Defence Statutory Bodies & Commissions/Committees Closing in 14 days TDR #57063295

Tender For Repair / Replacement Of Dg Set, Battery Bank, Apfc Panels And Allied Works At Dhana Mil Stn

Issued by Statutory Bodies & Commissions/Committees · Sagar, Madhya Pradesh
Tender Value
10 Lakhs
Estimated cost
Bid Submission
07 Sep 2026
14 days left
EMD
20000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Sagar → Madhya Pradesh
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair / Replacement Of Dg Set, Battery Bank, Apfc Panels And Allied Works At Dhana Mil Stn

BOQ

Name of Work:- REPAIR / REPLACEMENT OF DG SET, BATTERY BANK, APFC PANELS AND ALLIED WORKS AT DHANA MIL STN
Sl. No. Item Description
1Material & labour for Maintenance and servicing of DG set of capacity 140 KVA draining out of diesel from tank, cleaning the tank thoroughly and refilling drained diesel, drain out engine oil from the oil sump cleaning the sump and refilling the sump with new engine oil of Make K Oil 20W/40, to its maximum level, applying petroleum jelly on the Battery terminals and cleaning the entire DG set, checking and rectification of any defects of output voltage, RPM, exhaust leakages etc. Tightening the foundation & exhaust manifold bolts & nuts and testing as directed by the Engineer in Charge including replacement of following items complete all as directed and specified by Engr -In-Charge. (a) Fuel filter element (b) Oil filter elements (c) V-Belt (d) Air cleaner filter (e) Magnet Pickup (f) Hose pipe for radiator (g) Flexible Hose for vent (h) Fuel pipe return.NOTE :- Servicing of DG Set is done by authorised company of DG Set. Contractor will provide all documents regarding service.
2Material & labour for Maintenance and servicing of DG set of capacity 160 KVA draining out of diesel from tank, cleaning the tank thoroughly and refilling drained diesel, drain out engine oil from the oil sump cleaning the sump and refilling the sump with new engine oil of Make K Oil 20W/40, to its maximum level, applying petroleum jelly on the Battery terminals and cleaning the entire DG set, checking and rectification of any defects of output voltage, RPM, exhaust leakages etc. Tightening the foundation & exhaust manifold bolts & nuts and testing as directed by the Engineer in Charge including replacement of following items complete all as directed and specified by Engr -In-Charge. (a) Fuel filter element (b) Oil filter elements (c) V-Belt (d) Air cleaner filter (e) Magnet Pickup (f) Hose pipe for radiator (g) Flexible Hose for vent (h) Fuel pipe return NOTE :- Servicing of DG Set is done by authorised company of DG Set. Contractor will provide all documents regarding service.
3Material & labour for Maintenance and servicing of DG set of capacity 30 KVA draining out of diesel from tank, cleaning the tank thoroughly and refilling drained diesel, drain out engine oil from the oil sump cleaning the sump and refilling the sump with new engine oil of Make K Oil 20W/40, to its maximum level, applying petroleum jelly on the Battery terminals and cleaning the entire DG set, checking and rectification of any defects of output voltage, RPM, exhaust leakages etc. Tightening the foundation & exhaust manifold bolts & nuts and testing as directed by the Engineer in Charge including replacement of following items complete all as directed and specified by Engr -In-Charge. (a) Fuel filter element (b) Oil filter elements (c) V-Belt (d) Air cleaner filter (e) Magnet Pickup (f) Hose pipe for radiator (g) Flexible Hose for vent (h) Fuel pipe return NOTE :- Servicing of DG Set is done by authorised company of DG Set. Contractor will provide all documents regarding service.
4Material & labour for spray painting of DG Sets of capacity upto and including 160 KVA (in situ) any type, installed and located at different sites in scattered area at SI line complete all as specified and as directed including the following: -(a) Removal of burnt grease,dust, oil and other contaminants using de-greasing solvent. (b) De-rusting of surface and cleaning manually by scrubbing by brushing. (c) Washing thoroughly and dry properly. (d) Applying one coats of primer by spray machine (e) Final painting of two coats with super glossy synthetic enamel paint as recommended by OEM through spray machine over priming coat. (f) the colours of painting shall be as per existing colour matching including writing SM/ MES No.at top of the corner of the body.
5Material & labour for repairing of battery charger , 6-72 volts capacity by replacing Amp meter, volt meter, selector swtich, complete wiring , transformer etc including painting complete all as specified and directed.
6Material & labour for engine oil 15W 40 of approved make as approved by EIC Complete all as directed.
7Material & labour for dismantling existing unserviceable radiator and carrying out repair by draining out water/coolant,carring out pressure test and rectifying leakage by brazing/soldering test and reinstalling including topup/filling fresh coolant as on required basis all as directed and specified for DG set upto 160 KVA capacity
8Dismantling of unserviceable self starter 12 volts of DG Set of capacity 160/140/30 KVA including replacment of worn out parts like bendex, piston, bush housing etc including refixing and testing .complete all as diected and specified by Engr -In-charge.
9Dismantling of unserviceable dynamo/alternator of DG Set of capacity 140 KVA including replacment of worn out parts like carbon bushes,solenoid switch bearing, armature etc including refixing and testing .complete all as diected and specified by Engr -In-charge.
10Supply only distilled water in sealed bottle of one liter capacity complete all as specified and directed.
11Dismantling existing inside roof sheet with insulation of DG set capacity up to 140 KVA including repair of sheet with suitable insulation complete all as specified as directed.
12Material & labour for Earthing with GI earth plate electrode 600x600x6mm thick buried directly in ground (earth pit not less than 2.25 M deep below ground level) with top edge of the plate not less than 1.5 M below normal ground level, connected to galvanized steel strip of size 25X4mm including 40 mm dia light grade protection,pipe 20mm dia watering pipe with funnel,CI hinged cover,PCC chamberand excavation and earth work complete all as described and shown in EP plate No 3 of SSR part I 2009 print and testing on completion all as specified and directed.
13Supply & fixing GI earth strip of size 32 x 6mm complete as earth lead of wall conductors/ buried in ground including screws etc. and connections with existing earth test point complete all as specified and as directed by Engineer-in-charge.
14Supply and fix in repairs battery terminal made out of brass/bronze heavy duty suitable for 92 AH/180 AH 12 Volt Battery
15Replacement of Battery charger with variable voltage and current setting suitable for charging 2 x 12 V Battery in sheets steel cabinet complete with Internal and external wiring, including all measuring and control accessories/ instruments all as specified and directed.
16Supply only Grease Multipurpose to increase equipment/ bearing life, Excellent resistance to throw off & water wash, Maximum protection offered against rust & corrosion complete all as specified. Make- Castrol, Servo, Mobil
17Comprehensive maintenance and Repair/servicing of APFC Panel of follwoing capacity for maintaining Power factor including by replacing the connected items etc installed for water supply installation:(a) 90 KVAR APFC Panel at Bannad Pump HouseNote : Capacitor, Contactor, MCB will be measured and paid separately.
18(b) 60 KVAR APFC Panel at Filter Pump House
19Comprehensive maintenance and Repair/servicing of APFC Panel of follwoing capacity for maintaining Power factor including by replacing the connected items etc installed for Inf Bn Phase II transformers: (a) 60 KVAR APFC Panel at 12 Mli officer MessNote : Capacitor, Contactor, MCB will be measured and paid separately.
20(b) 60 KVAR APFC Panel at Inf Bn PH-II Area
21Taking down unserviceable capacitor and Supply and fix in replacement cylindrical capacitor metalized poly propylene heavy duty ( MPP - H ) for three phase 440 V and 50 Hz system for permissible non - linear load 15 % of 1 KVAR capacity. Make- Neptune, L&T, Epcos
22All as per item No 21 above but 2 KVAR capacity. Make- Neptune, L&T, Epcos
23All as per item No 21 above but 3 KVAR capacity. Make- Neptune, L&T, Epcos
24All as per item No 21 above but 6.5 KVAR capacity. Make- Neptune, L&T, Epcos
25All as per item No 21 above but 10 KVAR capacity. Make- Neptune, L&T, Epcos
26All as per item No 21 above but 12.5 KVAR capacity. Make- Neptune, L&T, Epcos
27All as per item No 21 above but 25 KVAR capacity. Make- Neptune, L&T, Epcos
28Supply & fixing in repair 3 pole contactor for capacitor switching 30 KVAR capacity, 220-240 Volts, 60 Hz complete all as specified and directed. Make- Cat no. UA30-30-10RA of ABB or equivalent in L &T, Schneider
29Supply & fixing in repair 3 pole contactor for capacitor switching 12.5 KVAR capacity, 220-240 Volts, 60 Hz complete all as specified and directed. Make- Cat no. UA16-30-10RA of ABB or equivalent in L &T, Schneider
30Supply & fixing in repair 3 pole contactor for capacitor switching 7.5 KVAR capacity, 220-240 Volts, 60 Hz complete all as specified and directed. Make- Cat no. UA9-30-10RA of ABB or equivalent in L &T, Schneider
31Painting to existing APFC /LT panel board only one coat of synthetic enamel paint over a coat of red oxide primer after scraping, cleaning of old surface of electric panel complete all as specified and directed.
32Taking down unserviceable volt meter and supply and fix digital volt meter range up to 500 Volt complete all as specified and directed.
33Taking down unserviceable Amp meter and supply and fix digital Amp meter range up to 300 Amp complete all as specified and directed.
34Taking down unserviceable lamp indicator RYB and supply and fix led lamp indicator RYB complete all as specified and directed.
35Supply laying and testing cable XLPE insulated screened PVC bedded galvanized steel strip or wire armoured electric power cables (heavy duty) 1100 volts grade with stranded copper conductor of size 70 sqmm single core complete all as specified and directed.
36Comprehensive maintenance and Repair/servicing of two zone fire alarm panel by checking all connections and minor repairs complete all as specified and directed.
37Comprehensive maintenance and Repair/servicing of six zone fire alarm panel by checking all connections and minor repairs complete all as specified and directed.
38Material & labour for repair/servicing of two zone fire alarm control panel, 230V, AC, 50Hz including replacement of following connected unserviceable items:- (a) Battery with Charger (b) Fault LED indicator (c) Reset/silence switch (d) Relay, complete all as specified and directed by Engr-in-charge.
39Supply and fix smoke detector complete all as specified and directed.
40Supply & fixing in replacement MCCB 4 pole 36 KA 400 A suitable for Adjustable type setting complete as specifed and directed.
41All as per item No 40 above but capacity 250 A.
42All as per item No 40 above but capacity 350 A.
43Supply and fix bus bar chamber weather proof boxes made out of 3mm thick CRCS sheet front opening double chamber type for providing four numbers aluminium bus bar strips of 400 Amps and 300 mm long each, insulators, nuts bolts and MCCB 250 amps 4 pole 35 KA incoming including terminating the existing incoming and outgoing cables etc alongwith painting with 2 coats of synthetic enamal paint over a coat of red oxide primer complete with proper fixing arrangements ofn ground with angle iron supports duly grouted on floor/ground all as specified and as directed.
44Supply and fixing LED flood light 120 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp.
45Disconnecting and dismantling existing unserviceable Air termination rod and supplying & fixing new single pointed copper rod 12mm dia, 300mm long with all connections with bolts and nuts complete all as specified and as directed.
46NOTE :- SCHEDULE OF CREDIT (Amount shall be deducted offline from the total quoted amount to workout the net contract sum to be considered for acceptance.) [(-) Rs 10480.00/- ] Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57063295
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 10 Lakhs
LAST DATE 07-09-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair / Replacement Of Dg Set, Battery Bank, Apfc Panels And Allied Works At Dhana Mil Stn
Basic Detail
Tender No 8300/DH/39/E8
Bidding Type Tender
Location
City Sagar
State Madhya Pradesh
Key Dates
Publish Date 17 Aug 2026
Submission Date 07 Sep 2026
Open Date 09 Sep 2026
Finance
Tender Value 10 Lakhs
Tender Fee 500
EMD 20000
Exemption Available
Document List
39SoC.pdf
39TENDERPAGES.pdf
577b83bd-5abe-4ee6-9700-cac51704151d.html
BOQ_879346.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 17, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 07, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 14 days
Sep 09, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 16 days

Tender Documents

Download All (ZIP) ↓
pdf

39SoC.pdf

pdf

39TENDERPAGES.pdf

html

577b83bd-5abe-4ee6-9700-cac51704151d.html

xls

BOQ_879346.xls

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders