Tender For Segregation Of 33 Kv Mattan-Pahalgam By Way Of Construction Of New 33Kv Line From Receiving Station Iqbalabad Including Lilo At Iqbalabad And Hutmurrah Receiving Station
Tender Overview
Project Description
Tender for Segregation Of 33 Kv Mattan-Pahalgam By Way Of Construction Of New 33Kv Line From Receiving Station Iqbalabad Including Lilo At Iqbalabad And Hutmurrah Receiving Station
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 27-Aug-2026 | Correction in Last date of bid submission | Technical Bid | 08-Sep-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | SITC of 13Mtr. Long Pole (ST-410 SP 69) |
| 2 | SITC of 11 Mtr. Long Pole( ST-410 SP 56) |
| 3 | SITC of GI Channel X-arm with Belting/Brace Angle Iron or V cross-arm with top Bracket including clamp inlcuding strips for double circuit line |
| 4 | Dismantling of existing GI Channel iron with top Bracket including clamp inlcuding strips and re-fixing of Channels including clamps, angles etc. |
| 5 | SITC of 100 mm² ACSR Conductor |
| 6 | SITC of PG Clamps for 100 mm² ACSR Conductor |
| 7 | Dismantling of existing ASCR 200 mm² ACSR Conductor and re-laying same for existing 33kv line and 33kv lline forming double ckt. |
| 8 | Dismantling of 33kV Polymeric composite Pin Insulator and re-fixing of same for existing 33kv DOUBLE ckt line |
| 9 | Dismantling of 33kV Polymeric composite Disc Insulator and re-fixing of same for existing 33kv DOUBLE ckt line |
| 10 | Dismantling of existing ASCR 100 mm² ACSR Conductor and re-laying same for existing 11kv line and 33kv lline forming double ckt. |
| 11 | Dismantling of 11kV Polymeric composite Pin Insulator and re-fixing of same for existing 11kv DOUBLE ckt line |
| 12 | Dismantling of 11kV Polymeric composite Disc Insulator and re-fixing of same for existing 11kv DOUBLE ckt line |
| 13 | SITC of 33kV Polymeric composite Pin Insulator 36kV, 10kN,Lighting Impulse 170kV Positive and 180kV Negative,creepage distance 900mm |
| 14 | SITC of 33kV Polymeric composite Disc Insulator 36kV,min failingload 70kN, Lighting Impulse 170kV Positive and 180kVNegative, creepage distance 900mm with fitting |
| 15 | SITC of Galvinized Nuts and Bolts. |
| 16 | SITC of Danger Plates with Clamps |
| 17 | SITC of Anti-Climbing Device with Clamps |
| 18 | SITC of Earthing Complete by GI Pipe 40 mm 3 mtr long or 2.5m long rod through GI Strip 25x3mm |
| 19 | SITC of Red oxide |
| 20 | SITC of Aluminium Paint |
| 21 | Cement bottoming 1:2:4 mix as per Standards 0.66 cum /pole |
| 22 | Cement bottoming 1:2:4 mix as per Standards 0.78 cum /pole |
| 23 | R&M of existing poles at various spots (include excavation pit , straightening of tilted poles and cement bottoming of same @ 0.3 cum ) |
| 24 | Replacement of jumpers |
| 25 | SITC of 33kv Heavy duty Porceilin link set with more then 8 MM thickness copper link/strip |
| 26 | Restringing of loose conductor |
| 27 | Striaghetening of tilted poles including pit excavation and refilling the soil |
| 28 | SITC of Galvanised Stay Set with 50x8mm stay clamp, guyinsulator(2Nos.), anchor plate (300x 300 x 8) mm, nut-bolts,2 Nos turn-buckles, 1.8m long,20 mm diameter solid GSstay rod & 7/4 mm dia GI stranded wire complete |
| 29 | SITC of Guard netting (BY using GI Channel X-arm (75x40x6) including clamps, braces GI Wire 6 SWG & 8 SWG and Eye Bolts) |
| 30 | Branch cutting of 33KV Line |
| 31 | 33kV C&R Panel along with O/C, E/F and Differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows withannunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port |
| 32 | 33 kV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type) |
| 33 | 33 kV VCB Foundation |
| 34 | Equipment Foundation |
| 35 | 33 kV Lightening Arrestors (33 kV, 10kA, Station class, ZnO, Polymer) gap less (1 No. per Φ) |
| 36 | 33 kV Current Transformer (33 kV, 1Φ, Multi Ratio Multi Core 400-800/5A, Outdoor) (1 No. per Φ) |
| 37 | 33 kV 10 kN Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m |
| 38 | G.I Pipe of Dia 150mm, 5.9 mm Thick 3 m long (03 No.s) with G.I Base Plate 8 mm Thick |
| 39 | 33 kV Isolator with Earthing Blade porcelin type (36kV,800A, Outdoor,3 poles, 25 kA) |
| 40 | 13Mtr. Long Pole (ST-410 SP 69) |
| 41 | 11 Mtr. Long Pole( ST-410 SP 56) |
| 42 | Cement bottoming 1:2:4 mix as per Standards 0.66 cum/pole |
| 43 | Cement bottoming 1:2:4 mix as per Standards 0.78 cum/pole |
| 44 | Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip.25x3mm |
| 45 | Red Oxide |
| 46 | Aluminium Paint |
| 47 | 12 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. |
| 48 | 4 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. |
| 49 | 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. |
| 50 | 200mm2 ACSR (Dog) |
| 51 | PG Clamps for 200 mm² ACSR Conductor |
| 52 | 33kV Polymeric composite Pin Insulator 36kV, 10kN,Lighting Impulse 170kV Positive and 180kV Negative,creepage distance 900mm |
| 53 | 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm with fitting |
| 54 | Galvinized Nuts and Bolts. |
| 55 | Clamps of sorts /Sizes. |
| 56 | GI flat for earthing Extensions (50x6) mm |
| 57 | Lugs, Ferrules etc. |
| 58 | Dismantling of existing tap changer Panel /C&R Panle and AC Distribution board and re-installing of same to create space for new C&R Panel for loop out circuit. |
| 59 | Dismantling of ST Pole 11/8/9 Mtr long old damaged poles |
| 60 | Dismantling of GI V cross-arm/Ch iron etc |
| 61 | Dismantling of Pin insulator |
| 62 | Dismantling of Disc insulator |
| 63 | Manual Carriage of dismantled material from site to roadside, loading , transportation upto stores with an avg lead of 10 km and unloading at stores complete Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 9 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 9 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender