Tender For Electrical Works For Construction Of Bunker For Installation Of High Dose Rate Brachtherapy System At Radiation Oncology Govt. Smhs Hospital Srinagar
Tender Value
4.09 Lakhs
Estimated cost
Bid Submission
25 Aug 2026
0 days left
EMD
8193
Bank guarantee accepted
Document Fee
300
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Srinagar → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Electrical Works For Construction Of Bunker For Installation Of High Dose Rate Brachtherapy System At Radiation Oncology Govt. Smhs Hospital Srinagar
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLSH PVC insulated copper conductor single core cable etc. as required as per IS Standard. (Acti-bacterial/anti-fungal)(Havells / Polycab / KEI) |
| 2 | Group C |
| 3 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required as per IS standard |
| 4 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. (Acti-bacterial/anti-fungal)(Legrand / L&K / ABB / Schneider) |
| 5 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings).(Legrand / L&K / ABB / Schneider) |
| 6 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. as per IS standard(Acti-bacterial/anti-fungal)(Legrand / L&K / ABB / Schneider) |
| 7 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.(Acti-bacterial/anti-fungal)(Legrand / L&K / ABB / Schneider) |
| 8 | 3 pin 5/6 A socket outlet |
| 9 | 5/6 A switch |
| 10 | 6 pin 15/16 A socket outlet |
| 11 | 15/16 A switch |
| 12 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLSH PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required (partially laid Conduit in slab) as per IS Standard. (Acti-bacterial/anti-fungal)(Havells / Polycab / KEI) |
| 13 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire. |
| 14 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire. |
| 15 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 16 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 17 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 18 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 19 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. |
| 20 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A \\"C\\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 21 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator) |
| 22 | 8 way (4 + 24), Double door |
| 23 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.(Legrand / L&K / ABB / Schneider) |
| 24 | Single pole |
| 25 | Single pole & Neutral |
| 26 | Supplying and fixing following rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 27 | 32A (DP) |
| 28 | 40A (DP) |
| 29 | 63A (TPN) |
| 30 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.(Havells / Crompton / Bajaj) |
| 31 | Supply, Installation, Testing and Commissioning of heavy duty 450mm dia sweep PVC body, 900±10% RPM Exhaust fan with guard and mounting arrangement.Commercial series(Havells / Crompton / Bajaj) |
| 32 | LED Panel light 2x2 ft. (System lumen efficacy ≥120 Lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends,CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing, complete in all respects i/c connections with 1.5 sq. mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm)(Phillips / LK / Wipro) |
| 33 | 36 Watt |
| 34 | LED Down lighter (SMD Type) (System lumen efficacy ≥120 lm/Watt ), Supplying, installation, Testing & Commissioning of LED Recessed / surface Down lighter (Round / square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), life time of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. \\"complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminum Body including trim.(Phillips / LK / Wipro) |
| 35 | 22 watt |
| 36 | Supply and fixing DP, SPN Residual Current Circuit Breaker 40 A(Legrand / L&K / ABB / Schneider) |
| 37 | Earthling with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with chemical and salt as required. The job includes providing and fixing 25 mm × 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 38 | Supply, Installation, Testing, Commissioning of 4MP IP Fixed bullet Camera (STQC Certified Only) |
| 39 | Supply, installation, Testing, Commissioning 4 Port Layer 2 Network POE Switch |
| 40 | Supply, Installation, Testing and commissioning of 4 Channel, NVR |
| 41 | Supply, Installation, Testing, Commissioning of fully loaded 2U Rack |
| 42 | HDMI Cable |
| 43 | Supply, Installation, Testing and commissioning of 2 TB HDD for NVR |
| 44 | Supply, installation, Testing Commissioning of Cat 6A Cable 23 AWG Solid Copper Conductor. |
| 45 | Wireless Mouse |
| 46 | Supply, Installation, Testing, Commissioning of 32 inch FHD TV Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 18, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 25, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
TodayAug 27, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 2 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender