Tender For Construction Of 220Kv Gis Substation Sector-155, G.B. Nagar, Noida On Turnkey Basis
Tender Value
112.04 Crore
Estimated cost
Bid Submission
10 Sep 2026
17 days left
EMD
1.12 Crore
Bank guarantee accepted
Document Fee
17700
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Lucknow → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender For Construction Of 220Kv Gis Substation Sector-155, G.B. Nagar, Noida On Turnkey Basis
BOQ
| Sl. No. | Item Description |
| 1 | Name of Bidder: Abstract of Cost for Engineering, Supply, Erection and Commissioning of SAS Based 220/132/33kV, (2x160MVA+3x63 MVA) GIS Substation Sector-155 (G.B. Nagar), Noida on Turnkey Basis E-Tender Specification No. SD-1042 SD-1042 Sl. No. DESCRIPTION Amount (in Rs.) (With GST) |
| 2 | Total Price for Plant and Equipment to be supplied, (Schedule -1) |
| 3 | Total Price for Installation Charges Including 02 (Two) years O&M charges (Schedule-2) |
| 4 | Total Prices of Mandatory Spare Parts (Schedule-3) |
| 5 | Total Price for Electrical Works |
| 6 | % Discount , if any on Electrical Works |
| 7 | Discount in Rs. on Electrical Works |
| 8 | NET Price for Electrical Works |
| 9 | Price for Civil Works (Schedule-4) |
| 10 | % Discount, if any on Civil Works |
| 11 | Discount in Rs. on Civil Works |
| 12 | NET Price for Civil works |
| 13 | Net Lum Sum Bid Price (Elect+Civil) after Discount Seal of Company Full Signature ……………………………………………………………. Name ………………………………………………………………………….. Designation ………………………………………………………………. Date …………………………………………………………………………… Name of Bidder: SCHEDULE- 1 Schedule for Supply of Equipments for construction of SAS Based 220/132/33kV, (2x160MVA+3x63 MVA) GIS Substation Sector-155 (G.B. Nagar), Noida on Turnkey Basis E-Tender Specification No. SD-1042 (Schedule-Q1) Sl. No. Description Unit Qty. Unit F.O.R. destn. Prices in Rs. (Including Pkg,fwdg,freight & insurance charges) Applicable GST Rate In % (Including CGST + UPGST/ IGST) Total unit wise GST Amount (Rs.) Total Unit F.O.R. Destination prices with GST (Rs.) (5+7) Total FORDestinationPriceswith GST (Rs.)(4*8) |
| 14 | Power Transformers (i) 220/132 kV 160MVA No 2.0 To be Provided by UPPTCL (ii) 132/33kV 63MVA No 3.0 To be Provided by UPPTCL |
| 15 | 250kVA Station Transformer |
| 16 | (i) Heat run test |
| 17 | (ii) Impulse test |
| 18 | 245kV GIS Equipments |
| 19 | Transformer Bay Module: 245 kV,1600A,40kA for 3 sec SF6 gas insulated transformer bay module each comprising of SF6 gas insulated circuit breaker (1600A), current transformer (1000-800-500-300/1-1-1-1-1A),having two bus-bar disconnectors (1600A) with common grounding switch, line disconnector with safety grounding switches suitable for Main-I & Main-II bus system, Local Control Cubicle, SF6 gas monitoring system for complete bay. Three 1–phase SF6 gas insulated terminal connection for connecting 3 nos of single phase 800 sq mm XLPE cable with cable termination enclosure, Local Control Cubicle and accessories with GIS etc. to complete transformer bay module as per technical specification. (02 NO. bay Module for 160MVA Transformer & 01Nos. spare bay Modulefor future Capacity Augmentation) |
| 20 | Feeder Bay Module: 245 kV,1600A,40kA for 3 sec SF6 gas insulated transformer bay module each comprising of SF6 gas insulated circuit breaker (1600A), current transformer (1000-800-500-300/1-1-1-1-1A),having two bus-bar disconnectors (1600A) with common grounding switch, line disconnector with safety grounding switches suitable for Main-I & Main-II bus system, Local Control Cubicle, SF6 gas monitoring system for complete bay. Three 1–phase SF6 gas insulated terminal connection for connecting 3 nos of single phase 1000 sq mm XLPE cable with cable termination enclosure, Local Control Cubicle and accessories with GIS etc. to complete feeder bay module as per technical specification. (02 NO. bay Module for Line & 02Nos. spare bay Module for future) |
| 21 | Bus Bars: 245kV, 3 single phase (isolated) units, SF6 gas insulated, metal enclosed 2000A bus bars each enclosed in bus enclosures running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus bar set shall be complete with voltage transformer, disconnector, safety grounding switch, Local Control Cubicle, SF6 gas monitoring system etc. as per technical specification. |
| 22 | Bus Coupler Bay Module: 245 kV,3000A,40kA for 3 sec SF6 gas insulated transformer bay module each comprising of SF6 gas insulated circuit breaker (2000A), current transformer (1000-800-500-300/1-1-1-1-1A), having two bus-bar disconnectors (2000A) with common grounding switch suitable for Main-I & Main-II bus system, Local Control Cubicle, SF6 gas monitoring system for complete bay. Local Control Cubicle and accessories with GIS etc. to complete Bus coupler bay module as per technical specification. |
| 23 | 145kV GIS Equipments |
| 24 | Transformer Bay Module: 145 kV,800A,40kA for 3 sec SF6 gas insulated transformer bay module each comprising of SF6 gas insulated circuit breaker (800A), current transformer (800-400-200/1-1-1A),having two bus-bar disconnectors (800A) with common grounding switch, line disconnector with safety grounding switches suitable for Main-I & Main-II bus system, Local Control Cubicle, SF6 gas monitoring system for complete bay. Three 1–phase SF6 gas insulated terminal connection for connecting 3 nos of single phase 630 sq mm XLPE cable with cable termination enclosure, Local Control Cubicle and accessories with GIS etc. to complete 160MVA transformer bay module as per technical specification. (02 NO. bay Module for 160MVA Transformer & 01Nos. spare bay Modulefor future Capacity Augmentation & 03 NO. bay Module for 63 MVA Transformer & 01Nos. spare bay Modulefor future Capacity Augmentation ) |
| 25 | Feeder Bay Module: 145 kV,800A,40kA for 3 sec SF6 gas insulated transformer bay module each comprising of SF6 gas insulated circuit breaker (800A), current transformer (800-400-200/1-1-1A),having two bus-bar disconnectors (800A) with common grounding switch, line disconnector with safety grounding switches suitable for Main-I & Main-II bus system, Local Control Cubicle, PT, SF6 gas monitoring system for complete bay. Three 1–phase SF6 gas insulated terminal connection for connecting 3 nos of single phase 630 sq mm XLPE cable with cable termination enclosure, Local Control Cubicle and accessories with GIS etc. to complete feeder bay module as per technical specification. (02 NO. bay Module for Line & 02Nos. spare bay Module for future) |
| 26 | Bus Bars: 145kV, 3 single phase (isolated) units, SF6 gas insulated, metal enclosed 1600A bus bars each enclosed in bus enclosures running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus bar set shall be complete with voltage transformer, disconnector, safety grounding switch, Local Control Cubicle, SF6 gas monitoring system etc. as per technical specification. |
| 27 | Bus Coupler Bay Module: 145 kV,1600A,40kA for 3 sec SF6 gas insulated transformer bay module each comprising of SF6 gas insulated circuit breaker (1600A), current transformer (1600-800-400/1-1-1A),having two bus-bar disconnectors (1600A) with common grounding switch suitable for Main-I & Main-II bus system, Local Control Cubicle, SF6 gas monitoring system for complete bay. Local Control Cubicle and accessories with GIS etc. to complete Bus coupler bay module as per technical specification. |
| 28 | 36kV GIS Equipments |
| 29 | Transformer Bay Module:36kV, 2500A, SF6 gas insulated transformer bay module each comprising of SF6 gas circuit breaker(2500A), current transformer (2000-1250/1-1-1A), two bus-bar disconnector (2500A) with common grounding switch, SF6 gas monitoring system for complete bay. Three 1–phase SF6 gas insulated terminal connection for connecting 3 nos of single phase 2x630 sq mm XLPE cable (Considering 120% continuously loading of 33 KV side of 40 MVA transformer) with cable termination enclosure and accessories with GIS, Local Control Cubicle etc. to complete transformer bay module as per technical specification. (03 NO. bay Module for 63 MVA Transformer & 01Nos. spare bay Modulefor future Capacity Augmentation ) |
| 30 | Feeder Bay Module: 36 kV, 1250A, SF6 gas insulated feeder bay module each comprising of SF6 gas insulated circuit breaker (1250A), current transformer (400-200/1-1-1A), two bus-bar disconnectors (1250A) with common grounding switch, Line disconnector (1250A) with one normal safety grounding switch, & one high speed fault make grounding switch, SF6 gas monitoring system for complete bay, PT, gas insulated terminal for connecting XLPE cable (considering 120% continuously loading) with cable termination enclosure/ and accessories with GIS, Local Control Cubicle etc. to complete Feeder bay module. ( (out of these 2 nos. bays for LT station transformer & 2 nos. bays for CAPACITOR BANK) ) as per technical specification. (12 NO. bay Module for Line & 04Nos. spare bay Module for future) For Feeder & Capacitor bank Module; three core 300 sq mm (Cu) XLPE cable. For LT Station Transformer; three core 95 sq mm (Cu) XLPE cable. |
| 31 | Bus Bars: 36kV, 2500A, 3-phase or 1-phase encapsulated unit, SF6 gas insulated, metal enclosed bus bars each enclosed in bus enclosures running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus bar set shall be complete with voltage transformer, disconnector, safety grounding switch, Local Control Cubicle, SF6 gas monitoring system etc. |
| 32 | Bus Coupler Bay Module: 36kV, 2500A, SF6 gas insulated bus coupler bay module comprising of SF6 gas circuit breaker (2500A), current transformer (ratio 2000-1250/1-1-1A), two bus-bar disconnectors (2500A) each with safety grounding switch, Local Control Cubicle, SF6 gas monitoring system for complete bay etc.as per technical specification |
| 33 | Bus Sectionaliser Bay Module:36kV, 2500A, SF6 gas insulated bus sectionaliser bay module comprising of SF6 gas insulated circuit breaker(2500A), current transformer(2000-1250/1-1-1A), disconnector (2500A) with safety grounding switch, SF6 gas monitoring system for complete bay etc. as per technical specification. |
| 34 | 220kV Equipments |
| 35 | 245kV CVT |
| 36 | CVT Junction Box |
| 37 | 198kV surge arrestor (Polymer) |
| 38 | 245kV Bus post insulator |
| 39 | 132kV Equipments |
| 40 | 120kV surge arrestor (Polymer) |
| 41 | 145kV PT 0.2s accuracy class |
| 42 | Junction box for 145kV PT 0.2s accuracy class |
| 43 | 145kV Bus post insulator |
| 44 | 33kV Equipments |
| 45 | 30kV surge arrestor |
| 46 | 36kV Bus Post Insulator |
| 47 | 36kv Line Isolatotr with one earth switch |
| 48 | 36kv Drop out fuse set with Post Insulators(For both 250kVA Station T/f) |
| 49 | Pale Fencing |
| 50 | Arrangement for connecting 220kV,132kV &36kV sides of 160MVA & 63MVA Transformers with XLPE Cable coming from GIS rooms. |
| 51 | 220kV,1-core 2000 mm2, XLPE copper conductor Power Cable (Line gantry to GIS) |
| 52 | 220kV,1-core 1200 mm2, XLPE copper conductor Power Cable (Line gantry to GIS) |
| 53 | 220kV, 1-core 800 mm2, XLPE copper conductor Power Cable (GIS TO TRANSFORMER) |
| 54 | 132 KV 1CX1000 Sq.mm Copper conductor, XLPE Power cable (construction as per IEC-60502-2 and testing as per IEC-60840) with all Accessories (Line Gantry to GIS) |
| 55 | 132kV,1-core 630 mm2, XLPE copper conductor Power Cable Meter (GIS TO 63 MVA TRANSFORMER) |
| 56 | 36kV, 1-core 630mm2, XLPE copper conductor Power Cable (GIS to Power Transformer) |
| 57 | 36kV 3-core 95 mm2 XLPE copper cable for S/S T/Fs at both ends. |
| 58 | Single core 500 sq mm copper conductor PVC insulated 6.6 kV grade earthing cable. |
| 59 | Single core 300 sq mm copper conductor PVC insulated 6.6 kV grade earthing cable. |
| 60 | Cable termination kits |
| 61 | 220kV,2000 mm2, XLPE Power Cable outdoor termination kit |
| 62 | 220kV,2000 mm2, XLPE Power Cable indoor termination kit (GIS end) |
| 63 | 220kV,1200 mm2, XLPE Power Cable outdoor termination kit |
| 64 | 220kV,1200 mm2, XLPE Power Cable indoor termination kit (GIS end) |
| 65 | 220kV, 800 mm2, XLPE Power Cable outdoor termination kit (220kV side of TRANSFORMER ) |
| 66 | 220kV 800 mm2, XLPE Power Cable indoor termination kit ( GIS END) |
| 67 | 132kV, 1CX1000 mm2, XLPE Power Cable outdoor termination kit (for 160MVA T/fs & Feeders) |
| 68 | 132kV, 1CX1000 mm2, XLPE Power Cable Indoor termination kit (for 160MVA T/fs & Feeders) |
| 69 | 132kV, 1CX630 mm2, XLPE Power Cable outdoor termination kit (for 63MVA TRANSFORMER ) |
| 70 | 132kV, 1CX630 mm2, XLPE Power Cable indoor termination kit (for 63MVA TRANSFORMER GIS end) |
| 71 | 33kV, 630 mm2, XLPE Power Cable outdoor termination kit (33kV side of TRANSFORMER ) |
| 72 | 33kV, 630 mm2, XLPE Power Cable indoor termination kit (GIS end) |
| 73 | Single phase link box with/without SVL |
| 74 | Cable route markers as per specific cable size and equipment labelling |
| 75 | 33kV, 95mm2,3 core XLPE Power Cable outdoor termination kit |
| 76 | 33kV, 95mm2, 3 core XLPE Power Cable indoor termination kit (GIS end) |
| 77 | Simplex type Control & Relay Panel suitable for GIS Substation i) 220 kV Simplex type T/F Control Panel for 160MVA T/F (as per technical specifications of SAS issued by UPPTCL) No. 3.0 ii) 220 kV Simplex Type T/F Protection Panel for 160MVA T/F (as per technical specifications of SAS issued by UPPTCL) No. 3.0 iii) 220 kV Simplex Type Feeder C&R Panel (as per technical specifications of SAS issued by UPPTCL)(with differential relay and 04Nos. Additional differential relay for other end) No. 4.0 iv) 220 kV Simplex Type Bus Coupler C&R Panel (as per technical specifications of SAS issued by UPPTCL) No. 1.0 v) 132 kV Simplex Type Feeder C&R Panel (as per technical specifications of SAS issued by UPPTCL) No. 2.0 vi) 133 kV Simplex Type Transformer C&R Panel for 63MVA T/F (as per technical specifications of SAS issued by UPPTCL) No. 4.0 vii) 132 kV Simplex Type Bus Coupler C&R Panel (as per technical specifications of SAS issued by UPPTCL) No. 1.0 viii) Simplex Tripple feeder control and relay panel as per technical specification for 33kV feeder + 1sectionalizer + 2 No. Stn. T/F+2no Bus coupler No. 7.0 ix) Distributed Type Bus Bar Protection Panel (as per technical specifications of SAS issued by UPPTCL) No. 2.0 x) Rotational Under Frequency Panel No 1.0 xi) SAS (complete set) as per the UPPTCL specifications LS 1.0 xii) Phasor measurement Unit(PMU) Lot 1.0 xiii) Optical fibre reqd for SAS as per the specifications Lot 1.0 |
| 78 | Battery & battery charger i) Battery Charger for 110V,500AH Batteries Nos. 2.0 ii) 110 V, 500AH Battery Set Set 2.0 iii) 110 V DC Distribution Board No. 3.0 iv) 415 V AC Distribution Board No. 2.0 v) 415 V AC Lighting Distribution Board(outdoor) No. 5.0 vi) 415 V AC Lighting Distribution Board(indoor) No. 6.0 |
| 79 | Energy Meters i) 0.2s accuracy class ABT Energy Meters module as per technical specification. Nos 54.0 ii) Metering cubicle for ABT energy meters Nos. 5.0 iii) AMR with all accessories Lot 1.0 |
| 80 | Earthing Material i 40mm MS rod Meter 5000.0 ii 40mm MS rod electrode 3000mm long Nos 200.0 iii 75x10mm MS Flat Meter 1000.0 iv 50x6mm MS Flat Meter 2000.0 v 75x12mm Copper Flat Meter 400.0 vi 50x6mm Copper Flat Meter 300.0 |
| 81 | Main & Auxiliary Structure (with MS angles, channels, plates, nuts, bolts, step bolts, U bolts, spring washers, etc. and any other required materials) i) Lattice Type Main Structures MT 100.0 ii) ERW Pipe Structure MT 50.0 |
| 82 | Conductors i) ACSR Tarantulla KM 1.5 ii) ACSR Moose KM 1.5 iii) ACSR Zebra KM 1.5 iv) 70kN Antifog Disc Insulator Nos. 500.0 |
| 83 | Single Suspension Fitting Suitable for: i) Tarantulla Nos. 30.0 ii) Moose Nos. 50.0 iii) Zebra Nos. 75.0 |
| 84 | Single Tension Fitting Suitable for: i) Tarantulla Nos. 30.0 ii) Moose Nos. 50.0 iii) Zebra Nos. 75.0 |
| 85 | Double Tesnion fitting Suitable For: i) Moose Nos. 30.0 ii) Zebra Nos. 50.0 |
| 86 | PG Clamp Suitable For: i) Tarantulla/Moose Nos. 150.0 ii) Tarantulla/Zebra Nos. 200.0 iii) Zebra/Zebra Nos. 250.0 iv) Moose/Moose Nos. 150.0 v) Tarantulla/Tarantulla Nos. 200.0 |
| 87 | Bus Post Clamp Suitable For: i) Tarantulla Nos. 30.0 ii) Zebra Nos. 50.0 iii) Moose Nos. 30.0 iv) Twin Zebra Nos. 20.0 v) Twin Moose Nos. 20.0 |
| 88 | Fire prevention & extinguishing system i Fire Protection and microprocessor based fire detection alarm system comprising of smoke & heat type detectors for GIS cum Control room buildings, Control & Relay panels rooms, DG set room, Battery room etc. as per technical specification. Lot 1.0 ii Portable AFF mechanical foam type Fire Extinguisher complete with initial charge hose pipe and all other accessories and fittings as as per IS 1024 trolley mounted 45/50 litre capacity Nos. 10.0 iii Supply of following fire extinguisher carbon dioxide as per IS specn. No. 2878/1986 and as per technical specification. a) 22.5 kg Nos. 5.0 b) 11/9 kg Nos. 4.0 c) 4.5 kg Nos. 6.0 v Supply of sand buckets as per technical specification. Nos. 50.0 vi Supply of sand bucket stand suitable for 10 bucket as per Technical Specn. Nos. 7.0 vii Water Mist and CAF fire extinguisher back pack capacity 10ltr. Using spl. AFFF compound with Fire rating 55A, 2338,1000V (i) One spare compressed air cylinder 2ltr x200bar (Carbon Composite) (ii) 10Nos O-rings for the pressure vessel (iii) One CAN 5ltr special AFFF compound (iv) Tool Kit -1 no Set 1.0 |
| 89 | Supply of 1.1kV PVC FRLS Armoured Power and Control Cables A) Armoured Aluminium Power Cables i 2Cx6 mm2 Metre 1200.0 ii 4Cx16 mm2 Metre 1000.0 iii 3.5Cx50 mm2 Metre 2000.0 iv 3.5Cx95 mm2 Metre 1200.0 v 3.5Cx70 mm2 Metre 1500.0 B) Armoured Copper Control Cables i 2Cx2.5 mm2 Metre 12000.0 ii 4Cx2.5 mm2 Metre 15000.0 iii 6Cx2.5 mm2 Metre 15000.0 iv 10Cx2.5 mm2 Metre 12000.0 v 14Cx2.5 mm2 Metre 8000.0 vi 27Cx2.5 mm2 Metre 6000.0 |
| 90 | Illumination System for 220/132/33kV substation (indoor + outdoor) i Control Room Building LS 1.0 ii GIS Halls LS 3.0 iii Relay & Protection Panel Rooms LS 3.0 iv DG Set Area LS 1.0 v Switchyard/ Street Lighting (High Mast Lighting System) LS 1.0 vi Self supported aluminium ladder as per technical specification No. 1.0 |
| 91 | 2 Ton Split Air conditioner unit (Hitachi/O-general/Daikin or equivalent make) complete with suitable voltage stablizer |
| 92 | Complete Mulsfiyre system for both 160MVA Transformers |
| 93 | GI perforated trays of various sizes as per requirement |
| 94 | 100kVA silent type DG set as per UPPTCL's specn. |
| 95 | EOT Crane for 132kV GIS room (6MT capacity) |
| 96 | EOT Crane for 220kV GIS room (6MT capacity) |
| 97 | AHU System |
| 98 | Supply of materials & equipments of sufficient capacity for AHU system (To maintain positive pressure in 220KV GIS Hall) |
| 99 | Supply of materials & equipments of sufficient capacity for AHU system (To maintain positive pressure in 132KV GIS Hall) |
| 100 | Supply of materials & equipments of sufficient capacity for AHU system (To maintain positive pressure in 33KV GIS Hall) |
| 101 | CCTV System |
| 102 | Comunication Equipments. |
| 103 | Fiber Optic Terminal Equipment (FOTE) SDH STM-16 i) Base equipment suitable for 04 directions in subrack fully equipped with all necessary common cards, power supply card, other hardware & acccessories including 10 Nos. optical pathch cords of lengths as per site requirements, DDF etc. with redundant CPU. No. 1.0 ii) Optical Base Card for 04 direction (STM-16), should support STM-1 & STM-4 interfaces. No. 2.0 iii) Short Haul, STM-16 1310nm SFP Transceiver- S-16.1 No. 2.0 iv) Long Haul, STM-16 1310nm SFP Transceiver- L-16.1 No. 4.0 v) E1 Interfaces (120Ohm) (32 Interfaces with 2 Cards) No. 1.0 vi) L2Etherner Interfaces 10/100 Base T (16 Interfaces with Minimum 2 Cards) No. 1.0 vii) VOIP Phone No. 1.0 viii) Equipment cabinet for SDH and DTPC 2200mm (h) including 100mm base, wxd should be suitable for 19\\" or 23\\" Rack. No. 1.0 ix) MDF (200 Pairs), mounted in cabinet. No. 1.0 x) GPS Clock No. 1.0 |
| 104 | 4 Command Standalone Digital Tele-Protection Coupler (DTPC) i) 04 Command Standalone Digital Tele-protection Couples fully equipped with all necessary common cards, power supply cards, other hardware accessories, connectors, cables, subrack with E1 pathe cord srt of 04 etc. No. 4.0 |
| 105 | Name plate, phase plate, Danger Plate as per IS/IEC and CEA guidelines |
| 106 | Testing & Maintenance Equipment for GIS Substation i) SF6 Gas Leakage Detector Nos. 2.0 ii) SF6 Gas filling and evacuation pumping unit Nos. 1.0 iii) SF6 Dew point meter Nos. 1.0 vi) Gas Mask Nos. 2.0 v) Earth Fault detection meter Nos. 1.0 vi) Digital Clamp Meter Nos. 1.0 vii) 10KV Digital battery operated meggar (Meggar or Equivelent make) Nos. 1.0 viii) Automatic Transformer Oil BDV Test Set Nos. 1.0 ix) Digital multi meter (Motvani or Equivelent make) Nos. 1.0 x) INFRARED THERMO-VISION CAMERA Nos. 1.0 xi) Universal Relay Test Kit as per TS Nos. 1.0 xii) All type of control Valves fo SF6 Gas for each type Nos. 1.0 Total (Rs.): Note : 1- Bidder is required to quote prices in this Schedule for all the individual items/sub-items. 2- Please confirm that the prices are after taking into account ITC benefits. As per section 171 of CGST act 2017 , \\" any reduction in rate of tax any supply of goods or services or the benefit of input tax credit shall be passed on to the recipient by way of commensureate reduction of prices. Hence supplier/ manufacture to ensure to passe the benefit of reduced prices to UPPTCL. Further prices quoted by supplier/manufacturer is subject to scrutiny under above section.\\" 3- Evaluation of Tender shall be made after loading 18% GST (present rate) on all items including supply, erection, Testing & commissioning and civil work asuming the work as Work Contract. Seal of Company Full Signature …………………………………………. Name …………………………………………………….. Designation ………………………………………………. Date ……………………………………………………………… Name of Bidder: SCHEDULE- 2 Schedule for Installation of Equipments for construction of SAS Based 220/132/33kV, (2x160MVA+3x63 MVA) GIS Substation Sector-155 (G.B. Nagar), Noida on Turnkey Basis E-Tender Specification No. SD-1042 (Schedule-Q2) Sl. No. Description Unit Qty. Unit F.O.R. destn. Prices in Rs. (Including Pkg,fwdg,freight & insurance charges) Applicable GST Rate In % (Including CGST + UPGST/ IGST) Total unit wise GST Amount (Rs.) Total Unit F.O.R. Destination prices with GST (Rs.) (5+7) Total FORDestinationPriceswith GST (Rs.)(4*8) |
| 107 | Power Transformers (i) 220/132 kV 160MVA No 2.0 To be Provided by UPPTCL (ii) 132/33kV 63MVA No 3.0 To be Provided by UPPTCL |
| 108 | 250kVA Station Transformer |
| 109 | (i) Heat run test |
| 110 | (ii) Impulse test |
| 111 | 245kV GIS Equipments |
| 112 | Transformer Bay Module: 245 kV,1600A,40kA for 3 sec SF6 gas insulated transformer bay module each comprising of SF6 gas insulated circuit breaker (1600A), current transformer (1000-800-500-300/1-1-1-1-1A),having two bus-bar disconnectors (1600A) with common grounding switch, line disconnector with safety grounding switches suitable for Main-I & Main-II bus system, Local Control Cubicle, SF6 gas monitoring system for complete bay. Three 1–phase SF6 gas insulated terminal connection for connecting 3 nos of single phase 800 sq mm XLPE cable with cable termination enclosure, Local Control Cubicle and accessories with GIS etc. to complete transformer bay module as per technical specification. (02 NO. bay Module for 160MVA Transformer & 01Nos. spare bay Modulefor future Capacity Augmentation) |
| 113 | Feeder Bay Module: 245 kV,1600A,40kA for 3 sec SF6 gas insulated transformer bay module each comprising of SF6 gas insulated circuit breaker (1600A), current transformer (1000-800-500-300/1-1-1-1-1A),having two bus-bar disconnectors (1600A) with common grounding switch, line disconnector with safety grounding switches suitable for Main-I & Main-II bus system, Local Control Cubicle, SF6 gas monitoring system for complete bay. Three 1–phase SF6 gas insulated terminal connection for connecting 3 nos of single phase 1000 sq mm XLPE cable with cable termination enclosure, Local Control Cubicle and accessories with GIS etc. to complete feeder bay module as per technical specification. (02 NO. bay Module for Line & 02Nos. spare bay Module for future) |
| 114 | Bus Bars: 245kV, 3 single phase (isolated) units, SF6 gas insulated, metal enclosed 2000A bus bars each enclosed in bus enclosures running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus bar set shall be complete with voltage transformer, disconnector, safety grounding switch, Local Control Cubicle, SF6 gas monitoring system etc. as per technical specification. |
| 115 | Bus Coupler Bay Module: 245 kV,3000A,40kA for 3 sec SF6 gas insulated transformer bay module each comprising of SF6 gas insulated circuit breaker (2000A), current transformer (1000-800-500-300/1-1-1-1-1A), having two bus-bar disconnectors (2000A) with common grounding switch suitable for Main-I & Main-II bus system, Local Control Cubicle, SF6 gas monitoring system for complete bay. Local Control Cubicle and accessories with GIS etc. to complete Bus coupler bay module as per technical specification. |
| 116 | 145kV GIS Equipments |
| 117 | Transformer Bay Module: 145 kV,800A,40kA for 3 sec SF6 gas insulated transformer bay module each comprising of SF6 gas insulated circuit breaker (800A), current transformer (800-400-200/1-1-1A),having two bus-bar disconnectors (800A) with common grounding switch, line disconnector with safety grounding switches suitable for Main-I & Main-II bus system, Local Control Cubicle, SF6 gas monitoring system for complete bay. Three 1–phase SF6 gas insulated terminal connection for connecting 3 nos of single phase 630 sq mm XLPE cable with cable termination enclosure, Local Control Cubicle and accessories with GIS etc. to complete 160MVA transformer bay module as per technical specification. (02 NO. bay Module for 160MVA Transformer & 01Nos. spare bay Modulefor future Capacity Augmentation & 03 NO. bay Module for 63 MVA Transformer & 01Nos. spare bay Modulefor future Capacity Augmentation ) |
| 118 | Feeder Bay Module: 145 kV,800A,40kA for 3 sec SF6 gas insulated transformer bay module each comprising of SF6 gas insulated circuit breaker (800A), current transformer (800-400-200/1-1-1A),having two bus-bar disconnectors (800A) with common grounding switch, line disconnector with safety grounding switches suitable for Main-I & Main-II bus system, Local Control Cubicle, PT, SF6 gas monitoring system for complete bay. Three 1–phase SF6 gas insulated terminal connection for connecting 3 nos of single phase 630 sq mm XLPE cable with cable termination enclosure, Local Control Cubicle and accessories with GIS etc. to complete feeder bay module as per technical specification. (02 NO. bay Module for Line & 02Nos. spare bay Module for future) |
| 119 | Bus Bars: 145kV, 3 single phase (isolated) units, SF6 gas insulated, metal enclosed 1600A bus bars each enclosed in bus enclosures running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus bar set shall be complete with voltage transformer, disconnector, safety grounding switch, Local Control Cubicle, SF6 gas monitoring system etc. as per technical specification. |
| 120 | Bus Coupler Bay Module: 145 kV,1600A,40kA for 3 sec SF6 gas insulated transformer bay module each comprising of SF6 gas insulated circuit breaker (1600A), current transformer (1600-800-400/1-1-1A),having two bus-bar disconnectors (1600A) with common grounding switch suitable for Main-I & Main-II bus system, Local Control Cubicle, SF6 gas monitoring system for complete bay. Local Control Cubicle and accessories with GIS etc. to complete Bus coupler bay module as per technical specification. |
| 121 | 36kV GIS Equipments |
| 122 | Transformer Bay Module:36kV, 2500A, SF6 gas insulated transformer bay module each comprising of SF6 gas circuit breaker(2500A), current transformer (2000-1250/1-1-1A), two bus-bar disconnector (2500A) with common grounding switch, SF6 gas monitoring system for complete bay. Three 1–phase SF6 gas insulated terminal connection for connecting 3 nos of single phase 2x630 sq mm XLPE cable (Considering 120% continuously loading of 33 KV side of 40 MVA transformer) with cable termination enclosure and accessories with GIS, Local Control Cubicle etc. to complete transformer bay module as per technical specification. (03 NO. bay Module for 63 MVA Transformer & 01Nos. spare bay Modulefor future Capacity Augmentation ) |
| 123 | Feeder Bay Module: 36 kV, 1250A, SF6 gas insulated feeder bay module each comprising of SF6 gas insulated circuit breaker (1250A), current transformer (400-200/1-1-1A), two bus-bar disconnectors (1250A) with common grounding switch, Line disconnector (1250A) with one normal safety grounding switch, & one high speed fault make grounding switch, SF6 gas monitoring system for complete bay, PT, gas insulated terminal for connecting XLPE cable (considering 120% continuously loading) with cable termination enclosure/ and accessories with GIS, Local Control Cubicle etc. to complete Feeder bay module. ( (out of these 2 nos. bays for LT station transformer & 2 nos. bays for CAPACITOR BANK) ) as per technical specification. (12 NO. bay Module for Line & 04Nos. spare bay Module for future) For Feeder & Capacitor bank Module; three core 300 sq mm (Cu) XLPE cable. For LT Station Transformer; three core 95 sq mm (Cu) XLPE cable. |
| 124 | Bus Bars: 36kV, 2500A, 3-phase or 1-phase encapsulated unit, SF6 gas insulated, metal enclosed bus bars each enclosed in bus enclosures running along the length of the switchgear to interconnect each of circuit breaker bay module. Each bus bar set shall be complete with voltage transformer, disconnector, safety grounding switch, Local Control Cubicle, SF6 gas monitoring system etc. |
| 125 | Bus Coupler Bay Module: 36kV, 2500A, SF6 gas insulated bus coupler bay module comprising of SF6 gas circuit breaker (2500A), current transformer (ratio 2000-1250/1-1-1A), two bus-bar disconnectors (2500A) each with safety grounding switch, Local Control Cubicle, SF6 gas monitoring system for complete bay etc.as per technical specification |
| 126 | Bus Sectionaliser Bay Module:36kV, 2500A, SF6 gas insulated bus sectionaliser bay module comprising of SF6 gas insulated circuit breaker(2500A), current transformer(2000-1250/1-1-1A), disconnector (2500A) with safety grounding switch, SF6 gas monitoring system for complete bay etc. as per technical specification. |
| 127 | 220kV Equipments |
| 128 | 245kV CVT |
| 129 | CVT Junction Box |
| 130 | 198kV surge arrestor (Polymer) |
| 131 | 245kV Bus post insulator |
| 132 | 132kV Equipments |
| 133 | 120kV surge arrestor (Polymer) |
| 134 | 145kV PT 0.2s accuracy class |
| 135 | Junction box for 145kV PT 0.2s accuracy class |
| 136 | 145kV Bus post insulator |
| 137 | 33kV Equipments |
| 138 | 30kV surge arrestor |
| 139 | 36kV Bus Post Insulator |
| 140 | 36kv Line Isolatotr with one earth switch |
| 141 | 36kv Drop out fuse set with Post Insulators(For both 250kVA Station T/f) |
| 142 | Pale Fencing |
| 143 | Laying of cable 220kV,132kV &36kV sides XLPE Cable. |
| 144 | 220kV,1-core 2000 mm2, XLPE copper conductor Power Cable (Line gantry to GIS) |
| 145 | 220kV,1-core 1200 mm2, XLPE copper conductor Power Cable (Line gantry to GIS) |
| 146 | 220kV, 1-core 800 mm2, XLPE copper conductor Power Cable (GIS TO TRANSFORMER) |
| 147 | 132 KV 1CX1000 Sq.mm Copper conductor, XLPE Power cable (construction as per IEC-60502-2 and testing as per IEC-60840) with all Accessories (Line Gantry to GIS) |
| 148 | 132kV,1-core 630 mm2, XLPE copper conductor Power Cable Meter (GIS TO 63 MVA TRANSFORMER) |
| 149 | 36kV, 1-core 630mm2, XLPE copper conductor Power Cable (GIS to Power Transformer) |
| 150 | 36kV 3-core 95 mm2 XLPE copper cable for S/S T/Fs at both ends. |
| 151 | Single core 500 sq mm copper conductor PVC insulated 6.6 kV grade earthing cable. |
| 152 | Single core 300 sq mm copper conductor PVC insulated 6.6 kV grade earthing cable. |
| 153 | Cable termination kits |
| 154 | 220kV,2000 mm2, XLPE Power Cable outdoor termination kit |
| 155 | 220kV,2000 mm2, XLPE Power Cable indoor termination kit (GIS end) |
| 156 | 220kV,1200 mm2, XLPE Power Cable outdoor termination kit |
| 157 | 220kV,1200 mm2, XLPE Power Cable indoor termination kit (GIS end) |
| 158 | 220kV, 800 mm2, XLPE Power Cable outdoor termination kit (220kV side of TRANSFORMER ) |
| 159 | 220kV 800 mm2, XLPE Power Cable indoor termination kit ( GIS END) |
| 160 | 132kV, 1CX1000 mm2, XLPE Power Cable outdoor termination kit (for 160MVA T/fs & Feeders) |
| 161 | 132kV, 1CX1000 mm2, XLPE Power Cable Indoor termination kit (for 160MVA T/fs & Feeders) |
| 162 | 132kV, 1CX630 mm2, XLPE Power Cable outdoor termination kit (for 63MVA TRANSFORMER ) |
| 163 | 132kV, 1CX630 mm2, XLPE Power Cable indoor termination kit (for 63MVA TRANSFORMER GIS end) |
| 164 | 33kV, 630 mm2, XLPE Power Cable outdoor termination kit (33kV side of TRANSFORMER ) |
| 165 | 33kV, 630 mm2, XLPE Power Cable indoor termination kit (GIS end) |
| 166 | Single phase link box with/without SVL |
| 167 | Cable route markers as per specific cable size and equipment labelling |
| 168 | 33kV, 95mm2,3 core XLPE Power Cable outdoor termination kit |
| 169 | 33kV, 95mm2, 3 core XLPE Power Cable indoor termination kit (GIS end) |
| 170 | Integration and installation of Simplex type Control & Relay Panel suitable for GIS Substation i) 220 kV Simplex type T/F Control Panel for 160MVA T/F (as per technical specifications of SAS issued by UPPTCL) No. 3.0 ii) 220 kV Simplex Type T/F Protection Panel for 160MVA T/F (as per technical specifications of SAS issued by UPPTCL) No. 3.0 iii) 220 kV Simplex Type Feeder C&R Panel (as per technical specifications of SAS issued by UPPTCL)(with differential relay and also for 04Nos. Additional differential relay at other end) No. 4.0 iv) 220 kV Simplex Type Bus Coupler C&R Panel (as per technical specifications of SAS issued by UPPTCL) No. 1.0 v) 132 kV Simplex Type Feeder C&R Panel (as per technical specifications of SAS issued by UPPTCL) No. 2.0 vi) 133 kV Simplex Type Transformer C&R Panel for 63MVA T/F (as per technical specifications of SAS issued by UPPTCL) No. 4.0 vii) 132 kV Simplex Type Bus Coupler C&R Panel (as per technical specifications of SAS issued by UPPTCL) No. 1.0 viii) Simplex Tripple feeder control and relay panel as per technical specification for 33kV feeder + 1sectionalizer + 2 No. Stn. T/F+2no Bus coupler No. 7.0 ix) Distributed Type Bus Bar Protection Panel (as per technical specifications of SAS issued by UPPTCL) No. 2.0 x) Rotational Under Frequency Panel No 1.0 xi) SAS (complete set) as per the UPPTCL specifications LS 1.0 xii) Phasor measurement Unit(PMU) Lot 1.0 xiii) Optical fibre reqd for SAS as per the specifications Lot 1.0 |
| 171 | Battery & battery charger i) Battery Charger for 110V,500AH Batteries Nos. 2.0 ii) 110 V, 500AH Battery Set Set 2.0 iii) 110 V DC Distribution Board No. 3.0 iv) 415 V AC Distribution Board No. 2.0 v) 415 V AC Lighting Distribution Board(outdoor) No. 5.0 vi) 415 V AC Lighting Distribution Board(indoor) No. 6.0 |
| 172 | Energy Meters i) 0.2s accuracy class ABT Energy Meters module as per technical specification. Nos 54.0 ii) Metering cubicle for ABT energy meters Nos. 5.0 iii) AMR with all accessories Lot 1.0 |
| 173 | Earthing Material i 40mm MS rod Meter 5000.0 ii 40mm MS rod electrode 3000mm long Nos 200.0 iii 75x10mm MS Flat Meter 1000.0 iv 50x6mm MS Flat Meter 2000.0 v 75x12mm Copper Flat Meter 400.0 vi 50x6mm Copper Flat Meter 300.0 |
| 174 | Erection of Main & Auxiliary Structure (with MS angles, channels, plates, nuts, bolts, step bolts, U bolts, spring washers, etc. and any other required materials) i) Lattice Type Main Structures MT 100.0 ii) ERW Pipe Structure MT 50.0 |
| 175 | Conductors i) ACSR Tarantulla KM 1.5 ii) ACSR Moose KM 1.5 iii) ACSR Zebra KM 1.5 iv) 70kN Antifog Disc Insulator Nos. 500.0 |
| 176 | Single Suspension Fitting Suitable for: i) Tarantulla Nos. 30.0 ii) Moose Nos. 50.0 iii) Zebra Nos. 75.0 |
| 177 | Single Tension Fitting Suitable for: i) Tarantulla Nos. 30.0 ii) Moose Nos. 50.0 iii) Zebra Nos. 75.0 |
| 178 | Double Tesnion fitting Suitable For: i) Moose Nos. 30.0 ii) Zebra Nos. 50.0 |
| 179 | PG Clamp Suitable For: i) Tarantulla/Moose Nos. 150.0 ii) Tarantulla/Zebra Nos. 200.0 iii) Zebra/Zebra Nos. 250.0 iv) Moose/Moose Nos. 150.0 v) Tarantulla/Tarantulla Nos. 200.0 |
| 180 | Bus Post Clamp Suitable For: i) Tarantulla Nos. 30.0 ii) Zebra Nos. 50.0 iii) Moose Nos. 30.0 iv) Twin Zebra Nos. 20.0 v) Twin Moose Nos. 20.0 |
| 181 | Complete Fire prevention & extinguishing system |
| 182 | Laying of 1.1kV PVC FRLS Armoured Power and Control Cables A) Armoured Aluminium Power Cables i 2Cx6 mm2 Metre 1200.0 ii 4Cx16 mm2 Metre 1000.0 iii 3.5Cx50 mm2 Metre 2000.0 iv 3.5Cx95 mm2 Metre 1200.0 v 3.5Cx70 mm2 Metre 1500.0 vi Armoured aluminium power Cable termination Lot 1.0 B) Armoured Copper Control Cables i 2Cx2.5 mm2 Metre 12000.0 ii 4Cx2.5 mm2 Metre 15000.0 iii 6Cx2.5 mm2 Metre 15000.0 iv 10Cx2.5 mm2 Metre 12000.0 v 14Cx2.5 mm2 Metre 8000.0 vi 27Cx2.5 mm2 Metre 6000.0 vii Armoured copper control Cable termination Lot 1.0 |
| 183 | Illumination System for 220/132/33kV substation (indoor + outdoor) |
| 184 | 2 Ton Split Air conditioner unit (Hitachi/O-general/Daikin or equivalent make) complete with suitable voltage stablizer |
| 185 | Complete Mulsfiyre system for both 160MVA Transformers |
| 186 | GI perforated trays of various sizes as per requirement |
| 187 | 100kVA silent type DG set as per UPPTCL's specn. |
| 188 | EOT Crane for 132kV GIS room (6MT capacity) |
| 189 | EOT Crane for 220kV GIS room (6MT capacity) |
| 190 | AHU System |
| 191 | Supply of materials & equipments of sufficient capacity for AHU system (To maintain positive pressure in 220KV GIS Hall) |
| 192 | Supply of materials & equipments of sufficient capacity for AHU system (To maintain positive pressure in 132KV GIS Hall) |
| 193 | Supply of materials & equipments of sufficient capacity for AHU system (To maintain positive pressure in 33KV GIS Hall) |
| 194 | CCTV System |
| 195 | O&M work for 02 Years |
| 196 | Installation of Comunication Equipments including DTPC, FOTE etc. Total (Rs.): Note : 1- Bidder is required to quote prices in this Schedule for all the individual items/sub-items. 2- Please confirm that the prices are after taking into account ITC benefits. As per section 171 of CGST act 2017 , \\" any reduction in rate of tax any supply of goods or services or the benefit of input tax credit shall be passed on to the recipient by way of commensureate reduction of prices. Hence supplier/ manufacture to ensure to passe the benefit of reduced prices to UPPTCL. Further prices quoted by supplier/manufacturer is subject to scrutiny under above section.\\" 3- Evaluation of Tender shall be made after loading 18% GST (present rate) on all items including supply, erection, Testing & commissioning and civil work asuming the work as Work Contract. Seal of Company Full Signature …………………………………………. Name …………………………………………………….. Designation ………………………………………………. Date ……………………………………………………………… Name of Bidder: SCHEDULE- 3 Bill of Quantition for Supply of Mandatory Spares Parts for construction of SAS Based 220/132/33kV, (2x160MVA+3x63 MVA) GIS Substation Sector-155 (G.B. Nagar), Noida on Turnkey Basis E-Tender Specification No. SD-1042 Sl.No. Item/ Equipments along with all accessories Unit Qty. Unit F.O.R. destn. Prices in Rs. (Including Pkg,fwdg,freight & insurance charges) Applicable GST Rate In % (Including CGST + UPGST/IGST) Total unit wise GST Amount (Rs.) Total Unit F.O.R. Destination prices with GST (Rs.) (5+7) Total FORDestination Priceswith GST (Rs.) (4*8) |
| 197 | Mandatory Spares for 220kV GIS i SF6 Gas Pressure Relief Devices, 3 Nos. of each type Set 1.0 ii SF6 Pressure gauge with coupling device cum switch or density monitors and pressure switch asapplicable (1 no. of each type) Set 1.0 iii Coupling device for pressure gauge cum switch for connecting Gas handling plant Set 1.0 iv Rubber Gaskets, “O” Rings and Seals for SF6 gas of each type Set 1.0 v Molecular filter for SF6 gas with filter bags (20% of total weight) Set 1.0 vi All types of Control Valves for SF6 gas of each type Set 1.0 vii SF6 gas (20 % of total gas) LS 1.0 viii All types of coupling for SF6 gas (1 no. of each type) Set 1.0 ix Density Monitors for SF6 gas No. 2.0 x Enclosures, Insulators & main circuit to replace on each phase, any compartment of Busbar or bay Set 1.0 xi Bottle for SF6 gas filled with SF6 Gas(40kG each) Nos 3.0 xii T&P for bushing erection including ladder/ platform for Bushing erection and subsequently during O&Mfor Transformer No. 1.0 xiii Cable Termination Enclosure Set 1.0 |
| 198 | Mandatory Spares for 132kV GIS i SF6 Gas Pressure Relief Devices, 3 Nos. of each type Set 1.0 ii SF6 Pressure gauge with coupling device cum switch or density monitors and pressure switch asapplicable (1 no. of each type) Set 1.0 iii Coupling device for pressure gauge cum switch for connecting Gas handling plant Set 1.0 iv Rubber Gaskets, “O” Rings and Seals for SF6 gas of each type Set 1.0 v Molecular filter for SF6 gas with filter bags (20% of total weight) Set 1.0 vi All types of Control Valves for SF6 gas of each type Set 1.0 vii SF6 gas (20 % of total gas) LS 1.0 viii All types of coupling for SF6 gas (1 no. of each type) Set 1.0 ix Density Monitors for SF6 gas No. 2.0 x Enclosures, Insulators & main circuit to replace on each phase, any compartment of Busbar or bay Set 1.0 xi Bottle for SF6 gas filled with SF6 Gas(40kG each) Nos 3.0 xii T&P for bushing erection including ladder/ platform for Bushing erection and subsequently during O&Mfor Transformer No. 1.0 xiii Cable Termination Enclosure Set 1.0 |
| 199 | Mandatory Spares for 33kV GIS i SF6 Gas Pressure Relief Devices, 3Nos. Of each type Set 1.0 ii SF6 Pressure gauge with coupling device cum switch or density monitors and pressure switch as applicable (1No. Of each type) Set 1.0 iii Coupling device for pressure gauge cum switch for connecting Gas handling plant Set 1.0 iv Rubber Gaskets, \\"O\\" Rings and Seals for SF6 gas of each type Set 1.0 v Molecular filter for SF6 gas with filter bags (20% of total weight) Set 1.0 vi SF6 Gas ( 20% of total gas) LS 1.0 vii Density Monitors for SF6 gas suitable for GIS module No. 2.0 Total (Rs.) : Name of Bidder: BILL OF QUANTITY S. No. Name of Work Pages Amount (Rs.) |
| 200 | Total Rs. 0.0 Special Conditions |
| 201 | Tenderers are advised to visit the site of work and make themselves acquainted with the site conditions. No claim whatsoever shall be entertained after submission of tender. |
| 202 | Tenderer shall quote rates inclusive of all type of taxes. Only GST will be paid extra . |
| 203 | No idling charge of T&P and labour will be paid for extended period of contract , if any . |
| 204 | Quantities are approximate and may vary upto any extent on either side as per requirement of the site conditions or may not be executed at all for which no extra claim shall be entertained. |
| 205 | All above works shall be executed as per U.P.P.W.D/ U.P.P.T.C.L specification or as directed by Engineer-In-charge. |
| 206 | The Work may be carried on newly allotted land and energized S/S Area having high voltage installations. contractor must employee trained supervisor and labour to work in such electrical hazardous area. Safety of all men & material shall be contractor's responsibility. |
| 207 | Income tax / other tax if any levied by government during contractual period as required shall be deducted by the deptt, form the contractor's bill. However GST shall be paid extra as legally applicable. |
| 208 | Contractor shall register the agreement and the labour engaged in construction work in the office of Dy. Labour Commissioner |
| 209 | Testing of material shall be born by the contractor. Nothing shall be paid extra by the department. |
| 210 | The contractor should have all relative T&P as concrete mixture, needle vibrator, surface vibrator, slump test equipment & mini earth compactor. |
| 211 | Contractor has to make platform for casting of trench covers as per the direction of Engineer-in-Charge. Nothing shall be paid extra for it. |
| 212 | Contractor has to put up all relevant drawing with design/layout to SE (Civil) Noida for approval at his own cost if requared; nothing shall be paid extra for it. |
| 213 | Contractor has to made available 12 No. Cube at site and will frequently fill the cibe at site . Accordingly cube test report will be submitted by contractor at his own cost . Final bill of work will be paid to contractor only after he submitts all satisfactory test result from authorised lab . |
| 214 | As per G.O No. 622/23-12-2012-2. Audit/08 TC dt. 08 June 2012, Contractor has to deposit extra Security/Performance guarantee, if the tendered rates are found below to the department rates. Special Conditions |
| 215 | As per section 171 of CGST Act, 2017 Any reduction in rate of tax on any supply of goods or services or the benefit of input tax credit shall be passed on to the recipient by way of commensurate reduction in prices. Hence supplier/manufacturer to ensure to pass the benefit of reduced prices to UPPTCL. Further price quoted by supplier/manufacturer is subject to scrutiny under above section.” A declaration towards anti profiteering clause under section 171 of the GST act 2017 as per annexure enclosed to be submitted by contractor on letter head. |
| 216 | All drawing & Layout should be approved by SE (civil) . |
| 217 | Column means length of column should be greater than or equal to 3 times of least dimension of column. |
| 218 | Painting work will be started after written approval of SDO after his inspection. |
| 219 | yscj lsl] jkW;YVh ,oa vU; leLr VSDl dh ns;rk QeZ@dkUVªsDVj dh gksxh] foHkkx }kjk ek= th0,l0Vh0 dk Hkqxrku fd;k tk;sxkA |
| 220 | [kuu foHkkx }kjk ftu eSVsfj;y ij jkW;YVh ykxw gS fd jkW;YVh izi= foHkkx] dks tek djuk vfuok;Z gksxk vU;Fkk fu;ekuqlkj dVkSrh dj vuqcU/k vfUre fd;k tk;sxkA |
| 221 | QeZ @ Bsdsnkj dks vuqcfU/kr vFkok foLrkfjr le;kof/k ¼vFkkZr dk;Z iw.kZ gksus rd½ esa yscj ,oa Vh0,.Mih0 ij Idling Charge es vFkok vksoj gsM 'kqYd ns; ugh gksxsaA |
| 222 | 'kklu }kjk fu/kkZfjr No Entry Zone esa fu/kkZfjr le; ds vuqlkj ;fn dk;Z ckf/kr gksrk gS] ml fLFkfr esa lEiw.kZ ftEesnkjh QeZ@Bsdsnkj dh gksxh] foHkkx }kjk dksbZ Hkh vfrfjDr Hkqxrku ugh fd;k tk;sxkA |
| 223 | vuqcU/k ds vUrZxr —r dk;ksZa ds lSEiy VsLV foHkkx ds Engineer Incharge ds funsZ'kkuqlkj NABL/PWD/Institue tks Hkh funsZf'kr fd;k tk;sxk ls vkbZ0,l0 dksM ds ekud ds vuq:i Bsdsnkj ds O;; ij djk;k@fd;k tk;sxkA |
| 224 | vuqcU/k ds vUrZxr —r dk;ksZa ds VsLV fjiksZV@odZ eSuf'ki larks\\"k tud u ik;s tkus ij mls rksMus ,oa mldk iqu% fuekZ.k fcuk fdlh vfrfjDr ns; ds QeZ@Bsdsnkj }kjk fd;s tkus dh vfuok;rkZ gksxhA |
| 225 | dk;Z ds nkSjku fuekZ.k LFky ij fu;qDr fd;s x;s ekuo 'kfDr ¼yscj] eslu bR;kfn½ dh lqj{kk dh lEiw.kZ ftEesnkjh QeZ@Bsdsnkj dh gksxh rFkk fdlh Hkh vfiz; ?kVuk dh lEiw.kZ ftEesnkjh QeZ@Bsdsnkj dh gksxhA |
| 226 | Bsdsnkj }kjk fuekZ.k ds nkSjku ikjs\\"k.k@tkuin LdU/k ds dfeZ;ksa@vf/kdkfj;ksa ds lkFk 'kkyhu O;ogkj lqfuf'pr djsa vU;Fkk dh fLFkfr esa fu;ekuqlkj fof/kd dk;Zokgh dh tk;sxhA |
| 227 | fuekZ.k ds fy;s JCB e'khu bR;kfn lEcfU/kr JE(C)/SDO(C) ds fyf[kr vuqefr ls gh S/Yard ys tk;k tk;sxkA dksbZ nq?kZVuk gksus ij {kfr dh lEiw.kZ ftEesnkjh fufonknkrk dh gksxhA |
| 228 | dk;Z ds nkSjku fuekZ.k LFky ij vko';drkuqlkj ty fudklh dk dk;Z QeZ@Bsdsnkj }kjk vius O;; ij fd;k tk;sxkA |
| 229 | dk;ZLFky ij tkuinh; dk;ksZa esa iz;ksx gksus okys ty dh O;oLFkk dk;Znk;h laLFkk dks Lo;a ds O;; ij djuh gksxhA |
| 230 | QSfczds'ku ds dk;Z gsrq tujsVj dh O;oLFkk dk;Znk;h laLFkk dks Lo;a ds O;; ij djuh gksxhA |
| 231 | Je foHkkx esa QeZ dk jftLVªs'ku vko';d gksxkA |
| 232 | ;g Bsdsnkj dh ftEesnkjh gksxh fd og vuqcU/k ds vUrXkZr tkuinh; dk;ksZa esa mi;ksx dh xbZ lHkh [kuu lkexzh ij ljdkjh ekunaMks ds vuqlkj jkW;YVh (eMM-11 form) Hkqxrku dk izek.k lEcfU/kr dk;kZy; esa miyC/k djk,aA |
| 233 | LOI fuxZr gksus ds mijkUr QeZ@Bsdsnkj }kjk vuqcU/k ls iwoZ vuqcfU/kr /kujkf'k dk 5 izfr'kr FDR ds :i esa vfxze lqj{kk /kujkf'k tek djk;h tkuh gksxhA |
| 234 | QeZ dks fufonk esa Hkkx ysus ls iwoZ fuekZ.k LFky dk voyksdu dj ysuk pkfg,A |
| 235 | ;g ekuk tk;sxk fd QeZ us fufonk esa Hkkx ysus ls iwoZ dk;Z LFky dk Hkyh Hkkafr voyksdu dj fy;k gSA |
| 236 | dk;ZLFky ls iqjkuh [kafMr ;k vuqi;ksxh lkexzh dks okil ugh fy;k tk;sxk rFkk bls fuEufyf[kr njksa ij Bsdsnkj dks tkjh fd;k tk;sxkAa. Scrap MS/CI/GE items @ Rs 29 Kg.b. Brick Work @ Rs. 1200/Cum.c. Brick bats @ Rs. 1000/Cum.d. In Dismantling of Brick Work 60% Bricks, 28% Brick Bat and 12% Debries will be treated as recovered. Debries will be issued free of cost. |
| 237 | Contractor has to use following brands – i. Cement - ACC,Ultratech & Ambuja make or equivalent. ii. Steel - TATA,SAIL,Rathi make or equivalent. iii. Aluminium work – Hindalko/Jindal make or equivalent. iv. Glass - Modi/Sant Gobin make or equivalent. v. False ceiling –Armstrong make or equivalent. vi. Chemical emulsion- Bagon make or equivalent. vii. Steel sheet –Tata Durashine make or equivalent. viii. Tiles work-Somany or Kajaria make or equivalent. ix. Exterior paint –ICI dulux weather shield max or equivalent. x. Intterior paint –ICI brand acrylic distemper or equivalent. xi. Putty – Birla or Sakarni or equivalent. xii. Wire –Finolex or havells or equivalent. xiii. Switch. –Anchor or Havells or equivalent. xiv. MCB –Havells make or equivalent. xv. Waterproof Compound –Dr. Fixit or equivalent. xvi. Plyboard/Blockboard – Reliance or Scorpio deep ISI mark or equivalent. xvii. PVC Pipe –Finolex or Supreme make or equivalent. xviii. Sub-Mercible/Monoblock Moter Pump –KSB , Crompton make Water seal or equivalent. xix. GI ‘B’ Class pipe –Jindal make or equivalent. xx. PVC water storage tank – Syntex , Euro make four layer or equivalent. xxi. PVC Cistern –Hindware make or equivalent. xxii. Looking Mirror –Atul make or equivalent. xxiii. Urinals –Hindware make or equivalent. xxiv. Wash Hand Basin- Hindware make or equivalent. xxv. WC Pan- Hindware make or equivalent. xxvi. Water Supply Fitting – L & K or Royal (Sonata) make or equivalent. xxvii. Enamel Paint – ICI dulux make or equivalent. xxviii. Flush Door –Kitply,Century,Duragaurd make or equivalent. xxix.Concertina Coil – Steel wire of Tata make or equivalent. Executive Engineer Gautambuddhnagar Name of Bidder: BILL OF QUANTITY Civil Works for Construction of 220/132/33 KV GIS Sub-Station Sector -155 , NOIDA (Gautambuddhnagar) including :-(a) Construction of Main Gantry, Auxillary Foundation, Cable Trenches with cover, Transformer Plinth with CTR tank, Substation Turfing, Station Transformer, Fire Protection wall, Control Room Building, 220kV,132kV and 33KV GIS Building Hall with LCC Room,AHU Room,Store Room, Sump House, FFPH Building, Mulsifier Tank, Drain, Culvert, C.C. Road, Park & Plantation, Water supply works, Tube Well Boring, Over Head Tank, Chain-link fencing, Earth Filling & Cutting, Water Harvesting & Recharge pit, Leveling & Dressing of site, Electrical wiring & fitting, Furniture and Misc. Development Works for completion of sub-station in all respect as per direction of Engineer in-charge.(b) Construction of residential quarters Type-IV (01 No), Type-III (01 No) , Type-II (04 No) complete in all respect as per direction of Engineer in-charge.(c) Construction of security wall, Security hut and Gates complete in all respect as per direction of Engineer in-charge. S.N. Service Code CSI DESCRIPTION UNIT Quantity Unit F.O.R. destn. Prices in Rs. (Including Pkg,fwdg,freight & insurance charges) Applicable GST Rate In % (Including CGST + UPGST/IGST) Total unit wise GST Amount (Rs.) Total Unit F.O.R. Destination prices with GST (Rs.) (5+7) Total FORDestination Priceswith GST (Rs.) (4*8) |
| 238 | TOTAL (Rs.) : |
AI Tender Summary
Tender Timeline
Aug 18, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 10, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysSep 11, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 18 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender