING CABLE TRENCH |
| 1520 | BRICK WORK 1:6 SUB STRUCTURE |
| 1521 | BRICK WORK 1:6 SUPER STRUCTURE |
| 1522 | CC WORK 1:1.5:2 |
| 1523 | SUPPLY&ERRECT GRAVEL PITCHING 1/2\\"- 3/4\\" |
| 1524 | ELECTRICAL INSPECTION FEE |
| 1525 | SPECIAL EARTHING |
| 1526 | FABRICATION OF STEEL |
| 1527 | FIXING OF GI PIPE |
| 1528 | ERECTION OF SINGLE SP-10 POLE |
| 1529 | ERECTION OF SP-55 DOUBLE POLE |
| 1530 | PAINTING OF SP-10 POLE |
| 1531 | PAINTING OF SP-55 POLE |
| 1532 | LAYING OF LT PVC CABLES(» 150 SQMM) |
| 1533 | LAYING OF U/G 11 KV CABLE IN TRENCH |
| 1534 | LAYING OF U/G 33 KV CABLE IN TRENCH |
| 1535 | FIXING OF LIGHTNING ARRESTOR |
| 1536 | FIXING OF 11 KV XLPE JOINTING KIT |
| 1537 | FIXING OF 33 KV XLPE JOINTING KIT |
| 1538 | CARTAGE OF PETTY MATERIAL,0-20 KM |
| 1539 | CARTAGE 11 KV PANELS, 0-20 KM |
| 1540 | CARTAGE OF PANELS, 0-20 KM |
| 1541 | CARTAGE 10/12.5 MVA POWER T/ F(0-20KM) |
| 1542 | MANUAL SHIFTING OF CONTROL PANEL |
| 1543 | ERECTION OF POWER T/F(12.5/10 MVA) |
| 1544 | ESCAVATION OF EARTH FOR STRUCT. ERECTION |
| 1545 | GROUTING OF STRUCTURE IN CC 1:3:6 |
| 1546 | FIXING OF 33 KV ISOLATOR VERTICAL TYPE |
| 1547 | LAYING OF CONTROL CABLE |
| 1548 | LAYING OF EARTH MAT |
| 1549 | EARTHING OF STRUCTURE USING GI STRIP |
| 1550 | COMM.OF 33/11KV VCB PANEL |
| 1551 | COMPLETE TESTING WIRING |
| 1552 | ERECTION & LAYING OF LT XLPE CABLE 2X6 |
| 1553 | INST. & FIXING OF CHEMICAL EARTHING |
| 1554 | INSTALLATION OF LINE/ BUS ISOLATOR |
| 1555 | INSTALLATION OF DCDB INCLUDING TESTING |
| 1556 | INSTALLATION OF ACDB INCLUDING TESTING |
| 1557 | ERECTION OF 33/0.433KV S/S TRANSFORMER |
| 1558 | ERECTION OF FLEXIBLE CU. CONN.500X50 MM |
| 1559 | ERECTION OF STAY POST |
| 1560 | ERRECTION OF 33KV PT |
| 1561 | ERREC. 12.65kV 4800kVAr, CAPACITOR BANK |
| 1562 | ERREC. 11KV, 630 AMP, OFF LOAD ISOLATOR |
| 1563 | ERECTION OF 110V BATTERY SET(300AH) |
| 1564 | ERECTION OF 110V BATTERY CHARGER(300AH) |
| 1565 | FIXING OF 11 KV FUSE SET |
| 1566 | FIXING OF 33 KV FUSE SET |
| 1567 | LAYING OF 4X10SQ MM LT PVC CABLE |
| 1568 | ERECTION OF EARTHING ELECTRODE&STRIP50X6 |
| 1569 | FIXING OF SODIUM/LED LIGHT AT YARD |
| 1570 | INSTALLATION OF FIRE EXTINGUISHERS |
| 1571 | ERECTION OF NAME PLATES |
| 1572 | ERECTION OF T&P ITEMS |
| 1573 | ERECTION OF MISC. GI STRUCTURES |
| 1574 | SHIFTING OF T/F B WORK |
| 1575 | Erection of 33kV LINE7.2.1 (DSR CODE 2014) |
| 1576 | NSI_EARTH FILLING |
| 1577 | EXACVATION FOR FOUNDATION |
| 1578 | CEMENT CONCRETING WORK IN RATIO1:4:8 |
| 1579 | CEMENT CONCRETING WORK IN RATIO1:2:4 |
| 1580 | BRICK WORK IN 1:4 RATIO |
| 1581 | CEMENT PLASTER WORK |
| 1582 | ELECTRICAL INSPECTION FEE |
| 1583 | ERECTION OF EARTHING ROAD |
| 1584 | FABRICATION OF STEEL |
| 1585 | FIXING OF GI PIPE |
| 1586 | FIXING OF RCC CABLE ROUTE MARKER |
| 1587 | ERECTION OF 33 KV STAY SET |
| 1588 | ERECTION OF SINGLE SP-72 POLE |
| 1589 | ERECTION OF SP-55 DOUBLE POLE |
| 1590 | ERECTION OF SP-72 DOUBLE POLE |
| 1591 | ERECTION OF SP-72(11KV/33 KV) FOUR POLE |
| 1592 | ERECTION OF BRACKET IN 11 KV LINE |
| 1593 | LAYING OF PANTHER CONDUCTOR IN HT LINE |
| 1594 | GUARDING OF 33 KV LINE |
| 1595 | FIXING OF 33 KV XLPE JOINTING KIT |
| 1596 | CARTAGE SP-21/23 POLE, 0-20 KM |
| 1597 | CARTAGE SP-55 POLE, 0-20 KM |
| 1598 | CARTAGE SP-72 POLE, 0-20 KM |
| 1599 | CARTAGE OF PATTY MATERIAL, 0-20 KM |
| 1600 | HEADLOAD CARTAGE SP-21/23POLE(0-1 KM) |
| 1601 | HEADLOAD CARTAGE SP-55 POLE(0-1 KM) |
| 1602 | HEADLOAD CARTAGE SP-72 POLE(0-1 KM) |
| 1603 | HEADLOAD CARTAGE OFMATERIAL(0-1 KM) |
| 1604 | ESCAVATION OF EARTH FOR STRUCT.ERECTION |
| 1605 | ROAD CUTTING AND REPAIRING |
| 1606 | Supply & LAYING OF HDPE PIPE |
| 1607 | FIXING OF 33 KV TENSION CLAMP WITHIPC |
| 1608 | FIXING OF 33 KV IPC FOR CC TO CCCOND. |
| 1609 | FIXING OF 33 KV IPC FOR CC TO BARECOND. |
| 1610 | FIXING OF 33 KV MID SPAN JOINTINGKIT |
| 1611 | FIXING OF 33 KV BIMETALIC LUG |
| 1612 | FIXING OF IPC WITH AL. BAIL FOREARTHING |
| 1613 | LAYING OF 33KV CABLE FOR POLERISING O/H |
| 1614 | FIXING OF 33KV CABLE TIES |
| 1615 | ERECTION OF TRI POLE FOR ST POLESP-72 |
| 1616 | LAYING, SAGGING OF COVERED COND FOR 33 KV |
| 1617 | COMPLETE TESTING WIRING |
| 1618 | MAKING LOOP OF 33 KV XLPE CABLE |
| 1619 | LAYING 33 KV CABLE IN HDPE PIPE HDD MACH. |
| 1620 | MANUAL DIGGING OF CABLE TRENCHUPTO 1 MT |
| 1621 | SUPPLY & LAYING OF HDPE PIPE INOPEN CUT |
| 1622 | PAINTING OF SINGLE POLE (SP-72) |
| 1623 | PAINTING OF DOUBLE POLE (SP-55) |
| 1624 | PAINTING OF DOUBLE POLE (SP-72) |
| 1625 | PAINTING OF TRI POLE (SP-72) |
| 1626 | PAINTING OF FOUR POLE (SP-72) |
| 1627 | ERECTION OF STUD STAY |
| 1628 | FIXING OF G.I PIPE 3 MTR LONG |
| 1629 | SHIFTING REALIGNMENT 11KV SP,DP/ LT LINE |
| 1630 | DELTA EARTHING WITH MS ROUNDELECTROD/GI |
| 1631 | FIXING OF 33 KV 630 AMP 3 WAY RMU |
| 1632 | LOOPING AND CHOPPING OF TREEBRANCHES |
| 1633 | Annual Maintenance Charges (AMC) and O&M of Project for 5 yearson per year basis. |
| 1634 | Control Room Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan), including dressing of sides and rammingof bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50m.All kinds of soil. |
| 1635 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also includingramming and watering of the earth in layers not exceeding 20cm in trenches, plinth, sides of foundation etc. complete |
| 1636 | Supplying and filling in plinth with Jamuna sand under floors, including watering, ramming, consolidating and dressing complete. |
| 1637 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level. 1:2:4 (1 Cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) |
| 1638 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level.1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40mm nominal size) |
| 1639 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate20 mm nominal size) |
| 1640 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level,excluding cost of centering, shuttering, finishing and reinforcement :1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate20 mm nominal size) |
| 1641 | Centering and shuttering including strutting, propping etc. and removal of form for :Foundations, footings, bases of columns, etc. for mass concrete |
| 1642 | Centering and shuttering including strutting, propping etc. and removal of form for: Suspended floors, roofs, landings, balconies and access platform |
| 1643 | Centering and shuttering including strutting, propping etc. and removal of form for:Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 1644 | Centering and shuttering including strutting, propping etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts |
| 1645 | Centering and shuttering including strutting, propping etc. and removal of form for:Edges of slabs and breaks in floors and walls.Under 20 cm wide. |
| 1646 | Centering and shuttering including strutting, propping etc. and removal of form for :Weather shade, Chajjas, corbels etc., including edges. |
| 1647 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete .Thermo-Mechanically Treated bars |
| 1648 | Smooth finishing of the exposed surface of R.C.C. work with 6 mm thick cement mortar 1:3 (1 Cement : 3 fine sand). |
| 1649 | Brick work with common burnt clay F.P.S. (non modular) bricks of classdesignation 7.5 in foundation and plinth in:Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 1650 | Brick work with common burnt clay F.P.S. (non modular) bricks of classdesignation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 1651 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level.Cement mortar 1:4 (1 cement :4 coarse sand) |
| 1652 | Providing and fixing Ist quality ceramic glazed wall tiles conforming toIS: 15622 (thickness to be specified by the manufacturer), of approvedmake, in all colours, shades except burgundy, bottle green, black ofany size as approved by Engineer-in-Charge, in skirting, risers of stepsand dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm,including pointing in white cement mixed with pigment of matching shadecomplete. |
| 1653 | Providing and fixing fly proof galvanized M.S. wire gauge to windows and clerestory windows using wire gauge with average width of aperture 1.4mm in both directions with wire of dia 0.63 mm all complete.With 12 mm mild steel U beading. |
| 1654 | Providing and fixing aluminium sliding door bolts, ISI marke anodised anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete :250x16 mm |
| 1655 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 150x10 mm |
| 1656 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete : 100mm |
| 1657 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing. |
| 1658 | Steel work welded in built up sections/ framed work, including cutting,hoisting, fixing in position and applying a priming coat of approved steelprimer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 1659 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete.40 mm thick with 20 mm nominal size stone aggregate . |
| 1660 | Providing and fixing glass strips in joints of terrazo/ cement concrete floors. 40 mm wide and 4 mm thick |
| 1661 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm(thickness to be specified by the manufacturer) of 1st quality conformingto IS : 15622 of approved make in colours such as White, Ivory, Grey,Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), including pointing the joints with white cement and matching pigment etc, complete. |
| 1662 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08%and conforming to IS : 15622, of approved make, in all colours and shades,laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm. |
| 1663 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion,(i) Single socketed pipes. 75 mm diameter |
| 1664 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion,(i) Single socketed pipes.110 mm diameter |
| 1665 | 12 mm cement plaster of mix :1:6 (1 cement: 6 coarse sand) |
| 1666 | 15 mm cement plaster on rough side of single or half brick wall of mix : 1:6 (1 cement: 6 coarse sand) |
| 1667 | cement plaster 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement. 12 mm cement plaster |
| 1668 | 6 mm cement plaster of mix:1:3 (1 cement : 3 fine sand) |
| 1669 | Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete. |
| 1670 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade :New work (two or more coats) over and including water tinna- ble priming coat with cement primer |
| 1671 | Finishing walls with textured exterior paint of required shade :New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/10 sqm. |
| 1672 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work |
| 1673 | Providing and fixing water closet squatting pan (Indian type W.C. pan ) with100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests. |
| 1674 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Flat back wash basin size 550x 400 mm with single 15 mm C.P. brass pillar tap. |
| 1675 | Providing and fixing P.V.C. waste pipe for sink or wash basin including PVC. waste fittings complete. Flexible pipe 32 mm dia |
| 1676 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete |
| 1677 | Providing and fixing PTMT towel ring trapezoidal shape 215 mm long, 200 mm wide with minimum distances of 37 mm from wall face with concealed fittings arrangement of approved quality and colour, weighing not less than 88 gms. |
| 1678 | Providing and fixing G.I. Pipes complete with G.I. fittings and clamps, i/c making good the walls etc. concealed pipe, including painting with anti corrosive bitumastic paint, cutting chases and making good the wall :15 mm dia nominal bore |
| 1679 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc.External work 20 mm dia nominal bore |
| 1680 | Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design :With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 |
| 1681 | Providing and fixing G.I. Union in G.I. pipe including cutting and threading the pipe and making long screws etc. complete (New work) :15 mm nominal bore |
| 1682 | Providing and placing on terrace (at all floor levels) polyethylene wate storage tank, ISI : 12701 marked, with cover and suitable lockin arrangement and making necessary holes for inlet, outlet and overflo pipes but without fittings and the base support for tank. |
| 1683 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 :15 mm nominal bore |
| 1684 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931. 18.52.1 15 mm nominal bore |
| 1685 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC/neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing and paneling to be paid for separately) :-For fixed portion---Powder coated aluminium |
| 1686 | For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 1687 | Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge.Pre-laminated particle board with decorative lamination on both sides. |
| 1688 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 4.0 mm thickness (weight not less than 10 kg/ sqm) |
| 1689 | Grading roof for water proofing treatment with Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 1690 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group B |
| 1691 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 1692 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 A switch |
| 1693 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 A socket outlet |
| 1694 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 1695 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required |
| 1696 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. |
| 1697 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 1698 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete withconnections, testing and commissioning etc. as required.Single pole |
| 1699 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 A |
| 1700 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan withBrush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2nos. canopies, shackle kit, safetyrope, copper winding, PowerFactor not less than 0.9, ServiceValue (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remainingaccessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 1701 | Supplying of Exhaust Fan 250 mm Sweep of Orient or equivalent make as approved by E.I. |
| 1702 | Supplying of 20 watt LED Tubelight Philps or equivalent make as approved by E.I. |
| 1703 | Land Development WorksEarth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan), including dressing of sides and rammingof bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50m.All kinds of soil. |
| 1704 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also includingramming and watering of the earth in layers not exceeding 20cm in trenches, plinth, sides of foundation etc. complete |
| 1705 | Supplying and filling in plinth with Jamuna sand under floors, including watering, ramming, consolidating and dressing complete. |
| 1706 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level. 1:2:4 (1 Cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) |
| 1707 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level.1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40mm nominal size) |
| 1708 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate20 mm nominal size) |
| 1709 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level,excluding cost of centering, shuttering, finishing and reinforcement :1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate20 mm nominal size) |
| 1710 | Centering and shuttering including strutting, propping etc. and removal of form for :Foundations, footings, bases of columns, etc. for mass concrete |
| 1711 | Centering and shuttering including strutting, propping etc. and removal of form for:Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 1712 | Centering and shuttering including strutting, propping etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts |
| 1713 | Providing, hoisting and fixing up to floor five level precast reinforced cementconcrete in small lintels not exceeding 1.5m clear span up to floor fivelevel, including the cost of required centering, shuttering but , excludingthe cost of reinforcement, with 1:1.5:3 (1 cement : 1.5 coarse sand(zoneIII) : 3 graded stone aggregate 20 mm nominal size). |
| 1714 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete .Thermo-Mechanically Treated bars |
| 1715 | Brick work with common burnt clay F.P.S. (non modular) bricks of classdesignation 7.5 in foundation and plinth in:Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 1716 | Brick work with common burnt clay F.P.S. (non modular) bricks of classdesignation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 1717 | Steel work welded in built up sections/ framed work, including cutting,hoisting, fixing in position and applying a priming coat of approved steelprimer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 1718 | Dry brick on edge flooring in required pattern with bricks of class designation 7.5 on a bed of 12 mm mud mortar, including filling joints with Jamuna sand, with common burnt clay non modular bricks. |
| 1719 | 12 mm cement plaster of mix :1:6 (1 cement: 6 coarse sand) |
| 1720 | 15 mm cement plaster on rough side of single or half brick wall of mix : 1:6 (1 cement: 6 coarse sand) |
| 1721 | 6 mm cement plaster of mix:1:3 (1 cement : 3 fine sand) |
| 1722 | Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete. |
| 1723 | Finishing walls with textured exterior paint of required shade :New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/10 sqm. |
| 1724 | Fencing with angle iron post placed at required distance embedded incement concrete blocks, every 15th post, last but one end post and corner post shall be strutted on both sides and end post on one side only andprovided with horizontal lines and two diagonals interwoven with horizontal wires, of barbed wire weighing 9.38 kg per 100 m (minimum), between the two posts fitted and fixed with G.I. staples, turn buckles etc. complete.(Cost of posts, struts, earth work and concrete work to be paid for separately). Payment to be made per metre cost of total length of barbed wire used. With G.I. barbed wire. |
| 1725 | Providing and laying 60mm thick faciory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with line sand etc. all complete as per the direction of Engineer-in-charge. |
| 1726 | Boring with 100 mm diameter casing pipe for hand pump / tubewell, in all soils except ordinary hard rocks requiring blasting, including removing the casing pipe after the hand pump / tube well is lowered and tested :Up to 6 metres depth Beyond 12 m and up to 18 m depth |
| 1727 | Supplying, assembling, lowering and fixing in vertical position in bore well, ERW (Electric Resistance Welded) FE 410 plain slotted (having slot of size 1.6/3.2 mm) mild steel threaded and socketed/ plain bevel ended pipe (type A) of required dia, conforming to IS: 8110, of reputed and approved make, having wall thickness not less than 5.40 mm, including painted with outside surface with two coats ofanticorrosive bitumestic paint of approved brand and manufacture, including hire & labour charges, fittings & accessories, all complete, for all depths, as per direction of Engineer -in-charge. |
| 1728 | Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of usable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by “V” notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, i/c disinfection of tubewell, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer-in-charge. |
| 1729 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 6.0 sq. mm + 1 X 6.0 sq. mm earth wire |
| 1730 | Supply of 33/11KV SUBSTATION8 m. LONG STP 410 SP-10 (BPHD GAL.) |
| 1731 | 11 MTR. LONGSTP 410 SP-55(BPHD GAL.) |
| 1732 | MS ROUND 32 mm |
| 1733 | 11 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 1734 | 33 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 1735 | DISC FIT. B&S TYPE FOR PANTHER 90 KN |
| 1736 | DISC FIT. B&S TYPE WEASEL/RABBIT 45 KN |
| 1737 | 9 KV 10 KA Polymeric Lightning Arrestor |
| 1738 | EARTHING ROD MS 20X2500mm |
| 1739 | GI WIRE 5mm/6 SWG |
| 1740 | STAY SET GI 16X1800mm |
| 1741 | STAY WIRE GI 7/3.15mm 7/10SWG |
| 1742 | ACSR DOG |
| 1743 | ACSR PANTHER |
| 1744 | CABLE AL 3X300 SQ. mm XLPE 11 kV |
| 1745 | CABLE AL 3X400 SQ. mm XLPE 11 kV |
| 1746 | CABLE AL 1X630 SQ. mm XLPE 11 kV |
| 1747 | CABLE AL 3X70 SQ. mm XLPE 33kV |
| 1748 | J/KIT FOR 3X300mm* 11kV XLPE CABLE(O/D) |
| 1749 | J/KIT FOR 3X400mm° 11kV XLPE CABLE (O/D) |
| 1750 | CONTROL CABLE 10X2.5 SQ. mm. |
| 1751 | CONTROL CABLE 2X2.5 SQ. mm. |
| 1752 | CONTROL CABLE 4X2.5 SQ. mm. |
| 1753 | CONTROL CABLE 6X2.5 SQ. mm. |
| 1754 | LT PVC CABLE 2X6 SQ.mm (ARMORED) |
| 1755 | LT XLPE CABLE 3.5.X 70 SQ. mm. |
| 1756 | LT PVC CABLE 4X10 SQ.mm |
| 1757 | 33 KV H.S. Cable J/K 3x70 sq. mm (O/D) |
| 1758 | 110 V BATTERY SET(300 AH) |
| 1759 | 110V BATTERY CHARGER(300 AH) |
| 1760 | JUNCTION BOX FOR 33kV PT |
| 1761 | 33kV PT of RATIO 33 kV/110V OUTDOOR |
| 1762 | 33 kV LIGHTNING ARRESTER |
| 1763 | PANTHER TO PANTHER CTYPE WEDGE CONNECTOR |
| 1764 | 33 kV FUSE SET |
| 1765 | 33/0.433 KV, 63 KVA Station Transformer |
| 1766 | MS STRUCTURE (ANGLE ,CHANNEL ETC.) |
| 1767 | GI ITEM (Rail,Joist,ChanneI,Angle) |
| 1768 | Cable Holding clamp with N&B |
| 1769 | Holding Clamp FPR GI Pipe 8/10\\"& MS Ch. |
| 1770 | PG CLAMP ALU ALLOY PANTHER TO DOG |
| 1771 | Stay Clamp for SP-55 With Nut & Bolt |
| 1772 | 33KV ISOLATOR CONN.CLAMP FOR PANTHER,N&B |
| 1773 | 33 KV ISOLATOR CLAMP FOR ACSR DOG |
| 1774 | PERFORATED TRAY 400MM FOR CABLE TRENCH |
| 1775 | PERFORATED TRAY 200MM FOR CABLE TRENCH |
| 1776 | PERFORATED TRAY 100MM FOR CABLE TRENCH |
| 1777 | FLEXIBLE COOPER CONNECTOR SOXSOMM |
| 1778 | DANGER BOARD |
| 1779 | GI Pipe 4\\"' Dia |
| 1780 | 250 W hpsv/led lamp with contrl gear |
| 1781 | Insulated Electrical Piller Taparia |
| 1782 | 11 KV Fuse Set |
| 1783 | KM-21 G.I. Pipe 6\\" dia 3 meter long |
| 1784 | Conne.Suitable for Panther for LA |
| 1785 | Connector of Power T/F HV Side |
| 1786 | Connector of Power T/F LV Side |
| 1787 | GI STRIP 65MMX6MM |
| 1788 | “HT' WARNING TAPE |
| 1789 | 11KV,630Amp off load Isolator |
| 1790 | Thimble junction box for cable support |
| 1791 | 33KV C&R PANEL I/C-D |
| 1792 | 33KV C&R PANEL O/G-D |
| 1793 | 33KV C&R PANEL BUS COUPLER-D |
| 1794 | 11KV C&R PANEL I/C-D |
| 1795 | 11KV C&R PANEL O/G-D |
| 1796 | 11KV C&R PANEL BUS COUPLER-D |
| 1797 | PP clamp with N&B (GI) |
| 1798 | G.I.Strip 35x4mm |
| 1799 | 11 KV HS cable END T/K 1x630 mm* O/D |
| 1800 | Cable Jointing Kit 1x630 Outdoor |
| 1801 | 33 KV XLPE Cable AL 1x630 sq. mm -D |
| 1802 | Iron Clad 30 Amp Switch |
| 1803 | Connector Suit for CT/PT for Panther/Dog |
| 1804 | 33 KV Isolator Vertical Type |
| 1805 | 11kv 3P(400A)3pin vert. mount GO AB TPMO |
| 1806 | Indoor type auto power factor controller |
| 1807 | 12.65kV, 3600kVAr, Capacitor bank |
| 1808 | 12KV C&R Panel with SCADA(Capacitor) |
| 1809 | 36KV 1250A Gang ope PMA VCB(I/C) |
| 1810 | 36KV 1250A Gang ope PMA VCB(O/G) |
| 1811 | 12KV 1250A Gang ope PMA VCB(I/C) |
| 1812 | 12KV 1250A Gang ope PMA VCB(O/G) |
| 1813 | 12KV 1250A Gang ope PMA VCB(Capacitor) |
| 1814 | 12KV 1250A Gang ope PMA VCB(B/C) |
| 1815 | 36KV 1250A Gang ope PMA VCB(B/C) |
| 1816 | 33kv Bus isolator manual&motor,SCADA COM |
| 1817 | 33kv line isolator manual&motor,SCADA co |
| 1818 | 11kv isolator manual&motor,SCADA comp. |
| 1819 | Wire Mesh Fencing |
| 1820 | 110V DC DISTRIBUTION BOARD-D |
| 1821 | Name Plate of Equip. TG,LI,BI,CT,CB ect. |
| 1822 | GI STRIP 50X6 MM |
| 1823 | SUNDRISE ITEM LUG GLADE ETC |
| 1824 | Alluminium Lug |
| 1825 | Stone Pad 300x300x75mm |
| 1826 | Connector Suitable. Panther for VCB |
| 1827 | Dustbin 20 Litre Capacity (Colour Green) |
| 1828 | RUBBER MAT(INSULATED )1MX1MX3MM |
| 1829 | Fire Extingushier |
| 1830 | Torch 3 Cell |
| 1831 | 33 KV Hand Gloves |
| 1832 | Earth Chain |
| 1833 | First aid box |
| 1834 | SHOCK TREATMENT CHART |
| 1835 | SHUT DOWN/ BREAK DOWN BOARD |
| 1836 | WALL CLOCK |
| 1837 | D-SPANNER SET |
| 1838 | PIPE WRENCH 12\\" |
| 1839 | 2.5 KV MEGGAR DIGITAL |
| 1840 | EARTH MEGGAR DIGITAL |
| 1841 | INSTRUCTION BOARD |
| 1842 | MAXIMUM & MINIMUM DISPLAY BOARD |
| 1843 | SUB STATION NAMED BOARD |
| 1844 | Portable Foam Type Fire Extinguisher SLT |
| 1845 | Single Line Diagram Board |
| 1846 | Door Mat |
| 1847 | Name plate of feeder |
| 1848 | Name plate of station \iI |
| 1849 | 11KV Danger Board with Clamp |
| 1850 | 33 KV Danger Board with Clamp |
| 1851 | Steel Almirah |
| 1852 | Office Table size (4x2.5) |
| 1853 | Fire Bucket Stand with Buckets |
| 1854 | Steel Cabinet |
| 1855 | Steel office Table |
| 1856 | Steel office chair Godrej |
| 1857 | Meggar 5 KV Digital |
| 1858 | Fire Bucket stand of MS angle |
| 1859 | Supply of 33kV LINE8 m. LONG STP 410 SP-10 (BPHD GAL.) |
| 1860 | 8.5 MRT. LONG STP 410 SP-23(BPHDGAL.) |
| 1861 | 9 MRT. LONG STP 410 SP-33(BPHD GAL.) |
| 1862 | 11 MTR. LONGSTP 410 SP-55(BPHDGAL.) |
| 1863 | STP 13.0 M-IS 410 SP-72 (BPHD GAL.) |
| 1864 | MS ANGLE 50X50X6 mm |
| 1865 | MS ANGLE 65X65X6 mm |
| 1866 | MS ANGLE 75X75X8 mm |
| 1867 | MS CHANNEL 100X50 mm |
| 1868 | MS CHANNEL 125X65 mm |
| 1869 | MS ROUND 32 mm |
| 1870 | Holding Clamp for ST Pole SP-23 with N&B |
| 1871 | 11 kV POLYMER DISC INSULATOR(B&S) TYPE |
| 1872 | 33 kV POLYMER DISC INSULATOR(B&S) TYPE |
| 1873 | 11 kV POLYMER PIN INSULATOR WITH PIN |
| 1874 | 33kV 10KN POLYMER PIN INSULATORWITH PIN |
| 1875 | DISC FIT. B&S TYPE DOG/RACOON 70KN |
| 1876 | DISC FIT B&S TYPE PANTHER 70KN(TENSION) |
| 1877 | DISC FIT. B&S TYPE FOR PANTHER 90KN |
| 1878 | DISC FIT. B&S TYPE WEASEL/RABBIT45 KN |
| 1879 | LT Shackle Insulator |
| 1880 | X ARM ANGLE 65X65X6 mm V TYPE 11kV |
| 1881 | X ARM CHANNEL 100X50 mm V TYPE 33kV |
| 1882 | Earth wire GI 7/1.6 mm 16 SWG |
| 1883 | EARTHING ROD MS 20X2500mm |
| 1884 | GI WIRE 4mm/8mm SWG |
| 1885 | GI WIRE 5mm/6 SWG |
| 1886 | STAY SET GI 20X1800mm |
| 1887 | STAY WIRE GI 7/4.0 mm 7/8 SWG |
| 1888 | ACSR RABBIT |
| 1889 | ACSR DOG |
| 1890 | ACSR PANTHER |
| 1891 | CABLE AL 3X400 SQ. mm XLPE 33 kV |
| 1892 | J/KIT FOR 3X400mm°33kV XLPE CABLE (O/D) |
| 1893 | CONTROL CABLE 10X2.5 SQ. mm. |
| 1894 | CONTROL CABLE 2X2.5 SQ. mm. |
| 1895 | CONTROL CABLE 4X2.5 SQ. mm. |
| 1896 | LT PVC CABLE 2X6 SQ.mm (UN-ARMORED) |
| 1897 | LT PVC CABLE 4X10 SQ.mm |
| 1898 | LT XLPE AB CABLE 3X120+1X95+1 X16 |
| 1899 | 33 KV Straight Through J/K 3x400 |
| 1900 | 33 kV VCB, 1250A, 24V |
| 1901 | CONTROL PANEL FDR 33 kV SINGLECKT |
| 1902 | JUNCTION BOX FOR 33kV CT |
| 1903 | 33 kV LIGHTNING ARRESTER |
| 1904 | PANTHER TO PANTHER CTYPE WEDGECONNECTOR |
| 1905 | 33 kV LINE ISOLATOR 400/800A |
| 1906 | 33 kV BUS ISOLATOR 400/800A |
| 1907 | MS NUT & BOLT OFF SIZE |
| 1908 | MS PLATE 225X225X8MM |
| 1909 | Bolt & Nut 150x12 mm |
| 1910 | Bolt & Nuts 50x16 mm |
| 1911 | Eye Bolt 190x16 mm With Nut & Bolt |
| 1912 | Bracing Clamp SP-72 |
| 1913 | Bracing Clamp for SP-55 with N/B |
| 1914 | LT Shackle Insulator Clamp |
| 1915 | E- CLAMP |
| 1916 | Universal I Hook |
| 1917 | F Clamp |
| 1918 | EARTH WIRE CLAMP FOR SP-55 WITHN/B |
| 1919 | PP & CLAMP WITH N&B ST POLE SP-55 |
| 1920 | STAY CLAMP FOR SP-23 WITH NUT &BOLT |
| 1921 | Stay Clamp for SP-55 With Nut & Bolt |
| 1922 | STAY CLAMP FOR SP-33 WITH NUT &BOLT |
| 1923 | EARTH WIRE CLAMP FOR SP-23 WITHN/B |
| 1924 | 33KV ISOLATOR CONN.CLAMP FORPANTHER,N&B |
| 1925 | PP & CLAMP WITH N&B ST POLE SP-33 |
| 1926 | PP & CLAMP WITH N&B ST POLE SP-72 |
| 1927 | STAY CLAMP FOR SP-72 WITH N/B |
| 1928 | PG Clamp For Dog Conductor |
| 1929 | SUSPENSION CLAMP |
| 1930 | EARTH WIRE CLAMP FOR SP-33 WITHN/B |
| 1931 | PP & CLAMP WITH N&B ST POLE SP-23 |
| 1932 | Stay Clamp D/E for SP33 With N&B |
| 1933 | NUMBER PLATE WITH CLAMP |
| 1934 | PERFORATED TRAY 400MM FORCABLE TRENCH |
| 1935 | PERFORATED TRAY 100MM FORCABLE TRENCH |
| 1936 | FLEXIBLE COOPER CONNECTORSOXSOMM |
| 1937 | Danger Board With Clamp N&B |
| 1938 | BRACING CLAMP BOTTOM FOR SP-23WITH N/B |
| 1939 | TOP BRACING CLAMP BOTTOM WITHN&B SP-33 |
| 1940 | MS Flat50x6mm 0.3x10x2x2x2 for CT Struc. |
| 1941 | 250 W hpsv/led lamp with contrl gear |
| 1942 | Bolt & Nuts off Size |
| 1943 | GI Pipe Dia 150 mm |
| 1944 | Cable Holding Clamp with N&B of Size |
| 1945 | Perforated Tray 300mm for Cable trench |
| 1946 | KM-21 G.I. Pipe 6\\" dia 3 meter long |
| 1947 | Conne.Suitable for Panther for LA |
| 1948 | STAY CLAMP FOR SP-55 WITH NUT & BOLT |
| 1949 | Earth Wire Clamp |
| 1950 | 33 KV Mid Span Jointing Kit |
| 1951 | 33KV Biometric crimping Lug |
| 1952 | 33 KV IPC with Al. Ball for Earthing |
| 1953 | 33 KV Tension clamp with Bail & IPC |
| 1954 | 33 KV IPC for covered to covered conduct |
| 1955 | 33 KV IPC for covered to Bare conductor |
| 1956 | 33 KV Cable Ties for Insulator |
| 1957 | Concrete route marker for HT cable |
| 1958 | PP & CLAMP WITH NUT & BOLT FORGUARDING |
| 1959 | PP CLAMP FOR SPECIAL TYPEBRACKET |
| 1960 | 33 KV Disc insulator polymer, 70KN B&S |
| 1961 | 33KV AAAC COVERED COND. AL-59,241SQ.MM. |
| 1962 | Iron Clad 30 Amp Switch |
| 1963 | Connector Suit for CT/PT for Panther/Dog |
| 1964 | 33 kV CT OUTDOOR CTR 400/200/1-1A |
| 1965 | Wire Mesh Fencing |
| 1966 | ALUMINIUM BINDING WIRE |
| 1967 | M.S.PLATE 400X400X8 mm |
| 1968 | Name Plate of Equip. TG,Ll,BI,CT,CB ect. |
| 1969 | MS Bar 12mm Dia for Steel Reinforcement |
| 1970 | G.I EARTH STRIP 65X6MM |
| 1971 | SUNDRISE ITEM LUG GLADE ETC |
| 1972 | BARBED WIRE |
| 1973 | GI Strip 40x6 mm |
| 1974 | Stone Pad 300x300x75mm |
| 1975 | Connector Suitable. Panther for VCB |
| 1976 | Single Line Diagram Board |
| 1977 | Erection of 33/11kV SUBSTATION7.2.1 (DSR CODE 2014) |
| 1978 | NSI_EARTH FILLING |
| 1979 | CEMENT CONCRETING WORK IN RATIO 1:4:8 |
| 1980 | CEMENT CONCRETING WORK IN RATIO 1:2:4 |
| 1981 | BRICK WORK IN 1:4 RATIO |
| 1982 | CEMENT PLASTER WORK |
| 1983 | FENCING OF YARD |
| 1984 | RCC 1:1.5:3 |
| 1985 | MAKING CABLE TRENCH |
| 1986 | BRICK WORK 1:6 SUB STRUCTURE |
| 1987 | BRICK WORK 1:6 SUPER STRUCTURE |
| 1988 | CC WORK 1:1.5:2 |
| 1989 | SUPPLY&ERRECT GRAVEL PITCHING 1/2\\"- 3/4\\" |
| 1990 | ELECTRICAL INSPECTION FEE |
| 1991 | SPECIAL EARTHING |
| 1992 | FABRICATION OF STEEL |
| 1993 | FIXING OF GI PIPE |
| 1994 | ERECTION OF SINGLE SP-10 POLE |
| 1995 | ERECTION OF SP-55 DOUBLE POLE |
| 1996 | PAINTING OF SP-10 POLE |
| 1997 | PAINTING OF SP-55 POLE |
| 1998 | LAYING OF LT PVC CABLES(» 150 SQMM) |
| 1999 | LAYING OF U/G 11 KV CABLE IN TRENCH |
| 2000 | LAYING OF U/G 33 KV CABLE IN TRENCH |
| 2001 | FIXING OF LIGHTNING ARRESTOR |
| 2002 | FIXING OF 11 KV XLPE JOINTING KIT |
| 2003 | FIXING OF 33 KV XLPE JOINTING KIT |
| 2004 | CARTAGE OF PETTY MATERIAL,0-20 KM |
| 2005 | CARTAGE 11 KV PANELS, 0-20 KM |
| 2006 | CARTAGE OF PANELS, 0-20 KM |
| 2007 | CARTAGE 5/8 MVA POWER T/ F(0-20KM) |
| 2008 | MANUAL SHIFTING OF CONTROL PANEL |
| 2009 | ERECTION OF POWER T/F(8/5 MVA) |
| 2010 | ESCAVATION OF EARTH FOR STRUCT. ERECTION |
| 2011 | GROUTING OF STRUCTURE IN CC 1:3:6 |
| 2012 | FIXING OF 33 KV ISOLATOR VERTICAL TYPE |
| 2013 | LAYING OF CONTROL CABLE |
| 2014 | LAYING OF EARTH MAT |
| 2015 | EARTHING OF STRUCTURE USING GI STRIP |
| 2016 | COMM.OF 33/11KV VCB PANEL |
| 2017 | COMPLETE TESTING WIRING |
| 2018 | ERECTION & LAYING OF LT XLPE CABLE 2X6 |
| 2019 | INST. & FIXING OF CHEMICAL EARTHING |
| 2020 | INSTALLATION OF LINE/ BUS ISOLATOR |
| 2021 | INSTALLATION OF DCDB INCLUDING TESTING |
| 2022 | INSTALLATION OF ACDB INCLUDING TESTING |
| 2023 | ERECTION OF 33/0.433KV S/S TRANSFORMER |
| 2024 | ERECTION OF FLEXIBLE CU. CONN.500X50 MM |
| 2025 | ERECTION OF STAY POST |
| 2026 | ERRECTION OF 33KV PT |
| 2027 | ERREC. 12.65kV 3600kVAr, CAPACITOR BANK |
| 2028 | ERREC. 11KV, 630 AMP, OFF LOAD ISOLATOR |
| 2029 | ERECTION OF 110V BATTERY SET(300AH) |
| 2030 | ERECTION OF 110V BATTERY CHARGER(300AH) |
| 2031 | FIXING OF 11 KV FUSE SET |
| 2032 | FIXING OF 33 KV FUSE SET |
| 2033 | LAYING OF 4X10SQ MM LT PVC CABLE |
| 2034 | ERECTION OF EARTHING ELECTRODE&STRIP50X6 |
| 2035 | FIXING OF SODIUM/LED LIGHT AT YARD |
| 2036 | INSTALLATION OF FIRE EXTINGUISHERS |
| 2037 | ERECTION OF NAME PLATES |
| 2038 | ERECTION OF T&P ITEMS |
| 2039 | ERECTION OF MISC. GI STRUCTURES |
| 2040 | SHIFTING OF T/F B WORK |
| 2041 | Erection of 33kV LINE7.2.1 (DSR CODE 2014) |
| 2042 | NSI_EARTH FILLING |
| 2043 | NSI_SPECIAL EARTHING |
| 2044 | NSI_SUPPLY OF GRAVEL |
| 2045 | CEMENT CONCRETING WORK IN RATIO1:4:8 |
| 2046 | BRICK WORK IN 1:4 RATIO |
| 2047 | CEMENT PLASTER WORK |
| 2048 | ERECTION OF TERMINAL GANTRY |
| 2049 | MAKING CABLE TRENCH |
| 2050 | BRICK WORK 1:6 SUB STRUCTURE |
| 2051 | ELECTRICAL INSPECTION FEE |
| 2052 | ERECTION OF EARTHING ROAD |
| 2053 | FABRICATION OF STEEL |
| 2054 | FIXING OF GI PIPE |
| 2055 | FIXING OF RCC CABLE ROUTE MARKER |
| 2056 | ERECTION OF 33 KV STAY SET |
| 2057 | ERECTION OF SINGLE SP-10 POLE |
| 2058 | ERECTION OF SINGLE SP-33 POLE |
| 2059 | ERECTION OF SINGLE SP-55 POLE |
| 2060 | ERECTION OF SINGLE SP-72 POLE |
| 2061 | ERECTION OF SP-33 DOUBLE POLE |
| 2062 | ERECTION OF SP-55 DOUBLE POLE |
| 2063 | ERECTION OF SP-72 DOUBLE POLE |
| 2064 | ERECTION OF SP-33(11KV/33 KV) FOUR POLE |
| 2065 | ERECTION OF SP-55(11KV/33 KV) FOUR POLE |
| 2066 | ERECTION OF SP-72(11KV/33 KV) FOUR POLE |
| 2067 | PAINTING OF SP-10 POLE |
| 2068 | PAINTING OF SP-33 POLE |
| 2069 | PAINTING OF TG |
| 2070 | LAYING OF U/G 33 KV CABLE INTRENCH |
| 2071 | ERECTION OF BRACKET IN 11 KV LINE |
| 2072 | GUARDING OF 33 KV LINE |
| 2073 | FIXING OF 33 KV XLPE JOINTING KIT |
| 2074 | CARTAGE SP-21/23 POLE, 21-50 KM |
| 2075 | CARTAGE SP-33 POLE, 21-50 KM |
| 2076 | CARTAGE SP-55 POLE, 21-50 KM |
| 2077 | CARTAGE SP-72 POLE, 21-50 KM |
| 2078 | CARTAGE OF PETTY MATERIAL,101-150KM |
| 2079 | CARTAGE OF PANELS, 0-20 KM |
| 2080 | HEADLOAD CARTAGE SP-21/23POLE(0-1 KM) |
| 2081 | HEADLOAD CARTAGE SP-33 POLE(0-1 KM) |
| 2082 | HEADLOAD CARTAGE SP-55 POLE(0-1 KM) |
| 2083 | HEADLOAD CARTAGE SP-72 POLE(0-1 KM) |
| 2084 | HEADLOAD CARTAGE OFMATERIAL(0-1 KM) |
| 2085 | MANUAL SHIFTING OF CONTROL PANEL |
| 2086 | ESCAVATION OF EARTH FOR STRUCT.ERECTION |
| 2087 | GROUTING OF STRUCTURE IN CC 1:3:6 |
| 2088 | ERECTION CHARGES OF STRUCTURE |
| 2089 | INSTALLATION OF 33 KV CT WITH ALLCONN. |
| 2090 | LAYING OF LTXLPE ABC 3X120+1X95+1X16 SQ. |
| 2091 | ROAD CUTTING AND REPAIRING |
| 2092 | CARTAGE OF PETTY MATERIAL,21-50KM |
| 2093 | FIXING OF 33 KV TENSION CLAMP WITHIPC |
| 2094 | FIXING OF 33 KV IPC FOR CC TO CCCOND. |
| 2095 | FIXING OF 33 KV IPC FOR CC TO BARECOND. |
| 2096 | FIXING OF 33 KV MID SPAN JOINTINGKIT |
| 2097 | FIXING OF 33 KV BIMETALIC LUG |
| 2098 | FIXING OF IPC WITH AL. BAIL FOREARTHING |
| 2099 | ERECTION OF 33 KV VCB |
| 2100 | LAYING OF 33KV CABLE FOR POLERISING O/H |
| 2101 | ERECTION & LAYING LT ARM CABLE4X10 |
| 2102 | FIXING OF 33KV CABLE TIES |
| 2103 | ERECTION OF TRI POLE FOR ST POLESP-55 |
| 2104 | ERECTION OF TRI POLE FOR ST POLESP-72 |
| 2105 | LAYING SPREADING,STRINGING AAAC CONDUCT. |
| 2106 | INSTALLATION / FIXING OF 33 KVISOLATOR |
| 2107 | LAYING OF CONTROL CABLE |
| 2108 | COMM.OF 33/11KV VCB PANEL |
| 2109 | ERECTION OF LINE ISOLATORSTRUCTURE |
| 2110 | COMPLETE TESTING WIRING |
| 2111 | MAKING LOOP OF 33 KV XLPE CABLE |
| 2112 | PAINTING OF 33KV VCB PANELS. |
| 2113 | MANUAL DIGGING OF CABLE TRENCHUPTO 1 MT |
| 2114 | SUPPLY & LAYING OF HDPE PIPE INOPEN CUT |
| 2115 | ERACTION PROVIDING & FIXING OFWIRE MESH |
| 2116 | ERECTION OF BUS ISOLATORSTRUCTURE |
| 2117 | PAINTING OF SINGLE POLE (SP-55) |
| 2118 | PAINTING OF SINGLE POLE (SP-72) |
| 2119 | PAINTING OF DOUBLE POLE (SP-33) |
| 2120 | PAINTING OF DOUBLE POLE (SP-55) |
| 2121 | PAINTING OF DOUBLE POLE (SP-72) |
| 2122 | PAINTING OF TRI POLE (SP-55) |
| 2123 | PAINTING OF TRI POLE (SP-72) |
| 2124 | PAINTING OF FOUR POLE (SP-33) |
| 2125 | PAINTING OF FOUR POLE (SP-55) |
| 2126 | PAINTING OF FOUR POLE (SP-72) |
| 2127 | INSTALLATION OF LINE/ BUS ISOLATOR |
| 2128 | ERECTION OF BUS GANTRY |
| 2129 | ERECTION OF BUS BAR |
| 2130 | ERECTION OF LIGHTNINGEQUIPMENTS |
| 2131 | ERECTION OF STAY POST |
| 2132 | FABRICATION OF R.S. JOIST 175X85SQ.MM. |
| 2133 | ERECTION OF 65X6 MM GI STRIP |
| 2134 | FIXING OF G.I PIPE 3 MTR LONG |
| 2135 | ERECTION OF 40X6MM GI STRIP |
| 2136 | SHIFTING REALIGNMENT 11KV SP,DP/ LT LINE |
| 2137 | DELTA EARTHING WITH MS ROUNDELECTROD/GI |
| 2138 | STRAIGHTENING AND LAYING OFEARTH MAT |
| 2139 | STRINING OF 3 PHASE ACSR DOG CONDUCTOR |
| 2140 | LOOPING AND CHOPPING OF TREEBRANCHES |
| 2141 | PAINTING OF ISOLATOR |
| 2142 | PAINTING OF BUS GANTRY |
| 2143 | ERECTION OF NAME PLATES |
| 2144 | PAINTING OF WIREMESH FENCING |
| 2145 | PAINTING OF ISOLATOR/LA/CT/ STRUCTURE |
| 2146 | PAINTING OF STAY POST |
| 2147 | Annual Maintenance Charges (AMC) and O&M of Project for 5 yearson per year basis. |
| 2148 | Control RoomEarth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 2149 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 and for all lift. |
| 2150 | Treatment of soil under existing floors using chemicalemulsion @one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement: 2 Coarse sand) to match the existing floor: 2.35.3.1 With Chlorpyriphos/Lindane E.C. 20% with 1 % concentration |
| 2151 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1 :2:4 (1 cement : 2 coarse sand (zone-Ill) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 2152 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) |
| 2153 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :1 :1.5:3 (1 cement : 1.5 coarse sand (zone-Ill) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 2154 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size) |
| 2155 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chanas, lintels, bands,plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1: 1.5:3 (1 cement : 1.5 coarse sand(zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). |
| 2156 | Centering and shuttering including strutting, propping etc. and removal of form for Foundations, footings, bases of columns, etc. for mass concrete |
| 2157 | Centering and shuttering including strutting, propping etc. and removal of form for : Suspended floors, roofs, landings, balconies and access platform |
| 2158 | Centering and shuttering including strutting, propping etc. and removal of form for Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 2159 | Centering and shuttering including strutting, propping etc. and removal of form for Columns, Pillars, Piers, Abutments, Posts and Struts. |
| 2160 | Providing, hoisting and fixing up to floor five level precast reinforcedcement concrete in small lintels not exceeding 1.5m clear span up tofloor five level, including the cost of required centering, shuttering but ,excluding the cost of reinforcement with 1 :1.5:3 (1 cement : 1.5 coarsesand (zone-Ill) derived from natural sources : 3 graded stone aggregate20 mm nominal size derived from natural sources). |
| 2161 | Centering and shuttering including strutting, propping etc. and removal of form for : Edges of slabs and breaks in floors and walls Under 20 cm wide |
| 2162 | Centering and shuttering including strutting, propping etc. and removal of form for : Weather shade, Chajjas, corbels etc., including edges. |
| 2163 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.Thermo-Mechanically Treated bars. |
| 2164 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 2165 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in:Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 2166 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 2167 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundations and plinth in:cement mortar 1 :4 ( 1 cement : 4 coarse sand) |
| 2168 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level.Cement mortar 1 :4 (1 cement :4 coarse sand) |
| 2169 | Providing and fixing 18mm thick gang saw cut mirror polished premoulded and prepolished) machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edge to give high gloss finish etc. complete at all levels. Granite stone slab of colour black, Cherry/Ruby red. upto 0.50 sqm |
| 2170 | Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge.Granite work |
| 2171 | Providing and fixing 1st quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1 :3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. |
| 2172 | Designing, fabricating, testing, installing and fixing in position Curtain Wall with Aluminium Composite Panel Cladding, with open grooves for linear as well as curvilinear portions of the building , for all heights and all levels etc. including: (a) Structural analysis & design and preparation of shop drawings for pressure equalisation or rain screen principle as required, proper drainage of water to make it watertight including checking of all the structural andfunctional design. (b) Providing, fabricating and supplying and fixing panels of aluminium composite panel cladding in pan shape in metalic colour of approved shades made out of 4 mm thick aluminium composite panel material consisting of 3 mm thick FR grade mineral core sandwiched between two Aluminium sheets (each 0.5 mm thick). The aluminium composite panel cladding sheet shall be coil coated, with Kynar 500 based PVDF I Lumiflon based fluoropolymer resin coating of approved colour and shade on face # 1 and polymer (Service) coating on face # 2 as specified using stainless steel screws, nuts, bolts, washers, cleats, weather silicone sealant, backer rods etc.(c) The fastening brackets of Aluminium alloy 6005 T5 I MS with Hot Dip Galvanised with serrations and serrated washers to arrest the windload movement, fasteners, SS 316 Pins and anchor bolts of approved make in SS 316, Nylon separators to prevent bi-metallic contacts all complete required to perfonn as per specification and drawing The itemincludes cost of all material & labour component, the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working curtain wall with aluminium composite panel cladding, cleaning and protection of the curtain wall with aluminium composite panel cladding till the handingover of the building for occupation. Base frame work for ACP cladding is payable under the relevant aluminium items. The Contractor shall provide curtain wall with aluminium composite panel cladding, havingall the perfonnance characteristics all complete , as per the Architectural drawings, as per item description, as specified, as per the approved shopdrawings and as directed by the Engineer-in-Charge. However, for the purpose of payment, only the actual area on the external face of the curtain wall with Aluminum Composite Panel Cladding (including width of groove) shall be measured in sqm. up to two decimal places. |
| 2173 | Providing and fixing ISi marked 85x42 mm oxidised M.S. pull bolt lock conforming to IS : 7534 with necessary screws bolts, nut and washers etc. complete (Copper oxidised as per IS 1378). |
| 2174 | Providing and fixing ISI marked aluminium butt hinges anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete:125x63x4 mmmm |
| 2175 | Providing and fixing aluminium sliding door bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc. complete : 300x16 mm |
| 2176 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 250x10 mm |
| 2177 | Providing and fixing aluminium handles ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete :125 mm |
| 2178 | Providing and fixing aluminium hanging floor door stopper ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade with necessary screws etc. complete. Twin rubber stopper |
| 2179 | Providing and fixing aluminium casement stays ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade with necessary screws etc. complete. |
| 2180 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.. |
| 2181 | Providing and fixing in position collapsible steel shutters with vertical channels 20x10x2 mm and braced with flat iron diagonals 20x5 mm size, with top and bottom rail of T-iron 40x40x6 mm, with 40 mm dia steel pulleys, complete with bolts, nuts, locking arrangement, stoppers, handles, including applying a priming coat of approved steel primer. |
| 2182 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applyinga priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished welded type tubes |
| 2183 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the comers. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing. |
| 2184 | Steel work welded in built up sections/ framed work including cutting,hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. |
| 2185 | Providing & fixing fly proof wire gauze to windows, clerestory windows & doors with M.S. Flat 15x3 mm and nuts & bolts complete.Stainless steel (grade 304) wire gauze of 0.5 mm dia wire and 1.4 mm aperture on both sides |
| 2186 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement including cement slurry, but excluding the cost of nosing of steps etc. complete.40mm thick with 20mm nominal size stone aggregate. |
| 2187 | Providing and fixing glass strips in joints of terrazo/ cement concrete floors.40 mm wide and 4 mm thick |
| 2188 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1 :4 (1 Cement: 4 Coarse sand), Jointing with grey cement slurry @ 3.3 kg/sqm including pointing the joints with white cement and matching pigment etc., complete. |
| 2189 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600x600 mm |
| 2190 | Providing and laying pressed clay tiles (as per approved pattern 20 mm nominal thickness of approved size) on roofs jointed with cement mortar1 :4 (1 cement : 4 coarse sand) mixed with 2% integral water proofing compound, laid over a bed of 20 mm thick cement mortar 1 :4 (1 cement : 4 coarse sand) and finished neat complete. |
| 2191 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes.110 mm diameter |
| 2192 | Providing and fixing precoated galvanised iron profile sheets {size, shape and pitch of corrugation as approved by Engineer-in-Charge) of total coated thickness 0.50 mm (base metal of minimum 0.45 mm thickness with total coating thickness of 0.05mm) with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 2193 | Providing and fixing precoated galvanised steel sheet roofing accessories of total coated thickness 0.50 mm (base metal of minimum 0.45 mm thickness with total coating thickness of 0.05 mm) with Zinc coating 120gram per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self tapping screws complete : Ridges plain (500 - 600mm) |
| 2194 | Providing and fixing precoated galvanised steel sheet roofing accessories of total coated thickness 0.50 mm (base metal of minimum 0.45 mm thickness with total coating thickness of 0.05 mm) with Zinc coating 120gram per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self tapping screws complete : Flashings/ Aprons.( Upto 600 mm) |
| 2195 | 12.5 mm thick fully Perforated Gypsum Board tile made from plasterboard having glass fibre conforming to IS: 2095 part I, of size 595x595 mm, having perforation of 9.7x9.7 mm at 19.4 mm c/c with center borders of 48 mm and the side borders of 30 mm, backed with non woven tissue on the back side, having an NRC (Noise Reduction Coefficient) of 0.79, with 50 mm resin bonded glass wool backing. |
| 2196 | 12 mm cement plaster of mix 1:6 (1 cement: 6 coarse sand) |
| 2197 | 15mm cement plaster on rough side of single or half brick wall of mix: 1:6 (1cement :6 coarse sand) |
| 2198 | 6 mm cement plaster of mix : 1:3 (1 cement : 3 fine sand) |
| 2199 | Extra for providing and mixing water proofing material in cement plaster work in proportion recommended by the manufacturers. |
| 2200 | Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved manufacturer and of required shade and colour all complete to achieve even shade and colour :New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC content less than 50 gram/litre |
| 2201 | Finishing walls with textured exterior paint of required shade for new work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including base coat of water proofing cement paint applied @ 2.20kg/10 sqm. |
| 2202 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade. Two or more coats on new work. |
| 2203 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surfaceto prepare the surface even and smooth complete. |
| 2204 | Providing and fixing water closet squatting pan (Indian type W.C. pan ) with100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests |
| 2205 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps,32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require :White Vitreous China Flat back wash basin size 550x400 mm with single 15 mm C.P. brass pillar tap. |
| 2206 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete.Flexible pipe-----32 mm dia |
| 2207 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 2208 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour..450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm, weighing not less than 170 gms |
| 2209 | Providing and fixing G.I. Pipes complete with G.I. fittings and clamps, including making good the walls etc. concealed pipe, including painting with anti corrosive bitumastic paint, cutting chases and making good the wall :15 mm dia nominal bore |
| 2210 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. External work 20 mm dia nominal bore |
| 2211 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete : 15 mm nominal bore |
| 2212 | Providing and fixing G.I. Union in existing G.I. pipe line, cutting and threading the pipe and making long screws including excavation, refilling the earth or cutting of wall and making good the same complete wherever required :15 mm nominal bore |
| 2213 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 2214 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931: 15 mm nominal bore |
| 2215 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931: 15 mm nominal bore |
| 2216 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 15 mm nominal bore |
| 2217 | Providing and fixing PTMT grating of approved quality and colour. Circular type. 100 mm nominal dia. |
| 2218 | Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements. Weighing not less than 106 gms. |
| 2219 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC/neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing and paneling to be paid for separately) :For fixed portion----Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 2220 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC/neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing and paneling to be paid for separately) : For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of PVC / neoprene gasket required (Fittings shall be paid for separately).----Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 2221 | Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double acting hydraulic floor spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge (Door handle, lock andstopper etc.to be paid separately). |
| 2222 | Grading roof for water proofing treatment with Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) |
| 2223 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with moduler type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single core cable etc as required. Group B |
| 2224 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required :2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 2225 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required :2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 2226 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required 2 Pair |
| 2227 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 20 mm |
| 2228 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required Telephone socket outlet |
| 2229 | Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 2230 | Supplying and fixing suitable size GI box with modular plate and cover in front on ...... providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection, painting etc. as required. |
| 2231 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. As required. |
| 2232 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed steel/ PVC conduit as required. 1 run cable |
| 2233 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar,interconnections, powder painted including earthing etc. as required. (But withoutMCB/RCCB/Isolator) 12 way , Double door |
| 2234 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 2235 | Supply and fixing following rating, 63 amps double pole, 240 volts, isolator in the existing MCB DB complete with connection, testing and commissioning etc. as required. |
| 2236 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 2237 | Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/termination with GI thimble etc. as required. |
| 2238 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase Supply, earthing etc. complete as required. |
| 2239 | Supply of 20Watt LED Tubelight Philips or equivalent make as approved by E.I. |
| 2240 | Supplying of exhaust Fan 250 mm sweep of Orient or equivalent make as approved by E.I. |
| 2241 | Supply and Installation of 0.5 H.P.water pump Havells or equivalent make all complete as per direction of engineer-in-charge.approved by S.E.(Civil)Letter no.832/ECC/Ddun/Extra Item,Dated-29-08-2022 |
| 2242 | Engaging of suitable beldar for petty work. |
| 2243 | Land Development Works Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 2244 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 and for all lift. |
| 2245 | Excavating, supplying, stacking and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including rammingand watering of the earth in layers not exceeding 20 cm in foundationtrenches, plinth, sides offoundation etc. complete for all lift. |
| 2246 | 1 :2:4 (1 cement : 2 coarse sand (zone-Ill) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 2247 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) |
| 2248 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size) |
| 2249 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chanas, lintels, bands,plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1: 1.5:3 (1 cement : 1.5 coarse sand(zone-111) derived from natural sources : 3 graded stone aggregate 20 mm nominal sizederived from natural sources). |
| 2250 | Centering and shuttering including strutting, propping etc. and removal of form for Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 2251 | Centering and shuttering including strutting, propping etc. and removal of form for Columns, Pillars, Piers, Abutments, Posts and Struts. |
| 2252 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.Thermo-Mechanically Treated bars. |
| 2253 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 2254 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 2255 | Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with : Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 2256 | Providing and fixing 1st quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approvedmake, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps anddados, over 12 mm thick bed of cement mortar 1 :3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, includingpointing in white cement mixed with pigment of matching shade complete. |
| 2257 | Steel work welded in built up sections/ framed work including cutting,hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. |
| 2258 | 12 mm cement plaster of mix 1:6 (1 cement: 6 coarse sand) |
| 2259 | 15mm cement plaster on rough side of single or half brick wall of mix: 1:6 (1cement :6 coarse sand) |
| 2260 | Pointing on stone work with cement mortar 1:3 (1 cement : 3 fine sand) : Flush/ Ruled pointing |
| 2261 | Finishing walls with water proofing cement paint of required shade : New work (Two or more coats applied @ 3.84 kg/10 sqm) |
| 2262 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade. Two or more coats on new work. |
| 2263 | Providing and laying 60 mm thick faciory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50 mm thick compactedbed of coarse sand, filling the joints with line sand etc. all complete as per the direction of Engineer-in-charge. |
| 2264 | Supply of 33/11kV SUBSTATIONT/F 33/11 kV 12.5MVA |
| 2265 | 8 m. LONG STP 410 SP-10 (BPHD GAL.) |
| 2266 | 11 MTR. LONGSTP 410 SP-55(BPHD GAL.) |
| 2267 | MS ROUND 32 mm |
| 2268 | 11 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 2269 | 33 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 2270 | DISC FIT. B&S TYPE FOR PANTHER 90 KN |
| 2271 | DISC FIT. B&S TYPE WEASEL/RABBIT 45 KN |
| 2272 | 9 KV 10 KA Polymeric Lightning Arrestor |
| 2273 | EARTHING ROD MS 20X2500mm |
| 2274 | GI WIRE 5mm/6 SWG |
| 2275 | STAY SET GI 16X1800mm |
| 2276 | STAY WIRE GI 7/3.15mm 7/10SWG |
| 2277 | ACSR DOG |
| 2278 | ACSR PANTHER |
| 2279 | CABLE AL 3X300 SQ. mm XLPE 11 kV |
| 2280 | CABLE AL 3X400 SQ. mm XLPE 11 kV |
| 2281 | CABLE AL 1X630 SQ. mm XLPE 11 kV |
| 2282 | CABLE AL 3X70 SQ. mm XLPE 33kV |
| 2283 | J/KIT FOR 3X300mm* 11kV XLPE CABLE(O/D) |
| 2284 | J/KIT FOR 3X400mm° 11kV XLPE CABLE (O/D) |
| 2285 | CONTROL CABLE 10X2.5 SQ. mm. |
| 2286 | CONTROL CABLE 2X2.5 SQ. mm. |
| 2287 | CONTROL CABLE 4X2.5 SQ. mm. |
| 2288 | CONTROL CABLE 6X2.5 SQ. mm. |
| 2289 | LT PVC CABLE 2X6 SQ.mm (ARMORED) |
| 2290 | LT XLPE CABLE 3.5.X 70 SQ. mm. |
| 2291 | LT PVC CABLE 4X10 SQ.mm |
| 2292 | 33 KV H.S. Cable J/K 3x70 sq. mm (O/D) |
| 2293 | 110 V BATTERY SET(300 AH) |
| 2294 | 110V BATTERY CHARGER(300 AH) |
| 2295 | JUNCTION BOX FOR 33kV PT |
| 2296 | 33kV PT of RATIO 33 kV/110V OUTDOOR |
| 2297 | 33 kV LIGHTNING ARRESTER |
| 2298 | PANTHER TO PANTHER CTYPE WEDGE CONNECTOR |
| 2299 | 33 kV FUSE SET |
| 2300 | 33/0.433 KV, 63 KVA Station Transformer |
| 2301 | MS STRUCTURE (ANGLE ,CHANNEL ETC.) |
| 2302 | GI ITEM (Rail,Joist,ChanneI,Angle) |
| 2303 | Cable Holding clamp with N&B |
| 2304 | Holding Clamp FPR GI Pipe 8/10\\"& MS Ch. |
| 2305 | PG CLAMP ALU ALLOY PANTHER TO DOG |
| 2306 | Stay Clamp for SP-55 With Nut & Bolt |
| 2307 | 33KV ISOLATOR CONN.CLAMP FOR PANTHER,N&B |
| 2308 | 33 KV ISOLATOR CLAMP FOR ACSR DOG |
| 2309 | PERFORATED TRAY 400MM FOR CABLE TRENCH |
| 2310 | PERFORATED TRAY 200MM FOR CABLE TRENCH |
| 2311 | PERFORATED TRAY 100MM FOR CABLE TRENCH |
| 2312 | FLEXIBLE COOPER CONNECTOR SOXSOMM |
| 2313 | DANGER BOARD |
| 2314 | GI Pipe 4\\"' Dia |
| 2315 | 250 W hpsv/led lamp with contrl gear |
| 2316 | Insulated Electrical Piller Taparia |
| 2317 | 11 KV Fuse Set |
| 2318 | KM-21 G.I. Pipe 6\\" dia 3 meter long |
| 2319 | Conne.Suitable for Panther for LA |
| 2320 | Connector of Power T/F HV Side |
| 2321 | Connector of Power T/F LV Side |
| 2322 | GI STRIP 65MMX6MM |
| 2323 | “HT' WARNING TAPE |
| 2324 | 11KV,630Amp off load Isolator |
| 2325 | Thimble junction box for cable support |
| 2326 | 33KV C&R PANEL I/C-D |
| 2327 | 33KV C&R PANEL O/G-D |
| 2328 | 33KV C&R PANEL BUS COUPLER-D |
| 2329 | 11KV C&R PANEL I/C-D |
| 2330 | 11KV C&R PANEL O/G-D |
| 2331 | 11KV C&R PANEL BUS COUPLER-D |
| 2332 | PP clamp with N&B (GI) |
| 2333 | G.I.Strip 35x4mm |
| 2334 | 11 KV HS cable END T/K 1x630 mm* O/D |
| 2335 | Cable Jointing Kit 1x630 Outdoor |
| 2336 | 33 KV XLPE Cable AL 1x630 sq. mm -D |
| 2337 | Iron Clad 30 Amp Switch |
| 2338 | Connector Suit for CT/PT for Panther/Dog |
| 2339 | 33 KV Isolator Vertical Type |
| 2340 | 11kv 3P(400A)3pin vert. mount GO AB TPMO |
| 2341 | Indoor type auto power factor controller |
| 2342 | 12.65kV, 4800kVAr, Capacitor bank |
| 2343 | 12KV C&R Panel with SCADA(Capacitor) |
| 2344 | 36KV 1250A Gang ope PMA VCB(I/C) |
| 2345 | 36KV 1250A Gang ope PMA VCB(O/G) |
| 2346 | 12KV 1250A Gang ope PMA VCB(I/C) |
| 2347 | 12KV 1250A Gang ope PMA VCB(O/G) |
| 2348 | 12KV 1250A Gang ope PMA VCB(Capacitor) |
| 2349 | 12KV 1250A Gang ope PMA VCB(B/C) |
| 2350 | 36KV 1250A Gang ope PMA VCB(B/C) |
| 2351 | 33kv Bus isolator manual&motor,SCADA COM |
| 2352 | 33kv line isolator manual&motor,SCADA co |
| 2353 | 11kv isolator manual&motor,SCADA comp. |
| 2354 | Wire Mesh Fencing |
| 2355 | 110V DC DISTRIBUTION BOARD-D |
| 2356 | Name Plate of Equip. TG,LI,BI,CT,CB ect. |
| 2357 | GI STRIP 50X6 MM |
| 2358 | SUNDRISE ITEM LUG GLADE ETC |
| 2359 | Alluminium Lug |
| 2360 | Stone Pad 300x300x75mm |
| 2361 | Connector Suitable. Panther for VCB |
| 2362 | Dustbin 20 Litre Capacity (Colour Green) |
| 2363 | RUBBER MAT(INSULATED )1MX1MX3MM |
| 2364 | Fire Extingushier |
| 2365 | Torch 3 Cell |
| 2366 | 33 KV Hand Gloves |
| 2367 | Earth Chain |
| 2368 | First aid box |
| 2369 | SHOCK TREATMENT CHART |
| 2370 | SHUT DOWN/ BREAK DOWN BOARD |
| 2371 | WALL CLOCK |
| 2372 | D-SPANNER SET |
| 2373 | PIPE WRENCH 12\\" |
| 2374 | 2.5 KV MEGGAR DIGITAL |
| 2375 | EARTH MEGGAR DIGITAL |
| 2376 | INSTRUCTION BOARD |
| 2377 | MAXIMUM & MINIMUM DISPLAY BOARD |
| 2378 | SUB STATION NAMED BOARD |
| 2379 | Portable Foam Type Fire Extinguisher SLT |
| 2380 | Single Line Diagram Board |
| 2381 | Door Mat |
| 2382 | Name plate of feeder |
| 2383 | Name plate of station \iI |
| 2384 | 11KV Danger Board with Clamp |
| 2385 | 33 KV Danger Board with Clamp |
| 2386 | Steel Almirah |
| 2387 | Office Table size (4x2.5) |
| 2388 | Fire Bucket Stand with Buckets |
| 2389 | Steel Cabinet |
| 2390 | Steel office Table |
| 2391 | Steel office chair Godrej |
| 2392 | Meggar 5 KV Digital |
| 2393 | Fire Bucket stand of MS angle |
| 2394 | Supply of 33kV LINE11 MTR. LONGSTP 410 SP-55(BPHD GAL.) |
| 2395 | STP 13.0 M-IS 410 SP-72 (BPHD GAL.) |
| 2396 | MS ANGLE 65X65X6 mm |
| 2397 | MS CHANNEL 100X50 mm |
| 2398 | MS CHANNEL 125X65 mm |
| 2399 | 11 kV POLYMER DISC INSULATOR(B&S) TYPE |
| 2400 | 33 kV POLYMER DISC INSULATOR(B&S) TYPE |
| 2401 | 11 kV POLYMER PIN INSULATOR WITH PIN |
| 2402 | 33kV 10KN POLYMER PIN INSULATORWITH PIN |
| 2403 | DISC FIT. B&S TYPE DOG/RACOON 70KN |
| 2404 | DISC FIT. B&S TYPE WEASEL/RABBIT45 KN |
| 2405 | LT Shackle Insulator |
| 2406 | X ARM ANGLE 65X65X6 mm V TYPE 11kV |
| 2407 | Earth wire GI 7/1.6 mm 16 SWG |
| 2408 | EARTHING ROD MS 20X2500mm |
| 2409 | GI WIRE 4mm/8mm SWG |
| 2410 | GI WIRE 5mm/6 SWG |
| 2411 | STAY SET GI 20X1800mm |
| 2412 | STAY WIRE GI 7/4.0 mm 7/8 SWG |
| 2413 | ACSR RABBIT |
| 2414 | ACSR PANTHER |
| 2415 | Bolt & Nut 150x12 mm |
| 2416 | Bolt & Nuts 50x16 mm |
| 2417 | Eye Bolt 190x16 mm With Nut & Bolt |
| 2418 | Bracing Clamp SP-72 |
| 2419 | LT Shackle Insulator Clamp |
| 2420 | Holding Clamp FPR GI Pipe 8/10'' & MS Channel |
| 2421 | E- CLAMP |
| 2422 | F Clamp |
| 2423 | EARTH WIRE CLAMP FOR SP-23 WITHN/B |
| 2424 | PP & CLAMP WITH N&B ST POLE SP-72 |
| 2425 | STAY CLAMP FOR SP-72 WITH N/B |
| 2426 | PP & CLAMP WITH N&B ST POLE SP-23 |
| 2427 | NUMBER PLATE WITH CLAMP |
| 2428 | Danger Board With Clamp N&B |
| 2429 | Cable Holding Clamp with N&B of Size |
| 2430 | PG Clamp For panther |
| 2431 | KM-21 G.I. Pipe 6\\" dia 3 meter long |
| 2432 | STAY CLAMP FOR SP-55 WITH NUT & BOLT |
| 2433 | Earth Wire Clamp |
| 2434 | Concrete route marker for HT cable |
| 2435 | PP & CLAMP WITH NUT & BOLT FORGUARDING |
| 2436 | 33 KV straight Through 1x630 sqmm |
| 2437 | Disc fitting for Panther 120 KN |
| 2438 | PP CLAMP FOR SPECIAL TYPEBRACKET |
| 2439 | Cable Jointing Kit 1x630 Outdoor |
| 2440 | 33 KV XLPE Cable AL 1x630 sqmm - D |
| 2441 | ALUMINIUM BINDING WIRE |
| 2442 | BARBED WIRE |
| 2443 | Stone Pad 300x300x75mm |
| 2444 | Erection of 33/11kV SUBSTATION7.2.1 (DSR CODE 2014) |
| 2445 | NSI_EARTH FILLING |
| 2446 | CEMENT CONCRETING WORK IN RATIO 1:4:8 |
| 2447 | CEMENT CONCRETING WORK IN RATIO 1:2:4 |
| 2448 | BRICK WORK IN 1:4 RATIO |
| 2449 | CEMENT PLASTER WORK |
| 2450 | FENCING OF YARD |
| 2451 | RCC 1:1.5:3 |
| 2452 | MAKING CABLE TRENCH |
| 2453 | BRICK WORK 1:6 SUB STRUCTURE |
| 2454 | BRICK WORK 1:6 SUPER STRUCTURE |
| 2455 | CC WORK 1:1.5:2 |
| 2456 | SUPPLY&ERRECT GRAVEL PITCHING 1/2\\"- 3/4\\" |
| 2457 | ELECTRICAL INSPECTION FEE |
| 2458 | SPECIAL EARTHING |
| 2459 | FABRICATION OF STEEL |
| 2460 | FIXING OF GI PIPE |
| 2461 | ERECTION OF SINGLE SP-10 POLE |
| 2462 | ERECTION OF SP-55 DOUBLE POLE |
| 2463 | PAINTING OF SP-10 POLE |
| 2464 | PAINTING OF SP-55 POLE |
| 2465 | LAYING OF LT PVC CABLES(» 150 SQMM) |
| 2466 | LAYING OF U/G 11 KV CABLE IN TRENCH |
| 2467 | LAYING OF U/G 33 KV CABLE IN TRENCH |
| 2468 | FIXING OF LIGHTNING ARRESTOR |
| 2469 | FIXING OF 11 KV XLPE JOINTING KIT |
| 2470 | FIXING OF 33 KV XLPE JOINTING KIT |
| 2471 | CARTAGE OF PETTY MATERIAL,0-20 KM |
| 2472 | CARTAGE 11 KV PANELS, 0-20 KM |
| 2473 | CARTAGE OF PANELS, 0-20 KM |
| 2474 | CARTAGE 10/12.5 MVA POWER T/ F(0-20KM) |
| 2475 | MANUAL SHIFTING OF CONTROL PANEL |
| 2476 | ERECTION OF POWER T/F(12.5/10 MVA) |
| 2477 | ESCAVATION OF EARTH FOR STRUCT. ERECTION |
| 2478 | GROUTING OF STRUCTURE IN CC 1:3:6 |
| 2479 | FIXING OF 33 KV ISOLATOR VERTICAL TYPE |
| 2480 | LAYING OF CONTROL CABLE |
| 2481 | LAYING OF EARTH MAT |
| 2482 | EARTHING OF STRUCTURE USING GI STRIP |
| 2483 | COMM.OF 33/11KV VCB PANEL |
| 2484 | COMPLETE TESTING WIRING |
| 2485 | ERECTION & LAYING OF LT XLPE CABLE 2X6 |
| 2486 | INST. & FIXING OF CHEMICAL EARTHING |
| 2487 | INSTALLATION OF LINE/ BUS ISOLATOR |
| 2488 | INSTALLATION OF DCDB INCLUDING TESTING |
| 2489 | INSTALLATION OF ACDB INCLUDING TESTING |
| 2490 | ERECTION OF 33/0.433KV S/S TRANSFORMER |
| 2491 | ERECTION OF FLEXIBLE CU. CONN.500X50 MM |
| 2492 | ERECTION OF STAY POST |
| 2493 | ERRECTION OF 33KV PT |
| 2494 | ERREC. 12.65kV 4800kVAr, CAPACITOR BANK |
| 2495 | ERREC. 11KV, 630 AMP, OFF LOAD ISOLATOR |
| 2496 | ERECTION OF 110V BATTERY SET(300AH) |
| 2497 | ERECTION OF 110V BATTERY CHARGER(300AH) |
| 2498 | FIXING OF 11 KV FUSE SET |
| 2499 | FIXING OF 33 KV FUSE SET |
| 2500 | LAYING OF 4X10SQ MM LT PVC CABLE |
| 2501 | ERECTION OF EARTHING ELECTRODE&STRIP50X6 |
| 2502 | FIXING OF SODIUM/LED LIGHT AT YARD |
| 2503 | INSTALLATION OF FIRE EXTINGUISHERS |
| 2504 | ERECTION OF NAME PLATES |
| 2505 | ERECTION OF T&P ITEMS |
| 2506 | ERECTION OF MISC. GI STRUCTURES |
| 2507 | SHIFTING OF T/F B WORK |
| 2508 | Erection of 33kV LINECEMENT CONCRETING WORK IN RATIO 1:4:8 |
| 2509 | ELECTRICAL INSPECTION FEE |
| 2510 | ERECTION OF EARTHING ROAD |
| 2511 | FABRICATION OF STEEL |
| 2512 | FIXING OF GI PIPE |
| 2513 | FIXING OF RCC CABLE ROUTE MARKER |
| 2514 | ERECTION OF 33 KV STAY SET |
| 2515 | ERECTION OF SINGLE SP-55 POLE |
| 2516 | ERECTION OF SINGLE SP-72 POLE |
| 2517 | ERECTION OF SP-72 DOUBLE POLE |
| 2518 | ERECTION OF SP-72(11KV/33 KV) FOUR POLE |
| 2519 | ERECTION OF BRACKET IN 11 KV LINE |
| 2520 | LAYING OF PANTHER CONDUCTOR IN HT LINE |
| 2521 | GUARDING OF 33 KV LINE |
| 2522 | FIXING OF 33 KV XLPE JOINTING KIT |
| 2523 | CARTAGE SP-55 POLE, 0-20 KM |
| 2524 | CARTAGE SP-72 POLE, 0-20 KM |
| 2525 | CARTAGE OF PATTY MATERIAL, 0-20 KM |
| 2526 | HEADLOAD CARTAGE SP-55 POLE(0-1 KM) |
| 2527 | HEADLOAD CARTAGE SP-72 POLE(0-1 KM) |
| 2528 | HEADLOAD CARTAGE OFMATERIAL(0-1 KM) |
| 2529 | ROAD CUTTING AND REPAIRING |
| 2530 | COMPLETE TESTING WIRING |
| 2531 | MANUAL DIGGING OF CABLE TRENCHUPTO 1 MT |
| 2532 | PAINTING OF DOUBLE POLE (SP-72) |
| 2533 | PAINTING OF FOUR POLE (SP-72) |
| 2534 | SHIFTING REALIGNMENT 11KV SP,DP/ LT LINE |
| 2535 | Annual Maintenance Charges (AMC) and O&M of Project for 5 yearson per year basis. |
| 2536 | Control RoomEarth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 2537 | Filling available excavated earth (excluding rock) in trenches, plinth sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5m |
| 2538 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also includingramming and watering of the earth in layers not exceeding 20cm in trenches, plinth, sides of foundation etc. complete |
| 2539 | Supplying and filling in plinth with Jamuna sand under floors including, watering, ramming consolidating and dressing complete. |
| 2540 | Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1:2 (1 cement : 2 Coarse sand) to match the existing floor : With Chlorpyriphos/Lindane E.C. 20% with 1% concentration. |
| 2541 | Providing and laying in position cement concrete in ratio 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 2542 | Providing and laying in position cement concrete in ratio 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 40 mm nominal size) of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 2543 | Providing and laying in position specified grade of reinforced cement concrete in ratio 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level |
| 2544 | Reinforced cement concrete work in 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level excluding cost of centering, shuttering, finishing and reinforcement. |
| 2545 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size). |
| 2546 | Centering and shuttering including strutting, propping etc. and removal of form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 2547 | Centering and shuttering including strutting, propping etc. and removal of form for Suspended floors, roofs, landings, balconies and access platform. |
| 2548 | Centering and shuttering including strutting propping etc. and removal of form for: Almira Shelves Bottem |
| 2549 | Centering and shuttering including strutting, propping etc. and removal of form for Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 2550 | Centering and shuttering including strutting, propping etc. and removal of form for Columns, Pillars, Piers, Abutments, Posts and Struts. |
| 2551 | Centering and shuttering including strutting, propping etc. and removal of form for : Edges of slabs and breaks in floors and walls. Under 20 cm wide |
| 2552 | Centering and shuttering including strutting, propping etc. and removal of form for Weather shade, Chajjas, corbels etc., including edges. |
| 2553 | Providing, hoisting and fixing up to floor five level precast reinforced cement concrete in small lintels not exceeding 1.5m clear span up to floor five level including the cost of required centering, shuttering and finishing smooth with 6 mm thick cement plaster 1:3 (1 cement : 3 fine sand) on exposed surfaces but excluding the cost of reinforcement with 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size). |
| 2554 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.Thermo-Mechanically Treated bars. |
| 2555 | Smooth finishing of the exposed surface of R.C.C. work with 6 mm thick cement mortar 1:3 (1 Cement : 3 fine sand). |
| 2556 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 2557 | Brick work with F.P.S. bricks of class designation 75 in foundation and plinth in Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 2558 | Brick work with F.P.S. bricks of class designation 75 in superstructure above plinth level up to floor V level in all shapes and sizes in Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 2559 | Half brick masonry with F.P.S. brick of class designation 75 in foundations and plinth in. cement mortar 1:4 (1 cement : 4 coarse sand) |
| 2560 | Half brick masonry with F.P.S. bricks of class designation 75 in superstructure above plinth level up to floor V level. |
| 2561 | Providing and fixing 18mm thick gang saw cut mirror polished premoulded and prepolished) machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edge to give high gloss finish etc. complete at all levels. Granite of any colour and shade. Area of slab upto 0.50 sqm |
| 2562 | Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge.Granite work |
| 2563 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS:15622(thickness to be specified by the manufacturer), of approved make,in all colours, shades except burgundy, bottle green, black of any size asapproved by Engineer-in-Charge, in skirting, risers of steps and dados,over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) andjointing with grey cement slurry @ 3.3kg per sqm, including pointingin white cement mixed with pigment of matching shade complete. |
| 2564 | Providing and fixing fly proof galvanized M.S. wire gauge to windows and clerestory windows using wire gauge with average width of aperture 1.4mm in both directions with wire of dia 0.63 mm all complete.With 12 mm mild steel U beading. |
| 2565 | Providing and fixing ISI marked aluminium butt hinges anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete: 100x63x4 mm |
| 2566 | Providing and fixing aluminium sliding door bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc. complete : 250x16 mm |
| 2567 | Providing and fixing aluminium tower bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade with necessary screws etc. complete : 150x10 mm |
| 2568 | Providing and fixing aluminium handles ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete :100 mm |
| 2569 | Providing and fixing aluminium hanging floor door stopper ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade with necessary screws etc. complete. Single rubber stopper |
| 2570 | Providing and fixing aluminium casement stays ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade with necessary screws etc. complete. |
| 2571 | Strutural steel work riveted bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete: |
| 2572 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp of internal dia 140mm, 73mm height, top lid of 1.5mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3mm dia. round headed screws, one lock at the corners. Clamp shall be made of 12mm dia M.S. bar bent to shape as per standard drawing. |
| 2573 | Steel work welded in built up sections/ framed work including cutting,hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. |
| 2574 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement including cement slurry, but excluding the cost of nosing of steps etc. complete.40mm thick with 20mm nominal size stone aggregate. |
| 2575 | Providing and fixing glass strips in joints of terrazo/ cement concrete floors.40 mm wide and 4 mm thick. |
| 2576 | Providing and laying Ceramic glazed floor tiles 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick Cement Mortar 1:4 (1 Cement : 4 Coarse sand) including pointing the joints with white cement and matching pigment etc., complete. |
| 2577 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600x600 mm |
| 2578 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes.75 mm diameter |
| 2579 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes.110 mm diameter |
| 2580 | 12 mm cement plaster of mix 1:6 (1 cement: 6 coarse sand) |
| 2581 | 15mm cement plaster on rough side of single or half brick wall of mix: 1:6 (1cement :6 coarse sand) |
| 2582 | 12 mm Cement plaster 1:3 (1 cement: 3 coarse sand) finished with a floating coat of neat cement. |
| 2583 | 6mm Cement plaster finished with a floating coat of neat cement 1:3. |
| 2584 | Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete |
| 2585 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade.New work (two or more coats) over and including priming coat with cement primer. |
| 2586 | Finishing walls with textured exterior paint of required shade for new work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including base coat of water proofing cement paint applied @ 2.20kg/10 sqm. |
| 2587 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work |
| 2588 | Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete including cutting and making good the walls and floors wherever required :White Vitreous china Orissa pattern W.C. pan of size 580x440mm with integral type foot rests. |
| 2589 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required :One urinal basin with 5 litre white P.V.C. automatic flushing cistern |
| 2590 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps,32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require :White Vitreous China Flat back wash basin size 550x400 mm with single 15 mm C.P. brass pillar tap. |
| 2591 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete.Flexible pipe-----32 mm dia |
| 2592 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 2593 | Providing and fixing PTMT towel ring trapezoidal shape 215 mm long, 200 mm wide with minimum distances of 37 mm from wall face with concealed fittings arrangement of approved quality and colour, weighing not less than 88 gms. |
| 2594 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply and all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall..15 mm nominal dia Pipes |
| 2595 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply and all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work -Exposed on wall 20 mm nominal dia Pipes |
| 2596 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :25 mm nominal bore |
| 2597 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete :15 mm nominal bore |
| 2598 | Providing and fixing uplasticised PVC connection pipe with brass unions : 30 cm length.15 mm nominal bore |
| 2599 | Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design :With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 |
| 2600 | Providing and fixing G.I. Union in G.I. pipe including cutting and threading the pipe and making long screws etc. complete (New work) :15 mm nominal bore |
| 2601 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 2602 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931: 15 mm nominal bore |
| 2603 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931: 15 mm nominal bore |
| 2604 | Providing and fixing PTMT grating of approved quality and colour. Circular type. 100 mm nominal dia |
| 2605 | Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighing not less than 106 gms. |
| 2606 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC/neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing and paneling to be paid for separately) : For.... fixed portion Powder coated aluminium (minimum thickness of powdercoating 50 micron) |
| 2607 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC/neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing and paneling to be paid for separately) : For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of PVC / neoprene gasket required (Fittings shall be paid for separately). Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 2608 | Providing and fixing 12mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge. Pre-laminated particle board with decorative lamination on both sides. |
| 2609 | Providing and fixing 100mm brass locks (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete. |
| 2610 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with PVC/ neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-incharge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 4 mm thickness |
| 2611 | Grading roof for water proofing treatment with Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 2612 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with moduler type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single core cable etc as required. Group B |
| 2613 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required :2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 2614 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 A switch |
| 2615 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 A socket outlet |
| 2616 | Supplying and fixing suitable size GI box with modular plate and cover in front on ...... providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection, painting etc. as required. |
| 2617 | Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. |
| 2618 | Supply and fixing following rating, 63 amps double pole, 240 volts, isolator in the existing MCB DB complete with connection, testing and commissioning etc. as required. |
| 2619 | Supply and fixing 5 amps to 32 amps rating, 240 volts, 'C' serise, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole and neutral |
| 2620 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar,interconnections, powder painted including earthing etc. as required. (But withoutMCB/RCCB/Isolator) 8 way , Double door |
| 2621 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan withBrush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2nos. canopies, shackle kit, safetyrope, copper winding, PowerFactor not less than 0.9, ServiceValue (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulationresistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 2622 | Supplying of Exhaust Fan 250 mm Sweep of Orient or equivalent make as approved by E.I. |
| 2623 | Supplying of 20 watt LED Tubelight Philps or equivalent make as approved by E.I. |
| 2624 | Engaging/S of suitable beldar for different type of works |
| 2625 | Engaging suitable electrician with kit for petty work. (Based on DSR Code 1001) |
| 2626 | Land Development WorksEarth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 2627 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 and for all lift. |
| 2628 | Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 moutside the periphery of the area cleared. |
| 2629 | 1 :2:4 (1 cement : 2 coarse sand (zone-Ill) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 2630 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) |
| 2631 | Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor etc., up to floor five level, excluding the cost of centering, shuttering and finishing: 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 2632 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :1 :1.5:3 (1 cement : 1.5 coarse sand (zone-Ill) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 2633 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size) |
| 2634 | Centering and shuttering including strutting, propping etc. and removal of form for Foundations, footings, bases of columns, etc. for mass concrete |
| 2635 | Centering and shuttering including strutting, propping etc. and removal of form for Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 2636 | Centering and shuttering including strutting, propping etc. and removal of form for Columns, Pillars, Piers, Abutments, Posts and Struts. |
| 2637 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.Thermo-Mechanically Treated bars. |
| 2638 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 2639 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 2640 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 2641 | Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with : Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 2642 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 2643 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.: ---Hot finished welded type tubes |
| 2644 | Steel work welded in built up sections/ framed work including cutting,hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. |
| 2645 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes.110 mm diameter |
| 2646 | 12 mm cement plaster of mix 1:6 (1 cement: 6 coarse sand) |
| 2647 | 15mm cement plaster on rough side of single or half brick wall of mix: 1:6 (1cement :6 coarse sand) |
| 2648 | Pointing on stone work with cement mortar 1:3 (1 cement : 3 fine sand) : Flush/ Ruled pointing |
| 2649 | Finishing walls with textured exterior paint of required shade for new work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including base coat of water proofing cement paint applied @ 2.20kg/10 sqm. |
| 2650 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade. Two or more coats on new work. |
| 2651 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 2652 | Fencing with angle iron post placed at required distance embedded in cement concrete blocks, every 15th post, last but one end post and cornerpost shall be strutted on both sides and end post on one side only and provided with horizontal lines and two diagonals interwoven with horizontalwires, of barbed wire weighing 9.38 kg per 100 m (minimum), between the two posts fitted and fixed with G.I. staples, turn buckles etc. complete. (Costof posts, struts, earth work and concrete work to be paid for separately). Payment to be made per metre cost of total length of barbed wire used. With G.I. barbed wire |
| 2653 | Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including makinggood the undulations etc. and re-rolling the sub grade and disposal of surplus earthwith lead upto 50 metres. |
| 2654 | Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge). |
| 2655 | Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge.80 mm thick C.C. paver block of M-30 grade with approved color design and pattern. |
| 2656 | Supply of 33/11kV SUBSTATIONT/F 33/11 kV 12.5MVA |
| 2657 | 8 m. LONG STP 410 SP-10 (BPHD GAL.) |
| 2658 | 11 MTR. LONGSTP 410 SP-55(BPHD GAL.) |
| 2659 | MS ROUND 32 mm |
| 2660 | 11 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 2661 | 33 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 2662 | DISC FIT. B&S TYPE FOR PANTHER 90 KN |
| 2663 | DISC FIT. B&S TYPE WEASEL/RABBIT 45 KN |
| 2664 | 9 KV 10 KA Polymeric Lightning Arrestor |
| 2665 | EARTHING ROD MS 20X2500mm |
| 2666 | GI WIRE 5mm/6 SWG |
| 2667 | STAY SET GI 16X1800mm |
| 2668 | STAY WIRE GI 7/3.15mm 7/10SWG |
| 2669 | ACSR DOG |
| 2670 | ACSR PANTHER |
| 2671 | CABLE AL 3X300 SQ. mm XLPE 11 kV |
| 2672 | CABLE AL 3X400 SQ. mm XLPE 11 kV |
| 2673 | CABLE AL 1X630 SQ. mm XLPE 11 kV |
| 2674 | CABLE AL 3X70 SQ. mm XLPE 33kV |
| 2675 | J/KIT FOR 3X300mm* 11kV XLPE CABLE(O/D) |
| 2676 | J/KIT FOR 3X400mm° 11kV XLPE CABLE (O/D) |
| 2677 | CONTROL CABLE 10X2.5 SQ. mm. |
| 2678 | CONTROL CABLE 2X2.5 SQ. mm. |
| 2679 | CONTROL CABLE 4X2.5 SQ. mm. |
| 2680 | CONTROL CABLE 6X2.5 SQ. mm. |
| 2681 | LT PVC CABLE 2X6 SQ.mm (ARMORED) |
| 2682 | LT XLPE CABLE 3.5.X 70 SQ. mm. |
| 2683 | LT PVC CABLE 4X10 SQ.mm |
| 2684 | 33 KV H.S. Cable J/K 3x70 sq. mm (O/D) |
| 2685 | 110 V BATTERY SET(300 AH) |
| 2686 | 110V BATTERY CHARGER(300 AH) |
| 2687 | JUNCTION BOX FOR 33kV PT |
| 2688 | 33kV PT of RATIO 33 kV/110V OUTDOOR |
| 2689 | 33 kV LIGHTNING ARRESTER |
| 2690 | PANTHER TO PANTHER CTYPE WEDGE CONNECTOR |
| 2691 | 33 kV FUSE SET |
| 2692 | 33/0.433 KV, 63 KVA Station Transformer |
| 2693 | MS STRUCTURE (ANGLE ,CHANNEL ETC.) |
| 2694 | GI ITEM (Rail,Joist,ChanneI,Angle) |
| 2695 | Cable Holding clamp with N&B |
| 2696 | Holding Clamp FPR GI Pipe 8/10\\"& MS Ch. |
| 2697 | PG CLAMP ALU ALLOY PANTHER TO DOG |
| 2698 | Stay Clamp for SP-55 With Nut & Bolt |
| 2699 | 33KV ISOLATOR CONN.CLAMP FOR PANTHER,N&B |
| 2700 | 33 KV ISOLATOR CLAMP FOR ACSR DOG |
| 2701 | PERFORATED TRAY 400MM FOR CABLE TRENCH |
| 2702 | PERFORATED TRAY 200MM FOR CABLE TRENCH |
| 2703 | PERFORATED TRAY 100MM FOR CABLE TRENCH |
| 2704 | FLEXIBLE COOPER CONNECTOR SOXSOMM |
| 2705 | DANGER BOARD |
| 2706 | GI Pipe 4\\"' Dia |
| 2707 | 250 W hpsv/led lamp with contrl gear |
| 2708 | Insulated Electrical Piller Taparia |
| 2709 | 11 KV Fuse Set |
| 2710 | KM-21 G.I. Pipe 6\\" dia 3 meter long |
| 2711 | Conne.Suitable for Panther for LA |
| 2712 | Connector of Power T/F HV Side |
| 2713 | Connector of Power T/F LV Side |
| 2714 | GI STRIP 65MMX6MM |
| 2715 | “HT' WARNING TAPE |
| 2716 | 11KV,630Amp off load Isolator |
| 2717 | Thimble junction box for cable support |
| 2718 | 33KV C&R PANEL I/C-D |
| 2719 | 33KV C&R PANEL O/G-D |
| 2720 | 33KV C&R PANEL BUS COUPLER-D |
| 2721 | 11KV C&R PANEL I/C-D |
| 2722 | 11KV C&R PANEL O/G-D |
| 2723 | 11KV C&R PANEL BUS COUPLER-D |
| 2724 | PP clamp with N&B (GI) |
| 2725 | G.I.Strip 35x4mm |
| 2726 | 11 KV HS cable END T/K 1x630 mm* O/D |
| 2727 | Cable Jointing Kit 1x630 Outdoor |
| 2728 | 33 KV XLPE Cable AL 1x630 sq. mm -D |
| 2729 | Iron Clad 30 Amp Switch |
| 2730 | Connector Suit for CT/PT for Panther/Dog |
| 2731 | 33 KV Isolator Vertical Type |
| 2732 | 11kv 3P(400A)3pin vert. mount GO AB TPMO |
| 2733 | Indoor type auto power factor controller |
| 2734 | 12.65kV, 4800kVAr, Capacitor bank |
| 2735 | 12KV C&R Panel with SCADA(Capacitor) |
| 2736 | 36KV 1250A Gang ope PMA VCB(I/C) |
| 2737 | 36KV 1250A Gang ope PMA VCB(O/G) |
| 2738 | 12KV 1250A Gang ope PMA VCB(I/C) |
| 2739 | 12KV 1250A Gang ope PMA VCB(O/G) |
| 2740 | 12KV 1250A Gang ope PMA VCB(Capacitor) |
| 2741 | 12KV 1250A Gang ope PMA VCB(B/C) |
| 2742 | 36KV 1250A Gang ope PMA VCB(B/C) |
| 2743 | 33kv Bus isolator manual&motor,SCADA COM |
| 2744 | 33kv line isolator manual&motor,SCADA co |
| 2745 | 11kv isolator manual&motor,SCADA comp. |
| 2746 | Wire Mesh Fencing |
| 2747 | 110V DC DISTRIBUTION BOARD-D |
| 2748 | Name Plate of Equip. TG,LI,BI,CT,CB ect. |
| 2749 | GI STRIP 50X6 MM |
| 2750 | SUNDRISE ITEM LUG GLADE ETC |
| 2751 | Alluminium Lug |
| 2752 | Stone Pad 300x300x75mm |
| 2753 | Connector Suitable. Panther for VCB |
| 2754 | Dustbin 20 Litre Capacity (Colour Green) |
| 2755 | RUBBER MAT(INSULATED )1MX1MX3MM |
| 2756 | Fire Extingushier |
| 2757 | Torch 3 Cell |
| 2758 | 33 KV Hand Gloves |
| 2759 | Earth Chain |
| 2760 | First aid box |
| 2761 | SHOCK TREATMENT CHART |
| 2762 | SHUT DOWN/ BREAK DOWN BOARD |
| 2763 | WALL CLOCK |
| 2764 | D-SPANNER SET |
| 2765 | PIPE WRENCH 12\\" |
| 2766 | 2.5 KV MEGGAR DIGITAL |
| 2767 | EARTH MEGGAR DIGITAL |
| 2768 | INSTRUCTION BOARD |
| 2769 | MAXIMUM & MINIMUM DISPLAY BOARD |
| 2770 | SUB STATION NAMED BOARD |
| 2771 | Portable Foam Type Fire Extinguisher SLT |
| 2772 | Single Line Diagram Board |
| 2773 | Door Mat |
| 2774 | Name plate of feeder |
| 2775 | Name plate of station \iI |
| 2776 | 11KV Danger Board with Clamp |
| 2777 | 33 KV Danger Board with Clamp |
| 2778 | Steel Almirah |
| 2779 | Office Table size (4x2.5) |
| 2780 | Fire Bucket Stand with Buckets |
| 2781 | Steel Cabinet |
| 2782 | Steel office Table |
| 2783 | Steel office chair Godrej |
| 2784 | Meggar 5 KV Digital |
| 2785 | Fire Bucket stand of MS angle |
| 2786 | Supply of 33kV LINE8.5 MRT. LONG STP 410 SP-23(BPHD GAL.) |
| 2787 | 9 MRT. LONG STP 410 SP-33(BPHD GAL.) |
| 2788 | 11 MTR. LONGSTP 410 SP-55(BPHDGAL.) |
| 2789 | STP 13.0 M-IS 410 SP-72 (BPHD GAL.) |
| 2790 | MS ANGLE 65X65X6 mm |
| 2791 | MS CHANNEL 100X50 mm |
| 2792 | MS CHANNEL 125X65 mm |
| 2793 | 11 kV POLYMER DISC INSULATOR(B&S) TYPE |
| 2794 | 33 kV POLYMER DISC INSULATOR(B&S) TYPE |
| 2795 | 11 kV POLYMER PIN INSULATOR WITH PIN |
| 2796 | 33kV 10KN POLYMER PIN INSULATORWITH PIN |
| 2797 | DISC FIT. B&S TYPE DOG/RACOON 70KN |
| 2798 | DISC FIT. B&S TYPE WEASEL/RABBIT45 KN |
| 2799 | LT Shackle Insulator |
| 2800 | X ARM ANGLE 65X65X6 mm V TYPE 11kV |
| 2801 | X ARM CHANNEL 100X50 mm V TYPE 33kV |
| 2802 | Earth wire GI 7/1.6 mm 16 SWG |
| 2803 | EARTHING ROD MS 20X2500mm |
| 2804 | GI WIRE 4mm/8mm SWG |
| 2805 | GI WIRE 5mm/6 SWG |
| 2806 | STAY SET GI 20X1800mm |
| 2807 | STAY WIRE GI 7/4.0 mm 7/8 SWG |
| 2808 | ACSR RABBIT |
| 2809 | ACSR PANTHER |
| 2810 | Bolt & Nut 150x12 mm |
| 2811 | Bolt & Nuts 50x16 mm |
| 2812 | Eye Bolt 190x16 mm With Nut & Bolt |
| 2813 | Bracing Clamp SP-72 |
| 2814 | LT Shackle Insulator Clamp |
| 2815 | Holding Clamp FPR GI Pipe 8/10'' & MS Channel |
| 2816 | E- CLAMP |
| 2817 | F Clamp |
| 2818 | EARTH WIRE CLAMP FOR SP-55 WITHN/B |
| 2819 | PP & CLAMP WITH N&B ST POLE SP-55 |
| 2820 | EARTH WIRE CLAMP FOR SP-23 WITHN/B |
| 2821 | PP & CLAMP WITH N&B ST POLE SP-72 |
| 2822 | STAY CLAMP FOR SP-72 WITH N/B |
| 2823 | PP & CLAMP WITH N&B ST POLE SP-23 |
| 2824 | NUMBER PLATE WITH CLAMP |
| 2825 | Danger Board With Clamp N&B |
| 2826 | BRACING CLAMP BOTTOM FOR SP-23WITH N/B |
| 2827 | Bolt & Nuts off Size |
| 2828 | Cable Holding Clamp with N&B of Size |
| 2829 | PG Clamp For panther |
| 2830 | KM-21 G.I. Pipe 6\\" dia 3 meter long |
| 2831 | STAY CLAMP FOR SP-55 WITH NUT & BOLT |
| 2832 | Earth Wire Clamp |
| 2833 | 33 KV Mid Span Jointing Kit |
| 2834 | 33KV Biometric crimping Lug |
| 2835 | 33 KV IPC with Al. Ball for Earthing |
| 2836 | 33 KV Tension clamp with Bail & IPC |
| 2837 | 33 KV IPC for covered to covered conduct |
| 2838 | 33 KV IPC for covered to Bare conductor |
| 2839 | 33 KV Cable Ties for Insulator |
| 2840 | Concrete route marker for HT cable |
| 2841 | PP & CLAMP WITH NUT & BOLT FORGUARDING |
| 2842 | 33 KV straight Through 1x630 sqmm |
| 2843 | Disc fitting for Panther 120 KN |
| 2844 | PP CLAMP FOR SPECIAL TYPEBRACKET |
| 2845 | 33KV AAAC COVERED COND. AL-59,241SQ.MM. |
| 2846 | Cable Jointing Kit 1x630 Indoor |
| 2847 | Cable Jointing Kit 1x630 Outdoor |
| 2848 | 33 KV XLPE Cable AL 1x630 sqmm - D |
| 2849 | 33 KV 630 Amp 3 Way RMU |
| 2850 | ALUMINIUM BINDING WIRE |
| 2851 | BARBED WIRE |
| 2852 | Stone Pad 300x300x75mm |
| 2853 | Erection of 33/11kV SUBSTATION7.2.1 (DSR CODE 2014) |
| 2854 | NSI_EARTH FILLING |
| 2855 | CEMENT CONCRETING WORK IN RATIO 1:4:8 |
| 2856 | CEMENT CONCRETING WORK IN RATIO 1:2:4 |
| 2857 | BRICK WORK IN 1:4 RATIO |
| 2858 | CEMENT PLASTER WORK |
| 2859 | FENCING OF YARD |
| 2860 | RCC 1:1.5:3 |
| 2861 | MAKING CABLE TRENCH |
| 2862 | BRICK WORK 1:6 SUB STRUCTURE |
| 2863 | BRICK WORK 1:6 SUPER STRUCTURE |
| 2864 | CC WORK 1:1.5:2 |
| 2865 | SUPPLY&ERRECT GRAVEL PITCHING 1/2\\"- 3/4\\" |
| 2866 | ELECTRICAL INSPECTION FEE |
| 2867 | SPECIAL EARTHING |
| 2868 | FABRICATION OF STEEL |
| 2869 | FIXING OF GI PIPE |
| 2870 | ERECTION OF SINGLE SP-10 POLE |
| 2871 | ERECTION OF SP-55 DOUBLE POLE |
| 2872 | PAINTING OF SP-10 POLE |
| 2873 | PAINTING OF SP-55 POLE |
| 2874 | LAYING OF LT PVC CABLES(» 150 SQMM) |
| 2875 | LAYING OF U/G 11 KV CABLE IN TRENCH |
| 2876 | LAYING OF U/G 33 KV CABLE IN TRENCH |
| 2877 | FIXING OF LIGHTNING ARRESTOR |
| 2878 | FIXING OF 11 KV XLPE JOINTING KIT |
| 2879 | FIXING OF 33 KV XLPE JOINTING KIT |
| 2880 | CARTAGE OF PETTY MATERIAL,0-20 KM |
| 2881 | CARTAGE 11 KV PANELS, 0-20 KM |
| 2882 | CARTAGE OF PANELS, 0-20 KM |
| 2883 | CARTAGE 10/12.5 MVA POWER T/ F(0-20KM) |
| 2884 | MANUAL SHIFTING OF CONTROL PANEL |
| 2885 | ERECTION OF POWER T/F(12.5/10 MVA) |
| 2886 | ESCAVATION OF EARTH FOR STRUCT. ERECTION |
| 2887 | GROUTING OF STRUCTURE IN CC 1:3:6 |
| 2888 | FIXING OF 33 KV ISOLATOR VERTICAL TYPE |
| 2889 | LAYING OF CONTROL CABLE |
| 2890 | LAYING OF EARTH MAT |
| 2891 | EARTHING OF STRUCTURE USING GI STRIP |
| 2892 | COMM.OF 33/11KV VCB PANEL |
| 2893 | COMPLETE TESTING WIRING |
| 2894 | ERECTION & LAYING OF LT XLPE CABLE 2X6 |
| 2895 | INST. & FIXING OF CHEMICAL EARTHING |
| 2896 | INSTALLATION OF LINE/ BUS ISOLATOR |
| 2897 | INSTALLATION OF DCDB INCLUDING TESTING |
| 2898 | INSTALLATION OF ACDB INCLUDING TESTING |
| 2899 | ERECTION OF 33/0.433KV S/S TRANSFORMER |
| 2900 | ERECTION OF FLEXIBLE CU. CONN.500X50 MM |
| 2901 | ERECTION OF STAY POST |
| 2902 | ERRECTION OF 33KV PT |
| 2903 | ERREC. 12.65kV 4800kVAr, CAPACITOR BANK |
| 2904 | ERREC. 11KV, 630 AMP, OFF LOAD ISOLATOR |
| 2905 | ERECTION OF 110V BATTERY SET(300AH) |
| 2906 | ERECTION OF 110V BATTERY CHARGER(300AH) |
| 2907 | FIXING OF 11 KV FUSE SET |
| 2908 | FIXING OF 33 KV FUSE SET |
| 2909 | LAYING OF 4X10SQ MM LT PVC CABLE |
| 2910 | ERECTION OF EARTHING ELECTRODE&STRIP50X6 |
| 2911 | FIXING OF SODIUM/LED LIGHT AT YARD |
| 2912 | INSTALLATION OF FIRE EXTINGUISHERS |
| 2913 | ERECTION OF NAME PLATES |
| 2914 | ERECTION OF T&P ITEMS |
| 2915 | ERECTION OF MISC. GI STRUCTURES |
| 2916 | SHIFTING OF T/F B WORK |
| 2917 | Erection of 33kV LINE7.2.1 (DSR CODE 2014) |
| 2918 | NSI_EARTH FILLING |
| 2919 | EXACVATION FOR FOUNDATION |
| 2920 | CEMENT CONCRETING WORK IN RATIO1:4:8 |
| 2921 | CEMENT CONCRETING WORK IN RATIO1:2:4 |
| 2922 | BRICK WORK IN 1:4 RATIO |
| 2923 | CEMENT PLASTER WORK |
| 2924 | ELECTRICAL INSPECTION FEE |
| 2925 | ERECTION OF EARTHING ROAD |
| 2926 | FABRICATION OF STEEL |
| 2927 | FIXING OF GI PIPE |
| 2928 | FIXING OF RCC CABLE ROUTE MARKER |
| 2929 | ERECTION OF 33 KV STAY SET |
| 2930 | ERECTION OF SINGLE SP-55 POLE |
| 2931 | ERECTION OF SINGLE SP-72 POLE |
| 2932 | ERECTION OF SP-55 DOUBLE POLE |
| 2933 | ERECTION OF SP-72 DOUBLE POLE |
| 2934 | ERECTION OF SP-72(11KV/33 KV) FOUR POLE |
| 2935 | ERECTION OF BRACKET IN 11 KV LINE |
| 2936 | LAYING OF PANTHER CONDUCTOR IN HT LINE |
| 2937 | GUARDING OF 33 KV LINE |
| 2938 | FIXING OF 33 KV XLPE JOINTING KIT |
| 2939 | CARTAGE SP-21/23 POLE, 0-20 KM |
| 2940 | CARTAGE SP-33 POLE, 0-20 KM |
| 2941 | CARTAGE SP-55 POLE, 0-20 KM |
| 2942 | CARTAGE SP-72 POLE, 0-20 KM |
| 2943 | CARTAGE OF PATTY MATERIAL, 0-20 KM |
| 2944 | HEADLOAD CARTAGE SP-21/23POLE(0-1 KM) |
| 2945 | HEADLOAD CARTAGE SP-33 POLE(0-1 KM) |
| 2946 | HEADLOAD CARTAGE SP-55 POLE(0-1 KM) |
| 2947 | HEADLOAD CARTAGE SP-72 POLE(0-1 KM) |
| 2948 | HEADLOAD CARTAGE OFMATERIAL(0-1 KM) |
| 2949 | ESCAVATION OF EARTH FOR STRUCT.ERECTION |
| 2950 | ROAD CUTTING AND REPAIRING |
| 2951 | Supply & LAYING OF HDPE PIPE |
| 2952 | FIXING OF 33 KV TENSION CLAMP WITHIPC |
| 2953 | FIXING OF 33 KV IPC FOR CC TO CCCOND. |
| 2954 | FIXING OF 33 KV IPC FOR CC TO BARECOND. |
| 2955 | FIXING OF 33 KV MID SPAN JOINTINGKIT |
| 2956 | FIXING OF 33 KV BIMETALIC LUG |
| 2957 | FIXING OF IPC WITH AL. BAIL FOREARTHING |
| 2958 | LAYING OF 33KV CABLE FOR POLERISING O/H |
| 2959 | FIXING OF 33KV CABLE TIES |
| 2960 | LAYING SPREADING,STRINGING AAAC CONDUCT. |
| 2961 | COMPLETE TESTING WIRING |
| 2962 | MAKING LOOP OF 33 KV XLPE CABLE |
| 2963 | LAYING 33 KV CABLE IN HDPE PIPE HDD MACH. |
| 2964 | MANUAL DIGGING OF CABLE TRENCHUPTO 1 MT |
| 2965 | SUPPLY & LAYING OF HDPE PIPE INOPEN CUT |
| 2966 | PAINTING OF SINGLE POLE (SP-72) |
| 2967 | PAINTING OF DOUBLE POLE (SP-55) |
| 2968 | PAINTING OF DOUBLE POLE (SP-72) |
| 2969 | PAINTING OF FOUR POLE (SP-72) |
| 2970 | FIXING OF G.I PIPE 3 MTR LONG |
| 2971 | SHIFTING REALIGNMENT 11KV SP,DP/ LT LINE |
| 2972 | DELTA EARTHING WITH MS ROUNDELECTROD/GI |
| 2973 | FIXING OF 33 KV 630 AMP 3 WAY RMU |
| 2974 | LOOPING AND CHOPPING OF TREEBRANCHES |
| 2975 | Annual Maintenance Charges (AMC) and O&M of Project for 5 yearson per year basis. |
| 2976 | Control RoomEarth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 2977 | Filling available excavated earth (excluding rock) in trenches, plinth sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5m |
| 2978 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also includingramming and watering of the earth in layers not exceeding 20cm in trenches, plinth, sides of foundation etc. complete |
| 2979 | Supplying and filling in plinth with Jamuna sand under floors including, watering, ramming consolidating and dressing complete. |
| 2980 | Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1:2 (1 cement : 2 Coarse sand) to match the existing floor : With Chlorpyriphos/Lindane E.C. 20% with 1% concentration. |
| 2981 | Providing and laying in position cement concrete in ratio 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 2982 | Providing and laying in position cement concrete in ratio 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 40 mm nominal size) of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 2983 | Providing and laying in position specified grade of reinforced cement concrete in ratio 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level |
| 2984 | Reinforced cement concrete work in 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level excluding cost of centering, shuttering, finishing and reinforcement. |
| 2985 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size). |
| 2986 | Centering and shuttering including strutting, propping etc. and removal of form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 2987 | Centering and shuttering including strutting, propping etc. and removal of form for Suspended floors, roofs, landings, balconies and access platform. |
| 2988 | Centering and shuttering including strutting propping etc. and removal of form for: Shelves (Cast in situ) |
| 2989 | Centering and shuttering including strutting, propping etc. and removal of form for Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 2990 | Centering and shuttering including strutting, propping etc. and removal of form for Columns, Pillars, Piers, Abutments, Posts and Struts. |
| 2991 | Centering and shuttering including strutting, propping etc. and removal of form for : Edges of slabs and breaks in floors and walls. Under 20 cm wide |
| 2992 | Centering and shuttering including strutting, propping etc. and removal of form for Weather shade, Chajjas, corbels etc., including edges. |
| 2993 | Providing, hoisting and fixing up to floor five level precast reinforced cement concrete in small lintels not exceeding 1.5m clear span up to floor five level including the cost of required centering, shuttering and finishing smooth with 6 mm thick cement plaster 1:3 (1 cement : 3 fine sand) on exposed surfaces but excluding the cost of reinforcement with 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size). |
| 2994 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.Thermo-Mechanically Treated bars. |
| 2995 | Smooth finishing of the exposed surface of R.C.C. work with 6 mm thick cement mortar 1:3 (1 Cement : 3 fine sand). |
| 2996 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 2997 | Brick work with F.P.S. bricks of class designation 75 in foundation and plinth in Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 2998 | Brick work with F.P.S. bricks of class designation 75 in superstructure above plinth level up to floor V level in all shapes and sizes in Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 2999 | Half brick masonry with F.P.S. brick of class designation 75 in foundations and plinth in. cement mortar 1:4 (1 cement : 4 coarse sand) |
| 3000 | Half brick masonry with F.P.S. bricks of class designation 75 in superstructure above plinth level up to floor V level. |
| 3001 | Providing and fixing 18mm thick gang saw cut mirror polished premoulded and prepolished) machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edge to give high gloss finish etc. complete at all levels. Granite of any colour and shade. Area of slab upto 0.50 sqm |
| 3002 | Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge.Granite work |
| 3003 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS:15622(thickness to be specified by the manufacturer), of approved make,in all colours, shades except burgundy, bottle green, black of any size asapproved by Engineer-in-Charge, in skirting, risers of steps and dados,over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) andjointing with grey cement slurry @ 3.3kg per sqm, including pointingin white cement mixed with pigment of matching shade complete. |
| 3004 | Providing and fixing fly proof galvanized M.S. wire gauge to windows and clerestory windows using wire gauge with average width of aperture 1.4mm in both directions with wire of dia 0.63 mm all complete.With 12 mm mild steel U beading. |
| 3005 | Providing and fixing ISI marked aluminium butt hinges anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete: 100x63x4 mm |
| 3006 | Providing and fixing aluminium sliding door bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc. complete : 250x16 mm |
| 3007 | Providing and fixing aluminium tower bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade with necessary screws etc. complete : 150x10 mm |
| 3008 | Providing and fixing aluminium handles ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete :100 mm |
| 3009 | Providing and fixing aluminium hanging floor door stopper ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade with necessary screws etc. complete. Single rubber stopper |
| 3010 | Providing and fixing aluminium casement stays ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade with necessary screws etc. complete. |
| 3011 | Strutural steel work riveted bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete: |
| 3012 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp of internal dia 140mm, 73mm height, top lid of 1.5mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3mm dia. round headed screws, one lock at the corners. Clamp shall be made of 12mm dia M.S. bar bent to shape as per standard drawing. |
| 3013 | Steel work welded in built up sections/ framed work including cutting,hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. |
| 3014 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement including cement slurry, but excluding the cost of nosing of steps etc. complete.40mm thick with 20mm nominal size stone aggregate. |
| 3015 | Providing and fixing glass strips in joints of terrazo/ cement concrete floors.40 mm wide and 4 mm thick. |
| 3016 | Providing and laying Ceramic glazed floor tiles 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick Cement Mortar 1:4 (1 Cement : 4 Coarse sand) including pointing the joints with white cement and matching pigment etc., complete. |
| 3017 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600x600 mm |
| 3018 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes.75 mm diameter |
| 3019 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes.110 mm diameter |
| 3020 | 12 mm cement plaster of mix 1:6 (1 cement: 6 coarse sand) |
| 3021 | 15mm cement plaster on rough side of single or half brick wall of mix: 1:6 (1cement :6 coarse sand) |
| 3022 | 12 mm Cement plaster 1:3 (1 cement: 3 coarse sand) finished with a floating coat of neat cement. |
| 3023 | 6mm Cement plaster finished with a floating coat of neat cement 1:3. |
| 3024 | Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete |
| 3025 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade.New work (two or more coats) over and including priming coat with cement primer. |
| 3026 | Finishing walls with textured exterior paint of required shade for new work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including base coat of water proofing cement paint applied @ 2.20kg/10 sqm. |
| 3027 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work |
| 3028 | Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete including cutting and making good the walls and floors wherever required :White Vitreous china Orissa pattern W.C. pan of size 580x440mm with integral type foot rests. |
| 3029 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required :One urinal basin with 5 litre white P.V.C. automatic flushing cistern |
| 3030 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps,32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require :White Vitreous China Flat back wash basin size 550x400 mm with single 15 mm C.P. brass pillar tap. |
| 3031 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete.Flexible pipe-----32 mm dia |
| 3032 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 3033 | Providing and fixing PTMT towel ring trapezoidal shape 215 mm long, 200 mm wide with minimum distances of 37 mm from wall face with concealed fittings arrangement of approved quality and colour, weighing not less than 88 gms. |
| 3034 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply and all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall..15 mm nominal dia Pipes |
| 3035 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply and all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work -Exposed on wall 20 mm nominal dia Pipes |
| 3036 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :25 mm nominal bore |
| 3037 | Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete :15 mm nominal bore |
| 3038 | Providing and fixing uplasticised PVC connection pipe with brass unions : 30 cm length.15 mm nominal bore |
| 3039 | Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design :With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 |
| 3040 | Providing and fixing G.I. Union in G.I. pipe including cutting and threading the pipe and making long screws etc. complete (New work) :15 mm nominal bore |
| 3041 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 3042 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931: 15 mm nominal bore |
| 3043 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931: 15 mm nominal bore |
| 3044 | Providing and fixing PTMT grating of approved quality and colour. Circular type. 100 mm nominal dia |
| 3045 | Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighing not less than 106 gms. |
| 3046 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC/neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing and paneling to be paid for separately) : For.... fixed portion Powder coated aluminium (minimum thickness of powdercoating 50 micron) |
| 3047 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC/neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing and paneling to be paid for separately) : For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of PVC / neoprene gasket required (Fittings shall be paid for separately). Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 3048 | Providing and fixing 12mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge. Pre-laminated particle board with decorative lamination on both sides. |
| 3049 | Providing and fixing 100mm brass locks (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete. |
| 3050 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with PVC/ neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-incharge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 4 mm thickness |
| 3051 | Grading roof for water proofing treatment with Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 3052 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with moduler type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single core cable etc as required. Group B |
| 3053 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required :2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 3054 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 A switch |
| 3055 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 A socket outlet |
| 3056 | Supplying and fixing suitable size GI box with modular plate and cover in front on ...... providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection, painting etc. as required. |
| 3057 | Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. |
| 3058 | Supply and fixing following rating, 63 amps double pole, 240 volts, isolator in the existing MCB DB complete with connection, testing and commissioning etc. as required. |
| 3059 | Supply and fixing 5 amps to 32 amps rating, 240 volts, 'C' serise, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole and neutral |
| 3060 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar,interconnections, powder painted including earthing etc. as required. (But withoutMCB/RCCB/Isolator) 8 way , Double door |
| 3061 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan withBrush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2nos. canopies, shackle kit, safetyrope, copper winding, PowerFactor not less than 0.9, ServiceValue (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulationresistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 3062 | Supplying of Exhaust Fan 250 mm Sweep of Orient or equivalent make as approved by E.I. |
| 3063 | Supplying of 20 watt LED Tubelight Philps or equivalent make as approved by E.I. |
| 3064 | Engaging/S of suitable beldar for different type of works |
| 3065 | Engaging suitable electrician with kit for petty work. (Based on DSR Code 1001) |
| 3066 | Land Development workEarth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 3067 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also includingramming and watering of the earth in layers not exceeding 20cm in trenches, plinth, sides of foundation etc. complete |
| 3068 | Providing and laying in position cement concrete in ratio 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 3069 | Providing and laying in position cement concrete in ratio 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 40 mm nominal size) of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 3070 | Providing and laying in position specified grade of reinforced cement concrete in ratio 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level |
| 3071 | Reinforced cement concrete work in 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level excluding cost of centering, shuttering, finishing and reinforcement. |
| 3072 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size). |
| 3073 | Centering and shuttering including strutting, propping etc. and removal of form for Foundations, footings, bases of columns, etc. for mass concrete. |
| 3074 | Centering and shuttering including strutting, propping etc. and removal of form for Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 3075 | Centering and shuttering including strutting, propping etc. and removal of form for Columns, Pillars, Piers, Abutments, Posts and Struts. |
| 3076 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.Thermo-Mechanically Treated bars. |
| 3077 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 3078 | Brick work with F.P.S. bricks of class designation 75 in foundation and plinth in Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 3079 | Brick work with F.P.S. bricks of class designation 75 in superstructure above plinth level up to floor V level in all shapes and sizes in Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 3080 | Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement: 6 coarse sand: 12 graded stone aggregate 20 mm nominal size) upto plinth level with: Cement mortar 1 :6 (1 cement : 6 coarse sand) |
| 3081 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS:15622(thickness to be specified by the manufacturer), of approved make,in all colours, shades except burgundy, bottle green, black of any size asapproved by Engineer-in-Charge, in skirting, risers of steps and dados,over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) andjointing with grey cement slurry @ 3.3kg per sqm, including pointingin white cement mixed with pigment of matching shade complete. |
| 3082 | Steel work welded in built up sections/ framed work including cutting,hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. |
| 3083 | Brick on edge flooring with bricks of class designation 7 .5 on a bed of 12 mm cement mortar, including filling the joints with same mortar, with common burnt clay non modular bricks: 11.1.1 1 :4 (1 cement : 4 coarse sand) |
| 3084 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.(i) Single socketed pipes.110 mm diameter |
| 3085 | 12 mm cement plaster of mix 1:6 (1 cement: 6 coarse sand) |
| 3086 | 15mm cement plaster on rough side of single or half brick wall of mix: 1:6 (1cement :6 coarse sand) |
| 3087 | Finishing walls with textured exterior paint of required shade for new work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including base coat of water proofing cement paint applied @ 2.20kg/10 sqm. |
| 3088 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work |
| 3089 | Preparation and consolidation of sub grade with power road roller of 8 to12 tonne capacity after excavating earth to an average of 22.5 cm depth,dressing to camber and consolidating with road roller including makinggood the undulations etc. and re-rolling the sub grade and disposal ofsurplus earthwith lead upto 50 metres. |
| 3090 | Supplying and stacking at site. 53 mm to 22.4 mm size stone aggregate |
| 3091 | Laying, spreading and compacting stone aggregate of specified sizesto WBM specifications in uniform thickness, hand picking, rolling with 3wheeled road/vibratory roller 8-10 tonne capacity in stages to proper grade and camber, applying and brooming requisite type of screening / binding material to fill up interstices of coarse aggregate, watering and compacting to the required density . |
| 3092 | Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5 mm), including making drainage opening wherever required complete etc. as per direction of Engineerin- charge (length of finished kerb edging shall be measured to calculate volume for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge). |
| 3093 | Providing and laying factory made chamfered edge Cement Concretepaver blocks in footpath, parks, lawns, drive ways or light traffic parkingetc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50 mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge.80 mm thick C.C. paver block of M-35 grade with approved colour design and pattern. |
| 3094 | Providing and laying Non Pressure NP-4 class (Heavy duty) R.C.C. pipesincluding collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. Complete 1200 mm dia RCC pipes. (Laying by manual/ machanicalmeans) |
| 3095 | Supply of 33/11kV SUBSTATIONT/F 33/11 kV 12.5MVA |
| 3096 | 8 m. LONG STP 410 SP-10 (BPHD GAL.) |
| 3097 | 11 MTR. LONGSTP 410 SP-55(BPHD GAL.) |
| 3098 | MS ROUND 32 mm |
| 3099 | 11 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 3100 | 33 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 3101 | DISC FIT. B&S TYPE FOR PANTHER 90 KN |
| 3102 | DISC FIT. B&S TYPE WEASEL/RABBIT 45 KN |
| 3103 | 9 KV 10 KA Polymeric Lightning Arrestor |
| 3104 | EARTHING ROD MS 20X2500mm |
| 3105 | GI WIRE 5mm/6 SWG |
| 3106 | STAY SET GI 16X1800mm |
| 3107 | STAY WIRE GI 7/3.15mm 7/10SWG |
| 3108 | ACSR DOG |
| 3109 | ACSR PANTHER |
| 3110 | CABLE AL 3X300 SQ. mm XLPE 11 kV |
| 3111 | CABLE AL 3X400 SQ. mm XLPE 11 kV |
| 3112 | CABLE AL 1X630 SQ. mm XLPE 11 kV |
| 3113 | CABLE AL 3X70 SQ. mm XLPE 33kV |
| 3114 | J/KIT FOR 3X300mm* 11kV XLPE CABLE(O/D) |
| 3115 | J/KIT FOR 3X400mm° 11kV XLPE CABLE (O/D) |
| 3116 | CONTROL CABLE 10X2.5 SQ. mm. |
| 3117 | CONTROL CABLE 2X2.5 SQ. mm. |
| 3118 | CONTROL CABLE 4X2.5 SQ. mm. |
| 3119 | CONTROL CABLE 6X2.5 SQ. mm. |
| 3120 | LT PVC CABLE 2X6 SQ.mm (ARMORED) |
| 3121 | LT XLPE CABLE 3.5.X 70 SQ. mm. |
| 3122 | LT PVC CABLE 4X10 SQ.mm |
| 3123 | 33 KV H.S. Cable J/K 3x70 sq. mm (O/D) |
| 3124 | 110 V BATTERY SET(300 AH) |
| 3125 | 110V BATTERY CHARGER(300 AH) |
| 3126 | JUNCTION BOX FOR 33kV PT |
| 3127 | 33kV PT of RATIO 33 kV/110V OUTDOOR |
| 3128 | 33 kV LIGHTNING ARRESTER |
| 3129 | PANTHER TO PANTHER CTYPE WEDGE CONNECTOR |
| 3130 | 33 kV FUSE SET |
| 3131 | 33/0.433 KV, 63 KVA Station Transformer |
| 3132 | MS STRUCTURE (ANGLE ,CHANNEL ETC.) |
| 3133 | GI ITEM (Rail,Joist,ChanneI,Angle) |
| 3134 | Cable Holding clamp with N&B |
| 3135 | Holding Clamp FPR GI Pipe 8/10\\"& MS Ch. |
| 3136 | PG CLAMP ALU ALLOY PANTHER TO DOG |
| 3137 | Stay Clamp for SP-55 With Nut & Bolt |
| 3138 | 33KV ISOLATOR CONN.CLAMP FOR PANTHER,N&B |
| 3139 | 33 KV ISOLATOR CLAMP FOR ACSR DOG |
| 3140 | PERFORATED TRAY 400MM FOR CABLE TRENCH |
| 3141 | PERFORATED TRAY 200MM FOR CABLE TRENCH |
| 3142 | PERFORATED TRAY 100MM FOR CABLE TRENCH |
| 3143 | FLEXIBLE COOPER CONNECTOR SOXSOMM |
| 3144 | DANGER BOARD |
| 3145 | GI Pipe 4\\"' Dia |
| 3146 | 250 W hpsv/led lamp with contrl gear |
| 3147 | Insulated Electrical Piller Taparia |
| 3148 | 11 KV Fuse Set |
| 3149 | KM-21 G.I. Pipe 6\\" dia 3 meter long |
| 3150 | Conne.Suitable for Panther for LA |
| 3151 | Connector of Power T/F HV Side |
| 3152 | Connector of Power T/F LV Side |
| 3153 | GI STRIP 65MMX6MM |
| 3154 | “HT' WARNING TAPE |
| 3155 | 11KV,630Amp off load Isolator |
| 3156 | Thimble junction box for cable support |
| 3157 | 33KV C&R PANEL I/C-D |
| 3158 | 33KV C&R PANEL O/G-D |
| 3159 | 33KV C&R PANEL BUS COUPLER-D |
| 3160 | 11KV C&R PANEL I/C-D |
| 3161 | 11KV C&R PANEL O/G-D |
| 3162 | 11KV C&R PANEL BUS COUPLER-D |
| 3163 | PP clamp with N&B (GI) |
| 3164 | G.I.Strip 35x4mm |
| 3165 | 11 KV HS cable END T/K 1x630 mm* O/D |
| 3166 | Cable Jointing Kit 1x630 Outdoor |
| 3167 | 33 KV XLPE Cable AL 1x630 sq. mm -D |
| 3168 | Iron Clad 30 Amp Switch |
| 3169 | Connector Suit for CT/PT for Panther/Dog |
| 3170 | 33 KV Isolator Vertical Type |
| 3171 | 11kv 3P(400A)3pin vert. mount GO AB TPMO |
| 3172 | Indoor type auto power factor controller |
| 3173 | 12.65kV, 4800kVAr, Capacitor bank |
| 3174 | 12KV C&R Panel with SCADA(Capacitor) |
| 3175 | 36KV 1250A Gang ope PMA VCB(I/C) |
| 3176 | 36KV 1250A Gang ope PMA VCB(O/G) |
| 3177 | 12KV 1250A Gang ope PMA VCB(I/C) |
| 3178 | 12KV 1250A Gang ope PMA VCB(O/G) |
| 3179 | 12KV 1250A Gang ope PMA VCB(Capacitor) |
| 3180 | 12KV 1250A Gang ope PMA VCB(B/C) |
| 3181 | 36KV 1250A Gang ope PMA VCB(B/C) |
| 3182 | 33kv Bus isolator manual&motor,SCADA COM |
| 3183 | 33kv line isolator manual&motor,SCADA co |
| 3184 | 11kv isolator manual&motor,SCADA comp. |
| 3185 | Wire Mesh Fencing |
| 3186 | 110V DC DISTRIBUTION BOARD-D |
| 3187 | Name Plate of Equip. TG,LI,BI,CT,CB ect. |
| 3188 | GI STRIP 50X6 MM |
| 3189 | SUNDRISE ITEM LUG GLADE ETC |
| 3190 | Alluminium Lug |
| 3191 | Stone Pad 300x300x75mm |
| 3192 | Connector Suitable. Panther for VCB |
| 3193 | Dustbin 20 Litre Capacity (Colour Green) |
| 3194 | RUBBER MAT(INSULATED )1MX1MX3MM |
| 3195 | Fire Extingushier |
| 3196 | Torch 3 Cell |
| 3197 | 33 KV Hand Gloves |
| 3198 | Earth Chain |
| 3199 | First aid box |
| 3200 | SHOCK TREATMENT CHART |
| 3201 | SHUT DOWN/ BREAK DOWN BOARD |
| 3202 | WALL CLOCK |
| 3203 | D-SPANNER SET |
| 3204 | PIPE WRENCH 12\\" |
| 3205 | 2.5 KV MEGGAR DIGITAL |
| 3206 | EARTH MEGGAR DIGITAL |
| 3207 | INSTRUCTION BOARD |
| 3208 | MAXIMUM & MINIMUM DISPLAY BOARD |
| 3209 | SUB STATION NAMED BOARD |
| 3210 | Portable Foam Type Fire Extinguisher SLT |
| 3211 | Single Line Diagram Board |
| 3212 | Door Mat |
| 3213 | Name plate of feeder |
| 3214 | Name plate of station \iI |
| 3215 | 11KV Danger Board with Clamp |
| 3216 | 33 KV Danger Board with Clamp |
| 3217 | Steel Almirah |
| 3218 | Office Table size (4x2.5) |
| 3219 | Fire Bucket Stand with Buckets |
| 3220 | Steel Cabinet |
| 3221 | Steel office Table |
| 3222 | Steel office chair Godrej |
| 3223 | Meggar 5 KV Digital |
| 3224 | Fire Bucket stand of MS angle |
| 3225 | Supply of 33kV LINE8.5 MRT. LONG STP 410 SP-23(BPHD GAL.) |
| 3226 | 11 MTR. LONGSTP 410 SP-55(BPHDGAL.) |
| 3227 | STP 13.0 M-IS 410 SP-72 (BPHD GAL.) |
| 3228 | MS ANGLE 65X65X6 mm |
| 3229 | MS CHANNEL 100X50 mm |
| 3230 | MS CHANNEL 125X65 mm |
| 3231 | 11 kV POLYMER DISC INSULATOR(B&S) TYPE |
| 3232 | 33 kV POLYMER DISC INSULATOR(B&S) TYPE |
| 3233 | 11 kV POLYMER PIN INSULATOR WITH PIN |
| 3234 | 33kV 10KN POLYMER PIN INSULATORWITH PIN |
| 3235 | DISC FIT. B&S TYPE DOG/RACOON 70KN |
| 3236 | DISC FIT. B&S TYPE WEASEL/RABBIT45 KN |
| 3237 | LT Shackle Insulator |
| 3238 | X ARM ANGLE 65X65X6 mm V TYPE 11kV |
| 3239 | X ARM CHANNEL 100X50 mm V TYPE 33kV |
| 3240 | Earth wire GI 7/1.6 mm 16 SWG |
| 3241 | EARTHING ROD MS 20X2500mm |
| 3242 | GI WIRE 4mm/8mm SWG |
| 3243 | GI WIRE 5mm/6 SWG |
| 3244 | STAY SET GI 20X1800mm |
| 3245 | STAY WIRE GI 7/4.0 mm 7/8 SWG |
| 3246 | ACSR RABBIT |
| 3247 | Bolt & Nut 150x12 mm |
| 3248 | Bolt & Nuts 50x16 mm |
| 3249 | Eye Bolt 190x16 mm With Nut & Bolt |
| 3250 | Bracing Clamp SP-72 |
| 3251 | LT Shackle Insulator Clamp |
| 3252 | Holding Clamp FPR GI Pipe 8/10'' & MS Channel |
| 3253 | E- CLAMP |
| 3254 | F Clamp |
| 3255 | EARTH WIRE CLAMP FOR SP-55 WITHN/B |
| 3256 | PP & CLAMP WITH N&B ST POLE SP-55 |
| 3257 | EARTH WIRE CLAMP FOR SP-23 WITHN/B |
| 3258 | PP & CLAMP WITH N&B ST POLE SP-72 |
| 3259 | STAY CLAMP FOR SP-72 WITH N/B |
| 3260 | PG Clamp For Dog Conductor |
| 3261 | PP & CLAMP WITH N&B ST POLE SP-23 |
| 3262 | NUMBER PLATE WITH CLAMP |
| 3263 | Danger Board With Clamp N&B |
| 3264 | BRACING CLAMP BOTTOM FOR SP-23WITH N/B |
| 3265 | Bolt & Nuts off Size |
| 3266 | Cable Holding Clamp with N&B of Size |
| 3267 | KM-21 G.I. Pipe 6\\" dia 3 meter long |
| 3268 | STAY CLAMP FOR SP-55 WITH NUT & BOLT |
| 3269 | Earth Wire Clamp |
| 3270 | 33 KV Mid Span Jointing Kit |
| 3271 | 33KV Biometric crimping Lug |
| 3272 | 33 KV IPC with Al. Ball for Earthing |
| 3273 | 33 KV Tension clamp with Bail & IPC |
| 3274 | 33 KV IPC for covered to covered conduct |
| 3275 | 33 KV IPC for covered to Bare conductor |
| 3276 | 33 KV Cable Ties for Insulator |
| 3277 | Concrete route marker for HT cable |
| 3278 | PP & CLAMP WITH NUT & BOLT FORGUARDING |
| 3279 | 33 KV straight Through 1x630 sqmm |
| 3280 | Disc fitting for Panther 120 KN |
| 3281 | PP CLAMP FOR SPECIAL TYPEBRACKET |
| 3282 | 33KV AAAC COVERED COND. AL-59,241SQ.MM. |
| 3283 | Cable Jointing Kit 1x630 Outdoor |
| 3284 | 33 KV XLPE Cable AL 1x630 sqmm - D |
| 3285 | ALUMINIUM BINDING WIRE |
| 3286 | BARBED WIRE |
| 3287 | Stone Pad 300x300x75mm |
| 3288 | Erection of 33/11kV SUBSTATION7.2.1 (DSR CODE 2014) |
| 3289 | NSI_EARTH FILLING |
| 3290 | CEMENT CONCRETING WORK IN RATIO 1:4:8 |
| 3291 | CEMENT CONCRETING WORK IN RATIO 1:2:4 |
| 3292 | BRICK WORK IN 1:4 RATIO |
| 3293 | CEMENT PLASTER WORK |
| 3294 | FENCING OF YARD |
| 3295 | RCC 1:1.5:3 |
| 3296 | MAKING CABLE TRENCH |
| 3297 | BRICK WORK 1:6 SUB STRUCTURE |
| 3298 | BRICK WORK 1:6 SUPER STRUCTURE |
| 3299 | CC WORK 1:1.5:2 |
| 3300 | SUPPLY&ERRECT GRAVEL PITCHING 1/2\\"- 3/4\\" |
| 3301 | ELECTRICAL INSPECTION FEE |
| 3302 | SPECIAL EARTHING |
| 3303 | FABRICATION OF STEEL |
| 3304 | FIXING OF GI PIPE |
| 3305 | ERECTION OF SINGLE SP-10 POLE |
| 3306 | ERECTION OF SP-55 DOUBLE POLE |
| 3307 | PAINTING OF SP-10 POLE |
| 3308 | PAINTING OF SP-55 POLE |
| 3309 | LAYING OF LT PVC CABLES(» 150 SQMM) |
| 3310 | LAYING OF U/G 11 KV CABLE IN TRENCH |
| 3311 | LAYING OF U/G 33 KV CABLE IN TRENCH |
| 3312 | FIXING OF LIGHTNING ARRESTOR |
| 3313 | FIXING OF 11 KV XLPE JOINTING KIT |
| 3314 | FIXING OF 33 KV XLPE JOINTING KIT |
| 3315 | CARTAGE OF PETTY MATERIAL,0-20 KM |
| 3316 | CARTAGE 11 KV PANELS, 0-20 KM |
| 3317 | CARTAGE OF PANELS, 0-20 KM |
| 3318 | CARTAGE 10/12.5 MVA POWER T/ F(0-20KM) |
| 3319 | MANUAL SHIFTING OF CONTROL PANEL |
| 3320 | ERECTION OF POWER T/F(12.5/10 MVA) |
| 3321 | ESCAVATION OF EARTH FOR STRUCT. ERECTION |
| 3322 | GROUTING OF STRUCTURE IN CC 1:3:6 |
| 3323 | FIXING OF 33 KV ISOLATOR VERTICAL TYPE |
| 3324 | LAYING OF CONTROL CABLE |
| 3325 | LAYING OF EARTH MAT |
| 3326 | EARTHING OF STRUCTURE USING GI STRIP |
| 3327 | COMM.OF 33/11KV VCB PANEL |
| 3328 | COMPLETE TESTING WIRING |
| 3329 | ERECTION & LAYING OF LT XLPE CABLE 2X6 |
| 3330 | INST. & FIXING OF CHEMICAL EARTHING |
| 3331 | INSTALLATION OF LINE/ BUS ISOLATOR |
| 3332 | INSTALLATION OF DCDB INCLUDING TESTING |
| 3333 | INSTALLATION OF ACDB INCLUDING TESTING |
| 3334 | ERECTION OF 33/0.433KV S/S TRANSFORMER |
| 3335 | ERECTION OF FLEXIBLE CU. CONN.500X50 MM |
| 3336 | ERECTION OF STAY POST |
| 3337 | ERRECTION OF 33KV PT |
| 3338 | ERREC. 12.65kV 4800kVAr, CAPACITOR BANK |
| 3339 | ERREC. 11KV, 630 AMP, OFF LOAD ISOLATOR |
| 3340 | ERECTION OF 110V BATTERY SET(300AH) |
| 3341 | ERECTION OF 110V BATTERY CHARGER(300AH) |
| 3342 | FIXING OF 11 KV FUSE SET |
| 3343 | FIXING OF 33 KV FUSE SET |
| 3344 | LAYING OF 4X10SQ MM LT PVC CABLE |
| 3345 | ERECTION OF EARTHING ELECTRODE&STRIP50X6 |
| 3346 | FIXING OF SODIUM/LED LIGHT AT YARD |
| 3347 | INSTALLATION OF FIRE EXTINGUISHERS |
| 3348 | ERECTION OF NAME PLATES |
| 3349 | ERECTION OF T&P ITEMS |
| 3350 | ERECTION OF MISC. GI STRUCTURES |
| 3351 | SHIFTING OF T/F B WORK |
| 3352 | Erection of 33kV LINECEMENT CONCRETING WORK IN RATIO 1:4:8 |
| 3353 | ELECTRICAL INSPECTION FEE |
| 3354 | ERECTION OF EARTHING ROAD |
| 3355 | FABRICATION OF STEEL |
| 3356 | FIXING OF GI PIPE |
| 3357 | FIXING OF RCC CABLE ROUTE MARKER |
| 3358 | ERECTION OF 33 KV STAY SET |
| 3359 | ERECTION OF SINGLE SP-55 POLE |
| 3360 | ERECTION OF SINGLE SP-72 POLE |
| 3361 | ERECTION OF SP-55 DOUBLE POLE |
| 3362 | ERECTION OF SP-72 DOUBLE POLE |
| 3363 | ERECTION OF SP-72(11KV/33 KV) FOUR POLE |
| 3364 | ERECTION OF BRACKET IN 11 KV LINE |
| 3365 | GUARDING OF 33 KV LINE |
| 3366 | FIXING OF 33 KV XLPE JOINTING KIT |
| 3367 | CARTAGE SP-21/23 POLE, 0-20 KM |
| 3368 | CARTAGE SP-55 POLE, 0-20 KM |
| 3369 | CARTAGE SP-72 POLE, 0-20 KM |
| 3370 | CARTAGE OF PATTY MATERIAL, 0-20 KM |
| 3371 | HEADLOAD CARTAGE SP-21/23POLE(0-1 KM) |
| 3372 | HEADLOAD CARTAGE SP-55 POLE(0-1 KM) |
| 3373 | HEADLOAD CARTAGE SP-72 POLE(0-1 KM) |
| 3374 | HEADLOAD CARTAGE OFMATERIAL(0-1 KM) |
| 3375 | ESCAVATION OF EARTH FOR STRUCT.ERECTION |
| 3376 | ROAD CUTTING AND REPAIRING |
| 3377 | Supply & LAYING OF HDPE PIPE |
| 3378 | FIXING OF 33 KV TENSION CLAMP WITH IPC |
| 3379 | FIXING OF 33 KV IPC FOR CC TO CC COND. |
| 3380 | FIXING OF 33 KV IPC FOR CC TO BARE COND. |
| 3381 | FIXING OF 33 KV MID SPAN JOINTING KIT |
| 3382 | FIXING OF 33 KV BIMETALIC LUG |
| 3383 | FIXING OF IPC WITH AL. BAIL FOR EARTHING |
| 3384 | LAYING OF 33KV CABLE FOR POLE RISING O/H |
| 3385 | FIXING OF 33KV CABLE TIES |
| 3386 | LAYING SPREADING,STRINGING AAAC CONDUCT. |
| 3387 | COMPLETE TESTING WIRING |
| 3388 | MAKING LOOP OF 33 KV XLPE CABLE |
| 3389 | MANUAL DIGGING OF CABLE TRENCH UPTO 1 MT |
| 3390 | SUPPLY & LAYING OF HDPE PIPE IN OPEN CUT |
| 3391 | PAINTING OF SINGLE POLE (SP-72) |
| 3392 | PAINTING OF DOUBLE POLE (SP-55) |
| 3393 | PAINTING OF DOUBLE POLE (SP-72) |
| 3394 | PAINTING OF FOUR POLE (SP-72) |
| 3395 | FIXING OF G.I PIPE 3 MTR LONG |
| 3396 | SHIFTING REALIGNMENT 11KV SP,DP/ LT LINE |
| 3397 | DELTA EARTHING WITH MS ROUNDELECTROD/GI |
| 3398 | LOOPING AND CHOPPING OF TREEBRANCHES |
| 3399 | Annual Maintenance Charges (AMC) and O&M of Project for 5 yearson per year basis. |
| 3400 | Control RoomEarth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan), including dressing of sides and rammingof bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50m.All kinds of soil. |
| 3401 | Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also includingramming and watering of the earth in layers not exceeding 20cm in trenches, plinth, sides of foundation etc. complete |
| 3402 | Supplying and filling in plinth with Jamuna sand under floors, including watering, ramming, consolidating and dressing complete. |
| 3403 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level. 1:2:4 (1 Cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) |
| 3404 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level.1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40mm nominal size) |
| 3405 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate20 mm nominal size) |
| 3406 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level,excluding cost of centering, shuttering, finishing and reinforcement :1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate20 mm nominal size) |
| 3407 | Centering and shuttering including strutting, propping etc. and removal of form for :Foundations, footings, bases of columns, etc. for mass concrete |
| 3408 | Centering and shuttering including strutting, propping etc. and removal of form for: Suspended floors, roofs, landings, balconies and access platform |
| 3409 | Centering and shuttering including strutting, propping etc. and removal of form for:Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 3410 | Centering and shuttering including strutting, propping etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts |
| 3411 | Centering and shuttering including strutting, propping etc. and removal of form for:Edges of slabs and breaks in floors and walls.Under 20 cm wide. |
| 3412 | Centering and shuttering including strutting, propping etc. and removal of form for :Weather shade, Chajjas, corbels etc., including edges. |
| 3413 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete .Thermo-Mechanically Treated bars |
| 3414 | Smooth finishing of the exposed surface of R.C.C. work with 6 mm thick cement mortar 1:3 (1 Cement : 3 fine sand). |
| 3415 | Brick work with common burnt clay F.P.S. (non modular) bricks of classdesignation 7.5 in foundation and plinth in:Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 3416 | Brick work with common burnt clay F.P.S. (non modular) bricks of classdesignation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 3417 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level.Cement mortar 1:4 (1 cement :4 coarse sand) |
| 3418 | Providing and fixing Ist quality ceramic glazed wall tiles conforming toIS: 15622 (thickness to be specified by the manufacturer), of approvedmake, in all colours, shades except burgundy, bottle green, black ofany size as approved by Engineer-in-Charge, in skirting, risers of stepsand dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm,including pointing in white cement mixed with pigment of matching shadecomplete. |
| 3419 | Providing and fixing fly proof galvanized M.S. wire gauge to windows and clerestory windows using wire gauge with average width of aperture 1.4mm in both directions with wire of dia 0.63 mm all complete.With 12 mm mild steel U beading. |
| 3420 | Providing and fixing aluminium sliding door bolts, ISI marke anodised anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete :250x16 mm |
| 3421 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 150x10 mm |
| 3422 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete : 100mm |
| 3423 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing. |
| 3424 | Steel work welded in built up sections/ framed work, including cutting,hoisting, fixing in position and applying a priming coat of approved steelprimer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 3425 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete.40 mm thick with 20 mm nominal size stone aggregate . |
| 3426 | Providing and fixing glass strips in joints of terrazo/ cement concrete floors. 40 mm wide and 4 mm thick |
| 3427 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm(thickness to be specified by the manufacturer) of 1st quality conformingto IS : 15622 of approved make in colours such as White, Ivory, Grey,Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), including pointing the joints with white cement and matching pigment etc, complete. |
| 3428 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08%and conforming to IS : 15622, of approved make, in all colours and shades,laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm. |
| 3429 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion,(i) Single socketed pipes. 75 mm diameter |
| 3430 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion,(i) Single socketed pipes.110 mm diameter |
| 3431 | 12 mm cement plaster of mix :1:6 (1 cement: 6 coarse sand) |
| 3432 | 15 mm cement plaster on rough side of single or half brick wall of mix : 1:6 (1 cement: 6 coarse sand) |
| 3433 | cement plaster 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement. 12 mm cement plaster |
| 3434 | 6 mm cement plaster of mix:1:3 (1 cement : 3 fine sand) |
| 3435 | Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete. |
| 3436 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade :New work (two or more coats) over and including water tinna- ble priming coat with cement primer |
| 3437 | Finishing walls with textured exterior paint of required shade :New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/10 sqm. |
| 3438 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work |
| 3439 | Providing and fixing water closet squatting pan (Indian type W.C. pan ) with100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests. |
| 3440 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Flat back wash basin size 550x 400 mm with single 15 mm C.P. brass pillar tap. |
| 3441 | Providing and fixing P.V.C. waste pipe for sink or wash basin including PVC. waste fittings complete. Flexible pipe 32 mm dia |
| 3442 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete |
| 3443 | Providing and fixing PTMT towel ring trapezoidal shape 215 mm long, 200 mm wide with minimum distances of 37 mm from wall face with concealed fittings arrangement of approved quality and colour, weighing not less than 88 gms. |
| 3444 | Providing and fixing G.I. Pipes complete with G.I. fittings and clamps, i/c making good the walls etc. concealed pipe, including painting with anti corrosive bitumastic paint, cutting chases and making good the wall :15 mm dia nominal bore |
| 3445 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc.External work 20 mm dia nominal bore |
| 3446 | Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design :With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 |
| 3447 | Providing and fixing G.I. Union in G.I. pipe including cutting and threading the pipe and making long screws etc. complete (New work) :15 mm nominal bore |
| 3448 | Providing and placing on terrace (at all floor levels) polyethylene wate storage tank, ISI : 12701 marked, with cover and suitable lockin arrangement and making necessary holes for inlet, outlet and overflo pipes but without fittings and the base support for tank. |
| 3449 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 :15 mm nominal bore |
| 3450 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931. 18.52.1 15 mm nominal bore |
| 3451 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC/neoprene felt etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing and paneling to be paid for separately) :-For fixed portion---Powder coated aluminium |
| 3452 | For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 3453 | Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge.Pre-laminated particle board with decorative lamination on both sides. |
| 3454 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 4.0 mm thickness (weight not less than 10 kg/ sqm) |
| 3455 | Grading roof for water proofing treatment with Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 3456 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group B |
| 3457 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 3458 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 A switch |
| 3459 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 A socket outlet |
| 3460 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 3461 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required |
| 3462 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. |
| 3463 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 3464 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete withconnections, testing and commissioning etc. as required.Single pole |
| 3465 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 A |
| 3466 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan withBrush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2nos. canopies, shackle kit, safetyrope, copper winding, PowerFactor not less than 0.9, ServiceValue (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remainingaccessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 3467 | Supplying of Exhaust Fan 250 mm Sweep of Orient or equivalent make as approved by E.I. |
| 3468 | Supplying of 20 watt LED Tubelight Philps or equivalent make as approved by E.I. |
| 3469 | Land Development WorksProviding and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level.1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40mm nominal size) |
| 3470 | Brick work with common burnt clay F.P.S. (non modular) bricks of classdesignation 7.5 in foundation and plinth in:Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 3471 | Providing and laying 60mm thick faciory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with line sand etc. all complete as per the direction of Engineer-in-charge. |
| 3472 | Supply for 33/11kV Substation:EARTHING ROD MS 20X2500MM |
| 3473 | 33 KV LIGHTNING ARRESTER |
| 3474 | 8 M. LONG STP 410 SP-10 (BPHD GAL.) |
| 3475 | LT PVC CABLE 4X10 SQ.MM |
| 3476 | 33 KV POLYMER DISC INSULATOR (B&S) TYPE |
| 3477 | 33 KV FUSE SET |
| 3478 | ACSR DOG |
| 3479 | CONTROL CABLE 10X2.5 SQ. MM. |
| 3480 | CABLE AL 3X240 SQ. MM XLPE 11 KV |
| 3481 | CONTROL CABLE 4X2.5 SQ. MM. |
| 3482 | J/KIT FOR 3X240MM² 11KV XLPE CABLE (O/D) |
| 3483 | CONTROL CABLE 6X2.5 SQ. MM. |
| 3484 | 9 KV 10KA LIGHTNING ARRESTER |
| 3485 | 9 KV 5KA LIGHTNING ARRESTER (POLYMER) |
| 3486 | GI WIRE 5MM/6 SWG |
| 3487 | STAY WIRE GI 7/3.15MM 7/10SWG |
| 3488 | STAY SET GI 16X1800MM |
| 3489 | DISC FIT. B&S TYPE WEASEL/RABBIT 45 KN |
| 3490 | 11 KV POLYMER DISC INSULATOR (B&S) TYPE |
| 3491 | 11 MTR. LONG STP 410 SP-55 (BPHD GAL.) |
| 3492 | LT XLPE CABLE 3.5.X 70 SQ. MM. |
| 3493 | PANTHER TO PANTHER CTYPE WEDGE CONNECTOR |
| 3494 | CABLE AL 3X70 SQ. MM XLPE 33KV |
| 3495 | DISC FIT. B&S TYPE FOR PANTHER 90 KN |
| 3496 | JUNCTION BOX FOR 33KV PT |
| 3497 | MS ROUND 32 mm Dia |
| 3498 | 33 KV H.S. CABLE J/K 3X70 SQ. MM (O/D) |
| 3499 | LT PVC CABLE 2X6 SQ.MM (ARMORED) |
| 3500 | J/KIT FOR 3X400mm² 11kV XLPE CABLE (O/D) |
| 3501 | CABLE AL 1X630 SQ. mm XLPE 11kV |
| 3502 | 33kV PT of RATIO 33 kV/110V OUTDOOR |
| 3503 | CABLE AL 3X400 SQ. mm XLPE 11kV |
| 3504 | CONTROL CABLE 2X2.5 SQ. mm. |
| 3505 | ACSR PANTHER |
| 3506 | DUSTBIN PLASTIC SIZE (SMALL) |
| 3507 | SHOCK TREATMENT CHART |
| 3508 | DANGER BOARD WITH CLAMP |
| 3509 | SHUT DOWN/ BREAK DOWN BOARD |
| 3510 | 33 KV HAND GLOVES |
| 3511 | WALL CLOCK |
| 3512 | HIGH INSULATED PLIER |
| 3513 | 12KV 1250A GANG OPE PMA VCB (CAPACITOR) |
| 3514 | D-SPANNER SET |
| 3515 | TORCH 3 CELL |
| 3516 | 12KV 1250A GANG Operated PMA VCB (I/C) |
| 3517 | 33KV C&R PANEL For O/G |
| 3518 | 33KV C&R PANEL For I/C |
| 3519 | 36KV 1250A Gang Operated PMA VCB(O/G) |
| 3520 | 36KV 1250A GANG Operated PMA VCB(I/C) |
| 3521 | STAY CLAMP FOR SP-55 WITH NUT & BOLT |
| 3522 | RUBBER MAT (12MM) 2M X1M X12MM |
| 3523 | Steel Almirah |
| 3524 | OFFICE TABLE SIZE (4X2.5) |
| 3525 | GI BOLTS & NUT WITH WASHERS. |
| 3526 | HT WARNING TAPE |
| 3527 | G.I. PIPE 6'' DIA 3 MTR LONG |
| 3528 | GI Pipe 4'\\" Dia |
| 3529 | Fire Bucket with Sand |
| 3530 | Fire Bucket stand of MS angle |
| 3531 | ST. LIGHT MANAG. TIMER SWITCH |
| 3532 | IRON CLAD 30 AMP SWITCH |
| 3533 | G.I STRIP 65X6MM |
| 3534 | 11 KV FUSE SET |
| 3535 | 33/0.433 KV, 63 KVA Station Transformer |
| 3536 | PP CLAMP WITH N&B (GI) |
| 3537 | Connector Suit for CT/PT for Panther/Dog |
| 3538 | 12.65kV, 3600kVAr, Capacitor bank |
| 3539 | Indoor type auto power factor controller |
| 3540 | Thimble junction box for cable support |
| 3541 | CONNE.SUITABLE FOR PANTHER FOR LA |
| 3542 | 2.5 KV MEGGAR DIGITAL |
| 3543 | 33KV C&R PANEL BUS COUPLER |
| 3544 | 36KV 1250A GANG OPE PMA VCB(B/C) |
| 3545 | MEGGAR 5 KV DIGITAL |
| 3546 | EARTH CHAIN |
| 3547 | JOINTING KIT 3X240 SQ.mm 33kV XLPE (I/D) |
| 3548 | MS STRUCTURE (ANGLE ,CHANNEL ETC.) |
| 3549 | GI ITEM (RAIL,JOIST,CHANNEL,ANGLE ETC.) |
| 3550 | DOOR MAT |
| 3551 | Connector of Power T/F LV Side |
| 3552 | 33KV ISOLATOR CONN.CLAMP FOR PANTHER |
| 3553 | Connector of Power T/F HV Side |
| 3554 | FLEXIBLE COPPER CONNECTOR 50X50MM |
| 3555 | 12KV 1250A GANG OPERATED PMA VCB(O/G) |
| 3556 | EARTH MEGGAR DIGITAL |
| 3557 | Connector Suitable. Panther for VCB |
| 3558 | 250W LED LAMP WITH CONTRL GEAR |
| 3559 | DCDB 24V |
| 3560 | 24 V BATTERY SET |
| 3561 | INVERTOR CUM BATTERY CHARGER |
| 3562 | Instruction Board |
| 3563 | Single Line Diagram Board |
| 3564 | MAXIMUM & MINIMUM DISPLAY BOARD |
| 3565 | SUB STATION NAMED BOARD |
| 3566 | NAME PLATE OF EQUIP. TG,LI,BI,CT,CB ETC. |
| 3567 | SUNDRISE ITEM LUG GLAND ETC |
| 3568 | Steel Cabinet |
| 3569 | 11KV C&R PANEL BUS COUPLER |
| 3570 | 33 KV ISOLATOR VERTICAL TYPE |
| 3571 | FIRST AID BOX |
| 3572 | 11KV ISOLATOR MANUAL & MOTORISED SCADA COMPATIBLE |
| 3573 | Name plate of station T/F |
| 3574 | Cable Holding clamp with N&B |
| 3575 | PG Clamp For Dog Conductor |
| 3576 | PG CLAMP ALU ALLOY PANTHER TO DOG |
| 3577 | ALLUMINIUM LUG |
| 3578 | G.I.STRIP 35X4MM |
| 3579 | PERFORATED TRAY 100MM FOR CABLE TRENCH |
| 3580 | Steel office chair |
| 3581 | 33KV LINE ISOLATOR MANUAL & MOTOR,SCADA CO |
| 3582 | WIRE MESH FENCING |
| 3583 | Portable Foam Type Fire Extinguisher 5 Ltr. |
| 3584 | STEEL OFFICE TABLE |
| 3585 | RAIL 90 LBS |
| 3586 | 11KV DANGER BOARD WITH CLAMP |
| 3587 | NAME PLATE OF FEEDER |
| 3588 | CABLE HOLDING CLAMP WITH N&B |
| 3589 | 11KV 3P(400A)3PIN VERT. MOUNT GO AB TPMO |
| 3590 | 11 KV HS CABLE END T/K 1X630 SQ MM I/D |
| 3591 | PP CLAMP WITH N&B (GI) |
| 3592 | 12KV C&R Panel with SCADA (Capacitor) |
| 3593 | 11KV C&R PANEL O/G |
| 3594 | 11KV C&R PANEL I/C |
| 3595 | 12KV 1250A Gang ope PMA VCB (B/C) |
| 3596 | PERFORATED TRAY 400MM FOR CABLE TRENCH |
| 3597 | PIPE WRENCH 12'' |
| 3598 | Holding Clamp for GI Pipe 8/10''& MS Ch. |
| 3599 | Connector Suitable for Panther for LA |
| 3600 | PERFORATED TRAY 200MM FOR CABLE TRENCH |
| 3601 | FIRE EXTINGUSHIER |
| 3602 | G.I. Plate 300x300x8 mm. |
| 3603 | Stone Pad 300x300x75mm |
| 3604 | GI STRIP 50X6 MM |
| 3605 | 11 KV HS cable END T/K 1x630 mm² O/D |
| 3606 | Cable Jointing Kit 1x630 Outdoor |
| 3607 | Cable Jointing Kit 1x630 Indoor |
| 3608 | PG CLAMP ACSR PANTHER TO ACSR DOG |
| 3609 | PG CLAMP ALU ALLOY PANTHER TO PANTHER |
| 3610 | 33 KV XLPE Cable AL 1x630 sq. mm |
| 3611 | Supply for 33kV Line33 KV POLYMER DISC INSULATOR (B&S) TYPE |
| 3612 | DISC FIT. B&S TYPE DOG/RACOON 70 KN |
| 3613 | MS ANGLE 65X65X6 MM |
| 3614 | STAY WIRE GI 7/4.0 MM 7/8 SWG |
| 3615 | STAY SET GI 20X1800MM |
| 3616 | GI WIRE 4MM/8MM SWG |
| 3617 | J/KIT FOR 3X400MM²33KV XLPE CABLE (O/D) |
| 3618 | MS CHANNEL 100X50 MM |
| 3619 | 33 KV STRAIGHT THROUGH J/K 3X400 |
| 3620 | ACSR RABBIT |
| 3621 | ACSR WEASEL |
| 3622 | 11KV DISC FITTING T&C RABBIT/WEASEL 45KN |
| 3623 | 11 KV POLYMER PIN INSULATOR WITH PIN |
| 3624 | 11 KV POLYMER DISC INSULATOR (B&S) TYPE |
| 3625 | MS CHANNEL 125X65 MM |
| 3626 | CABLE AL 3X400 SQ. MM XLPE 33 KV |
| 3627 | EARTH WIRE GI 7/1.6MM 16 SWG |
| 3628 | ACSR DOG |
| 3629 | MS ANGLE 75X75X6 MM |
| 3630 | GI WIRE 5MM/6 SWG |
| 3631 | EARTHING ROD MS 20X2500MM |
| 3632 | X ARM CHANNEL 100X50 MM V TYPE 33 KV |
| 3633 | 11 MTR. LONGSTP 410 SP-55(BPHD GAL.) |
| 3634 | STP 13.0 M-IS 410 SP-72 (BPHD GAL.) |
| 3635 | 33KV 10KN POLYMER PIN INSULATOR WITH PIN |
| 3636 | NUMBER PLATE WITH CLAMP (SP-55) |
| 3637 | Bracing Clamp Bottom SP-55 with N/B |
| 3638 | STAY CLAMP WITH N&B |
| 3639 | PP & CLAMP WITH N&B ST POLE SP-55 |
| 3640 | STONE PAD 300X300X75MM |
| 3641 | TOP CHANNEL CLAMP FOR SP-55 |
| 3642 | PG Clamp For Dog Conductor |
| 3643 | STAY INSULATOR |
| 3644 | BOLT & NUT 150X12 MM |
| 3645 | EYE BOLT |
| 3646 | HOLDING CLAMP FOR SP-55 WITH N/B |
| 3647 | BRACING CLAMP TOP WITH N&B SP-55 |
| 3648 | E-CLAMP FOR 33KV 75X10MM WITH N&B |
| 3649 | X ARM CLAMP FOR ST POLE SP-55 WITH N/B |
| 3650 | DANGER BOARD WITH CLAMP N&B |
| 3651 | BOLT & NUTS OFF SIZE |
| 3652 | EARTH WIRE CLAMP FOR SP-55 WITH N/B |
| 3653 | BARBED WIRE |
| 3654 | BOLT & NUTS 50X16 MM |
| 3655 | G.I. PIPE 6 INCH |
| 3656 | Erection/Labour Work for Substation:ERECTION & LAYING OF 11KV CABLE 3X240 SQ MM |
| 3657 | ERECTION OF 33/0.433KV S/S TRANSFORMER |
| 3658 | PAINTING OF DOUBLE POLE (SP-55) |
| 3659 | PROVIDING & LAYING OF GRAVELLING IN SWITCHYARD. |
| 3660 | EXCAVATION IN SOIL BY MAUNAL/ MECHANICAL MEANS I.E. BACKHOE LOADER. |
| 3661 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETE OF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - ALL WORKS UPTO PLINTH LEVEL (I) 1:4:8 (1 - CEMENT; 4 - COARSE SAND; 8 - GRADED STONE AGGREGATE 40MM NOMINAL SIZE. |
| 3662 | RANDOM RUBBLE MASSONARY WITH HAND STONE IN SUPERSTRUCTURE ABOVE PLINTH LEVEL AND UPTO FLOOR FIVE LEVEL INCLUDING LEVELLING UP WITH CEMENT CONCRETE 1:6:12 (1 CEMENT: 6 COARSE SAND: 2 GRADED STONE AGGREGATE 20 mm NOMINAL SIZE). |
| 3663 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETE OF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - (I) 1:2:4 (1- CEMENT; 2 - COARSE SAND; 8 - GRADED STONE AGGREGATE 20MM NOMINAL SIZE).( ROAD REPAIRING /OTHER WORK). |
| 3664 | CEMENT PLASTER WORK IN 1:4 (1- CEMENT,4-COARSE SAND) |
| 3665 | RCC 1:1.5:3 |
| 3666 | BRICK WORK WITH COMMON BURNT CLAP BRICKS WITH CEMNT MORTAR 1:4 |
| 3667 | ERRECTION OF 33KV PT |
| 3668 | Erection of Sp-55 double support pole in proper level and alignment along with fixing of all accessories like top channel,X bracings ,& clamps as per RESPO manual. |
| 3669 | Erection of SP-10 single support pole in proper level and alignment along with fixing of all accessories like top channel,& clamps a s per RESPO manual. |
| 3670 | Laying of Control cable of all sizes through trench, proper connection at both ends outside in switchyard equipments & inside control room in VCB, control & relay Panels with proper marking, lugs , labelling & ferrules etc. |
| 3671 | MAKING CABLE TRENCH |
| 3672 | laying of MS bar 32 mm for making earth mat in switchyard area after fabrication / cutting in required size, laying at 2 mtr apart, also in crossing ( Making Net ), proper welding at each joint, laying at atleast 1 mtr depth in switchyard area for providing earthing. |
| 3673 | FIXING AND ERECTION OF CAPACITOR BANK |
| 3674 | PROVIDING AND LAYING IN POSITION SPECIFIED GRADE OF REINFORCED CEMENT CONCRETE EXCLUDING THE COST OF CENTERING, SHUTTERING, FINISHING AND REINFORCEMENT - ALL WORKS UPTO PLINTH LEVEL (I) 1:1.5:3 (1-CEMENT; 1.5 - COARSE SAND; 3 - GRADED STONE AGGREGATE 20MM. |
| 3675 | BRICK WORK 1:6 SUB STRUCTURE |
| 3676 | CIVIL WORK (INCLUDING FOUNDATION OF CAPACITOR CUBICAL ETC. AS PER REQUIREMENT) EARTH WORK |
| 3677 | INSTALLATION OF FOAM TYPE FIRE EXTINGUSHER |
| 3678 | ERECTION OF T&P ITEMS |
| 3679 | ERECTION OF SUB-STATION NAMED BOARD |
| 3680 | INSTALLATION OF ACDB COMPLETE ON SUFACE OR WALL WITH THE HELP OF WALL ANCHOR BOLT FASTENERS 04NOS. COMPLETE TESTING AND COMMISSIONG OF DCDB AS PER SIDE REQUIREMENT AND NARRATED BY ENGINEER IN CHARGE OF THE WORK. |
| 3681 | INSTALLATION OF DCDB COMPLETE ON SUFACE OR WALL WITH THE HELP OF WALL ANCHOR BOLT FASTENERS 04NOS. COMPLETE TESTING AND COMMISSIONING OF DCDB. |
| 3682 | ERECTION OF 24 VOLT BATTERY CHARGER |
| 3683 | ERECTION OF 24 VOLT BATTERY SET |
| 3684 | LAYING OF 4X10SQ MM LT PVC CABLE |
| 3685 | FIXING OF SODIUM/LED LIGHT AT YARD |
| 3686 | EARTHING OF STRUCTURE USING GI STRIP |
| 3687 | Cartage of the 11 KV VCB(I/C,O/G,Buscoupler) from store center to construction site with loading and unloading at both points.(Dista nce 0-20 Km) |
| 3688 | Earthing with two Nos. G.I earth plates 600mm x 600mm x 6mm thick(1.5 meter minimum in between distance) including accessories and providing double masonry enclosure with cover plate having locking arrangement and watering pipe of 3 meter long etc. |
| 3689 | Digging of trench of size 0.60x0.15 x1.5 mtr. and laying of underground 11 KV XLPE cable with making of brick housing and filling of sand including filling of earth with ramming. & repairing of road including cost of cement sand and stone blast. |
| 3690 | DELTA EARTHING OF T/F NEUTRAL POINT WITH 3 NOS. MS EARTH ROD GI STRIP & EARTH WIRE. |
| 3691 | Laying and erection of L.T. PVC single lead Cable including crimping of lugs of size 1x240, 400, 630 Sq.mm etc. (Including all cost of material). |
| 3692 | Jointing and fixing of cable jointing kit indoor/outdoor 33 KV XLPE heat shrinkable cable boxes. |
| 3693 | FIXING OF 33 KV LINE ISOLATOR VERTICAL TYPE ON ST POLE. |
| 3694 | Earth filling under floor and in sub-station area including cost of earth. Earth to be obtained from outside the corporation area in cluding its cartage and ramming, watering, dressing in 20 cm's thick layers including cost of earth with all lead and lift. |
| 3695 | ERECTION OF STAY POST |
| 3696 | FENCING OF YARD |
| 3697 | EXCAVATION IN SOIL IN HILLY AREA/RIVER BED BY MECHANICAL MEANS I.E. BACKHOE LOADER. |
| 3698 | Erection of Sp-55 double support pole in proper level and alignment along with fixing of all accessories like top channel,X bracings ,& clamps as per RESPO manual. |
| 3699 | Jointing and fixing of cable jointing kit indoor/outdoor 11 KV XLPE heat shrinkable cable boxes. |
| 3700 | ERECTION OF BUS BAR |
| 3701 | ERECTION OF FLEXIBLE CU. CONN. 500X50 MM |
| 3702 | Earthing of distribution transformer including digging of pit of size 2.5 Mtr depth and make hole of size 150 mm. Placing of earthin g electrode (to be supplied by contractor as per drawing No. A) as drawing B, connecting the same with G.I. Strip. |
| 3703 | Jointing and fixing of cable jointing kit indoor/outdoor 11 KV XLPE heat shrinkable cable boxes. |
| 3704 | 11KV, 630 AMP, OFF LOAD ISOLATOR WITH EARTH SWITCH AND MOUNTING STRUCTURE\\" |
| 3705 | Making of Trench cover with 40x40x5 mm angle frame, 10 mm ironbars inside for strengthning at 90 -100 mm apart, also in crossing with cement concrete ratio 1:2:4, providing both side handles for lifting. |
| 3706 | Painting of SP-10 pole with angle and channel and all steel part by one coat of Red Oxide Primer and two coats of aluminium Paint an d two strip of fluorescent altemate Red and White paint 30 Cm wide upto 1.5 Mtrs. From ground level. |
| 3707 | EARTH WORK IN EXCAVATION BY MECHNICAL MEANS / MANUAL MEANS OVER AREAS CC/HARDROCK. |
| 3708 | Shifting of 5 MVA Power Transformer from road site to work site/ store center to loading site place with the manual pulling. |
| 3709 | Erection of 5 MVA T/F at transformer plinth & erection of all accessories i.e. radiators, conservator tank, vent pipee etc. with the help of special type of T&P / crane etc. fitting cable etc. and refilling the fresh oil in radiator and conservator. |
| 3710 | Erection of cable stand neutral stand including fabrication cutting and welding work. |
| 3711 | Grouting of structure in CC 1:3:6 in size (2x1.1x0.3x0.3) mtr. |
| 3712 | Mounting and Fixing of Lightning arrestor set (3 Nos.) on double pole structure including making all connections by G.I. strip size 35x6 mm to earth point complete work (excluding cost of G.I.Strip). |
| 3713 | Fixing of GI pipe. |
| 3714 | Jointing and fixing of cable jointing kit indoor/outdoor 33 KV XLPE heat shrinkable cable boxes. |
| 3715 | Fabrication of MS Channel angle iron etc in required sizes with drilling of holes upto good finish for top channel,bracing and spec ial type bracket etc. as per RESPO schedule and local approced drawing. |
| 3716 | Cartage of the 33 KV VCB,feeder panels(O/D),T/F Control panel from store center to construction site with loading and unloading at both points.(Distance 21-50 Km) |
| 3717 | Mannual shifting /Pulling of Control Relay Panel for Single T/F / Single Feeder from existing site to plinth/ nearby place distanc e upto 200 mtrs. |
| 3718 | COMMISSIONING OF 33/11KV VCB PANEL WITH RESPECT WORK |
| 3719 | ERECTION OF MISC. GI STRUCTURES |
| 3720 | Cartage of other material (other than poles) by vehicle from Store Center to nearest construction site Store including loading and unloading at both ends(distance 21-50 Km) |
| 3721 | Cartage of 5 MVA Power transformer by road(loading/unloading / shifting)(21-50 KM) |
| 3722 | Digging of trench of size 0.60x0.15 x1.5 mtr. and laying of underground 33 KV XLPE cable with making of brick housing and filling of sand including filling of earth with ramming. & repairing of road including cost of cement sand and stone blast. |
| 3723 | Installation / Fixing of 33 KV Isolator on structure at 33 Kv switchyard with proper alignment & Connections with busbar complete. |
| 3724 | Erection/Labour Work for 33kV Line:Jointing and fixing of cable jointing kit straight thru 33 KV XLPE heat shrinkable cable boxes |
| 3725 | HIPOT CABLE TESTING BEFORE ENERGIZING |
| 3726 | Cartage of other material (other than poles) by vehicle from Store Center to nearest construction site Store including loading and unloading at both ends(distance 51-70 Km). |
| 3727 | SHIFTING REALIGNMENT OF 11 KV SP, DP/LT LINE INCLUDING COMPLETE WORK |
| 3728 | Digging of trench of size 0.60x0.15 x1.5 mtr. and laying of underground 33 KV XLPE cable with making of brick housing and filling of sand including filling of earth with ramming. & repairing of road including cost of cement sand and stone blast. |
| 3729 | Guarding of 33 KV Line over (Telephone / Road / L.T. line crossing as per drawing with 6/8 SWG G.I. wire including fixing of guardin g channel/ angle as per RESPO manual. |
| 3730 | ERECTION OF 33 KV STAY SET |
| 3731 | Grouting of Stay in size 0.6x0.6x0.3 in CC ratio 1:4:8 (1 cement : 4 graded stone 20mm nominal size : 8 coarse sand ) block includ ing cost of Cement,sand and stone ballast back filling of soil and boulders in pit and ramming and proper alignment. |
| 3732 | Excavation of earth for stay pit of size 0.6x0.6x1.2 mtr in all types of soil including proper dressing of sides and ramming of bott om including getting out the excavated soil and disposal of surplus excavated soil as directed complete work |
| 3733 | EXCAVATION IN SOIL IN HILLY AREA/RIVER BED BY MECHANICAL MEANS I.E. BACKHOE LOADER |
| 3734 | Erection of SP-55 single support pole in proper level and alignment along with fixing of all accessories like top channel,& clamps a s per RESPO manual. |
| 3735 | Grouting of pole in size 0.45x4.45x1/9 of the support in CC ration 1:4:8(1 cement:4 graded stone20 mm niminal size: 8 coarse sand) b lock including cost of cement, sand and stone ballast back filling of soil and boulders in pit and ramming. |
| 3736 | Muffing of poles size 0.45x0.60 cm radius with 1:3:6(1 cement:3 coarse sand :graded stone 10 mm nominal size) block size 45 cm heigh t from ground level including cost of cement,stone and sand etc. |
| 3737 | Fabrication of MS Channel angle iron etc in required sizes with drilling of holes upto good finish for top channel,bracing and spec ial type bracket etc. as per RESPO schedule and local approced drawing. |
| 3738 | PAINTING OF SINGLE POLE (SP-55) |
| 3739 | Erection of Sp-55 double support pole in proper level and alignment along with fixing of all accessories like top channel,X bracings ,& clamps as per RESPO manual |
| 3740 | Fixing of GI pipe. |
| 3741 | MAKING PIT OF SIZE 5X2X1.2 MTR FOR FILLING AND FIXING OF STRAIGHT THROUGH JOINT KIT WITH BAG FILLING RAMMING AND COMPACTION UPTO COMPLETE RESTORATION. |
| 3742 | PAINTING OF DOUBLE POLE (SP-55) |
| 3743 | Erection of SP-72 double support pole in proper level and alignment along with fixing of all accessories like top channel,X bracings ,& clamps as per RESPO manual. |
| 3744 | PAINTING OF DOUBLE POLE (SP-72) |
| 3745 | ERECTION OF TRI POLE FOR ST POLE SP-55 |
| 3746 | PAINTING OF TRI POLE (SP-55) |
| 3747 | PAINTING OF FOUR POLE (SP-55) |
| 3748 | Erection of SP-55(11KV/33 KV)four pole support pole in proper level and alignment along with fixing of all accessories like top chan nel,X bracings,& clamps as per RESPO manual. |
| 3749 | Earthing of support with M.S. Earth rod of 2.5 meter long by hammaring of M.S. Rod to proper depth and connecting the earth electrod e with the help of G.I. wire as per construction manual. |
| 3750 | Laying, Spreading, Stringing and sagging of 11 KV / 33 KV line in 3 phase (3 Phase 3 wire) of ACSR Dog as phase wire with G.I. earth wire complete including fixing of all accessories in 3 Nos. conductor in parallel with binding and jumpering. |
| 3751 | FIXING OF ACCESSORIES |
| 3752 | EARTH WORK IN EXCAVATION BY MECHNICAL MEANS / MANUAL MEANS OVER AREAS CC/HARDROCK. |
| 3753 | SUPPLY AND LAYING OF HDPE PIPE 160 MM OUTER DIA 6 MM THICKNESS. |
| 3754 | ERECTION AND LAYING OF HT 33 KV XLPE ALU. ARMOURED CABLE 3 X 400 SQ. MM. IN HDPE PIPE MIXED SOIL INCLUDING BACK FILLING OF EARTH & ERECTION ON POLE USING MS CHANNEL, ANGLE & CLAMPS ETC. |
| 3755 | Annual Maintenance Charges (AMC) and O&M of Project for 5 years on per year basis. |
| 3756 | Construction of S.G.R. Building, Boundary Wall, Approach Road and Other misc. civil works:Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m inwidth or 10 sqm on plan), including dressing of sides and ramming ofbottoms, lift upto 1.5 m, including getting out the within a lead of 50 m.All kinds of soil. |
| 3757 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. |
| 3758 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. |
| 3759 | Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared. |
| 3760 | P/laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:1½:3 (1 Cement: 1½ coarse sand: 3 graded stone aggregate 20 mm nominal size) |
| 3761 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinthlevel :1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) |
| 3762 | Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III): 4 graded stone aggregate 12.5mm nominal size) |
| 3763 | Extra for providing and mixing water proofing material in cement concrete work in doses by weight of cement as per manufacturer’s specification. |
| 3764 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :sand: 3 graded stone aggregate 20 cm nominal size).1:1.5:3 (1 cement : 1.5coarse sand : 3 graded stone aggregate 20 mm nominal size) |
| 3765 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size) |
| 3766 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size). |
| 3767 | Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns, etc. for mass concrete |
| 3768 | Centering and shuttering including strutting, propping etc. and removal of form for : Suspended floors, roofs, landings, balconies and access platform |
| 3769 | Centering and shuttering including strutting, propping etc. and removal of form for : Shelves (Cast in situ) |
| 3770 | Centering and shuttering including strutting, propping etc. and removal of form for : Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 3771 | Centering and shuttering including strutting, propping etc. and removal of form for : Columns, Pillars, Piers, Abutments, Posts and Struts |
| 3772 | Centering and shuttering including strutting, propping etc. and removal of form for : Weather shade, Chajjas, corbels etc., including edges |
| 3773 | Steel reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete upto plinth level Thermo-Mechanically Treated bars |
| 3774 | Steel reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete above plinth level.Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 3775 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 3776 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 3777 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 3778 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure V level in all shapes and sizes in :Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 3779 | Half brick masonry with F.P.S. bricks of class designation 75 in superstructure above planth level up to floor V level. Cement morat 1:4 ( 1 cement : 4 coarse sand) |
| 3780 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Raj Nagar Plain white marble/ Udaipur green marble/ Zebra black marble. Area of slab upto 0.50 sqm |
| 3781 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Raj Nagar Plain white marble/ Udaipur green marble/ Zebra black marble. Area of slab over 0.50 sqm |
| 3782 | Providing and fixing glazed shutters for doors, windows and clerestory windows using 4 mm thick float glass panes, including ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws. Second class teak wood 35 mm thick |
| 3783 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws |
| 3784 | Providing and fixing ISI marked oxidised M.S. sliding door bolts with nuts and screws etc. complete : 250x16 mm |
| 3785 | Providing and fixing ISI marked oxidised M.S. tower bolt black finish (Barrel type) with necessary screws etc. complete : 200x10 mm |
| 3786 | Providing and fixing ISI marked oxidised M.S. tower bolt black finish (Barrel type) with necessary screws etc. complete : 150x10 mm |
| 3787 | Providing and fixing ISI marked oxidised M.S. tower bolt black finish (Barrel type) with necessary screws etc. complete : 100x10 mm |
| 3788 | Providing and fixing ISI marked oxidised M.S. handles conforming to IS:4992 with necessary screws etc. complete :125 mm |
| 3789 | Providing and fixing aluminium sliding door bolts, ISI marked anodised anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete : 250x16 mm |
| 3790 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete :(200x10mm) |
| 3791 | Providing and fixing aluminium tower door bolts ISI marked anodised (Anodic coating not less than grade AC 10 as per IS:1868)transparent or dyed to required colour or shade with nuts and screws etc. complete: (150x10mm) |
| 3792 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete :100x10 mm |
| 3793 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete :125mm |
| 3794 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete :100mm |
| 3795 | Providing and fixing aluminium handles floor door stopper ISI marked anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour or shade with necessary scerews etc. complet: Single rubber stopper |
| 3796 | Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete. Twin rubber stopper |
| 3797 | Providing and fixing wire gauge shutters using stainless steel grade 304 wire gauge with wire of dia 0.5 mm and average width of aperture 1.4 mm in both directions for doors, windows and clerestory windows with necessary screws :35 mm thick shutters with ISI marked M.S. pressed butt hinges bright finished of required size Second class teak wood |
| 3798 | Providing and fixing in position collapsible steel shutters with vertical channels 20x10x2 mm and braced with flat iron diagonals 20x5 mm size, with top and bottom rail of T-iron 40x40x6 mm, with 40 mm dia steel pulleys, complete with bolts, nuts, locking arrangement, stoppers, handles, including applying a priming coat of approved steel primer. |
| 3799 | Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge:Profile B Fixing with adjustable lugs with split end tail to each jamb |
| 3800 | Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge:Profile C Fixing with adjustable lugs with split end tail to each jamb |
| 3801 | Steel work in built up tubular ( round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished welded type tubes |
| 3802 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard rawing.surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing. |
| 3803 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 3804 | Providing & fixing fly proof wire gauze to windows, clerestory windows & doors with M.S. Flat 15x3 mm and nuts & bolts complete. Galvanised M.S. Wire gauze with 0.63 mm dia wire and 1.4 mm aperture on both sides |
| 3805 | Providing & fixing glass panes with putty and glazing clips in steel doors, windows, clerestory windows, all complete with :5.5 mm thick glass panes |
| 3806 | Cement concrete flooring 1:2:4 (1 cement : 2coarse sand : 4 gradd stone aggregate) finished with a floating coat of neat cement including cement slurry, (40 mm thick with 20mm nomnal sxe stone aggregate). |
| 3807 | Providing and fixing glass strips in joints of terrazo/ cement concrete floors. 40 mm wide and 4 mm thick |
| 3808 | P/F Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. |
| 3809 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in all colours, shades, except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick bed of cement mortar 1:4 (1 Cement : 4 Coarse sand), including pointing the joints with white cement and matching pigments etc., complet |
| 3810 | Providing and laying polished vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption,s less than 0.08% and conforming to IS 15622 of approved make in all colours and shades, laid on 20mm thick cement mortar 1:4 ( 1 cement: 4 coarse sand ) including grouting the joints with white cement and matching pigments etc, complete. (size of Tile 60x60cm) |
| 3811 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete.Size of Tile 600x600 mm |
| 3812 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS: 13592 (i) Single socketed pipes (75mm diameter) |
| 3813 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes 110 mm diameter |
| 3814 | 12 mm cement plaster of mix 1:4(1 cement: 4 coarse sand) |
| 3815 | 12 mm cement plaster of mix : 1:6 (1 cement : 6 coarse sand) |
| 3816 | 15 mm cement plaster on rough side of single or half brick wall of mix:1:6 (1 cement: 6 coarse sand) |
| 3817 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade : New work (two or more coats) over and including water tinnable priming coat with cement primer |
| 3818 | Finishing walls with textured exterior paint of required shade : New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/ 10 sqm |
| 3819 | Finishing walls with Acrylic Smooth exterior paint of required shade :New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm) |
| 3820 | Painting with synthetic enamel paint of approved brand andmanufacture to give an even shade :Two or more coats on new work |
| 3821 | Providing and applying white cement based putty of average thickness 1mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 3822 | Supplying and stacking at site.Good earth |
| 3823 | Providing and laying 60mm thick factory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge. |
| 3824 | Providing and laying C.C. pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator , vacuum dewatering process and finally finished by floating, brooming with wire brush etc. complete as per specifications and directions of Engineer-incharge. (The panel shuttering work shall be aid for separately).Deduct for using of M-20 grade concrete instead of M-25 grade concrete in C.C. pavement. |
| 3825 | Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever)conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests |
| 3826 | Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I.brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required : 17.3.1 W.C. pan with ISI marked white solid plastic seat and lid |
| 3827 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required : One urinal basin with 5 litre white P.V.C. automatic flushing cistern |
| 3828 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brasspillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: |
| 3829 | Providing and fixing white vitreous china pedestal for wash basin completely recessed at the back for the reception of pipes and fittings. |
| 3830 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 3831 | Providing and fixing terminal guard : 75 mm Sand cast iron S&S as per IS - 1729 |
| 3832 | Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : 100 mm inlet and 100 mm outlet (Sand cast iron S&S as per IS: 3989) |
| 3833 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. 450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm, weighing not less than 170 gms |
| 3834 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall 20 mm nominal outer dia Pipes |
| 3835 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall 25 mm nominal outer dia Pipes |
| 3836 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 20 mm nominal outer dia Pipes |
| 3837 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement ,trenching ,refilling & testing of joints complete as per direction of Engineer in Charge.External work 15 mm nominal outer dia Pipes |
| 3838 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement ,trenching ,refilling & testing of joints complete as per direction of Engineer in Charge.External work 20 mm nominal outer dia Pipes |
| 3839 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement ,trenching ,refilling & testing of joints complete as per direction of Engineer in Charge.External work 25 mm nominal outer dia Pipes |
| 3840 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement ,trenching ,refilling & testing of joints complete as per direction of Engineer in Charge.External work 32 mm nominal outer dia Pipes |
| 3841 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement ,trenching ,refilling & testing of joints complete as per direction of Engineer in Charge.External work 40 mm nominal outer dia Pipes |
| 3842 | Constructing masonry Chamber 30x30x50 cm inside, in brick work incement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stoneaggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design : With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 |
| 3843 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, ISI : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 3844 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 15 mm nominal bore |
| 3845 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.(15 mm nominal bore) |
| 3846 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931.(15 mm nominal bore) |
| 3847 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 a) 15 mm nominal bore 15mm nominal bore |
| 3848 | Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighing not less than 106 gms. |
| 3849 | P/Fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron) |
| 3850 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15) Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 3851 | Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge. Pre-laminated particle board with decorative lamination on one side and balancing lamination on other side |
| 3852 | Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge.With stainless steel cover plate minimum 1.25 mm thickness |
| 3853 | Providing and fixing 100mm brass locks (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete. |
| 3854 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer-in-charge, upto 90 metre depth below ground level.All types of soil 300 mm dia |
| 3855 | Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer -in-charge.100 mm nominal size dia |
| 3856 | Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge.100 mm nominal size dia |
| 3857 | Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. |
| 3858 | Engaging suitable Beldar for petty works (Basis rate labour) |
| 3859 | Stone Aggregate (Single size) : 20 mm nominal size |
| 3860 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. GROUP B |
| 3861 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 3862 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 3863 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 3864 | Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 3865 | Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 amps socket outlet and 15/16 amps piano type switch, connection, painting etc. as required. |
| 3866 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq. mm FR PVC insulated, copper conductor, single core cable and earthing etc. as required.. |
| 3867 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.Upto 450 mm sweep |
| 3868 | Supplying and Drawing of UTP 4 pair Cat 6 Lane Cable in the existing Surface /recessed Steel/ PVC Conduit as Required.2 run of cable |
| 3869 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way , Double door |
| 3870 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 3871 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps |
| 3872 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 3873 | Supplying of 20Watt LED Tubelight Philips or equivalent make as approved by E.I. S.E. letter no-832 /ECC/D.Dun/Extra Item Dated-29-08-2022 |
| 3874 | Supplying of Exhaust Fan 250mm sweep of Orient or equivalent make as approved by E.I. S.E. letter no-832 /ECC/D.Dun/Extra Item Dated-29-08-2022 |
| 3875 | \\"Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos.blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. file no-E-9059857/9(new technology)/C.E.(Ren.)CSQ/2019 Dated-18/11/2019\\" |
| 3876 | Supply and Installation 40mm outlet size submersible pump set 1.00HP, I stage of crompton greaves or equivalent make as approved by E.I. |
| 3877 | Supply and Placing single phase panel board/ box crompton greaves or equivalent make as approved by E.I. |
| 3878 | Supplying of Exhaust Fan 450mm sweep of Orient or equivalent make as approved by E.I. S.E. letter no-832 /ECC/D.Dun/Extra Item Dated-29-08-2022 |
| 3879 | Supply and Installation Water Purifier (15LPH) kent or Equivalent make approved by E.I. S.E. letter no-1154 /ECC/D.Dun/Extra Item Dated-15-11-2022 |
| 3880 | Supply and Placing 20/40 LTR Storage Water Cooler SS Body USHA make or Equivalent make approved by E.I. S.E. letter no-1154 /ECC/D.Dun/Extra Item Dated-15-11-2023 |
| 3881 | Supply of 33/11kV SUBSTATIONJUNCTION BOX FOR 33KV PT |
| 3882 | 33 KV LIGHTNING ARRESTER |
| 3883 | DISC FIT. B&S TYPE FOR PANTHER 90 KN |
| 3884 | 11 MTR. LONGSTP 410 SP-55(BPHD GAL.) |
| 3885 | CABLE AL 3X70 SQ. MM XLPE 33KV |
| 3886 | 33 KV LIGHTNING ARRESTER |
| 3887 | PANTHER TO PANTHER CTYPE WEDGE CONNECTOR |
| 3888 | LT XLPE CABLE 3.5.X 70 SQ. MM. |
| 3889 | 11 MTR. LONGSTP 410 SP-55(BPHD GAL.) |
| 3890 | 11 KV POLYMER DISC INSULATOR (B&S) TYPE |
| 3891 | DISC FIT. B&S TYPE WEASEL/RABBIT 45 KN |
| 3892 | STAY SET GI 16X1800MM |
| 3893 | STAY WIRE GI 7/3.15MM 7/10SWG |
| 3894 | EARTHING ROD MS 20X2500MM |
| 3895 | GI WIRE 5MM/6 SWG |
| 3896 | 9 KV 5KA LIGHTNING ARRESTER (POLYMER) |
| 3897 | CONTROL CABLE 4X2.5 SQ. MM. |
| 3898 | MS ROUND 32 MM |
| 3899 | J/KIT FOR 3X400MM² 11KV XLPE CABLE (O/D) |
| 3900 | CABLE AL 1X630 SQ. MM XLPE 11 KV |
| 3901 | LT PVC CABLE 2X6 SQ.MM (ARMORED) |
| 3902 | DISC FIT. B&S TYPE FOR PANTHER 90 KN |
| 3903 | 33KV PT OF RATIO 33 KV/110V OUTDOOR |
| 3904 | CABLE AL 3X400 SQ. MM XLPE 11 KV |
| 3905 | CONTROL CABLE 2X2.5 SQ. MM. |
| 3906 | CONTROL CABLE 10X2.5 SQ. MM. |
| 3907 | ACSR PANTHER |
| 3908 | 33 KV H.S. CABLE J/K 3X70 SQ. MM (O/D) |
| 3909 | T/F 33/11 KV 12.5MVA |
| 3910 | 33 KV POLYMER DISC INSULATOR (B&S) TYPE |
| 3911 | ACSR DOG |
| 3912 | 33 KV FUSE SET |
| 3913 | 33 KV POLYMER DISC INSULATOR (B&S) TYPE |
| 3914 | LT PVC CABLE 4X10 SQ.MM |
| 3915 | 8 M. LONG STP 410 SP-10 (BPHD GAL.) |
| 3916 | 33 KV LIGHTNING ARRESTER |
| 3917 | EARTHING ROD MS 20X2500MM |
| 3918 | CONTROL CABLE 6X2.5 SQ. MM. |
| 3919 | J/KIT FOR 3X240MM² 11KV XLPE CABLE (O/D) |
| 3920 | CONTROL CABLE 4X2.5 SQ. MM. |
| 3921 | CABLE AL 3X240 SQ. MM XLPE 11 KV |
| 3922 | CONTROL CABLE 10X2.5 SQ. MM. |
| 3923 | 9 KV 10KA LIGHTNING ARRESTER |
| 3924 | PP CLAMP WITH N&B (GI) |
| 3925 | 11 KV HS CABLE END T/K 1X630 SQ MM I/D |
| 3926 | 11KV 3P(400A)3PIN VERT. MOUNT GO AB TPMO |
| 3927 | CABLE HOLDING CLAMP WITH N&B |
| 3928 | NAME PLATE OF FEEDER |
| 3929 | 11KV DANGER BOARD WITH CLAMP |
| 3930 | RAIL 90 LBS |
| 3931 | STEEL OFFICE TABLE |
| 3932 | PORTABLE FOAM TYPE FIRE EXTINGUISHER 5LT |
| 3933 | WIRE MESH FENCING |
| 3934 | 33KV LINE ISOLATOR MANUAL&MOTOR,SCADA CO |
| 3935 | STEEL OFFICE CHAIR GODREJ |
| 3936 | PERFORATED TRAY 100MM FOR CABLE TRENCH |
| 3937 | G.I.STRIP 35X4MM |
| 3938 | ALLUMINIUM LUG |
| 3939 | PG CLAMP ALU ALLOY PANTHER TO DOG |
| 3940 | PG CLAMP FOR DOG CONDUCTOR |
| 3941 | CABLE HOLDING CLAMP WITH N&B |
| 3942 | NAME PLATE OF STATION T/F |
| 3943 | 33 KV DANGER BOARD WITH CLAMP |
| 3944 | 11KV ISOLATOR MANUAL&MOTOR,SCADA COMP. |
| 3945 | FIRST AID BOX |
| 3946 | CABLE BOX2MM THICK CRCA SHEET100X600X500 |
| 3947 | GI STRIP 50X6 MM |
| 3948 | 11 KV HS CABLE END T/K 1X630MM² O/D |
| 3949 | GI STRIP 50X6 MM |
| 3950 | G.I. PLATE 300X300X8 MM. |
| 3951 | STONE PAD 300X300X75MM |
| 3952 | CABLE JOINTING KIT 1X630 INDOOR |
| 3953 | CABLE JOINTING KIT 1X630 OUTDOOR |
| 3954 | PG CLAMP ACSR PANTHER TO ACSR DOG |
| 3955 | PG CLAMP ALU ALLOY PANTHER TO PANTHER |
| 3956 | 33 KV XLPE CABLE AL 1X630 SQ. MM -D |
| 3957 | FIRE EXTINGUSHIER |
| 3958 | GI PIPE 4'\\" DIA |
| 3959 | PERFORATED TRAY 200MM FOR CABLE TRENCH |
| 3960 | GI BOLTS & NUT WITH WASHERS. |
| 3961 | CONNE.SUITABLE FOR PANTHER FOR LA |
| 3962 | HOLDING CLAMP FPR GI PIPE 8/10''& MS CH. |
| 3963 | GI PIPE 4'\\" DIA |
| 3964 | MS PLATE 300X300X8 MM. |
| 3965 | GI BOLTS & NUT WITH WASHERS. |
| 3966 | PIPE WRENCH 12'' |
| 3967 | PERFORATED TRAY 400MM FOR CABLE TRENCH |
| 3968 | 12KV 1250A GANG OPE PMA VCB(B/C) |
| 3969 | 11KV C&R PANEL I/C-D |
| 3970 | 11KV C&R PANEL O/G-D |
| 3971 | 12KV C&R PANEL WITH SCADA(CAPACITOR) |
| 3972 | GI BOLTS & NUT WITH WASHERS. |
| 3973 | PP CLAMP WITH N&B (GI) |
| 3974 | 33/0.433 KV, 63 KVA STATION TRANSFORMER |
| 3975 | 11 KV FUSE SET |
| 3976 | G.I EARTH STRIP 65X6MM |
| 3977 | IRON CLAD 30 AMP SWITCH |
| 3978 | ST. LIGHT MANAG. TIMER SWITCH WITH METER |
| 3979 | FIRE BUCKET STAND OF MS ANGLE |
| 3980 | FIRE BUCKET STAND WITH BUCKETS |
| 3981 | GI PIPE 4'\\" DIA |
| 3982 | KM-21 G.I. PIPE 6'' DIA 3 METER LONG |
| 3983 | #HT# WARNING TAPE |
| 3984 | GI BOLTS & NUT WITH WASHERS. |
| 3985 | OFFICE TABLE SIZE (4X2.5) |
| 3986 | STEEL ALMIRAH |
| 3987 | RUBBER MAT (12MM) 2M X1M X12MM |
| 3988 | STAY CLAMP FOR SP-55 WITH NUT & BOLT |
| 3989 | 36KV 1250A GANG OPE PMA VCB(I/C) |
| 3990 | 36KV 1250A GANG OPE PMA VCB(O/G) |
| 3991 | 33KV C&R PANEL I/C-D |
| 3992 | 33KV C&R PANEL O/G-D |
| 3993 | 12KV 1250A GANG OPE PMA VCB(I/C) |
| 3994 | TORCH 3 CELL |
| 3995 | D-SPANNER SET |
| 3996 | 12KV 1250A GANG OPE PMA VCB(CAPACITOR) |
| 3997 | HIGH INSULATED PLIER |
| 3998 | WALL CLOCK |
| 3999 | 33 KV HAND GLOVES |
| 4000 | SHUT DOWN/ BREAK DOWN BOARD |
| 4001 | DANGER BOARD |
| 4002 | SHOCK TREATMENT CHART |
| 4003 | DUSTBIN PLASTIC SIZE (SMALL) |
| 4004 | GI ITEM (RAIL,JOIST,CHANNEL,ANGLE) |
| 4005 | 33 KV ISOLATOR VERTICAL TYPE |
| 4006 | 11KV C&R PANEL BUS COUPLER-D |
| 4007 | STEEL CABINET |
| 4008 | SUNDRISE ITEM LUG GLADE ETC |
| 4009 | NAME PLATE OF EQUIP. TG,LI,BI,CT,CB ECT. |
| 4010 | SUB STATION NAMED BOARD |
| 4011 | MAXIMUM & MINIMUM DISPLAY BOARD |
| 4012 | SINGLE LINE DIAGRAM BOARD |
| 4013 | INSTRUCTION BOARD |
| 4014 | INVERTOR |
| 4015 | 24 V BATTERY SET |
| 4016 | DCDB 24V |
| 4017 | 250 W HPSV/LED LAMP WITH CONTRL GEAR |
| 4018 | CONNECTOR SUITABLE. PANTHER FOR VCB |
| 4019 | EARTH MEGGAR DIGITAL |
| 4020 | 12KV 1250A GANG OPE PMA VCB(O/G) |
| 4021 | FLEXIBLE COOPER CONNECTOR 50X50MM |
| 4022 | CONNECTOR OF POWER T/F HV SIDE |
| 4023 | 33KV ISOLATOR CONN.CLAMP FOR PANTHER,N&B |
| 4024 | CONNECTOR OF POWER T/F LV SIDE |
| 4025 | DOOR MAT |
| 4026 | JOINTING KIT 3X240 SQ.MM 33KV XLPE (I/D) |
| 4027 | MS STRUCTURE (ANGLE ,CHANNEL ETC.) |
| 4028 | EARTH CHAIN |
| 4029 | MEGGAR 5 KV DIGITAL |
| 4030 | 36KV 1250A GANG OPE PMA VCB(B/C) |
| 4031 | 2.5 KV MEGGAR DIGITAL |
| 4032 | 33KV C&R PANEL BUS COUPLER-D |
| 4033 | CONNE.SUITABLE FOR PANTHER FOR LA |
| 4034 | INDOOR TYPE AUTO POWER FACTOR CONTROLLER |
| 4035 | THIMBLE JUNCTION BOX FOR CABLE SUPPORT |
| 4036 | CONNECTOR SUIT FOR CT/PT FOR PANTHER/DOG |
| 4037 | 12.65KV, 4800KVAR, CAPACITOR BANK |
| 4038 | Supply of 33kV LINEEARTHING ROD MS 20X2500mm |
| 4039 | GI WIRE 5mm/6 SWG |
| 4040 | GI WIRE 4mm/8mm SWG |
| 4041 | CABLE AL 3X400 SQ. mm XLPE 33kV |
| 4042 | J/KIT FOR 3X400mm²33kV XLPE CABLE (O/D) |
| 4043 | MS CHANNEL 100X50 mm |
| 4044 | X ARM CHANNEL 100X50 mm V TYPE 33 kV |
| 4045 | MS CHANNEL 125X65 mm |
| 4046 | 33kV 10KN POLYMER PIN INSULATOR WITH PIN |
| 4047 | DISC FIT. B&S TYPE DOG/RACOON 70 KN |
| 4048 | MS ANGLE 65X65X6 mm |
| 4049 | 33kV 10KN POLYMER PIN INSULATOR WITH PIN |
| 4050 | STAY SET GI 20X1800mm |
| 4051 | MS ANGLE 75X75X6 mm |
| 4052 | 11 MTR. LONGSTP 410 SP-55(BPHD GAL.) |
| 4053 | Holding Clamp for ST Pole SP-55 with N&B |
| 4054 | 33 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 4055 | MS CHANNEL 125X65 mm |
| 4056 | 11 MTR. LONGSTP 410 SP-55(BPHD GAL.) |
| 4057 | 11 MTR. LONGSTP 410 SP-55(BPHD GAL.) |
| 4058 | EARTH WIRE GI 7/1.6mm 16 SWG |
| 4059 | ACSR DOG |
| 4060 | MS ANGLE 65X65X6 mm |
| 4061 | 33kV 10KN POLYMER PIN INSULATOR WITH PIN |
| 4062 | DISC FIT. B&S TYPE DOG/RACOON 70 KN |
| 4063 | 33 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 4064 | MS CHANNEL 125X65 mm |
| 4065 | STAY WIRE GI 7/3.15mm 7/10SWG |
| 4066 | GI WIRE 5mm/6 SWG |
| 4067 | Stay Clamp for SP-55 With Nut & Bolt |
| 4068 | Top Chennel Clamp With N&B |
| 4069 | Bolt & Nuts off Size |
| 4070 | E- CLAMP |
| 4071 | PG Clamp For Dog Conductor |
| 4072 | Earth wire clamp 33 KV for SP-72-N&B |
| 4073 | Earth wire clamp 33 KV for SP-72-N&B |
| 4074 | Bolt & Nuts 50x16 mm |
| 4075 | Stone Pad 300x300x75mm |
| 4076 | Bolt & Nut 150x12 mm |
| 4077 | Stone Pad 300x300x75mm |
| 4078 | Stone Pad 300x300x75mm |
| 4079 | Top Chennel Clamp With N&B |
| 4080 | Bolt & Nuts off Size |
| 4081 | E- CLAMP |
| 4082 | EARTH WIRE CLAMP FOR SP-55 WITH N/B |
| 4083 | PG Clamp For Dog Conductor |
| 4084 | Bolt & Nuts off Size |
| 4085 | E- CLAMP |
| 4086 | Top Chennel Clamp With N&B |
| 4087 | HT Stay Insulator |
| 4088 | PP & CLAMP WITH N&B ST POLE SP-72 |
| 4089 | BRACING CLAMP BOTTOM WITH N&B SP-55 |
| 4090 | BRACING CLAMP BOTTOM WITH N&B SP-55 |
| 4091 | NUMBER PLATE WITH CLAMP |
| 4092 | NUMBER PLATE WITH CLAMP |
| 4093 | NUMBER PLATE WITH CLAMP |
| 4094 | BARBED WIRE |
| 4095 | BARBED WIRE |
| 4096 | BARBED WIRE |
| 4097 | BRACING CLAMP TOP WITH N&B SP-55 |
| 4098 | BRACING CLAMP TOP WITH N&B SP-55 |
| 4099 | Holding Clamp for SP-55 with N/B |
| 4100 | Eye Bolt Size 100x16 |
| 4101 | 33 KV Danger Board with Clamp |
| 4102 | 33 KV Danger Board with Clamp |
| 4103 | 33 KV Danger Board with Clamp |
| 4104 | 160 MM HDPE CONDUIT PIPE |
| 4105 | Erection of 33/11kV SUBSTATIONPainting of SP-10 pole with angle and channel and all steel part by one coat of Red Oxide Primer and two coats of aluminium Paint an d two strip of fluorescent altemate Red and White paint 30 Cm wide upto 1.5 Mtrs. From ground level. |
| 4106 | Making of Trench cover with 40x40x5 mm angle frame, 10 mm ironbars inside for strengthning at 90 -100 mm apart, also in crossing with cement concrete ratio 1:2:4, providing both side handles for lifting. |
| 4107 | 11KV, 630 AMP, OFF LOAD ISOLATOR WITH EARTH SWITCH AND MOUNTING STRUCTURE\\" |
| 4108 | Jointing and fixing of cable jointing kit indoor/outdoor 11 KV XLPE heat shrinkable cable boxes |
| 4109 | MAKING CABLE TRENCH |
| 4110 | Earthing of distribution transformer including digging of pit of size 2.5 Mtr depth and make hole of size 150 mm. Placing of earthin g electrode (to be supplied by contractor as per drawing No. A) as drawing B, connecting the same with G.I. Strip (to be |
| 4111 | ERECTION OF FLEXIBLE CU. CONN. 500X50 MM |
| 4112 | ERECTION OF BUS BAR |
| 4113 | Jointing and fixing of cable jointing kit indoor/outdoor 11 KV XLPE heat shrinkable cable boxes |
| 4114 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETEOF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - ALL WORKS UPTO PLINTH LEVEL (I) 1:4:8 (1 - CEMENT; 4 - COARSE SAND; 8 - GRADED STONE AGGREGATE 40MM NOMINAL SIZE).( FOUNDATIO |
| 4115 | Erection of Sp-55 double support pole in proper level and alignment along with fixing of all accessories like top channel,X bracings ,& clamps as per RESPO manual |
| 4116 | CEMENT PLASTER WORK |
| 4117 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETEOF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - ALL WORKS UPTO PLINTH LEVEL (I) 1:4:8 (1 - CEMENT; 4 - COARSE SAND; 8 - GRADED STONE AGGREGATE 40MM NOMINAL SIZE).( FOUNDATIO |
| 4118 | EXCAVATION IN SOIL IN HILLY AREA/RIVER BED BY MECHANICAL MEANS I.E. BACKHOE LOADER |
| 4119 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETEOF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - ALL WORKS UPTO PLINTH LEVEL (I) 1:4:8 (1 - CEMENT; 4 - COARSE SAND; 8 - GRADED STONE AGGREGATE 40MM NOMINAL SIZE).( FOUNDATIO |
| 4120 | EXCAVATION IN SOIL IN HILLY AREA/RIVER BED BY MECHANICAL MEANS I.E. BACKHOE LOADER |
| 4121 | FENCING OF YARD |
| 4122 | ERECTION OF STAY POST |
| 4123 | Earth filling under floor and insub-station area including cost of earth. Earth to be obtained from outside the corporation area in cluding its cartage and ramming, watering, dressing in 20 cm's thick layers including cost of earth with all lead and lif |
| 4124 | FIXING OF 33 KV LINE ISOLATOR VERTICAL TYPE ON ST POLE |
| 4125 | Jointing and fixing of cable jointing kit indoor/outdoor 33 KV XLPE heat shrinkable cable boxes |
| 4126 | Laying and erection of L.T. PVC single lead Cable including crimping of lugs of size 1x240, 400, 630 Sq.mm etc. (Including all cost of material) |
| 4127 | EXCAVATION IN SOIL IN HILLY AREA/RIVER BED BY MECHANICAL MEANS I.E. BACKHOE LOADER |
| 4128 | Fabrication of MS Channel angle iron etc in required sizes with drilling of holes upto good finish for top channel,bracing and spec ial type bracket etc. as per RESPO schedule and local approced drawing. |
| 4129 | Cartage of the 33 KV VCB,feeder panels(O/D),T/F Control panel from store center to construction site with loading and unloading at b oth points.(Distance 51-70 Km) |
| 4130 | Mannual shifting /Pulling of Control Relay Panel for Single T/F / Single Feeder from existing site to plinth/ nearby place distanc e upto 200 mtrs. |
| 4131 | COMM.OF 33/11KV VCB PANEL WITH RESPECT WORK |
| 4132 | ERECTION OF MISC. GI STRUCTURES |
| 4133 | Cartage of other material (other than poles) by vehicle from Store Center to nearest construction site Store including loading and u nloading at both ends(distance 51-70 Km) |
| 4134 | Cartage of 10/12.5 MVA Power transformer by road(loading/unloading/shifting to be charged extra)(51-70 KM) |
| 4135 | Digging of trench of size 0.60x0.15 x1.5 mtr. and laying of underground 33 KV XLPE cable with making of brick housing and filling of sand including filling of earth with ramming. & repairing of road including cost of cement sand and stone blast |
| 4136 | Installation / Fixing of 33 Kv Isolator on structure at 33 Kv switchyard with proper alignment <(>&<)> Connections with busbar comp lete. |
| 4137 | Jointing and fixing of cable jointing kit indoor/outdoor 33 KV XLPE heat shrinkable cable boxes |
| 4138 | Fixing of GI pipe. |
| 4139 | CEMENT PLASTER WORK |
| 4140 | Mounting and Fixing of Lightning arrestor set (3 Nos.) on double pole structure including making all connections by G.I. strip size 35x6 mm to earth point complete work (excluding cost of G.I.Strip) |
| 4141 | CEMENT PLASTER WORK |
| 4142 | Grouting of structure in CC 1:3:6 in size (2x1.1x0.3x0.3) mtr. |
| 4143 | EXCAVATION IN SOIL IN HILLY AREA/RIVER BED BY MECHANICAL MEANS I.E. BACKHOE LOADER |
| 4144 | Erection of cable stand neutral stand including fabrication cutting and welding work. |
| 4145 | Erection of (12.5, 10) MVA T/F at transformer plinth & erection of all accessories i.e. radiators, conservator tank, vent pipee etc. , with the help of special type of T&P / crane etc. fitting cable etc. and refilling the fresh oil in radiator and conser |
| 4146 | Shifting of 12.5 MVA Power Transformer from road site to work site/ store center to loading site place with the manual pulling. |
| 4147 | EARTH WORK IN EXCAVATION BY MECHNICAL MEANS / MANUAL MEANS OVER AREAS CC/HARDROCK |
| 4148 | DELTA EARTHING OF T/F NEUTRAL POINT WITH 3 NOS. MS EARTH ROD GI STRIP <(>&<)> EARTH WIRE |
| 4149 | MAKING CABLE TRENCH |
| 4150 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETEOF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - ALL WORKS UPTO PLINTH LEVEL (I) 1:4:8 (1 - CEMENT; 4 - COARSE SAND; 8 - GRADED STONE AGGREGATE 40MM NOMINAL SIZE).( FOUNDATIO |
| 4151 | Laying of Control cable of all sizes through trench, proper connection at both ends outside in switchyard equipments <(>&<)> inside control room in VCB, control <(>&<)> relay Panels with proper marking, lugs ,labelling <(>&<)> ferrules etc |
| 4152 | Erection of SP-10 single support pole in proper level and alignment along with fixing of all accessories like top channel,& clamps a s per RESPO manual |
| 4153 | BRICK WORK WITH COMMON BURNT CLAP BRICKS WITH CEMNT MORTAR 1:4 |
| 4154 | CEMENT PLASTER WORK |
| 4155 | Erection of Sp-55 double support pole in proper level and alignment along with fixing of all accessories like top channel,X bracings ,& clamps as per RESPO manual |
| 4156 | ERRECTION OF 33KV PT |
| 4157 | PAINTING OF DOUBLE POLE (SP-55) |
| 4158 | EXCAVATION IN SOIL IN HILLY AREA/RIVER BED BY MECHANICAL MEANS I.E. BACKHOE LOADER |
| 4159 | BRICK WORK WITH COMMON BURNT CLAP BRICKS WITH CEMNT MORTAR 1:4 |
| 4160 | ERECTION <(>&<)> LAYING OF 11KV CABLE 3X240 SQ MM |
| 4161 | ERECTION OF 33/0.433KV S/S TRANSFORMER |
| 4162 | PAINTING OF DOUBLE POLE (SP-55) |
| 4163 | ERECTION OF PROVIDING <(>&<)> LAYING OF GRAVELLING SWITCHYARD |
| 4164 | EXCAVATION IN SOIL IN HILLY AREA/RIVER BED BY MECHANICAL MEANS I.E. BACKHOE LOADER |
| 4165 | RCC 1:1.5:3 |
| 4166 | CEMENT PLASTER WORK |
| 4167 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETEOF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - (I) 1:2:4 (1 -CEMENT; 2 - COARSE SAND; 8 - GRADED STONE AGGREGATE 20MM NOMINAL SIZE).( ROAD REPAIRING /OTHER WORK) |
| 4168 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETEOF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - ALL WORKS UPTO PLINTH LEVEL (I) 1:4:8 (1 - CEMENT; 4 - COARSE SAND; 8 - GRADED STONE AGGREGATE 40MM NOMINAL SIZE).( FOUNDATIO |
| 4169 | Random rubble masonry with hard stone in superstructure above plinth level and upto floor five level, including leveling up with cem ent concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) at window sills, ceiling le |
| 4170 | laying of MS bar 32 mm for making earth mat in switchyard area after fabrication / cutting in required size, laying at 2 mtr apart, also in crossing ( Making Net ), proper welding at each joint, laying at atleast 1 mtr depth in switchyard area for provi |
| 4171 | Digging of trench of size 0.60x0.15 x1.5 mtr. and laying of underground 11 KV XLPE cable with making of brick housing and filling of sand including filling of earth with ramming. & repairing of road including cost of cement sand and stone blast |
| 4172 | Earthing with two Nos. G.I earth plates 600mm x 600mm x 6mm thick(1.5 meter minimum in between distance) including accessories and p roviding double masonry enclosure with cover plate having locking arrangement and watering pipe of 3 meter long etc. With |
| 4173 | EXCAVATION IN SOIL IN HILLY AREA/RIVER BED BY MECHANICAL MEANS I.E. BACKHOE LOADER |
| 4174 | Cartage of the 11 KV VCB(I/C,O/G,Buscoupler) from store center to construction site with loading and unloading at both points.(Dista nce 51-70 Km) |
| 4175 | EARTHING OF STRUCTURE USING GI STRIP |
| 4176 | FIXING OF SODIUM/LED LIGHT AT YARD |
| 4177 | LAYING OF 4X10SQ MM LT PVC CABLE |
| 4178 | ERECTION OF 24 VOLT BATTERY SET |
| 4179 | ERECTION OF 24 VOLT BATTERY CHARGER |
| 4180 | INSTALLATION OF DCDB COMPLETE ON SUFACE OR WALL WITH THE HELP OF WALL ANCHOR BOLT FASTENERS 04NOS. COMPLETE TESTING AND COMMISSIONG OF DCDB AS PER SIDE REQUIREMENT AND NARRATED BY ENGINEER IN CHARGE OF THE WORK. |
| 4181 | INSTALLATION OF ACDB COMPLETE ON SUFACE OR WALL WITH THE HELP OF WALL ANCHOR BOLT FASTENERS 04NOS. COMPLETE TESTING AND COMMISSIONG OF DCDB AS PER SIDE REQUIREMENT AND NARRATED BY ENGINEER IN CHARGE OF THE WORK. |
| 4182 | ERECTION OF SUB-STATION NAMED BOARD |
| 4183 | ERECTION OF T<(>&<)>P ITEMS |
| 4184 | INSTALLATION OF FOAM TYPE FIRE EXTINGUSHER |
| 4185 | CIVIL WORK (INCLUDING FOUNDATION OF CAPACITOR CUBICAL ETC. AS PER REQUIREMENT) EARTH WORK |
| 4186 | BRICK WORK 1:6 SUB STRUCTURE |
| 4187 | BRICK WORK 1:6 SUB STRUCTURE |
| 4188 | CEMENT PLASTER WORK |
| 4189 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETEOF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - (I) 1:2:4 (1 -CEMENT; 2 - COARSE SAND; 8 - GRADED STONE AGGREGATE 20MM NOMINAL SIZE).( ROAD REPAIRING /OTHER WORK) |
| 4190 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETEOF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - ALL WORKS UPTO PLINTH LEVEL (I) 1:4:8 (1 - CEMENT; 4 - COARSE SAND; 8 - GRADED STONE AGGREGATE 40MM NOMINAL SIZE).( FOUNDATIO |
| 4191 | PROVIDING AND LAYING IN POSITION SPECIFIED GRADE OF REINFORCED CEMENT CONCRETE EXCLUDING THE COST OF CENTERING, SHUTTERING, FINISHING AND REINFORCEMENT - ALL WORKS UPTO PLINTH LEVEL (I) 1:1.5:3 (1-CEMENT; 1.5 - COARSE SAND; 3 - GRADED STONE AGGREGATE 20 |
| 4192 | FIXING AND ERECTION OF CAPACITOR BANK |
| 4193 | Erection of 33kV LINEDigging of trench of size 0.60x0.15 x1.5 mtr. and laying of underground 33 KV XLPE cable with making of brick housing and filling of sand including filling of earth with ramming. & repairing of road including cost of cement sand and stone blast |
| 4194 | ERECTION OF CONCRETE ROUTE MARKER FOR HT CABLE |
| 4195 | PAINTING OF SINGLE POLE (SP-55) |
| 4196 | Fabrication of MS Channel angle iron etc in required sizes with drilling of holes upto good finish for top channel,bracing and spec ial type bracket etc. as per RESPO schedule and local approced drawing. |
| 4197 | Grouting of pole in size 0.45x4.45x1/9 of the support in CC ration 1:4:8(1 cement:4 graded stone20 mm niminal size: 8 coarse sand) b lock including cost of cement, sand and stone ballast back filling of soil and boulders in pit and ramming and proper ali |
| 4198 | Erection of SP-55 single support pole in proper level and alignment along with fixing of all accessories like top channel,& clamps a s per RESPO manual |
| 4199 | Excavation of earth for pole pit of size 0.9x0.6x1/6 of full length of pole for erection of pole in all types of soil including prop er dressing of sides and ramming of bottom including etting out the excavated soil and disposal of surplus excavated soil |
| 4200 | Laying, Spreading, Stringing and sagging of 11 KV / 33 KV line in 3 phase (3 Phase 3 wire) of ACSR Dog as phase wire with G.I. earth wire complete including fixing of all accessories in 3 Nos. conductor in parallel with binding and jumpering as per prof |
| 4201 | Excavation of earth for pole pit of size 0.9x0.6x1/6 of full length of pole for erection of pole in all types of soil including prop er dressing of sides and ramming of bottom including etting out the excavated soil and disposal of surplus excavated soil |
| 4202 | Fabrication of MS Channel angle iron etc in required sizes with drilling of holes upto good finish for top channel,bracing and spec ial type bracket etc. as per RESPO schedule and local approced drawing. |
| 4203 | Guarding of 33 KV Line over (Telephone / Road / L.T. line crossing as per drawing with 6/8 SWG G.I. wire including fixing of guardin g channel/ angle as per RESSPO manual. |
| 4204 | PAINTING OF DOUBLE POLE (SP-55) |
| 4205 | Excavation of earth for stay pit of size 0.6x0.6x1.2 mtr in all types of soil including proper dressing of sides and ramming of bott om including getting out the excavated soil and disposal of surplus excavated soil as directed complete work |
| 4206 | Grouting of Stay in size 0.6x0.6x0.3 in CC ratio 1:4:8 (1 cement : 4 graded stone 20mm nominal size : 8 coarse sand ) block includ ing cost of Cement,sand and stone ballast back filling of soil and boulders in pit and ramming and proper alignment, lev |
| 4207 | Fixing,tightening and nozzling of stay with pole and stay rod on required tension as per drawing/manual in 33 KV line |
| 4208 | Earthing of support with M.S. Earth rod of 2.5 meter long by hammaring of M.S. Rod to proper depth and connecting the earth electrod e with the help of G.I. wire as per construction manual. |
| 4209 | Fabrication of MS Channel angle iron etc in required sizes with drilling of holes upto good finish for top channel,bracing and spec ial type bracket etc. as per RESPO schedule and local approced drawing. |
| 4210 | ERECTION AND LAYING OF HT 33 KV XLPE ALU. ARMOURED CABLE 3 X 400 SQ. MM. IN HDPE PIPE MIXED SOIL INCLUDING BACK FILLING OF EARTH <(>&<)> ERECTION ON POLE USING MS CHANNEL, ANGLE<(>&<)> CLAMPS ETC. |
| 4211 | MAKING OF 33KV XLPE CABLE LOOP AFTER DIGGING AND BACK FILLING OF EARTH SOIL AT BOTH END OF DP SECTION |
| 4212 | Supply <(>&<)> Fixing of G.I. Pipe Pole dia 4 Inch, Length (28 Feet) on Rental basis including Carriage, Loading, Unloading <(>&<)> Erection of 1 Phase Two Wire Line by PVC Cable of Size 1x10 Sqmm or as required including Fixing of Insulators<(>&<)> Nut |
| 4213 | FIXING OF CABLE HOLDING CLAMP |
| 4214 | Jointing and fixing of cable jointing kit indoor/outdoor 33 KV XLPE heat shrinkable cable boxes |
| 4215 | Cartage of other material (other than poles) by vehicle from Store Center to nearest construction site Store including loading and u nloading at both ends(distance 51-70 Km) |
| 4216 | Muffing of poles size 0.45x0.60 cm radius with 1:3:6(1 cement:3 coarse sand :graded stone 10 mm nominal size) block size 45 cm heigh t from ground level including cost of cement,stone and sand etc. |
| 4217 | Erection of SP-55(11KV/33 KV)four pole support pole in proper level and alignment along with fixing of all accessories like top chan nel,X bracings,& clamps as per RESPO manual |
| 4218 | Fabrication of MS Channel angle iron etc in required sizes with drilling of holes upto good finish for top channel,bracing and spec ial type bracket etc. as per RESPO schedule and local approced drawing. |
| 4219 | PAINTING OF FOUR POLE (SP-55) |
| 4220 | Muffing of poles size 0.45x0.60 cm radius with 1:3:6(1 cement:3 coarse sand :graded stone 10 mm nominal size) block size 45 cm heigh t from ground level including cost of cement,stone and sand etc. |
| 4221 | Fabrication of MS Channel angle iron etc in required sizes with drilling of holes upto good finish for top channel,bracing and spec ial type bracket etc. as per RESPO schedule and local approced drawing. |
| 4222 | Erection of Sp-55 double support pole in proper level and alignment along with fixing of all accessories like top channel,X bracings ,& clamps as per RESPO manual |
| 4223 | Muffing of poles size 0.45x0.60 cm radius with 1:3:6(1 cement:3 coarse sand :graded stone 10 mm nominal size) block size 45 cm heigh t from ground level including cost of cement,stone and sand etc. |
| 4224 | Grouting of pole in size 0.45x4.45x1/9 of the support in CC ration 1:4:8(1 cement:4 graded stone20 mm niminal size: 8 coarse sand) b lock including cost of cement, sand and stone ballast back filling of soil and boulders in pit and ramming and proper ali |
| 4225 | Excavation of earth for pole pit of size 0.9x0.6x1/6 of full length of pole for erection of pole in all types of soil including prop er dressing of sides and ramming of bottom including etting out the excavated soil and disposal of surplus excavated soil |
| 4226 | Grouting of pole in size 0.45x4.45x1/9 of the support in CC ration 1:4:8(1 cement:4 graded stone20 mm niminal size: 8 coarse sand) b lock including cost of cement, sand and stone ballast back filling of soil and boulders in pit and ramming and proper ali |
| 4227 | ERECTION OF 6\\" HDPE PIPE IN GROUND OR AS PER INSTRUCTION OF THE ENGINEER FOR CONNECTIONS OF OVERHEAD LINE TO UG LINE, CSS TO HT METERING CUBICLE AND FROM FEEDER PILLAR TO CONSUMER BUS BAR/METER |
| 4228 | Annual Maintenance Charges (AMC) and O&M of Project for 5 yearson per year basis. |
| 4229 | Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m inwidth or 10 sqm on plan), including dressing of sides and ramming ofbottoms, lift upto 1.5 m, including getting out the within a lead of 50 m.All kinds of soil. |
| 4230 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. |
| 4231 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. |
| 4232 | Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared. |
| 4233 | P/laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:1½:3 (1 Cement: 1½ coarse sand: 3 graded stone aggregate 20 mm nominal size) |
| 4234 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinthlevel :1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) |
| 4235 | Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III): 4 graded stone aggregate 12.5mm nominal size) |
| 4236 | Extra for providing and mixing water proofing material in cement concrete work in doses by weight of cement as per manufacturer’s specification. |
| 4237 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :sand: 3 graded stone aggregate 20 cm nominal size).1:1.5:3 (1 cement : 1.5coarse sand : 3 graded stone aggregate 20 mm nominal size) |
| 4238 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size) |
| 4239 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size). |
| 4240 | Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns, etc. for mass concrete |
| 4241 | Centering and shuttering including strutting, propping etc. and removal of form for : Suspended floors, roofs, landings, balconies and access platform |
| 4242 | Centering and shuttering including strutting, propping etc. and removal of form for : Shelves (Cast in situ) |
| 4243 | Centering and shuttering including strutting, propping etc. and removal of form for : Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 4244 | Centering and shuttering including strutting, propping etc. and removal of form for : Columns, Pillars, Piers, Abutments, Posts and Struts |
| 4245 | Centering and shuttering including strutting, propping etc. and removal of form for : Weather shade, Chajjas, corbels etc., including edges |
| 4246 | Steel reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete upto plinth level Thermo-Mechanically Treated bars |
| 4247 | Steel reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete above plinth level.Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 4248 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 4249 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 4250 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 4251 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure V level in all shapes and sizes in :Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 4252 | Half brick masonry with F.P.S. bricks of class designation 75 in superstructure above planth level up to floor V level. Cement morat 1:4 ( 1 cement : 4 coarse sand) |
| 4253 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Raj Nagar Plain white marble/ Udaipur green marble/ Zebra black marble. Area of slab upto 0.50 sqm |
| 4254 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Raj Nagar Plain white marble/ Udaipur green marble/ Zebra black marble. Area of slab over 0.50 sqm |
| 4255 | Providing and fixing glazed shutters for doors, windows and clerestory windows using 4 mm thick float glass panes, including ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws. Second class teak wood 35 mm thick |
| 4256 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws |
| 4257 | Providing and fixing ISI marked oxidised M.S. sliding door bolts with nuts and screws etc. complete : 250x16 mm |
| 4258 | Providing and fixing ISI marked oxidised M.S. tower bolt black finish (Barrel type) with necessary screws etc. complete : 200x10 mm |
| 4259 | Providing and fixing ISI marked oxidised M.S. tower bolt black finish (Barrel type) with necessary screws etc. complete : 150x10 mm |
| 4260 | Providing and fixing ISI marked oxidised M.S. tower bolt black finish (Barrel type) with necessary screws etc. complete : 100x10 mm |
| 4261 | Providing and fixing ISI marked oxidised M.S. handles conforming to IS:4992 with necessary screws etc. complete :125 mm |
| 4262 | Providing and fixing aluminium sliding door bolts, ISI marked anodised anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete : 250x16 mm |
| 4263 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete :(200x10mm) |
| 4264 | Providing and fixing aluminium tower door bolts ISI marked anodised (Anodic coating not less than grade AC 10 as per IS:1868)transparent or dyed to required colour or shade with nuts and screws etc. complete: (150x10mm) |
| 4265 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete :100x10 mm |
| 4266 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete :125mm |
| 4267 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete :100mm |
| 4268 | Providing and fixing aluminium handles floor door stopper ISI marked anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour or shade with necessary scerews etc. complet: Single rubber stopper |
| 4269 | Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete. Twin rubber stopper |
| 4270 | Providing and fixing wire gauge shutters using stainless steel grade 304 wire gauge with wire of dia 0.5 mm and average width of aperture 1.4 mm in both directions for doors, windows and clerestory windows with necessary screws :35 mm thick shutters with ISI marked M.S. pressed butt hinges bright finished of required size Second class teak wood |
| 4271 | Providing and fixing in position collapsible steel shutters with vertical channels 20x10x2 mm and braced with flat iron diagonals 20x5 mm size, with top and bottom rail of T-iron 40x40x6 mm, with 40 mm dia steel pulleys, complete with bolts, nuts, locking arrangement, stoppers, handles, including applying a priming coat of approved steel primer. |
| 4272 | Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge:Profile B Fixing with adjustable lugs with split end tail to each jamb |
| 4273 | Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge:Profile C Fixing with adjustable lugs with split end tail to each jamb |
| 4274 | Steel work in built up tubular ( round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished welded type tubes |
| 4275 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard rawing.surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing. |
| 4276 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 4277 | Providing & fixing fly proof wire gauze to windows, clerestory windows & doors with M.S. Flat 15x3 mm and nuts & bolts complete. Galvanised M.S. Wire gauze with 0.63 mm dia wire and 1.4 mm aperture on both sides |
| 4278 | Providing & fixing glass panes with putty and glazing clips in steel doors, windows, clerestory windows, all complete with :5.5 mm thick glass panes |
| 4279 | Cement concrete flooring 1:2:4 (1 cement : 2coarse sand : 4 gradd stone aggregate) finished with a floating coat of neat cement including cement slurry, (40 mm thick with 20mm nomnal sxe stone aggregate). |
| 4280 | Providing and fixing glass strips in joints of terrazo/ cement concrete floors. 40 mm wide and 4 mm thick |
| 4281 | P/F Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. |
| 4282 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in all colours, shades, except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick bed of cement mortar 1:4 (1 Cement : 4 Coarse sand), including pointing the joints with white cement and matching pigments etc., complet |
| 4283 | Providing and laying polished vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption,s less than 0.08% and conforming to IS 15622 of approved make in all colours and shades, laid on 20mm thick cement mortar 1:4 ( 1 cement: 4 coarse sand ) including grouting the joints with white cement and matching pigments etc, complete. (size of Tile 60x60cm) |
| 4284 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete.Size of Tile 600x600 mm |
| 4285 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS: 13592 (i) Single socketed pipes (75mm diameter) |
| 4286 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes 110 mm diameter |
| 4287 | 12 mm cement plaster of mix 1:4(1 cement: 4 coarse sand) |
| 4288 | 12 mm cement plaster of mix : 1:6 (1 cement : 6 coarse sand) |
| 4289 | 15mm cement plaster on rough side of single or half brick wall of mix: 1:6 (1cement :6coarse sand) |
| 4290 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade : New work (two or more coats) over and including water tinnable priming coat with cement primer |
| 4291 | Finishing walls with textured exterior paint of required shade : New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/ 10 sqm |
| 4292 | Finishing walls with Acrylic Smooth exterior paint of required shade :New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) |
| 4293 | Painting with synthetic enamel paint of approved brand andmanufacture to give an even shade :Two or more coats on new work |
| 4294 | Providing and applying white cement based putty of average thickness 1mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 4295 | Supplying and stacking at site.Good earth |
| 4296 | Extra for providing and mixing hardening compound of approved quality as per manufacturer’s specification in cement concrete. |
| 4297 | Providing and fixing in position pre-moulded joint filler in expansion per cm depth joint. |
| 4298 | Providing and laying 60mm thick factory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge. |
| 4299 | Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever)conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests |
| 4300 | Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I.brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required : 17.3.1 W.C. pan with ISI marked white solid plastic seat and lid |
| 4301 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required : One urinal basin with 5 litre white P.V.C. automatic flushing cistern |
| 4302 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brasspillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: |
| 4303 | Providing and fixing white vitreous china pedestal for wash basin completely recessed at the back for the reception of pipes and fittings. |
| 4304 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 4305 | Providing and fixing terminal guard : 75 mm Sand cast iron S&S as per IS - 1729 |
| 4306 | Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : 100 mm inlet and 100 mm outlet (Sand cast iron S&S as per IS: 3989) |
| 4307 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. 450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm, weighing not less than 170 gms |
| 4308 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall 20 mm nominal outer dia Pipes |
| 4309 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall 25 mm nominal outer dia Pipes |
| 4310 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 20 mm nominal outer dia Pipes |
| 4311 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement ,trenching ,refilling & testing of joints complete as per direction of Engineer in Charge.External work 15 mm nominal outer dia Pipes |
| 4312 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement ,trenching ,refilling & testing of joints complete as per direction of Engineer in Charge.External work 20 mm nominal outer dia Pipes |
| 4313 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement ,trenching ,refilling & testing of joints complete as per direction of Engineer in Charge.External work 25 mm nominal outer dia Pipes |
| 4314 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement ,trenching ,refilling & testing of joints complete as per direction of Engineer in Charge.External work 32 mm nominal outer dia Pipes |
| 4315 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement ,trenching ,refilling & testing of joints complete as per direction of Engineer in Charge.External work 40 mm nominal outer dia Pipes |
| 4316 | Constructing masonry Chamber 30x30x50 cm inside, in brick work incement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stoneaggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design : With common burnt clay F.P.S.(non modular) bricks of class designation 7.5 |
| 4317 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, ISI : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 4318 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 15 mm nominal bore |
| 4319 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.(15 mm nominal bore) |
| 4320 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931.(15 mm nominal bore) |
| 4321 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 a) 15 mm nominal bore 15mm nominal bore |
| 4322 | Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighing not less than 106 gms. |
| 4323 | P/Fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron) |
| 4324 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15) Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 4325 | Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge. Pre-laminated particle board with decorative lamination on one side and balancing lamination on other side |
| 4326 | Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge.With stainless steel cover plate minimum 1.25 mm thickness |
| 4327 | Providing and fixing 100mm brass locks (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete. |
| 4328 | Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer-in-charge, upto 90 metre depth below ground level.All types of soil 300 mm dia |
| 4329 | Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer -in-charge.100 mm nominal size dia |
| 4330 | Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge.100 mm nominal size dia |
| 4331 | Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. |
| 4332 | Engaging suitable Beldar for petty works (Basis rate labour) |
| 4333 | Stone Aggregate (Single size) : 20 mm nominal size |
| 4334 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. GROUP B |
| 4335 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 4336 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 4337 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 4338 | Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 4339 | Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 amps socket outlet and 15/16 amps piano type switch, connection, painting etc. as required. |
| 4340 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq. mm FR PVC insulated, copper conductor, single core cable and earthing etc. as required.. |
| 4341 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.Upto 450 mm sweep |
| 4342 | Supplying and Drawing of UTP 4 pair Cat 6 Lane Cable in the existing Surface /recessed Steel/ PVC Conduit as Required.2 run of cable |
| 4343 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way , Double door |
| 4344 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 4345 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps |
| 4346 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 4347 | Supplying of 20Watt LED Tubelight Philips or equivalent make as approved by E.I. S.E. letter no-832 /ECC/D.Dun/Extra Item Dated-29-08-2022 |
| 4348 | Supplying of Exhaust Fan 250mm sweep of Orient or equivalent make as approved by E.I. S.E. letter no-832 /ECC/D.Dun/Extra Item Dated-29-08-2022 |
| 4349 | \\"Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos.blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. file no-E-9059857/9(new technology)/C.E.(Ren.)CSQ/2019 Dated-18/11/2019\\" |
| 4350 | Supply and Installation 40mm outlet size submersible pump set 1.00HP, I stage of crompton greaves or equivalent make as approved by E.I. |
| 4351 | Supply and Placing single phase panel board/ box crompton greaves or equivalent make as approved by E.I. |
| 4352 | Supplying of Exhaust Fan 450mm sweep of Orient or equivalent make as approved by E.I. S.E. letter no-832 /ECC/D.Dun/Extra Item Dated-29-08-2022 |
| 4353 | Supply and Installation Water Purifier (15LPH) kent or Equivalent make approved by E.I. S.E. letter no-1154 /ECC/D.Dun/Extra Item Dated-15-11-2022 |
| 4354 | Supply and Placing 20/40 LTR Storage Water Cooler SS Body USHA make or Equivalent make approved by E.I. S.E. letter no-1154 /ECC/D.Dun/Extra Item Dated-15-11-2023 |
| 4355 | Supply for 33/11kV SubstationEARTHING ROD MS 20X2500MM |
| 4356 | 33 kV LIGHTNING ARRESTER |
| 4357 | 8 m. LONG STP 410 SP-10 (BPHD GAL.) |
| 4358 | LT PVC CABLE 4X10 SQ.mm |
| 4359 | 33 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 4360 | 33 kV FUSE SET |
| 4361 | ACSR DOG |
| 4362 | CONTROL CABLE 10X2.5 SQ. mm. |
| 4363 | CABLE AL 3X240 SQ. MM XLPE 11 KV |
| 4364 | CONTROL CABLE 4X2.5 SQ. mm. |
| 4365 | J/KIT FOR 3X240MM² 11KV XLPE CABLE (O/D) |
| 4366 | CONTROL CABLE 6X2.5 SQ. mm. |
| 4367 | 9 kV 10KA LIGHTNING ARRESTER |
| 4368 | 9 kV 5KA LIGHTNING ARRESTER (POLYMER) |
| 4369 | GI WIRE 5mm/6 SWG |
| 4370 | STAY WIRE GI 7/3.15mm 7/10SWG |
| 4371 | STAY SET GI 16X1800mm |
| 4372 | DISC FIT. B&S TYPE WEASEL/RABBIT 45 KN |
| 4373 | 11 kV POLYMER DISC INSULATOR (B&S) TYPE |
| 4374 | 11 MTR. LONGSTP 410 SP-55(BPHD GAL.) |
| 4375 | LT XLPE CABLE 3.5.X 70 SQ. MM. |
| 4376 | PANTHER TO PANTHER CTYPE WEDGE CONNECTOR |
| 4377 | CABLE AL 3X70 SQ. MM XLPE 33KV |
| 4378 | DISC FIT. B&S TYPE FOR PANTHER 90 KN |
| 4379 | JUNCTION BOX FOR 33KV PT |
| 4380 | MS ROUND 32 mm |
| 4381 | 33 KV H.S. Cable J/K 3x70 sq. mm (O/D) |
| 4382 | J/KIT FOR 3X400mm² 11kV XLPE CABLE (O/D) |
| 4383 | CABLE AL 1X630 SQ. mm XLPE 11kV |
| 4384 | LT PVC CABLE 2X6 SQ.mm (ARMORED) |
| 4385 | 33KV PT OF RATIO 33 KV/110V OUTDOOR |
| 4386 | CABLE AL 3X400 SQ. mm XLPE 11kV |
| 4387 | CONTROL CABLE 2X2.5 SQ. mm. |
| 4388 | ACSR PANTHER |
| 4389 | Dustbin Plastic Size (Small) |
| 4390 | SHOCK TREATMENT CHART |
| 4391 | DANGER BOARD |
| 4392 | SHUT DOWN/ BREAK DOWN BOARD |
| 4393 | 33 KV Hand Gloves |
| 4394 | WALL CLOCK |
| 4395 | High Insulated plier |
| 4396 | 12KV 1250A Gang ope PMA VCB(Capacitor) |
| 4397 | D-SPANNER SET |
| 4398 | Torch 3 Cell |
| 4399 | 12KV 1250A Gang ope PMA VCB(I/C) |
| 4400 | 33KV C&R PANEL O/G-D |
| 4401 | 33KV C&R PANEL I/C-D |
| 4402 | 36KV 1250A Gang ope PMA VCB(O/G) |
| 4403 | 36KV 1250A Gang ope PMA VCB(I/C) |
| 4404 | Stay Clamp for SP-55 With Nut & Bolt |
| 4405 | Rubber Mat (12mm) 2M X1M X12mm |
| 4406 | Steel Almirah |
| 4407 | Office Table size (4x2.5) |
| 4408 | GI bolts & nut with washers. |
| 4409 | #HT# WARNING TAPE |
| 4410 | KM-21 G.I. Pipe 6'' dia 3 meter long |
| 4411 | GI Pipe 4'\\" Dia |
| 4412 | Fire Bucket Stand with Buckets |
| 4413 | Fire Bucket stand of MS angle |
| 4414 | ST. LIGHT MANAG. TIMER SWITCH WITH METER |
| 4415 | Iron Clad 30 Amp Switch |
| 4416 | G.I EARTH STRIP 65X6MM |
| 4417 | 11 KV Fuse Set |
| 4418 | 33/0.433 KV, 63 KVA STATION TRANSFORMER |
| 4419 | 12.65KV, 3600KVAR, CAPACITOR BANK |
| 4420 | CONNECTOR SUIT FOR CT/PT FOR PANTHER/DOG |
| 4421 | THIMBLE JUNCTION BOX FOR CABLE SUPPORT |
| 4422 | INDOOR TYPE AUTO POWER FACTOR CONTROLLER |
| 4423 | CONNE.SUITABLE FOR PANTHER FOR LA |
| 4424 | 33KV C&R PANEL BUS COUPLER-D |
| 4425 | 2.5 KV MEGGAR DIGITAL |
| 4426 | 36KV 1250A GANG OPE PMA VCB(B/C) |
| 4427 | Meggar 5 KV Digital |
| 4428 | Earth Chain |
| 4429 | MS STRUCTURE (ANGLE ,CHANNEL ETC.) |
| 4430 | JOINTING KIT 3X240 SQ.MM 33KV XLPE (I/D) |
| 4431 | Door Mat |
| 4432 | GI ITEM (RAIL,JOIST,CHANNEL,ANGLE) |
| 4433 | CONNECTOR OF POWER T/F LV SIDE |
| 4434 | 33KV ISOLATOR CONN.CLAMP FOR PANTHER,N&B |
| 4435 | CONNECTOR OF POWER T/F HV SIDE |
| 4436 | FLEXIBLE COOPER CONNECTOR 50X50MM |
| 4437 | 12KV 1250A Gang ope PMA VCB(O/G) |
| 4438 | EARTH MEGGAR DIGITAL |
| 4439 | CONNECTOR SUITABLE. PANTHER FOR VCB |
| 4440 | 250 W hpsv/led lamp with contrl gear |
| 4441 | DCDB 24V |
| 4442 | 24 V BATTERY SET |
| 4443 | Invertor |
| 4444 | INSTRUCTION BOARD |
| 4445 | Single Line Diagram Board |
| 4446 | MAXIMUM & MINIMUM DISPLAY BOARD |
| 4447 | SUB STATION NAMED BOARD |
| 4448 | Name Plate of Equip. TG,LI,BI,CT,CB ect. |
| 4449 | SUNDRISE ITEM LUG GLADE ETC |
| 4450 | Steel Cabinet |
| 4451 | 11KV C&R PANEL BUS COUPLER-D |
| 4452 | 33 KV Isolator Vertical Type |
| 4453 | First aid box |
| 4454 | 11kv isolator manual&motor,SCADA comp. |
| 4455 | 33 KV Danger Board with Clamp |
| 4456 | Name plate of station t/f |
| 4457 | Cable Holding clamp with N&B |
| 4458 | PG Clamp For Dog Conductor |
| 4459 | PG CLAMP ALU ALLOY PANTHER TO DOG |
| 4460 | Alluminium Lug |
| 4461 | G.I.Strip 35x4mm |
| 4462 | PERFORATED TRAY 100MM FOR CABLE TRENCH |
| 4463 | Steel office chair Godrej |
| 4464 | 33kv line isolator manual&motor,SCADA co |
| 4465 | Wire Mesh Fencing |
| 4466 | Portable Foam Type Fire Extinguisher 5LT |
| 4467 | Steel office Table |
| 4468 | RAIL 90 LBS |
| 4469 | 11KV Danger Board with Clamp |
| 4470 | Name plate of feeder |
| 4471 | 11kv 3P(400A)3pin vert. mount GO AB TPMO |
| 4472 | 11 KV HS cable END T/K 1x630 sq mm I/D |
| 4473 | PP clamp with N&B (GI) |
| 4474 | 12KV C&R Panel with SCADA(Capacitor) |
| 4475 | 11KV C&R PANEL O/G-D |
| 4476 | 11KV C&R PANEL I/C-D |
| 4477 | 12KV 1250A Gang ope PMA VCB(B/C) |
| 4478 | PERFORATED TRAY 400MM FOR CABLE TRENCH |
| 4479 | PIPE WRENCH 12'' |
| 4480 | MS Plate 300x300x8 mm. |
| 4481 | Holding Clamp FPR GI Pipe 8/10''& MS Ch. |
| 4482 | Conne.Suitable for Panther for LA |
| 4483 | PERFORATED TRAY 200MM FOR CABLE TRENCH |
| 4484 | Fire Extingushier |
| 4485 | GI STRIP 50X6 MM |
| 4486 | 11 KV HS cable END T/K 1x630 mm² O/D |
| 4487 | G.I. Plate 300x300x8 mm. |
| 4488 | Stone Pad 300x300x75mm |
| 4489 | Cable Jointing Kit 1x630 Indoor |
| 4490 | Cable Jointing Kit 1x630 Outdoor |
| 4491 | PG CLAMP ACSR PANTHER TO ACSR DOG |
| 4492 | PG CLAMP ALU ALLOY PANTHER TO PANTHER |
| 4493 | 33 KV XLPE Cable AL 1x630 sq. mm-D |
| 4494 | Supply for 33kV Line:33 KV POLYMER DISC INSULATOR (B&S) TYPE |
| 4495 | 33KV 10KN POLYMER PIN INSULATOR WITH PIN |
| 4496 | DISC FIT. B&S TYPE DOG/RACOON 70 KN |
| 4497 | MS CHANNEL 125X65 MM |
| 4498 | 11 MTR. LONGSTP 410 SP-55(BPHD GAL.) |
| 4499 | X ARM CHANNEL 100X50 MM V TYPE 33 KV |
| 4500 | MS ANGLE 65X65X6 MM |
| 4501 | STAY SET GI 20X1800mm |
| 4502 | STAY WIRE GI 7/3.15mm 7/10SWG |
| 4503 | EARTHING ROD MS 20X2500mm |
| 4504 | GI WIRE 5mm/6 SWG |
| 4505 | EARTH WIRE GI 7/1.6MM 16 SWG |
| 4506 | ACSR DOG |
| 4507 | GI WIRE 4mm/8mm SWG |
| 4508 | MS ANGLE 75X75X6 mm |
| 4509 | MS CHANNEL 100X50 mm |
| 4510 | 11 KV POLYMER DISC INSULATOR (B&S) TYPE |
| 4511 | DISC FIT. B&S TYPE WEASEL/RABBIT 45 KN |
| 4512 | 11 KV POLYMER PIN INSULATOR WITH PIN |
| 4513 | ACSR WEASEL |
| 4514 | 9 MRT. LONG STP 410 SP-33(BPHD GAL.) |
| 4515 | 8.5 MRT. LONG STP 410 SP-23(BPHD GAL.) |
| 4516 | X ARM ANGLE 65X65X6 MM V TYPE 11 KV |
| 4517 | BRACING CLAMP TOP WITH N&B SP-55 |
| 4518 | BRACING CLAMP BOTTOM WITH N&B SP-55 |
| 4519 | TOP CHENNEL CLAMP WITH N&B |
| 4520 | HOLDING CLAMP FOR SP-55 WITHN/B |
| 4521 | EARTH WIRE CLAMP FOR SP-55 WITH N/B |
| 4522 | 33 KV DANGER BOARD WITH CLAMP |
| 4523 | Stay Clamp for SP-55 With Nut & Bolt |
| 4524 | HT Stay Insulator |
| 4525 | BARBED WIRE |
| 4526 | NUMBER PLATE WITH CLAMP |
| 4527 | PG Clamp For Dog Conductor |
| 4528 | Stone Pad 300x300x75mm |
| 4529 | BOLT & NUTS OFF SIZE |
| 4530 | E- CLAMP |
| 4531 | Bolt & Nut 150x12 mm |
| 4532 | EYE BOLT SIZE 100X16 |
| 4533 | PP & CLAMP WITH N&B ST POLE SP-55 |
| 4534 | Bolt & Nuts 50x16 mm |
| 4535 | PP & CLAMP WITH N&B ST POLE SP-33 |
| 4536 | BRACING SET CLAMP TOP WITH N/B FOR SP-33 |
| 4537 | EARTH WIRE CLAMP FOR SP-33 WITH N/B |
| 4538 | SHACKLE INSULATOR 100X115 MM WITH N&B |
| 4539 | LT CLAMP WITH N&B ST POLE SP-33 |
| 4540 | F CLAMP |
| 4541 | PG CLAMP FOR DOG/WEASEL |
| 4542 | 33 KV E- CLAMP |
| 4543 | Erection/Labour Work for Substation:Random rubble masonry with hard stone in superstructure above plinth level and upto floor five level, including leveling up with cem ent concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) at window sills, ceiling le |
| 4544 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETEOF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - ALL WORKS UPTO PLINTH LEVEL (I) 1:4:8 (1 - CEMENT; 4 - COARSE SAND; 8 - GRADED STONE AGGREGATE 40MM NOMINAL SIZE).( FOUNDATION |
| 4545 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETEOF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - (I) 1:2:4 (1 -CEMENT; 2 - COARSE SAND; 8 - GRADED STONE AGGREGATE 20MM NOMINAL SIZE).( ROAD REPAIRING /OTHER WORK) |
| 4546 | CEMENT PLASTER WORK |
| 4547 | RCC 1:1.5:3 |
| 4548 | EXCAVATION IN SOIL IN HILLY AREA/RIVER BED BY MECHANICAL MEANS I.E. BACKHOE LOADER |
| 4549 | ERECTION OF PROVIDING <(>&<)> LAYING OF GRAVELLING SWITCHYARD |
| 4550 | PAINTING OF DOUBLE POLE (SP-55) |
| 4551 | ERECTION OF 33/0.433KV S/S TRANSFORMER |
| 4552 | ERECTION <(>&<)> LAYING OF 11KV CABLE 3X240 SQ MM |
| 4553 | BRICK WORK WITH COMMON BURNT CLAP BRICKS WITH CEMNT MORTAR 1:4 |
| 4554 | EXCAVATION IN SOIL IN HILLY AREA/RIVER BED BY MECHANICAL MEANS I.E. BACKHOE LOADER |
| 4555 | PAINTING OF DOUBLE POLE (SP-55) |
| 4556 | ERRECTION OF 33KV PT |
| 4557 | Erection of Sp-55 double support pole in proper level and alignment along with fixing of all accessories like top channel,X bracings ,& clamps as per RESPO manual |
| 4558 | CEMENT PLASTER WORK |
| 4559 | BRICK WORK WITH COMMON BURNT CLAP BRICKS WITH CEMNT MORTAR 1:4 |
| 4560 | Erection of SP-10 single support pole in proper level and alignment along with fixing of all accessories like top channel,& clamps a s per RESPO manual |
| 4561 | Laying of Control cable of all sizes through trench, proper connection at both ends outside in switchyard equipments <(>&<)> inside control room in VCB, control <(>&<)> relay Panels with proper marking, lugs , labelling <(>&<)> ferrules etc |
| 4562 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETEOF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - ALL WORKS UPTO PLINTH LEVEL (I) 1:4:8 (1 - CEMENT; 4 - COARSE SAND; 8 - GRADED STONE AGGREGATE 40MM NOMINAL SIZE).( FOUNDATIO |
| 4563 | MAKING CABLE TRENCH |
| 4564 | laying of MS bar 32 mm for making earth mat in switchyard area after fabrication / cutting in required size, laying at 2 mtr apart, also in crossing ( Making Net ), proper welding at each joint, laying at atleast 1 mtr depth in switchyard area for provi |
| 4565 | FIXING AND ERECTION OF CAPACITOR BANK |
| 4566 | PROVIDING AND LAYING IN POSITION SPECIFIED GRADE OF REINFORCED CEMENT CONCRETE EXCLUDING THE COST OF CENTERING, SHUTTERING, FINISHING AND REINFORCEMENT - ALL WORKS UPTO PLINTH LEVEL (I) 1:1.5:3 (1-CEMENT; 1.5 - COARSE SAND; 3 - GRADED STONE AGGREGATE 20 |
| 4567 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETEOF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - ALL WORKS UPTO PLINTH LEVEL (I) 1:4:8 (1 - CEMENT; 4 - COARSE SAND; 8 - GRADED STONE AGGREGATE 40MM NOMINAL SIZE).( FOUNDATIO |
| 4568 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETEOF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - (I) 1:2:4 (1 -CEMENT; 2 - COARSE SAND; 8 - GRADED STONE AGGREGATE 20MM NOMINAL SIZE).( ROAD REPAIRING /OTHER WORK) |
| 4569 | CEMENT PLASTER WORK |
| 4570 | BRICK WORK 1:6 SUB STRUCTURE |
| 4571 | BRICK WORK 1:6 SUB STRUCTURE |
| 4572 | CIVIL WORK (INCLUDING FOUNDATION OF CAPACITOR CUBICAL ETC. AS PER REQUIREMENT) EARTH WORK |
| 4573 | INSTALLATION OF FOAM TYPE FIRE EXTINGUSHER |
| 4574 | ERECTION OF T<(>&<)>P ITEMS |
| 4575 | ERECTION OF SUB-STATION NAMED BOARD |
| 4576 | INSTALLATION OF ACDB COMPLETE ON SUFACE OR WALL WITH THE HELP OF WALL ANCHOR BOLT FASTENERS 04NOS. COMPLETE TESTING AND COMMISSIONG OF DCDB AS PER SIDE REQUIREMENT AND NARRATED BY ENGINEER IN CHARGE OF THE WORK. |
| 4577 | INSTALLATION OF DCDB COMPLETE ON SUFACE OR WALL WITH THE HELP OF WALL ANCHOR BOLT FASTENERS 04NOS. COMPLETE TESTING AND COMMISSIONG OF DCDB AS PER SIDE REQUIREMENT AND NARRATED BY ENGINEER IN CHARGE OF THE WORK. |
| 4578 | ERECTION OF 24 VOLT BATTERY CHARGER |
| 4579 | ERECTION OF 24 VOLT BATTERY SET |
| 4580 | LAYING OF 4X10SQ MM LT PVC CABLE |
| 4581 | FIXING OF SODIUM/LED LIGHT AT YARD |
| 4582 | EARTHING OF STRUCTURE USING GI STRIP |
| 4583 | Cartage of the 11 KV VCB(I/C,O/G,Buscoupler) from store center to construction site with loading and unloading at both points.(Dista nce 0-20 Km) |
| 4584 | EXCAVATION IN SOIL IN HILLY AREA/RIVER BED BY MECHANICAL MEANS I.E. BACKHOE LOADER |
| 4585 | Earthing with two Nos. G.I earth plates 600mm x 600mm x 6mm thick(1.5 meter minimum in between distance) including accessories and p roviding double masonry enclosure with cover plate having locking arrangement and watering pipe of 3 meter long etc. With |
| 4586 | Digging of trench of size 0.60x0.15 x1.5 mtr. and laying of underground 11 KV XLPE cable with making of brick housing and filling of sand including filling of earth with ramming. & repairing of road including cost of cement sand and stone blast |
| 4587 | DELTA EARTHING OF T/F NEUTRAL POINT WITH 3 NOS. MS EARTH ROD GI STRIP <(>&<)> EARTH WIRE |
| 4588 | Laying and erection of L.T. PVC single lead Cable including crimping of lugs of size 1x240, 400, 630 Sq.mm etc. (Including all cost of material) |
| 4589 | Jointing and fixing of cable jointing kit indoor/outdoor 33 KV XLPE heat shrinkable cable boxes |
| 4590 | FIXING OF 33 KV LINE ISOLATOR VERTICAL TYPE ON ST POLE |
| 4591 | Earth filling under floor and insub-station area including cost of earth. Earth to be obtained from outside the corporation area in cluding its cartage and ramming, watering, dressing in 20 cm's thick layers including cost of earth with all lead and lif |
| 4592 | ERECTION OF STAY POST |
| 4593 | FENCING OF YARD |
| 4594 | EXCAVATION IN SOIL IN HILLY AREA/RIVER BED BY MECHANICAL MEANS I.E. BACKHOE LOADER |
| 4595 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETEOF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - ALL WORKS UPTO PLINTH LEVEL (I) 1:4:8 (1 - CEMENT; 4 - COARSE SAND; 8 - GRADED STONE AGGREGATE 40MM NOMINAL SIZE).( FOUNDATIO |
| 4596 | EXCAVATION IN SOIL IN HILLY AREA/RIVER BED BY MECHANICAL MEANS I.E. BACKHOE LOADER |
| 4597 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETEOF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - ALL WORKS UPTO PLINTH LEVEL (I) 1:4:8 (1 - CEMENT; 4 - COARSE SAND; 8 - GRADED STONE AGGREGATE 40MM NOMINAL SIZE).( FOUNDATIO |
| 4598 | CEMENT PLASTER WORK |
| 4599 | Erection of Sp-55 double support pole in proper level and alignment along with fixing of all accessories like top channel,X bracings ,& clamps as per RESPO manual |
| 4600 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETEOF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - ALL WORKS UPTO PLINTH LEVEL (I) 1:4:8 (1 - CEMENT; 4 - COARSE SAND; 8 - GRADED STONE AGGREGATE 40MM NOMINAL SIZE).( FOUNDATIO |
| 4601 | Jointing and fixing of cable jointing kit indoor/outdoor 11 KV XLPE heat shrinkable cable boxes |
| 4602 | ERECTION OF BUS BAR |
| 4603 | ERECTION OF FLEXIBLE CU. CONN. 500X50 MM |
| 4604 | Earthing of distribution transformer including digging of pit of size 2.5 Mtr depth and make hole of size 150 mm. Placing of earthin g electrode (to be supplied by contractor as per drawing No. A) as drawing B, connecting the same with G.I. Strip (to be |
| 4605 | MAKING CABLE TRENCH |
| 4606 | Jointing and fixing of cable jointing kit indoor/outdoor 11 KV XLPE heat shrinkable cable boxes |
| 4607 | 11KV, 630 AMP, OFF LOAD ISOLATOR WITH EARTH SWITCH AND MOUNTING STRUCTURE\\" |
| 4608 | Making of Trench cover with 40x40x5 mm angle frame, 10 mm ironbars inside for strengthning at 90 -100 mm apart, also in crossing with cement concrete ratio 1:2:4, providing both side handles for lifting. |
| 4609 | Painting of SP-10 pole with angle and channel and all steel part by one coat of Red Oxide Primer and two coats of aluminium Paint an d two strip of fluorescent altemate Red and White paint 30 Cm wide upto 1.5 Mtrs. From ground level. |
| 4610 | EARTH WORK IN EXCAVATION BY MECHNICAL MEANS / MANUAL MEANS OVER AREAS CC/HARDROCK |
| 4611 | Shifting of 5/ 3 MVA Power Transformer from road site to work site/ store center to loading site place with the manual pulling. |
| 4612 | Erection of (8,5) MVA T/F at transformer plinth & erection of all accessories i.e. radiators, conservator tank, vent pipee etc., wit h the help of special type of T&P / crane etc. fitting cable etc. and refilling the fresh oil in radiator and conservator |
| 4613 | Erection of cable stand neutral stand including fabrication cutting and welding work. |
| 4614 | EXCAVATION IN SOIL IN HILLY AREA/RIVER BED BY MECHANICAL MEANS I.E. BACKHOE LOADER |
| 4615 | Grouting of structure in CC 1:3:6 in size (2x1.1x0.3x0.3) mtr. |
| 4616 | CEMENT PLASTER WORK |
| 4617 | Mounting and Fixing of Lightning arrestor set (3 Nos.) on double pole structure including making all connections by G.I. strip size 35x6 mm to earth point complete work (excluding cost of G.I.Strip) |
| 4618 | CEMENT PLASTER WORK |
| 4619 | Fixing of GI pipe. |
| 4620 | Jointing and fixing of cable jointing kit indoor/outdoor 33 KV XLPE heat shrinkable cable boxes |
| 4621 | Installation / Fixing of 33 Kv Isolator on structure at 33 Kv switchyard with proper alignment <(>&<)> Connections with busbar comp lete. |
| 4622 | Digging of trench of size 0.60x0.15 x1.5 mtr. and laying of underground 33 KV XLPE cable with making of brick housing and filling of sand including filling of earth with ramming. & repairing of road including cost of cement sand and stone blast |
| 4623 | Cartage of 5/8 MVA Power transformer by road(loading/unloading/shifting to be charged extra)(151-200 KM) |
| 4624 | Cartage of other material (other than poles) by vehicle from Store Center to nearest construction site Store including loading and u nloading at both ends(distance 151-200 Km) |
| 4625 | ERECTION OF MISC. GI STRUCTURES |
| 4626 | COMM.OF 33/11KV VCB PANEL WITH RESPECT WORK |
| 4627 | Mannual shifting /Pulling of Control Relay Panel for Single T/F / Single Feeder from existing site to plinth/ nearby place distanc e upto 200 mtrs. |
| 4628 | Cartage of the 33 KV VCB,feeder panels(O/D),T/F Control panel from store center to construction site with loading and unloading at both points.(Distance 151-200 Km) |
| 4629 | Fabrication of MS Channel angle iron etc in required sizes with drilling of holes upto good finish for top channel,bracing and spec ial type bracket etc. as per RESPO schedule and local approced drawing. |
| 4630 | EXCAVATION IN SOIL IN HILLY AREA/RIVER BED BY MECHANICAL MEANS I.E. BACKHOE LOADER |
| 4631 | Erection/Labour Work for 33kV Line:PAINTING OF DOUBLE POLE (SP-55) |
| 4632 | Fabrication of MS Channel angle iron etc in required sizes with drilling of holes upto good finish for top channel,bracing and spec ial type bracket etc. as per RESPO schedule and local approced drawing. |
| 4633 | Erection of Sp-55 double support pole in proper level and alignment along with fixing of all accessories like top channel,X bracings ,& clamps as per RESPO manual |
| 4634 | Muffing of poles size 0.45x0.60 cm radius with 1:3:6(1 cement:3 coarse sand :graded stone 10 mm nominal size) block size 45 cm heigh t from ground level including cost of cement,stone and sand etc. |
| 4635 | Grouting of pole in size 0.45x4.45x1/9 of the support in CC ration 1:4:8(1 cement:4 graded stone20 mm niminal size: 8 coarse sand) b lock including cost of cement, sand and stone ballast back filling of soil and boulders in pit and ramming and proper ali |
| 4636 | BACK HEAD LOAD CARTAGE OF SMALL LINE MATERIAL ABOVE 3 KM |
| 4637 | Cartage of other material (other than poles) by vehicle from Store Center to nearest construction site Store including loading and u nloading at both ends(distance 151-200 Km) |
| 4638 | Headload cartage of SP-55 Pole from road to site(distance 1-3 Km) |
| 4639 | Cartage of ST pole SP-55 Poles from store centre to construction site with loading, unloading at both points and proper stacking.(Distance 151-200 Km) |
| 4640 | Grouting of pole in size 0.45x4.45x1/9 of the support in CC ration 1:4:8(1 cement:4 graded stone20 mm niminal size: 8 coarse sand) b lock including cost of cement, sand and stone ballast back filling of soil and boulders in pit and ramming and proper ali |
| 4641 | Muffing of poles size 0.45x0.60 cm radius with 1:3:6(1 cement:3 coarse sand :graded stone 10 mm nominal size) block size 45 cm heigh t from ground level including cost of cement,stone and sand etc. |
| 4642 | Erection of SP-55(11KV/33 KV)four pole support pole in proper level and alignment along with fixing of all accessories like top chan nel,X bracings,& clamps as per RESPO manual |
| 4643 | Fabrication of MS Channel angle iron etc in required sizes with drilling of holes upto good finish for top channel,bracing and spec ial type bracket etc. as per RESPO schedule and local approced drawing. |
| 4644 | PAINTING OF FOUR POLE (SP-55) |
| 4645 | Excavation of earth for stay pit of size 0.6x0.6x1.2 mtr in all types of soil including proper dressing of sides and ramming of bott om including getting out the excavated soil and disposal of surplus excavated soil as directed complete work |
| 4646 | Grouting of Stay in size 0.6x0.6x0.3 in CC ratio 1:4:8 (1 cement : 4 graded stone 20mm nominal size : 8 coarse sand ) block includ ing cost of Cement,sand and stone ballast back filling of soil and boulders in pit and ramming and proper alignment, lev |
| 4647 | Fabrication of MS Channel angle iron etc in required sizes with drilling of holes upto good finish for top channel,bracing and spec ial type bracket etc. as per RESPO schedule and local approced drawing. |
| 4648 | PAINTING OF SINGLE POLE (SP-55) |
| 4649 | Excavation of earth for pole pit of size 0.9x0.6x1/6 of full length of pole for erection of pole in all types of soil including prop er dressing of sides and ramming of bottom including etting out the excavated soil and disposal of surplus excavated soil |
| 4650 | Excavation of earth for pole pit of size 0.9x0.6x1/6 of full length of pole for erection of pole in all types of soil including prop er dressing of sides and ramming of bottom including etting out the excavated soil and disposal of surplus excavated soil |
| 4651 | Excavation of earth for pole pit of size 0.9x0.6x1/6 of full length of pole for erection of pole in all types of soil including prop er dressing of sides and ramming of bottom including etting out the excavated soil and disposal of surplus excavated soil |
| 4652 | Erection of SP-55 single support pole in proper level and alignment along with fixing of all accessories like top channel,& clamps a s per RESPO manual |
| 4653 | Grouting of pole in size 0.45x4.45x1/9 of the support in CC ration 1:4:8(1 cement:4 graded stone20 mm niminal size: 8 coarse sand) b lock including cost of cement, sand and stone ballast back filling of soil and boulders in pit and ramming and proper ali |
| 4654 | Muffing of poles size 0.45x0.60 cm radius with 1:3:6(1 cement:3 coarse sand :graded stone 10 mm nominal size) block size 45 cm heigh t from ground level including cost of cement,stone and sand etc |
| 4655 | Laying, Spreading, Stringing and sagging of 11 KV / 33 KV line in 3 phase (3 Phase 3 wire) of ACSR Dog as phase wire with G.I. earth wire complete including fixing of all accessories in 3 Nos. conductor in parallel with binding and jumpering as per prof |
| 4656 | Fixing,tightening and nozzling of stay with pole and stay rod on required tension as per drawing/manual in 33 KV line |
| 4657 | Guarding of 33 KV Line over (Telephone / Road / L.T. line crossing as per drawing with 6/8 SWG G.I. wire including fixing of guardin g channel/ angle as per RESSPO manual. |
| 4658 | Fabrication of MS Channel angle iron etc in required sizes with drilling of holes upto good finish for top channel,bracing and spec ial type bracket etc. as per RESPO schedule and local approced drawing. |
| 4659 | Earthing of support with M.S. Earth rod of 2.5 meter long by hammaring of M.S. Rod to proper depth and connecting the earth electrod e with the help of G.I. wire as per construction manual. |
| 4660 | H.P stone filling in back of walls including cost of all materials, royality,T & P etc. Complete |
| 4661 | Grouting of structure in CC 1:3:6 in size (2x1.1x0.3x0.3) mtr. |
| 4662 | Coursed rubble masonry (first sort) with hard stone in foundation and plinth with : Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 4663 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETEOF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - ALL WORKS UPTO PLINTH LEVEL (I) 1:4:8 (1 - CEMENT; 4 - COARSE SAND; 8 - GRADED STONE AGGREGATE 40MM NOMINAL SIZE).( FOUNDATION |
| 4664 | EXCAVATION IN SOIL IN HILLY AREA/RIVER BED BY MECHANICAL MEANS I.E. BACKHOE LOADER |
| 4665 | SHIFTING REALIGNMENT OF 11 KV SP, DP/LT LINE INCLUDING COMPLETE WORK |
| 4666 | Annual Maintenance Charges (AMC) and O&M of Project for 5 years on per year basis. |
| 4667 | Construction of S.G.R Building , Boundary wall , C.C Aproch Road, Land devlopmentEarth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and for all lift, as directed by Engineer-in-charge.2.6.1 All kinds of soil |
| 4668 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, for all lift, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.Earth work in excavation by mechanical means (Hydraulic excavator )/ manual means in foundation tranches (All kinds of soil). Columns Footing F1 |
| 4669 | Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared. |
| 4670 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 and for all lift. |
| 4671 | Supplying and filling in plinth with Jamuna/local sand under floors including. Watering, ramming |
| 4672 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering -All work up to plinth level:1:4 :8 |
| 4673 | Providing and laying damp-proof course 40 cm thick with cement concrete 1:2:4 |
| 4674 | Extra for providing and mixing water proofing material in cement concrete work @ 1 kg per 50 kg of cement. |
| 4675 | Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centering, shuttering,up to plinth level: 1:1:5:3 |
| 4676 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, posts reinforcement. 1:1:5:3 Columns |
| 4677 | Reinforced cement concrete working beams, suspended floors, roofs having slope up to 1.5 landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases with 1:1.5:3 |
| 4678 | Centering and shuttering including strutting propping etc. and removal of form for: Foundations footings, bases of columns, etc. For mass concrete. |
| 4679 | Centering and shuttering including strutting propping etc. and removal of form for: Suspended floors, roofs, l |
| 4680 | Centering and shuttering including strutting propping etc. and removal of form for: |
| 4681 | Centering and shuttering including strutting propping etc. and removal of form for: Lintels, beams, plinth beams girders, |
| 4682 | Centering and shuttering including strutting propping etc. and removal of form for:. Columns, Pillars, Piers, Abutments, |
| 4683 | Centering and shuttering including strutting propping etc. and removal of form for. Weather shade, Chaffas, corbels etc. including edges. |
| 4684 | Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. (TMT bars ). |
| 4685 | Brick work with F.P.S. bricks of class designation 75 in foundation and plinth in: Cement mortar 1:4 |
| 4686 | Brick work with F.P.S. bricks of class designation 75 in foundation and plinth in: Cement mortar 1:6 |
| 4687 | Brick work with F.P.S. Bricks of class designation 75 in superstructure above plinth level : Cement mortar 1:6 ( 1 cement : 6 coarse sand) |
| 4688 | Half brick masonry with F.P.S. bricks …. in superstructure above plinth level Cement morat 1:4 ( 1 cement : 4 coarse sand) |
| 4689 | Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 4690 | Random rubble masonry with hard stone in superstructure above plinth level and upto floor five level, including leveling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) at window sills, ceiling level and the like. Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 4691 | Providing and fixing aluminium sliding door bolts ISI marked anodised (200x10mm) |
| 4692 | Providing and fixing aluminium sliding door bolts ISI marked anodised….. with nuts and screws etc. complete: (150x10mm) |
| 4693 | Providing and fixing aluminium tower bolts ISI marked anodised (100x10mm) |
| 4694 | Providing and fixing aluminium handles ISI marked anodised. complet: 125mm |
| 4695 | Providing and fixing aluminium handles complet: 100mm |
| 4696 | Providing and fixing aluminium handles floor door stopper ISI marked anodised Twin rubber stopper |
| 4697 | P/F in position collapisble steel shutter |
| 4698 | Fixing standard steel glazed doors, Fixing with 15x3 mm lugs 10 cm. long embedded in cement concrete block 15x10x10 cm of C.C. 1:3:6windows |
| 4699 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applyinga priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. |
| 4700 | P/F circular/ Hexagonal cast iron or M.S. each sheet box for ceiling fan |
| 4701 | steel work welded in built up sections/ framed work including cutting, hoisting fixing in position |
| 4702 | Providing & fixing fly proff wire gauze to windows,clerestory windows & doors with M.S. Flat 15x3 m and nuts |
| 4703 | Cement concrete pavement with 1:2:4 (1 cement: 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including finishing complete. |
| 4704 | Extra for making chequers of approved pattern on cement concrete floors, steps, landings, pavements etc. |
| 4705 | Cement concrete flooring 1:2:4 finished with a floating coat of neat cement |
| 4706 | Providing and fixing glass strips in goints of terrazo/cement concrete floors. |
| 4707 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to |.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joint with white cement & matching pigments etc Size of Tile 600x600 mm |
| 4708 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approvedmake, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.Providing and fixing Ist quality ceramic glazed wall tiles |
| 4709 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), Jointing with grey cement slurry @ 3.3 kg/sqm including pointing the joints with white cement and matching pigment etc., complete.Providing and laying Ceramic glazed floor tiles 300x300 mm |
| 4710 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i)Single socketed pipes. 12.41.1 75 mm diameterProviding and fixing on wall face unplasticised Rigid PVC rain water pipes (75mm diameter) |
| 4711 | Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion.P/F on wall face unplasticised Rigid PVC rain water pipes(110mm diameter) |
| 4712 | 12mm cement plaster of mix: 1:4 (1cement : 4coarse sand) |
| 4713 | 12mm cement plaster of mix: 1:6 (1cement :6coarse sand) |
| 4714 | 15mm cement plaster on rough side of single or half brick wall of mix: 1:6 (1cement :6coarse sand) |
| 4715 | Add or deduct for plaster drip course/ groove in plastered surface or moulding to R.C.C.projections. |
| 4716 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surfaceto prepare the surface even and smooth complete |
| 4717 | Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved manufacturer and of requiredshade and colour all complete to achieve even shade and colour :New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC contentDistempering with oil bound washable distemper New work (two or more coats ) |
| 4718 | Finishing walls with textured exterior paint of required shade : 13.45.1 New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/10 sqmFinishing wall with textured exterior paint of required shade: New work (two or moar coats |
| 4719 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade : Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacturePainting with synthetic enamel paint of ..Two or more coats on new work over an under coat |
| 4720 | Providing and fixing water closet squatting pan (Indian type W.C. pan) White Vitreous china Orissa patern W.C. pan of size 580x440mm with integral type foot rests. |
| 4721 | Providing and fixing wash basin White Vitreous china Flat back wash basin size 550x400mm with a pair of 15mm C.P. brass pillar tap. In Toilet |
| 4722 | Providing and fixing P.V.C. low level flushing cistern with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete. 10 litre capacity - WhiteProviding and fixing P.V.C. low level flushing cistern 10 litre capacity-White |
| 4723 | P/F P.V.C. waste pipe for sink or wash basin including P.V.C.Flexible pipe 32mmdia |
| 4724 | Providing and fixing 600x450mm beveled edge mirror of superior glass In Toilet |
| 4725 | Providing and fixing PTMT soap Dish Holder having length of 138mm, |
| 4726 | Providing anf fixing soil, waste and vent pipes: 100mm dia( Sand cast iron S&S pipe |
| 4727 | Providing and filling the joints with spun yarn cement 100mm dia pipe |
| 4728 | Providing and fixing plain bend of required degree. 100mm ( Sand cast iron S&S as per IS-1729) |
| 4729 | Providing and fixing terminal guard: :75mm (Sand cast iron S&S as per IS- 1729) |
| 4730 | Providing lead caulked joints to sand cast 100mm |
| 4731 | Providing and fixing trap of self cleansing100 mm inlet and 100mm outlet (Sand cast iron S&S ) |
| 4732 | Concealed pipe including painting with anti corrosive bitumasiic paint cutting chases15mm dia nominal bore |
| 4733 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. External work 15mm dia nominal bore |
| 4734 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. External work 20mm dia nominal bore |
| 4735 | P/f ball valve (brass)High or low pressure with plastic floats 15 mm nominal bore |
| 4736 | Constructing masonry Chamber 30x30x50 cm inside with 75 class designation brick work in cement mortar 1:4 (1cement : 4coarse sand) |
| 4737 | Providing and placing on terrace (at all floor levels) polyethylene water stonrage tank |
| 4738 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS: 8931 (15mm nominal bore). |
| 4739 | Providing and fixing C.P. brass angle valve (15mm nominal bore) |
| 4740 | Providing and fixing aluminium work for doors, windows ventilators and partitions... including necessary filling up of gapu at junctions at top bottom and sides with required PVC/ neoperene felt etc. For fixed portion. Window W |
| 4741 | Providing and fixing aluminium work for doors, windows ventilators and partitions |
| 4742 | Providing and fixing 12mm thick prelaminated particle board flat pressed three layer or graded wood particle borad |
| 4743 | Providing and fixing glazing in aluminium door, window ventilator shutters and partitons etc. |
| 4744 | Providing and fixing double action hydraulic floor spring of approved brand and manufacture |
| 4745 | Wiring for light point/fan point/exhaust fan point/call bell point with 1.5 sqmm FR PVC insulated copper GROUP B |
| 4746 | Wiring for circuit/ submain wiring alongwith earth wire in surface/ sub main wiring in PVC codute 2*2.5 Sq.M*1*2.5Sq.M |
| 4747 | S/F stepped type electronic fan regulator on the existing moduler plate switch box including connection.. |
| 4748 | Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface ..and fixing 6 pin 5/6 & 15/16 amps socket outlet and 15/16 amps piano type switch, |
| 4749 | Supplying and flxing brass batten/angle holder including connection etc. as required |
| 4750 | S/F 8ways double door singke pole and netural,sheet steel,MCB D.B 240 volts on |
| 4751 | S/F 5amp to 32amp rating 240 volts,B series,MCB suitable for lighting and other loads of single pole |
| 4752 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB comp. 40AMP rating double pole 240 V isolater |
| 4753 | Earthing with GI earth plate 600x600x6mm thick including accessories and providing masonary enclosure with cover plate having locking arrengment and watering pipe OF 2.7 Mt. long etc. with charcoal or coke and salt as required. |
| 4754 | Supply of 20 watt LED Tubelight Philips or eqvivalent make as approved by E.I. |
| 4755 | Spreading of 20mm size gravel in switch yard in depth of 50mm thickness |
| 4756 | Engaging Suitable beldar in petty works |
| 4757 | Supply for 33/11kV SubstationEARTHING ROD MS 20X2500MM |
| 4758 | 33 KV LIGHTNING ARRESTER |
| 4759 | 8 M. LONG STP 410 SP-10 (BPHD GAL.) |
| 4760 | LT PVC CABLE 4X10 SQ.MM |
| 4761 | 33 KV POLYMER DISC INSULATOR (B&S) TYPE |
| 4762 | 33 KV FUSE SET |
| 4763 | ACSR DOG |
| 4764 | CONTROL CABLE 10X2.5 SQ. MM. |
| 4765 | CABLE AL 3X240 SQ. MM XLPE 11 KV |
| 4766 | CONTROL CABLE 4X2.5 SQ. MM. |
| 4767 | J/KIT FOR 3X240MM² 11KV XLPE CABLE (O/D) |
| 4768 | CONTROL CABLE 6X2.5 SQ. MM. |
| 4769 | 9 KV 10KA LIGHTNING ARRESTER |
| 4770 | 9 KV 5KA LIGHTNING ARRESTER (POLYMER) |
| 4771 | GI WIRE 5MM/6 SWG |
| 4772 | STAY WIRE GI 7/3.15MM 7/10SWG |
| 4773 | STAY SET GI 16X1800MM |
| 4774 | DISC FIT. B&S TYPE WEASEL/RABBIT 45 KN |
| 4775 | 11 KV POLYMER DISC INSULATOR (B&S) TYPE |
| 4776 | 11 MTR. LONG STP 410 SP-55 (BPHD GAL.) |
| 4777 | LT XLPE CABLE 3.5.X 70 SQ. MM. |
| 4778 | PANTHER TO PANTHER CTYPE WEDGE CONNECTOR |
| 4779 | CABLE AL 3X70 SQ. MM XLPE 33KV |
| 4780 | DISC FIT. B&S TYPE FOR PANTHER 90 KN |
| 4781 | JUNCTION BOX FOR 33KV PT |
| 4782 | MS ROUND 32 mm Dia |
| 4783 | 33 KV H.S. CABLE J/K 3X70 SQ. MM (O/D) |
| 4784 | LT PVC CABLE 2X6 SQ.MM (ARMORED) |
| 4785 | J/KIT FOR 3X400mm² 11kV XLPE CABLE (O/D) |
| 4786 | CABLE AL 1X630 SQ. mm XLPE 11kV |
| 4787 | 33kV PT of RATIO 33 kV/110V OUTDOOR |
| 4788 | CABLE AL 3X400 SQ. mm XLPE 11kV |
| 4789 | CONTROL CABLE 2X2.5 SQ. mm. |
| 4790 | ACSR PANTHER |
| 4791 | DUSTBIN PLASTIC SIZE (SMALL) |
| 4792 | SHOCK TREATMENT CHART |
| 4793 | DANGER BOARD WITH CLAMP |
| 4794 | SHUT DOWN/ BREAK DOWN BOARD |
| 4795 | 33 KV HAND GLOVES |
| 4796 | WALL CLOCK |
| 4797 | HIGH INSULATED PLIER |
| 4798 | 12KV 1250A GANG OPE PMA VCB (CAPACITOR) |
| 4799 | D-SPANNER SET |
| 4800 | TORCH 3 CELL |
| 4801 | 12KV 1250A GANG Operated PMA VCB (I/C) |
| 4802 | 33KV C&R PANEL For O/G |
| 4803 | 33KV C&R PANEL For I/C |
| 4804 | 36KV 1250A Gang Operated PMA VCB(O/G) |
| 4805 | 36KV 1250A GANG Operated PMA VCB(I/C) |
| 4806 | STAY CLAMP FOR SP-55 WITH NUT & BOLT |
| 4807 | RUBBER MAT (12MM) 2M X1M X12MM |
| 4808 | Steel Almirah |
| 4809 | OFFICE TABLE SIZE (4X2.5) |
| 4810 | GI BOLTS & NUT WITH WASHERS. |
| 4811 | HT WARNING TAPE |
| 4812 | G.I. PIPE 6'' DIA 3 MTR LONG |
| 4813 | GI Pipe 4'\\" Dia |
| 4814 | Fire Bucket with Sand |
| 4815 | Fire Bucket stand of MS angle |
| 4816 | ST. LIGHT MANAG. TIMER SWITCH |
| 4817 | IRON CLAD 30 AMP SWITCH |
| 4818 | G.I STRIP 65X6MM |
| 4819 | 11 KV FUSE SET |
| 4820 | 33/0.433 KV, 63 KVA Station Transformer |
| 4821 | PP CLAMP WITH N&B (GI) |
| 4822 | Connector Suit for CT/PT for Panther/Dog |
| 4823 | 12.65kV, 3600kVAr, Capacitor bank |
| 4824 | Indoor type auto power factor controller |
| 4825 | Thimble junction box for cable support |
| 4826 | CONNE.SUITABLE FOR PANTHER FOR LA |
| 4827 | 2.5 KV MEGGAR DIGITAL |
| 4828 | 33KV C&R PANEL BUS COUPLER |
| 4829 | 36KV 1250A GANG OPE PMA VCB(B/C) |
| 4830 | MEGGAR 5 KV DIGITAL |
| 4831 | EARTH CHAIN |
| 4832 | JOINTING KIT 3X240 SQ.mm 33kV XLPE (I/D) |
| 4833 | MS STRUCTURE (ANGLE ,CHANNEL ETC.) |
| 4834 | GI ITEM (RAIL,JOIST,CHANNEL,ANGLE ETC.) |
| 4835 | DOOR MAT |
| 4836 | Connector of Power T/F LV Side |
| 4837 | 33KV ISOLATOR CONN.CLAMP FOR PANTHER |
| 4838 | Connector of Power T/F HV Side |
| 4839 | FLEXIBLE COPPER CONNECTOR 50X50MM |
| 4840 | 12KV 1250A GANG OPERATED PMA VCB(O/G) |
| 4841 | EARTH MEGGAR DIGITAL |
| 4842 | Connector Suitable. Panther for VCB |
| 4843 | 250W LED LAMP WITH CONTRL GEAR |
| 4844 | DCDB 24V |
| 4845 | 24 V BATTERY SET |
| 4846 | INVERTOR CUM BATTERY CHARGER |
| 4847 | Instruction Board |
| 4848 | Single Line Diagram Board |
| 4849 | MAXIMUM & MINIMUM DISPLAY BOARD |
| 4850 | SUB STATION NAMED BOARD |
| 4851 | NAME PLATE OF EQUIP. TG,LI,BI,CT,CB ETC. |
| 4852 | SUNDRISE ITEM LUG GLAND ETC |
| 4853 | Steel Cabinet |
| 4854 | 11KV C&R PANEL BUS COUPLER |
| 4855 | 33 KV ISOLATOR VERTICAL TYPE |
| 4856 | FIRST AID BOX |
| 4857 | 11KV ISOLATOR MANUAL & MOTORISED SCADA COMPATIBLE |
| 4858 | Name plate of station T/F |
| 4859 | Cable Holding clamp with N&B |
| 4860 | PG Clamp For Dog Conductor |
| 4861 | PG CLAMP ALU ALLOY PANTHER TO DOG |
| 4862 | ALLUMINIUM LUG |
| 4863 | G.I.STRIP 35X4MM |
| 4864 | PERFORATED TRAY 100MM FOR CABLE TRENCH |
| 4865 | Steel office chair |
| 4866 | 33KV LINE ISOLATOR MANUAL & MOTOR,SCADA CO |
| 4867 | WIRE MESH FENCING |
| 4868 | Portable Foam Type Fire Extinguisher 5 Ltr. |
| 4869 | STEEL OFFICE TABLE |
| 4870 | RAIL 90 LBS |
| 4871 | 11KV DANGER BOARD WITH CLAMP |
| 4872 | NAME PLATE OF FEEDER |
| 4873 | CABLE HOLDING CLAMP WITH N&B |
| 4874 | 11KV 3P(400A)3PIN VERT. MOUNT GO AB TPMO |
| 4875 | 11 KV HS CABLE END T/K 1X630 SQ MM I/D |
| 4876 | PP CLAMP WITH N&B (GI) |
| 4877 | 12KV C&R Panel with SCADA (Capacitor) |
| 4878 | 11KV C&R PANEL O/G |
| 4879 | 11KV C&R PANEL I/C |
| 4880 | 12KV 1250A Gang ope PMA VCB (B/C) |
| 4881 | PERFORATED TRAY 400MM FOR CABLE TRENCH |
| 4882 | PIPE WRENCH 12'' |
| 4883 | Holding Clamp for GI Pipe 8/10''& MS Ch. |
| 4884 | Connector Suitable for Panther for LA |
| 4885 | PERFORATED TRAY 200MM FOR CABLE TRENCH |
| 4886 | FIRE EXTINGUSHIER |
| 4887 | G.I. Plate 300x300x8 mm. |
| 4888 | Stone Pad 300x300x75mm |
| 4889 | GI STRIP 50X6 MM |
| 4890 | 11 KV HS cable END T/K 1x630 mm² O/D |
| 4891 | Cable Jointing Kit 1x630 Outdoor |
| 4892 | Cable Jointing Kit 1x630 Indoor |
| 4893 | PG CLAMP ACSR PANTHER TO ACSR DOG |
| 4894 | PG CLAMP ALU ALLOY PANTHER TO PANTHER |
| 4895 | 33 KV XLPE Cable AL 1x630 sq. mm |
| 4896 | Supply for 33kV LineMS ANGLE 65X65X6 MM |
| 4897 | 33KV 10KN POLYMER PIN INSULATOR WITH PIN |
| 4898 | MS CHANNEL 125X65 mm |
| 4899 | X ARM CHANNEL 100X50 mm V TYPE 33 kV |
| 4900 | 11 MTR. LONGSTP 410 SP-55 (BPHD GAL.) |
| 4901 | 33 KV POLYMER DISC INSULATOR (B&S) TYPE |
| 4902 | STAY SET GI 20X1800MM |
| 4903 | STAY WIRE GI 7/3.15MM 7/10SWG |
| 4904 | EARTHING ROD MS 20X2500MM |
| 4905 | MS ANGLE 75X75X8 MM |
| 4906 | GI WIRE 5MM/6 SWG |
| 4907 | GI WIRE 4MM/8MM SWG |
| 4908 | CABLE AL 3X400 SQ. MM XLPE 33 KV |
| 4909 | J/KIT FOR 3X400MM²33KV XLPE CABLE (O/D) |
| 4910 | MS CHANNEL 100X50 MM |
| 4911 | DISC FIT. B&S TYPE DOG/RACOON 70 KN |
| 4912 | ACSR RABBIT |
| 4913 | 11 KV POLYMER DISC INSULATOR (B&S) TYPE |
| 4914 | 11 KV POLYMER PIN INSULATOR WITH PIN |
| 4915 | ACSR WEASEL |
| 4916 | 11KV DISC FITTING T&C RABBIT/WEASEL 45KN |
| 4917 | MS ANGLE 50X50X6 MM |
| 4918 | EARTH WIRE GI 7/1.6MM 16 SWG |
| 4919 | ACSR DOG |
| 4920 | HOLDING CLAMP FOR ST POLE SP-55 WITH N&B |
| 4921 | TOP CHANNEL CLAMP WITH N&B |
| 4922 | E- CLAMP |
| 4923 | BOLT & NUTS OFF SIZE |
| 4924 | PG CLAMP FOR DOG CONDUCTOR |
| 4925 | STAY CLAMP FOR SP-55 WITH NUT & BOLT |
| 4926 | PG CLAMP FOR DOG CONDUCTOR |
| 4927 | GI STRIP 50X6 MM |
| 4928 | 33KV XLPE HS J/K 3X400MM² STRAIGHT |
| 4929 | EARTH WIRE CLAMP 33 KV FOR SP-72-N&B |
| 4930 | BOLT & NUTS 50X16 MM |
| 4931 | STONE PAD 300X300X75MM |
| 4932 | G.I. PIPE 6 INCH |
| 4933 | BRACING CLAMP BOTTOM WITH N&B SP-55 |
| 4934 | EARTH WIRE CLAMP FOR SP-55 WITH N/B |
| 4935 | STONE PAD 300X300X75MM |
| 4936 | PP & CLAMP WITH N&B ST POLE SP-72 |
| 4937 | BOLT & NUT 150X12 MM |
| 4938 | HT STAY INSULATOR |
| 4939 | CABLE HOLDING CLAMP WITH N&B |
| 4940 | BRACING CLAMP BOTTOM WITH N&B SP-55 |
| 4941 | NUMBER PLATE WITH CLAMP |
| 4942 | BARBED WIRE |
| 4943 | BRACING CLAMP TOP WITH N&B SP-55 |
| 4944 | HOLDING CLAMP FOR SP-55 WITH N/B |
| 4945 | EYE BOLT SIZE 100X16 |
| 4946 | 33 KV DANGER BOARD WITH CLAMP |
| 4947 | Erection Work for Substation:ERECTION & LAYING OF 11KV CABLE 3X240 SQ MM |
| 4948 | ERECTION OF 33/0.433KV S/S TRANSFORMER |
| 4949 | PAINTING OF DOUBLE POLE (SP-55) |
| 4950 | PROVIDING & LAYING OF GRAVELLING IN SWITCHYARD. |
| 4951 | EXCAVATION IN SOIL BY MAUNAL/ MECHANICAL MEANS I.E. BACKHOE LOADER. |
| 4952 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETE OF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - ALL WORKS UPTO PLINTH LEVEL (I) 1:4:8 (1 - CEMENT; 4 - COARSE SAND; 8 - GRADED STONE AGGREGATE 40MM NOMINAL SIZE. |
| 4953 | RANDOM RUBBLE MASSONARY WITH HAND STONE IN SUPERSTRUCTURE ABOVE PLINTH LEVEL AND UPTO FLOOR FIVE LEVEL INCLUDING LEVELLING UP WITH CEMENT CONCRETE 1:6:12 (1 CEMENT: 6 COARSE SAND: 2 GRADED STONE AGGREGATE 20 mm NOMINAL SIZE). |
| 4954 | PROVIDING AND LAYING IN POSITION CEMENT CONCRETE OF SPECIFIED GRADE EXCLUDING THE COST OF CENTERING AND SHUTTERING - (I) 1:2:4 (1- CEMENT; 2 - COARSE SAND; 8 - GRADED STONE AGGREGATE 20MM NOMINAL SIZE).( ROAD REPAIRING /OTHER WORK). |
| 4955 | CEMENT PLASTER WORK IN 1:4 (1- CEMENT,4-COARSE SAND) |
| 4956 | RCC 1:1.5:3 |
| 4957 | BRICK WORK WITH COMMON BURNT CLAP BRICKS WITH CEMNT MORTAR 1:4 |
| 4958 | ERRECTION OF 33KV PT |
| 4959 | Erection of Sp-55 double support pole in proper level and alignment along with fixing of all accessories like top channel,X bracings ,& clamps as per RESPO manual. |
| 4960 | Erection of SP-10 single support pole in proper level and alignment along with fixing of all accessories like top channel,& clamps a s per RESPO manual. |
| 4961 | Laying of Control cable of all sizes through trench, proper connection at both ends outside in switchyard equipments & inside control room in VCB, control & relay Panels with proper marking, lugs , labelling & ferrules etc. |
| 4962 | MAKING CABLE TRENCH |
| 4963 | laying of MS bar 32 mm for making earth mat in switchyard area after fabrication / cutting in required size, laying at 2 mtr apart, also in crossing ( Making Net ), proper welding at each joint, laying at atleast 1 mtr depth in switchyard area for providing earthing. |
| 4964 | FIXING AND ERECTION OF CAPACITOR BANK |
| 4965 | PROVIDING AND LAYING IN POSITION SPECIFIED GRADE OF REINFORCED CEMENT CONCRETE EXCLUDING THE COST OF CENTERING, SHUTTERING, FINISHING AND REINFORCEMENT - ALL WORKS UPTO PLINTH LEVEL (I) 1:1.5:3 (1-CEMENT; 1.5 - COARSE SAND; 3 - GRADED STONE AGGREGATE 20MM. |
| 4966 | BRICK WORK 1:6 SUB STRUCTURE |
| 4967 | CIVIL WORK (INCLUDING FOUNDATION OF CAPACITOR CUBICAL ETC. AS PER REQUIREMENT) EARTH WORK |
| 4968 | INSTALLATION OF FOAM TYPE FIRE EXTINGUSHER |
| 4969 | ERECTION OF T&P ITEMS |
| 4970 | ERECTION OF SUB-STATION NAMED BOARD |
| 4971 | INSTALLATION OF ACDB COMPLETE ON SUFACE OR WALL WITH THE HELP OF WALL ANCHOR BOLT FASTENERS 04NOS. COMPLETE TESTING AND COMMISSIONG OF DCDB AS PER SIDE REQUIREMENT AND NARRATED BY ENGINEER IN CHARGE OF THE WORK. |
| 4972 | INSTALLATION OF DCDB COMPLETE ON SUFACE OR WALL WITH THE HELP OF WALL ANCHOR BOLT FASTENERS 04NOS. COMPLETE TESTING AND COMMISSIONING OF DCDB. |
| 4973 | ERECTION OF 24 VOLT BATTERY CHARGER |
| 4974 | ERECTION OF 24 VOLT BATTERY SET |
| 4975 | LAYING OF 4X10SQ MM LT PVC CABLE |
| 4976 | FIXING OF SODIUM/LED LIGHT AT YARD |
| 4977 | EARTHING OF STRUCTURE USING GI STRIP |
| 4978 | Cartage of the 11 KV VCB(I/C,O/G,Buscoupler) from store center to construction site with loading and unloading at both points.(Dista nce 0-20 Km) |
| 4979 | Earthing with two Nos. G.I earth plates 600mm x 600mm x 6mm thick(1.5 meter minimum in between distance) including accessories and providing double masonry enclosure with cover plate having locking arrangement and watering pipe of 3 meter long etc. |
| 4980 | Digging of trench of size 0.60x0.15 x1.5 mtr. and laying of underground 11 KV XLPE cable with making of brick housing and filling of sand including filling of earth with ramming. & repairing of road including cost of cement sand and stone blast. |
| 4981 | DELTA EARTHING OF T/F NEUTRAL POINT WITH 3 NOS. MS EARTH ROD GI STRIP & EARTH WIRE. |
| 4982 | Laying and erection of L.T. PVC single lead Cable including crimping of lugs of size 1x240, 400, 630 Sq.mm etc. (Including all cost of material). |
| 4983 | Jointing and fixing of cable jointing kit indoor/outdoor 33 KV XLPE heat shrinkable cable boxes. |
| 4984 | FIXING OF 33 KV LINE ISOLATOR VERTICAL TYPE ON ST POLE. |
| 4985 | Earth filling under floor and in sub-station area including cost of earth. Earth to be obtained from outside the corporation area in cluding its cartage and ramming, watering, dressing in 20 cm's thick layers including cost of earth with all lead and lift. |
| 4986 | ERECTION OF STAY POST |
| 4987 | FENCING OF YARD |
| 4988 | EXCAVATION IN SOIL IN HILLY AREA/RIVER BED BY MECHANICAL MEANS I.E. BACKHOE LOADER. |
| 4989 | Erection of Sp-55 double support pole in proper level and alignment along with fixing of all accessories like top channel,X bracings ,& clamps as per RESPO manual. |
| 4990 | Jointing and fixing of cable jointing kit indoor/outdoor 11 KV XLPE heat shrinkable cable boxes. |
| 4991 | ERECTION OF BUS BAR |
| 4992 | ERECTION OF FLEXIBLE CU. CONN. 500X50 MM |
| 4993 | Earthing of distribution transformer including digging of pit of size 2.5 Mtr depth and make hole of size 150 mm. Placing of earthin g electrode (to be supplied by contractor as per drawing No. A) as drawing B, connecting the same with G.I. Strip. |
| 4994 | Jointing and fixing of cable jointing kit indoor/outdoor 11 KV XLPE heat shrinkable cable boxes. |
| 4995 | 11KV, 630 AMP, OFF LOAD ISOLATOR WITH EARTH SWITCH AND MOUNTING STRUCTURE\\" |
| 4996 | Making of Trench cover with 40x40x5 mm angle frame, 10 mm ironbars inside for strengthning at 90 -100 mm apart, also in crossing with cement concrete ratio 1:2:4, providing both side handles for lifting. |
| 4997 | Painting of SP-10 pole with angle and channel and all steel part by one coat of Red Oxide Primer and two coats of aluminium Paint an d two strip of fluorescent altemate Red and White paint 30 Cm wide upto 1.5 Mtrs. From ground level. |
| 4998 | EARTH WORK IN EXCAVATION BY MECHNICAL MEANS / MANUAL MEANS OVER AREAS CC/HARDROCK. |
| 4999 | Shifting of 5 MVA Power Transformer from road site to work site/ store center to loading site place with the manual pulling. |
| 5000 | Erection of 5 MVA T/F at transformer plinth & erection of all accessories i.e. radiators, conservator tank, vent pipee etc. with the help of special type of T&P / crane etc. fitting cable etc. and refilling the fresh oil in radiator and conservator. |
| 5001 | Erection of cable stand neutral stand including fabrication cutting and welding work. |
| 5002 | Grouting of structure in CC 1:3:6 in size (2x1.1x0.3x0.3) mtr. |
| 5003 | Mounting and Fixing of Lightning arrestor set (3 Nos.) on double pole structure including making all connections by G.I. strip size 35x6 mm to earth point complete work (excluding cost of G.I.Strip). |
| 5004 | Fixing of GI pipe. |
| 5005 | Jointing and fixing of cable jointing kit indoor/outdoor 33 KV XLPE heat shrinkable cable boxes. |
| 5006 | Fabrication of MS Channel angle iron etc in required sizes with drilling of holes upto good finish for top channel,bracing and spec ial type bracket etc. as per RESPO schedule and local approced drawing. |
| 5007 | Cartage of the 33 KV VCB,feeder panels(O/D),T/F Control panel from store center to construction site with loading and unloading at both points.(Distance 21-50 Km) |
| 5008 | Mannual shifting /Pulling of Control Relay Panel for Single T/F / Single Feeder from existing site to plinth/ nearby place distanc e upto 200 mtrs. |
| 5009 | COMMISSIONING OF 33/11KV VCB PANEL WITH RESPECT WORK |
| 5010 | ERECTION OF MISC. GI STRUCTURES |
| 5011 | Cartage of other material (other than poles) by vehicle from Store Center to nearest construction site Store including loading and unloading at both ends(distance 21-50 Km) |
| 5012 | Cartage of 5 MVA Power transformer by road(loading/unloading / shifting)(21-50 KM) |
| 5013 | Digging of trench of size 0.60x0.15 x1.5 mtr. and laying of underground 33 KV XLPE cable with making of brick housing and filling of sand including filling of earth with ramming. & repairing of road including cost of cement sand and stone blast. |
| 5014 | Installation / Fixing of 33 KV Isolator on structure at 33 Kv switchyard with proper alignment & Connections with busbar complete. |
| 5015 | Erection Work for 33kV Line:FIXIXNG OF GI PIPE. |
| 5016 | HIPOT CABLE TESTING BEFORE ENERGIZING |
| 5017 | MAKING OF 33KV XLPE CABLE LOOP AFTER DIGGING AND BACK FILLING OF EARTH SOIL AT BOTH END OF DP SECTION. |
| 5018 | EARTH WORK IN EXCAVATION BY MECHNICAL MEANS / MANUAL MEANS OVER AREAS CC/HARDROCK. |
| 5019 | Jointing and fixing of cable jointing kit straight thru 33 KV XLPE heat shrinkable cable boxes |
| 5020 | SUPPLY AND LAYING OF HDPE PIPE 160 MM OUTER DIA 6 MM THICKNESS |
| 5021 | ERECTION OF TRI POLE FOR ST POLE SP-55 |
| 5022 | Fabrication of X-Arm. |
| 5023 | Excavation of earth for pole pit of size 0.9x0.6x1/6 of full length of pole for erection of pole in all types of soil including prop er dressing of sides and ramming of bottom including etting out the excavated soil and disposal of surplus excavated soil. |
| 5024 | Erection of SP-55 single support pole in proper level and alignment along with fixing of all accessories like top channel,& clamps a s per RESPO manual. |
| 5025 | Grouting of pole in size 0.45x4.45x1/9 of the support in CC ration 1:4:8(1 cement:4 graded stone20 mm niminal size: 8 coarse sand) b lock including cost of cement, sand and stone ballast back filling of soil and boulders in pit and ramming and proper. |
| 5026 | Muffing of poles size 0.45x0.60 cm radius with 1:3:6(1 cement:3 coarse sand :graded stone 10 mm nominal size) block size 45 cm heigh t from ground level including cost of cement,stone and sand etc. |
| 5027 | Fabrication of MS Channel angle iron etc in required sizes with drilling of holes upto good finish for top channel,bracing and spec ial type bracket etc. as per RESPO schedule and local approced drawing. |
| 5028 | PAINTING OF SINGLE POLE (SP-55) |
| 5029 | Grouting of structure in CC 1:3:6 in size (2x1.1x0.3x0.3) mtr. |
| 5030 | Erection of cable stand neutral stand including fabrication cutting and welding work. |
| 5031 | Excavation of earth for stay pit of size 0.6x0.6x1.2 mtr in all types of soil including proper dressing of sides and ramming of bott om including getting out the excavated soil and disposal of surplus excavated soil as directed complete work. |
| 5032 | Grouting of Stay in size 0.6x0.6x0.3 in CC ratio 1:4:8 (1 cement : 4 graded stone 20mm nominal size : 8 coarse sand ) block includ ing cost of Cement,sand and stone ballast back filling of soil and boulders in pit and ramming and proper alignment. |
| 5033 | Fixing,tightening and nozzling of stay with pole and stay rod on required tension as per drawing/manual in 33 KV line. |
| 5034 | Earthing of support with M.S. Earth rod of 2.5 meter long by hammaring of M.S. Rod to proper depth and connecting the earth electrod e with the help of G.I. wire as per construction manual. |
| 5035 | Digging of trench of size 0.60x0.15 x1.5 mtr. and laying of underground 33 KV XLPE cable with making of brick housing and filling of sand including filling of earth with ramming. & repairing of road including cost of cement sand and stone blast. |
| 5036 | ERECTION AND LAYING OF HT 33 KV XLPE ALU. ARMOURED CABLE 3 X 400 SQ. MM. IN HDPE PIPE MIXED SOIL INCLUDING BACK FILLING OF EARTH & ERECTION ON POLE USING MS CHANNEL, ANGLE & CLAMPS ETC. |
| 5037 | LAYING OF 33 KV CABLE FOR POLE RISING / OVER HEAD ETC. |
| 5038 | Supply & Fixing of G.I. Pipe Pole dia 4 Inch, Length (28 Feet) on Rental basis including Carriage, Loading, Unloading & Erection of 1 Phase Two Wire Line by PVC Cable of Size 1x10 Sqmm or as required including Fixing of Insulators & Nut. |
| 5039 | Jointing and fixing of cable jointing kit indoor/outdoor 33 KV XLPE heat shrinkable cable boxes. |
| 5040 | ERECTION OF MISC. ITEMS |
| 5041 | MAKING PIT OF SIZE 5X2X1.2 MTR FOR FILLING AND FIXING OF STRAIGHT THROUGH JOINT KIT WITH BAG FILLING RAMMING AND COMPACTION UPTO COMPLETE RESTORATION. |
| 5042 | PAINTING OF DOUBLE POLE (SP-72) |
| 5043 | Erection of Sp-55 double support pole in proper level and alignment along with fixing of all accessories like top channel,X bracings ,& clamps as per RESPO manual. |
| 5044 | PAINTING OF TRI POLE (SP-55) |
| 5045 | PAINTING OF FOUR POLE (SP-55) |
| 5046 | Erection of SP-55 four pole support pole in proper level and alignment along with fixing of all accessories like top chan nel,X bracings,& clamps as per RESPO manual. |
| 5047 | SHIFTING REALIGNMENT OF 11 KV SP, DP/LT LINE INCLUDING COMPLETE WORK. |
| 5048 | Cartage of other material (other than poles) by vehicle from Store Center to nearest construction site Store including loading and u nloading at both ends(distance 51-70 Km) |
| 5049 | EARTH WORK IN EXCAVATION BY MECHNICAL MEANS / MANUAL MEANS OVER AREAS CC/HARDROCK. |
| 5050 | Laying, Spreading, Stringing and sagging of 33 KV line in 3 phase (3 Phase 3 wire) of ACSR Dog as phase wire with G.I. earth wire complete including fixing of all accessories in 3 Nos. conductor in parallel with binding and jumpering. |
| 5051 | Guarding of 33 KV Line over (Telephone / Road / L.T. line crossing as per drawing with 6/8 SWG G.I. wire including fixing of guardin g channel/ angle as per RESSPO manual. |
| 5052 | ERECTION OF CONCRETE ROUTE MARKER FOR HT CABLE. |
| 5053 | Painting of MS Frame / Ladder/Stair/ Railing of Existing CSS and RMU Structure. |
| 5054 | Annual Maintenance Charges (AMC) and O&M of Project for 5 years on per year basis. |
| 5055 | Construction of SGR Building:Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50m. All kinds of soil. |
| 5056 | Supplying and filling in plinth with Jamuna sand under floors, including watering, ramming, consolidating and dressing complete. |
| 5057 | Supplying and stacking at site.Good earth |
| 5058 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. |
| 5059 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) |
| 5060 | Extra for providing and mixing water proofing material in cement concrete work in doses by weight of cement as per manufacturer’s specification. |
| 5061 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :sand: 3 graded stone aggregate 20 cm nominal size).1:1.5:3 (1 cement : 1.5coarse sand : 3 graded stone aggregate 20 mm nominal size) |
| 5062 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size)C1 |
| 5063 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement, with 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size). |
| 5064 | Centering and shuttering including strutting propping etc. and removal of form for: Foundations footings, bases of columns, etc. For mass concrete. |
| 5065 | Centering and shuttering including strutting propping etc. and removal of form for: Suspended floors, roofs, landings, balconies and access platform. |
| 5066 | Centering and shuttering including strutting propping etc. and removal of form for: Shelves (Cast in situ) |
| 5067 | Centering and shuttering including strutting propping etc. and removal of form for: Lintels, beams, plinth beams girders, bressumers and cantilevers, |
| 5068 | Centering and shuttering including strutting propping etc. and removal of form for:. Columns, Pillars, Piers, Abutments, Posts and Struts. |
| 5069 | Centering and shuttering including strutting propping etc. and removal of form for. Weather shade, Chaffas, corbels etc. including edges. |
| 5070 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars |
| 5071 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 5072 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 5073 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 5074 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level.Cement mortar 1:4 (1 cement :4 coarse sand) |
| 5075 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size,approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Granite of any colour and shade Area of slab upto 0.50 sqm |
| 5076 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Granite of any colour and shade Area of slab over 0.50 sqm |
| 5077 | Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge Granite work |
| 5078 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters.35 mm thick including ISI marked Stainless Steel butt hinges with necessary screwsmatched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. 35 mm thick including ISI marked Stainless Steel butt hingeswith necessary screws |
| 5079 | Providing and fixing ISI marked oxidised M.S. sliding door bolts with nuts and screws etc. complete :250x16 mm |
| 5080 | Providing and fixing ISI marked oxidised M.S. tower bolt black finish (Barrel type) with necessary screws etc. complete : 200x10 mm |
| 5081 | Providing and fixing ISI marked oxidised M.S. tower bolt black finish (Barrel type) with necessary screws etc. complete : 150x10 mm |
| 5082 | Providing and fixing ISI marked oxidised M.S. tower bolt black finish (Barrel type) with necessary screws etc. complete : 100x10 mm |
| 5083 | Providing and fixing ISI marked oxidised M.S. handles conforming to IS:4992 with necessary screws etc. complete :125 mm |
| 5084 | Providing and fixing aluminium sliding door bolts, ISI marked anodised anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete : 250x16 mm |
| 5085 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete :(200x10mm) |
| 5086 | Providing and fixing aluminium tower door bolts ISI marked anodised (Anodic coating not less than grade AC 10 as per IS:1868)transparent or dyed to required colour or shade with nuts and screws etc. complete: (150x10mm) |
| 5087 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete :100x10 mm |
| 5088 | Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete :125mm |
| 5089 | Providing and fixing aluminium handles floor door stopper ISI marked anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour or shade with necessary scerews etc. complet: Single rubber stopper |
| 5090 | Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete. Twin rubber stopper |
| 5091 | Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge.With stainless steel cover plate minimum 1.25 mm thickness |
| 5092 | Providing and fixing wire gauge shutters using stainless steel grade 304 wire gauge with wire of dia 0.5 mm and average width of aperture 1.4 mm in both directions for doors, windows and clerestory windows with necessary screws : 35 mm thick shutters with ISI marked M.S. pressed butt hinges bright finished of required size Second class teak wood |
| 5093 | Providing and fixing in position collapsible steel shutters with vertical channels 20x10x2 mm and braced with flat iron diagonals 20x5 mm size, with top and bottom rail of T-iron 40x40x6 mm, with 40 mm dia steel pulleys, complete with bolts, nuts, locking arrangement, stoppers, handles, including applying a priming coat of approved steel primer. |
| 5094 | Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strikeplate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineerin-charge:Profile B Fixing with adjustable lugs with split end tail to each jamb |
| 5095 | Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strikeplate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineerin-charge:Profile C Fixing with adjustable lugs with split end tail to each jamb |
| 5096 | Steel work in built up tubular ( round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished welded type tubes |
| 5097 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard rawing.surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing. |
| 5098 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 5099 | Providing & fixing fly proof wire gauze to windows, clerestory windows & doors with M.S. Flat 15x3 mm and nuts & bolts complete. Galvanised M.S. Wire gauze with 0.63 mm dia wire and 1.4 mm aperture on both sides |
| 5100 | Providing & fixing glass panes with putty and glazing clips in steel doors, windows, clerestory windows, all complete with :5.5 mm thick glass panes |
| 5101 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. 40 mm thick with 20 mm nominal size stone aggregate20mm nomnal sxe stone aggregate). |
| 5102 | Providing and fixing glass strips in joints of terrazo/ cement concrete floors. 40 mm wide and 4 mm thick |
| 5103 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados,over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 oarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. |
| 5104 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in all colours, shades, except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick bed of cement mortar 1:4 (1 Cement : 4 Coarse sand), including pointing the joints with white cement and matching pigments etc., complet |
| 5105 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete.Size of Tile 600x600 mm |
| 5106 | Providing and laying full body vitrified tile in floor of minimum thickness 15mm with water absorption less than 0.06% and conforming to 1S:15622,of approved make, brand and manufacturer, laid on 20 mm thick basecement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cementslurry @3.30 kg / sqm including grouting the joints with white cementand matching pigments etc. The slab must be cut with the zero chippingdiamond cutter only. Laying of slab will be done with the help of notchtrowel, wedge, clips of required thickness, vacuum cups for lifting,leveling system and rubber mallet for placing the slab gently and easily.Size of tile 800x2400 mm of all colours and shades.. |
| 5107 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. (75mm diameter) |
| 5108 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes.( 110mm diameter) |
| 5109 | 12mm cement plaster of mix: 1:4 (1cement : 4coarse sand) |
| 5110 | 12mm cement plaster of mix: 1:6 (1cement :6coarse sand) |
| 5111 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 5112 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 5113 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade : New work (two or more coats) over and including water tinnable priming coat with cement primer. |
| 5114 | Finishing walls with textured exterior paint of required shade : New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/ 10 sqm |
| 5115 | Finishing walls with Acrylic Smooth exterior paint of required shade :New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) |
| 5116 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture |
| 5117 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:1½:3 (1 Cement: 1½ coarse sand: 3 graded stone aggregate 20 mm nominal size) |
| 5118 | Providing and laying 60mm thick factory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge. |
| 5119 | Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests |
| 5120 | Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I.brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required : W.C. pan with ISI marked white solid plastic seat and lid |
| 5121 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: White Vitreous China Flat back wash basin size 550x 400 mm with single 15 mm C.P. brass pillar tap |
| 5122 | Providing and fixing white vitreous china pedestal for wash basin completely recessed at the back for the reception of pipes and fittings. |
| 5123 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 5124 | Providing and fixing terminal guard : 75 mm Sand cast iron S&S as per IS - 1729 |
| 5125 | Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : 100 mm inlet and 100 mm outlet Sand cast iron S&S as per IS: 3989 |
| 5126 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. 450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm, weighing not less than 170 gms |
| 5127 | Providing and fixing G.I. Pipes complete with G.I. fittings and clamps, i/c making good the walls etc. concealed pipe, including painting with anti corrosive bitumastic paint, cutting chases and making good the wall : 15 mm dia nominal bore |
| 5128 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. External work 15 mm dia nominal bore |
| 5129 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. External work 20mm dia nominal bore |
| 5130 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. External work 25 mm dia nominal bore |
| 5131 | Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. External work 40 mm dia nominal bore |
| 5132 | Constructing masonry Chamber 30x30x50 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design : With common burnt clay F.P.S.(non modular) bricks of classdesignation 7.5 |
| 5133 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, ISI : 12701 marked, with cover and suitable locking arrangement and making ecessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 5134 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 : 15 mm nominal bore |
| 5135 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.(15 mm nominal bore) |
| 5136 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931. 15 mm nominal bore |
| 5137 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 a) 15 mm nominal bore 15mm nominal bore |
| 5138 | Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighing not less than 106 gms. |
| 5139 | P/Fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron) |
| 5140 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15) Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 5141 | Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge. Pre-laminated particle board with decorative lamination on one side and balancing lamination on other side |
| 5142 | Engazing suitable beldar for petty works ( basic rates labour ) |
| 5143 | Engazing suitable fitter for electrical works ( basic rates labour ) |
| 5144 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. GROUP C |
| 5145 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 5146 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required2*2.5 Sq.M*1*2.5Sq.M |
| 5147 | Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including nnections but excluding modular plate etc. as required. |
| 5148 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted ncluding earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way , Double door |
| 5149 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 5150 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps |
| 5151 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 5152 | Supply and Installation 1.00HP water pump Havells and equivalent make all compl.as per direction of E.I. |
| 5153 | Supply of 20 watt LED Tubelight Philips or equivalent make approved by E.I. |
| 5154 | Supplying of Exaust Fan 450 mm sweep of orient or equivalent make as apporoved by E.I |
| 5155 | (1.41) Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 5156 | (1.50.1)Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required Upto 450 mm sweep |
| 5157 | Supply ,Installation,Testing and Commissioning 1200 mm sweep, BEE 5 star rated,ceiling fan with brush less direct current (BLDC)Motor,class of insulation:B, 3 no. blades, 30 cm long down rod ,2 nos canopies,shakle kit,safety rope,copper winding ,power factor not less then 0.9,service value(cmm/w)minimum 6.85,aire delivery minnimum 215 cmm, 350 rpm(tollerance as per IS : 374/219),THD less then 10%,remote of electronic regulator unit 4 speed controll and all remaining accesories including safety pin ,nut bolts,washers,temperature rise equal to75 degree c (max), insulation resistance more then 2 mega ohm ,suitable for 230 v ,50 Hz ,single phase AC supply , earthing etc complete as required. |
| 5158 | Construction of Store:Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50m. All kinds of soil. |
| 5159 | Supplying and filling in plinth with Jamuna sand under floors, including watering, ramming, consolidating and dressing complete. |
| 5160 | Supplying and stacking at site.Good earth |
| 5161 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. |
| 5162 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) |
| 5163 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :sand: 3 graded stone aggregate 20 cm nominal size).1:1.5:3 (1 cement : 1.5coarse sand : 3 graded stone aggregate 20 mm nominal size) |
| 5164 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) |
| 5165 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement, with 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size). |
| 5166 | Centering and shuttering including strutting propping etc. and removal of form for: Foundations footings, bases of columns, etc. For mass concrete. |
| 5167 | Centering and shuttering including strutting propping etc. and removal of form for: Suspended floors, roofs, landings, balconies and access platform. |
| 5168 | Centering and shuttering including strutting propping etc. and removal of form for: Shelves (Cast in situ) |
| 5169 | Centering and shuttering including strutting propping etc. and removal of form for: Lintels, beams, plinth beams girders, bressumers and cantilevers, |
| 5170 | Centering and shuttering including strutting propping etc. and removal of form for:. Columns, Pillars, Piers, Abutments, Posts and Struts. |
| 5171 | Centering and shuttering including strutting propping etc. and removal of form for. Weather shade, Chaffas, corbels etc. including edges. |
| 5172 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars |
| 5173 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 5174 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 5175 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level.Cement mortar 1:4 (1 cement :4 coarse sand) |
| 5176 | P/ fixing M.S. grills of required pattem in frames of windows etc. with M.S. flats square or round bars etc. all complete. (Fixed to openings /wooden frames with rawl plugs screws etc.) |
| 5177 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters.35 mm thick including ISI marked Stainless Steel butt hinges with necessary screwsmatched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. 35 mm thick including ISI marked Stainless Steel butt hingeswith necessary screws |
| 5178 | Providing and fixing ISI marked oxidised M.S. sliding door bolts with nuts and screws etc. complete :250x16 mm |
| 5179 | Providing and fixing ISI marked oxidised M.S. tower bolt black finish (Barrel type) with necessary screws etc. complete : 200x10 mm |
| 5180 | Providing and fixing ISI marked oxidised M.S. tower bolt black finish (Barrel type) with necessary screws etc. complete : 150x10 mm |
| 5181 | Providing and fixing ISI marked oxidised M.S. tower bolt black finish (Barrel type) with necessary screws etc. complete : 100x10 mm |
| 5182 | Providing and fixing ISI marked oxidised M.S. handles conforming to IS:4992 with necessary screws etc. complete :125 mm |
| 5183 | Providing and fixing aluminium handles floor door stopper ISI marked anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour or shade with necessary scerews etc. complet: Single rubber stopper |
| 5184 | Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete. Twin rubber stopper |
| 5185 | Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge.With stainless steel cover plate minimum 1.25 mm thickness |
| 5186 | Providing and fixing wire gauge shutters using stainless steel grade 304 wire gauge with wire of dia 0.5 mm and average width of aperture 1.4 mm in both directions for doors, windows and clerestory windows with necessary screws : 35 mm thick shutters with ISI marked M.S. pressed butt hinges bright finished of required size Second class teak wood |
| 5187 | Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. 80x1.20 mm M.S. laths with 1.20 mm thick top cover |
| 5188 | Providing and fixing ball bearing for rolling shutters. |
| 5189 | Extra for providing mechanical device chain and crank operation for operating rolling shutters. Exceeding 10.00 sqm and upto 16.80 sqm in the area |
| 5190 | Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strikeplate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineerin-charge:Profile B Fixing with adjustable lugs with split end tail to each jamb |
| 5191 | Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strikeplate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineerin-charge:Profile C Fixing with adjustable lugs with split end tail to each jamb |
| 5192 | Steel work in built up tubular ( round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished welded type tubes |
| 5193 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard rawing.surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing. |
| 5194 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 5195 | Providing & fixing fly proof wire gauze to windows, clerestory windows & doors with M.S. Flat 15x3 mm and nuts & bolts complete. Galvanised M.S. Wire gauze with 0.63 mm dia wire and 1.4 mm aperture on both sides |
| 5196 | Providing & fixing glass panes with putty and glazing clips in steel doors, windows, clerestory windows, all complete with :5.5 mm thick glass panes |
| 5197 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. 40 mm thick with 20 mm nominal size stone aggregate20mm nomnal sxe stone aggregate). |
| 5198 | Providing and fixing glass strips in joints of terrazo/ cement concrete floors. 40 mm wide and 4 mm thick |
| 5199 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. (75mm diameter) |
| 5200 | 12mm cement plaster of mix: 1:4 (1cement : 4coarse sand) |
| 5201 | 12mm cement plaster of mix: 1:6 (1cement :6coarse sand) |
| 5202 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 5203 | Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete. |
| 5204 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade : New work (two or more coats) over and including water tinnable priming coat with cement primer. |
| 5205 | Finishing walls with textured exterior paint of required shade : New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/ 10 sqm |
| 5206 | Finishing walls with Acrylic Smooth exterior paint of required shade :New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) |
| 5207 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture |
| 5208 | P/Fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron) |
| 5209 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15) Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 5210 | Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge. Pre-laminated particle board with decorative lamination on one side and balancing lamination on other side |
| 5211 | Engazing suitable beldar for petty works ( basic rates labour ) for replacing old s tin shed |
| 5212 | Engazing suitable fitter for electrical works ( basic rates labour ) |
| 5213 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. GROUP B |
| 5214 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. GROUP C |
| 5215 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 5216 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required2*2.5 Sq.M*1*2.5Sq.M |
| 5217 | Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including nnections but excluding modular plate etc. as required. |
| 5218 | (1.41) Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 5219 | (1.50.1)Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required Upto 450 mm sweep |
| 5220 | Supply of 20 watt LED Tubelight Philips or equivalent make approved by E.I. |
| 5221 | Supplying of Exaust Fan 450 mm sweep of orient or equivalent make as apporoved by E.I |
| 5222 | Supply ,Installation,Testing and Commissioning 1200 mm sweep, BEE 5 star rated,ceiling fan with brush less direct current (BLDC)Motor,class of insulation:B, 3 no. blades, 30 cm long down rod ,2 nos canopies,shakle kit,safety rope,copper winding ,power factor not less then 0.9,service value(cmm/w)minimum 6.85,aire delivery minnimum 215 cmm, 350 rpm(tollerance as per IS : 374/219),THD less then 10%,remote of electronic regulator unit 4 speed controll and all remaining accesories including safety pin ,nut bolts,washers,temperature rise equal to75 degree c (max), insulation resistance more then 2 mega ohm ,suitable for 230 v ,50 Hz ,single phase AC supply , earthing etc complete as required. |
| 5223 | Land Development Work:Earth work in excavation by mechanical means (Hydraulic excavator ) manual means in foundation tranches (not exceeding 1.5m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift up to 1.5m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50m. (All kinds of soil) For Toe Wall |
| 5224 | Supplying and filling in plinth with Jamuna sand under floors, including watering, ramming, consolidating and dressing complete. |
| 5225 | P/laying in position cement concrete of specified grade excluding the cost of centering and shuttering -All work up to plinth level:1:4 :8 (1 Cement :4 coarse sand: 8 graded stone aggregate 40 mm nominal size)In Yard for turffing |
| 5226 | Random Rubble Masonry with hard stone in foundation and plinth including levelling up with cement concrete 1 : 6 : 12 (1 Cement : 6 Coarse Sand : 12 graded Stone Aggregate 20 mm nominal size ) at plinth Level with Cement Mortar 1 : 6 ( 1 Cement : 6 Coarse Sand) |
| 5227 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. 40 mm thick with 20 mm nominal size stone aggregate20mm nomnal sxe stone aggregate). |
| 5228 | Cement concrete pavement with 1:2:4 including finishing complete. Road c.c. |
| 5229 | 12mm cement plaster of mix: 1:6 (1cement :6coarse sand) |
| 5230 | Stone Aggregate (Single size) : 20 mm nominal size In Yard |
| 5231 | Engazing suitable beldar for petty works ( basic rates labour ) Gravel Spreading Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 19, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 02, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 9 daysSep 03, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 10 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender