Tender For special Repair/ Replacement Lt Overhead Line Into Lt Ug Cable For Perimeter Security Light Incl Connected Works At Fol Gp,B Coy Asc (Sup) Type A And 04 Nos Other Sanctioned Works At Mil Stn Jasai Under Ge Army Barmer[Job No. (I)- 01/Sr (Bl
Tender Overview
Project Description
Tender for special Repair/ Replacement Lt Overhead Line Into Lt Ug Cable For Perimeter Security Light Incl Connected Works At Fol Gp,B Coy Asc (Sup) Type A And 04 Nos Other Sanctioned Works At Mil Stn Jasai Under Ge Army Barmer[Job No. (I)- 01/Sr (Bldg)/Jasai/2026-27 (Ii)- 01/Rv/Rwh/Jasai/2026-27 (Iii)- 01/Mw/Jasai/2026-27, (Iv)- 01/Sr (E&M)/Jasai/2026-27), (Iv)- 03/Sr (Bldg)/Jasai/2026-27
BOQ
| Sl. No. | Item Description |
| 1 | Supply, install, testing & commissioning of LT control panel board \\"out-door type\\" of size 1200 mm (height) x 1200 mm (breadth) x 350 mm (depth) (minimum dimensions), factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & high grade Copper bus-bar wrapped with coloured PVC tape /sleeves of rating in conformity to the Incoming ACB/MCCB rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.00 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame of size 50X50X6mm fixed at 75 cm height from groud level & MC channel base suitable for 3 Phase, 4 wire system 415 /440 volts grade including complete internal wiring with not less than 2.5 Sqmm copper wire including cable glands and lugs of suitable sizes with suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) complete all as specified & as directed with & including the following accessories : |
| 2 | (i) BUS-BAR & INTERNAL CONNECTIONS :(X-mer panel)The bus-bars shall be made up of 04 Nos high grade Copper with rating should be suitable as per incoming Breaker, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized \\"F\\" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc.PROVISION FOR CABLE ENTRY :The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.INCOMING :(a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 100-125 Amps - 01 . (b) Onload changeover switch, open-execution modular construction type, confirming to IS/IEC 60947-3, rated current 100 Amps, 415 Volts, 4 Pole, AC - 01 No. |
| 3 | OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 03 Nos. (b) MCB TPN \\"C\\" series having breaking capacity 10 KA of rating 40 to 63 Amps - 03 No.(c) MCB SPN \\"C\\" series having breaking capacity 10 KA of rating 40 Amps - 06 No. |
| 4 | INSTRUMENTATION SYSTEM :(a) Digital type Multi-Function meter with built in selector Switch & 03 Nos CTs matching with the I/C breaker, Accuracy Class - 1.0, 3 phase, (b) Indicator lamp with integral circuit (230/240 Volts) & cluster LED (Red, Orange, Blue) - 01 Set.(c) Danger notice plate of size 20 x 15 cm of 1.6mm thick mild-steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal-red colour and fixed with MS clamps, bolts and nuts of approved size, for LT conforming to IS-2551 - 02 Nos (Front & Back).(d) Door opening key - 02 Nos |
| 5 | All as per item 1 here in before but of size 1200 mm (height) x 1200 mm (breadth) x 350 mm (depth) (minimum dimensions) with & including the following accessories: (PUMP Room panel) (i) BUS-BAR & INTERNAL CONNECTIONS :The bus-bars shall be made up of 04 Nos high grade Copper with rating should be suitable as per incoming Breaker, duly insulated with 1100 Volts grade standard colour coded PVC sleeves & rigidly mounted on suitable sized \\"F\\" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc.PROVISION FOR CABLE ENTRY :The provision for cable entry /exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.INCOMING :(a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 100-125 Amps - 01 . |
| 6 | OUTGOINGS : (a) MCCB 4 Pole (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting, suitable for isolation, having breaking capacity 25 KA & of rating 63 to 80 A - 02 Nos. (b) MCB TPN \\"C\\" series having breaking capacity 10 KA of rating 40 to 63 Amps - 04 Nos.(c) MCB SPN \\"C\\" series having breaking capacity 10 KA of rating 40 Amps - 20 Nos. |
| 7 | INSTRUMENTATION SYSTEM :(a) Digital type Multi-Function meter with built in selector Switch & 03 Nos CTs matching with the I/C breaker, Accuracy Class - 1.0, 3 phase, (b) Indicator lamp with integral circuit (230/240 Volts) & cluster LED (Red, Orange, Blue) - 01 Set.(c) Danger notice plate of size 20 x 15 cm of 1.6mm thick mild-steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal-red colour and fixed with MS clamps, bolts and nuts of approved size, for LT conforming to IS-2551 - 02 Nos (Front & Back).(d) Door opening key - 02 Nos |
| 8 | S&F loop in- loop out fuse junction box of internal dimension 200x140x95mm made out of FRP sheet and locking screw fitted with and incl 6 Amps SP MCB - 1 No , 20 Amps rated 4 Way connectors for 3 phase and neutral incoming/out going, mounted in the box, fixing on steel tubular/Rail poles including necessary aluminium clamps, suitable glands, lugs,GI nut and bolts including taking down old u/s junction box complete all as specified and directed by Engr-in-Charge. Make : Sintex Cat No GSJB-2014 or techno-commercially equivalant in Hensel/OBO. |
| 9 | Supply,fix and test, in replacement of LED Street light fitting of capacity 45 Watts, CRI >70, Power factor > 0.95, colour temperature 5700K, luminous Efficacy not less than 100 lumen/watt, 4500 Lumens output with IP 66 protection and impact resistance of IK-08 having lens embedded PC Cover bottom opening seprate driver compartment including taking down old u/s Street light fitting complete all as specified and directed by Engr-in-Charge. |
| 10 | Supply and fix in replacement bracket suitable for street light, made out of 40 mm dia 1.5 mtr length GI pipe light grade bent to shape fixed with suitable size of clamps (2 Nos), bolts, nuts and washers incl painting with one primer coat and two coat of aluminium paint complete incl taking down old unsv one and all as specified and directed by Engr-in-Charge. |
| 11 | S & F Rigid Non-metallic PVC conduits medium grade (for passing the pvc insulated cable along the pole) of external dia not less than 20 mm including GI/Aluminium clamp for fixing the conduit exclusive of boxes (junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories with aluminium clamp,bolt, nuts etc for fixing complete all as specified and directed by Engr-in-Charge.NOTE: PVC insulated cable shall be measured and paid separately. |
| 12 | S&F in replacement of PVC insulated and pvc round sheathed flexible multicore round copper conductor cable for voltage grade 1100V of size 3 core 1.5 Sqmm including necessary end connector fixed in PVC Conduit along with pole structure etc with all fixing & connecting accessories complete all as specified and directed by Engr-in-Charge.NOTE: PVC conduit shall be measured and paid separately. |
| 13 | Excavation in trenches n.exc 1.5m wide and n.exc 1.5m in depth for taking out/laying of UG Cables, GI Pipe etc. and getting out in soft/loose soil complete. |
| 14 | Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25cm thick. |
| 15 | Removing of excavated material n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point. |
| 16 | Supply and spreading Tibba Sand including watering and consolidation in trenches for cushioning/cable protection all as specified and directed by Engr-in-Charge. Note : Punned thickness shall be measured and paid |
| 17 | Supply and laying un-reinforced precast concrete cable cover, class LV, type 1, flat size 250 mm x 150 mm x 40 mm and abutting each other with gap between adjacent precast concrete cable cover not exceeding 10 mm over underground cables in trenches for cable protection of U/G cables with width equal to length of bricks complete all as specified and directed Please Enable Macros to View BoQ information |
| 18 | Supply and laying un-reinforced precast concrete cable cover, class LV, type 1, flat size 250 mm x 150 mm x 40 mm and abutting each other with gap between adjacent precast concrete cable cover not exceeding 10 mm over underground cables in trenches for cable protection of U/G cables with width equal to length of bricks complete all as specified and directed Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 16 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 18 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender